ABOUT US
Complete selectivity
Unique feature of lcu=lcs=lcw for 1 second across the entire range. This ensures complete selectivity for
system with time based discrimination.
Optimal compactness
Designed to ensure
l
Low inherent temperature rise
l
Adequate interface clearances
Safety
marked for C, S1 & H ranges
l
Superior quality engineering grade plastics used for insulation purpose; conforms to Glow wire test
(Ref: IEC 60695-2-1)
l
In-built mechanical anti-pumping to prevent auto-reclosing of ACB on persisting faults
l
In-built rating error preventor in drawout ACBs ensure correct rating of drawout portion in corresponding
cradle
l
Safety shutters prevent accidental contact with live cradle terminals
l
Variety of Safety Interlocks
l
Easily removable arc chutes without use of any tool
l
Operating voltage ranges from 10% Un to 110% Un for shunt release ensures intentional tripping even at
high voltage drops during short-circuit
Transparent safety shutter offers easy inspection of cradle contacts & reduces the maintenance time
l
l
Conformance to standards
IEC - 60947 (Part 1 & 2)
IS/IEC - 60947 (Part 1 & 2)
l
IEC 60695 - 2 - 1
l
BS EN 60947 - 2
l
l
Special applications
690V Application for C Power ACB
Solution for 690V application available in C Power Family. For further details please consult our nearest
branch office.
RANGE
Breaking capacities:
Icu = Ics = Icw for 1 sec
Rated Current
400A
630A
800A
1000A
1250A
1600A
2000A
CN-CS : E
50kA
50kA
50kA
50kA
50kA
50kA
50kA
50kA
50kA
50kA
2500A
3200A
60kA
60kA
4000A
5000A
6300A
95kA
95kA
Frame-1
50kA
CN-CS : S1
50kA
50kA
50kA
Frame-1
Frame-2
CN-CS : C
50kA
50kA
50kA
50kA
55kA
60kA
CN-CS : H
65kA
65kA
65kA
65kA
75kA
75kA
CN-CS : H2
NEW
CN-CS : H1/H
Frame-1
Frame-2
75kA
75kA
100kA
100kA
Frame-3
Frame-4
400
Rating (A)
400/
630
630
800
1250
1000
2500
2000
1600
NEW
Type Designation
S1
S1
S1
S1
S1
S1
S1
S1
5000 6300
4000
3200
NEW
H2
H1
H2
In
Ue*
415
415
415
415
415
415
415
415
415
415
415
Ui
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000 1000
Icu
Ics
Icw
800
1250
1000
2500
2000
1600
3/4
5000 6300
4000
3200
3/4
3/4
415
3/4
3/4
95
95
3/4
50
50
50
50
50
50
65
50
50
50
65
50
50
50
65
50
50
50
65
50
50
55
75
60
60
75
60
75
100
75
100
70
35
50
35
50
35
50
35
50
40
65
40
65
65
85
65
85
D
D
D
50
50
50
50
50
50
65
50
50
50
65
50
50
50
65
50
50
50
65
50
50
55
75
60
60
75
60
75
100
75
100
70
35
50
35
50
35
50
35
50
40
65
40
65
65
85
65
85
D
D
D
0.5 sec
50
50
50
50
50
50
65
50
50
50
65
50
50
50
65
50
50
50
65
50
50
55
75
60
60
75
60
75
100
75
100
70
95
95
1 sec
50
50
50
50
50
50
65
50
50
50
65
50
50
50
65
50
50
50
65
50
50
55
75
60
60
75
60
75
100
75
100
70
95
95
3 sec
35
50
35
50
35
50
35
50
50
65
55
65
70
85
70
85
D
D
D
105
105
105
105
105
105
143
105
105
105
143
105
105
105
143
105
105
105
143
105
105
121
165
132
132
165
132
165
220
165
220
73.5
105
73.5
105
73.5
105
73.5
105
84
143
84
143
143
187
143
187
12
No. of poles
Rated ultimate short circuit breaking
capacity 50/60Hz (kA rms)
630
400
380/415/500V
690V
380/415/500V
690V
380/415/500V
3/4
3/4
3/4
3/4
3/4
154
95
209
95
209
Icm
Uimp
Uimp
40
40
40
40
40
60
60
60
60
60
Utilization category
PP
Fixed
x
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
Draw out
Manual
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
690V
Electrical
x
P
x
P
12
x
P
P
P
x
P
P
P
20000
x
P
P
P
x
P
P
P
15000
6000
12
8000
8000
6000
12
12
12
12
40
40
40
40
40
40
40
60
60
60
60
60
60
60
P
P
x
P
P
x
P
P
P
x
P
P
P
7000
12
12
20000
20000
8000
D
D
D
7000
12
x
P
P
P
x
P
P
P
12
6000
7000
7000
4500
5000
10000
20000
20000
7000
P
P
P
P
P
P
P
P
P
P
P
P
P
P
20000
7000
x
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
5000
5000
10000
5000 5000 5000 5000 5000 5000 5000 5000 2500 2500 2500
385
385
394
385
394
385
394
385
394
385
394
385
394
394
3 Pole
316
316
326
316
326
316
326
316
326
316
326
316
482
482
4 Pole
414
414
414
414
414
628
628
431 423.5
431
423.5
431
423.5
431
423.5
431
423.5
431
431
583
583
583
Fixed H
W
D
423.5 423.5
Draw out H
468
468
468
468
468
468
468
468
468
468
468
3 Pole
399
399
399
399
399
399
555
555
555
701
701
711
913
913
4 Pole
487
487
487
487
487
487
701
701
701
909
909
913
1182
1182
587
587
587
587
587
587
587
587
587
587
587
691
691
691
W
D
* Please consult us for application at dc voltages & higher operational voltage upto 690V AC.
Electrical life = Mechanical life. However, arcing contacts need to be replaced depending upon wear & tear.
D
Please consult us.
PROTECTION RELEASES
Thermo-magnetic Release Type - DN1
DN1 thermo-magnetic release offers reliable protection against overload, short-circuit
and earth faults via multitap Cts. with ambient temperature compensation
from -50C to 500C.
Protection
Overload Protection (Phase)
l
Unique individual phase O/L setting adjustment helps to avoid the nuisance
tripping of ACBs in unbalance load condition (due to single phase loads) on
distribution transformer. Overload pick-up range: 0.75 to 1 times In
Short-Circuit Protection
l
Two taps on CTs (working as rating plug) help in selecting operating threshold.
Short-Circuit pickup range: 5.5 to 7.5 times In with minimum impulsion time of
25 ms to prevent nuisance tripping due to transients
Earth Fault Protection
l
Offered with auxiliary earth fault release module. Earth-fault pick-up
range: 0.2 to 0.5 times In
Comprehensive protection
- SR18: Overload (Phase) and Short-Circuit
- SR18G: Overload (Phase), Short-Circuit and Earth fault protection
l
True Hot & Cold characteristics & switchable thermal memory
l
Multi-state LED to indicate
- Power ON condition
- Test mode
l
Individual fault annunciation through LEDs
l
AN1 module for remote fault indication through LEDs with changeover contact
for each kind of fault
l
Provision for Self-diagnostic test (without tripping the breaker)
l
Test kit (SRT-2) available for testing the releases
l
Conformance to EMI/EMC standards
l
Type of
Protection
Overload
(Phase)
Short-Circuit
Instantaneous
Earth Fault*
Setting Range
Pick-up Current
Time Delay
2 to 10 times In
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10
20 ms to 600 ms
Steps: 20, 60, 100, 160, 200,260, 300, 400, 500, 600 ms
6 & 12 In
100 to 400 ms
Steps : 100, 200, 300, 400 ms & OFF
PROTECTION RELEASES
Microprocessor Based Release - SR18G with display
Salient Features
Self powered &True RMS sensing
True Hot & Cold characteristics & switchable Thermal Memory
Unique 3 line O-LED display (Organic LED)
l
Offers comprehensive protection against Overload - Phase &
l
Neutral, Short-Circuit, Instantaneous, Earth Fault
l
Settable Overload delay
l
Settable Instantaneous setting with provision of OFF
2
I t ON/OFF for Short-Circuit and Earth Fault protection
l
Individual Fault LED indication
l
Provision for Self-diagnostic test
l
Conformance to EMI/EMC standards
l
Testing through Test kit
l
l
Separate version with Zone Selective Interlocking (ZSI) - SR18Gi
with display
l
l
Setting Range
Type of
Protection
Pick-up current
Time Delay
Overload (Phase)
Overload (Neutral)
2 to 10 times In
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10
2 to 16 times In
Steps : 2, 3, 4, 6, 8, 10, 12, 14, 16, OFF
Short-Circuit
Instantaneous
Earth fault*
*In 3 phase, 4 wire system, Neutral CT is required for earth fault protection
Test-kit UN-ES1
Salient Features
Test-kit for SR18G/SR18Gi with display
Operates from 230V AC supply & generates single-phase voltage test signals
l
Tests the release for
- Phase fault i.e. for overload, short-circuit and instantaneous protection
- Earht fault protection
l
Test current multiples
- For phase faults: 2.5 In, 4.5 In, 6.5 In, 9.5 In, 11 In, 13 In
- For earth fault: 0.25 In, 0.35 In, 0.45 In, 0.55 In
l
Five 7-segments LED display indicates the trip time (two places after decimal)
l
PROTECTION RELEASES
Microprocessor Based Release - SR21i
Salient Features
Self-powered & True RMS sensing
Inbuilt Zone Selective Interlocking (ZSI)
l
Provision for Self-diagnostic test(without tripping the breaker)
l
True Hot & Cold characteristics & switchable Thermal Memory
Multi-state LED to indicate
l
- Power ON condition
- Test mode
l
Individual fault annunciation through LEDs
l
Provision for AN1 module for remote fault indication through LEDs with
changeover contact for each kind of fault
l
Direct tripping of breaker-reliable tripping with minimum time delay
l
Test kit available for testing the release (SRT-2)
l
Realistic hot and cold curves which take into account integrated heating
effect
l
Conformance to EMI/EMC standards
l
l
Setting Range
Type of
Protection
Overload
(Phase)
Pick-up Current
Time Delay
2 to 10 times In
Steps : 2, 3, 4, 5, 6, 7, 8, 9, 10
20 ms to 600 ms
Steps : 20, 60, 100, 160, 200, 260, 300, 400, 500, 600 ms
2 to 16 times In
Steps : 2, 3, 4, 6, 8, 10, 12, 14, 16, OFF
100 to 400 ms
Steps : 100, 200, 300, 400 ms & OFF
Short-Circuit
Instantaneous
Earth Fault*
Test-kit SRT-2
Salient Features
Test-Kit for SR18/SR18G/SR21i Releases
Operates from 230V AC supply & generates single-phase voltage test signals
PROTECTION RELEASES
Microprocessor-based, Communication-capable Release - SR71
Salient Features
True RMS sensing
Offers comprehensive protection for overload, short-circuit,
instantaneous, earth fault and neutral overload
l
High resolution backlit LCD display
l
Intelligent Pre-trip alarm to prevent system shutdown
l
Password protected settings and commands
l
MODBUS RTU protocol with intrinsic RS 485 port
l
LED indication for POWER ON, different faults and Pre-trip alarm
l
2 sets of storable protection settings
Last 5 trips & 128 Event records with time & date stamping
l
l
3 programmable contacts-1 for micro controller failure, 2 for basic
fault annunciation
l
4 relay contacts for indication of exceeding maximum demand, Pre-trip
alarm and control on breaker (closing and opening)
l
Rating-plug for precise protection at lower load currents
l
Auto-doubling features to prevent nuisance tripping
l
Selectable I2t based current for short-time and earth fault zones
l
Thermal reflectivity enables faster tripping on recurrent overloads
Inbuilt Zone Selective Interlocking
l
Provision for Self-diagnostic test
l
l
Conformance to EMI/EMC standards
l
Overload
(Phase)
Neutral Fault
Short-Circuit
Parameter
Screen
Abbreviation
Details
Factory
Settings
PICK-UP
1.0 In
TMS-Tr
0.5-1-2-4-6-12-18-24-30
30 sec
PREALAR
0.95 Ir
Thermal Reflectivity
THM-MEM
ON / OFF
OFF
Function
FUNC
Enable / Disable
PICK-UP
0.5-1.0
1.0 Ir
DELAY
30 sec
PICK-UP
2 to 10 In in steps of 0.5 In
10 In
20-100-200-300-400
400 msec
DELAY
20-100-200-300-400
400 msec
PREALAR
0.95 Is
l t ON
Pre-trip Alarm Settings
2
Instantaneous
Earth Fault
lt
lt
ON / OFF
Cold-load Pick-up
COLDPIC
Enable / Disable
Disable
CP-DLY
0.1 sec
Function
FUNC
Enable / Disable
Enable
PICK-UP
2 to 16 In in steps of 0.1 In
16 In
Function
FUNC
Enable / Disable
Enable
PICK-UP
0.6 In
DELAY
3 sec
PREALAR
0.95 Ig
l2t
l2t
ON / OFF
OFF
Cold-load Pick-up
COLDPIC
Enable / Disable
Disable
Note: Both Protection Groups 1 & 2 carry the same factory settings.
10
ADDITIONAL PROTECTIONS
Parameter
Under Current
Current Unbalance
Over Voltage #
Under Voltage #
Under Frequency #
Over Frequency #
Reverse Power #
Phase Sequence #
Breaker Failure
Maximum Demand
Exceed
i - Discrimination
Screen
Abbreviation
Details
Factory
Settings
Function
FUNC
Enable / Disable
Disable
PICK-UP
0.8 In
DELAY
1 second
Trip / Alarm
MODE
Either / Both
Alarm
Function
FUNC
Enable / Disable
Disable
PICKUP
0.2 In
DELAY
1 to 10 in steps of 5 secs
2.0 secs
Function
FUNC
Enable / Disable
Disable
PICK-UP
1.2 Vn
DELAY
5.0 secs
Reset Voltage
RSTSET
0.95 Vs
Trip / Alarm
MODE
Either / Both
Alarm
Function
FUNC
Enable / Disable
Disable
PICK-UP
0.6 Vn
DELAY
1 second
Reset Voltage
RSTSET
1.02 Vs
Trip / Alarm
MODE
Either / Both
Alarm
Function
FUNC
Enable / Disable
Disable
48.0Hz
59.0Hz
PICK-UP
DELAY
0.2 secs
DRPOFF
0.1Hz
Trip / Alarm
MODE
Either / Both
Alarm
Function
FUNC
Enable / Disable
Disable
PICK-UP
52.0Hz
61.0Hz
DELAY
0.2 secs
DRPOFF
0.1Hz
Trip / Alarm
MODE
Either / Both
Alarm
Function
FUNC
Enable / Disable
Disable
Settings (kW)
PICK-UP
0.2 Pn
DELAY
2.0 secs
Trip Alarm
MODE
Either / Both
Alarm
Function
FUNC
Enable / Disable
Disable
Settings
PICK-UP
123 - 132
123
DELAY
2 secs
Trip / Alarm
MODE
Either / Both
Alarm
Function
FUNC
Enable / Disable
Disable
DELAY
1.0 second
Function
FUNC
Enable / Disable
Disable
Settings (kW)
PICK-UP
40 kW - 1600 kW
100 kW
Step
DELAY
10 kW - 1000 kW
10 kW
i -Discrimination
Enable / Disable
Disable
# Requires SR71-PM module
11
METERING
Parameter
Screen Abbreviation
Details
Current
Imax
%Load
Percent Loading
Phase-Neutral
Vph-Vph
Phase-Phase
Frequency #
System Frequency
Power Factor #
PF
Power #
kW
kVAr
Voltage#
Energy #
Harmonic-Current
Harmonic-Voltage #
kVA
kW
kWh
kVArh
kVAh
I1HAR
I2HAR
I3HAR
V1HAR
V2HAR
V3HAR
Display
ADDITIONAL FEATURES
Parameter
Screen Abbreviation
Details
LED Indications
Auxiliary Power ON
Overload
Short-Circuit
Instantaneous
Earth Fault
Neutral Fault
Trip
Alarm
Auxiliary Supply
24V DC
Digital Inputs
4 Nos.
Output Relays
Rating Plug
In Multiplier
630-800-1000-1250-2000-3200-5000
Communication
Protocol
MODBUS RTU
Link used
RS 485
Maintenance Indication
I2t based
Trip Records
Testing
Supplementary Modules
Self-Diagnostic Test
Comunication Module (SR71-COM)
12
PROTECTION CHARACTERISTIC
Time-current
(DN1)
10000
Operating Limits
}1.05
Thermal
1.2
1000
100
10
Overload
(SR18/18G)
0.4
0.3
1000
M1
0.2
M2
0.1
DN1
25ms
Total Operating Time
Min. Impulsion Time
0.01
100
0.7
3 4 5 678910
20 304050
100
400
1000
10
0.1
1
1.2 1.5
6 7 8 9 10
13
20
PROTECTION CHARACTERISTIC
Short-Circuit
(SR18/18G)
1
10
2
0.6
0.6
0.5
0.5
0.4
0.4
0.3
0.3
0.26
0.2
0.2
0.1
0.1
0.06
Earth Fault
(SR18G)
1
0.02
0.2
0.6
0.4
0.3
0.01
1
4 5 6 7 8 910
20
100
0.2
0.16
0.1
0.1
0.01
0.1
10
100
14
PROTECTION CHARACTERISTIC
Overload
(SR18G/SR18Gi with display)
10000
1000
100
30s
10
17s
12s
6s
3.5s
2s
1.5s
1s
0.5s
0.1
0.2s
0.01
1
6 7
8 10
Short-Circuit I2t ON
(SR18G/SR18Gi with display)
10
400ms
300ms
200ms
0.1
100ms
20ms
0.01
1
15
10
PROTECTION CHARACTERISTIC
Short-Circuit I2t OFF
(SR18G/SR18Gi with display)
1
400ms
300ms
0.1
100ms
20ms
trip time
40ms
0.01
1
10
Instantaneous
(SR18G/SR18Gi with display)
200ms
20ms
0.01
1
10
100
16
PROTECTION CHARACTERISTIC
2
Earth Fault I t ON
(SR18G/SR18Gi with display)
10
0.1
400ms
300ms
200ms
100ms
trip time 20%
0.01
0.1
10
400ms
300ms
200ms
0.1
0.1
1
Current Multiples (xIn)
17
PROTECTION CHARACTERISTIC
Overload
(SR21i)
10000
1000
30
10
17
12
6
Short-Circuit
(SR21i)
3.5
1
2.0
1.5
1.0
0.5
10
0.1
0.6
0.6
0.5
0.5
0.4
0.4
0.3
0.3
0.2
0.01
1 1.2 1.5
0.26
6 7 8 9 10
0.2
0.2
0.16
100
0.1
0.1
0.06
0.02
0.01
1
4 5 6 7 8 9 10
20
100
18
PROTECTION CHARACTERISTIC
Earth Fault
(SR21i)
1
0.2
0.6
0.4
0.3
0.2
0.1
0.1
Overload Curve
(SR71)
10,000
1000
0.01
0.1
10
100
100
10
30 sec
24 sec
18 sec
12 sec
6 sec
4 sec
1
2 sec
1 sec
0.5 sec
Tolerance:
Trip Time: 20%
0.01
1.5
19
PROTECTION CHARACTERISTIC
Short-Circuit - I2t ON
(SR71)
10,000
0.6
1000
1.0
1.5
2.0
100
3.0
4.0
6.0
9.0
10
10.0
1
10,000
0.4
0.3
0.2
0.1
0.1
0.6
1000
1.0
0.02
1.5
2.0
0.01
0.05
0.1
1
Current Multiples ( x In)
10
50
100
3.0
4.0
6.0
8.0
8.0
9.0
10
10.0
0.4
0.3
0.2
0.1
0.01
0.05
0.1
0.1
10
50
20
PROTECTION CHARACTERISTIC
Instantaneous
(SR71)
10.000
1000
100
10
2.0
3.0
4.0
5.0
6.0
10,000
8.0
10.0
16.0
0.1
1000
0.01
0.05
0.1
10
50
100
10
0.2
0.3
0.4
0.5
0.6
0.4s
0.1s
0.1
0.01
0.05
0.1
0.8
2.4
1
21
10
50
PROTECTION CHARACTERISTIC
Earth Fault - I2t OFF
(SR71)
10,000
1000
100
0.2
0.3
0.4
0.5
0.6
10
5.0
1.0
0.4s
0.3s
0.2s
0.1
0.1s
0.01
0.05
0.1
10
50
22
Protection &
Control Unit
81
SR21i/SR71
DN1/SR18
SR18G/SR18G+D
82
EA/
EA1
Aux
NC
Shunt
Release
40
Aux
NC
AS+
(+24V DC)
Power
Supply
For
SR18G+D
AS-
Aux
NO
(-24V DC)
Aux
NC
10
Aux
NC
14
10
Aux
NO
16
11
Closing
Coil
12
Electric
Charging
Device
5. When using An1 Annunciator Module with SR18G/18Gi (with display releases)
A) AS+ & AS- always appear after 5,6 nos. of the SIC.
B) If 1,2,3,4,5,6 nos. of SICs are not there, AS+ & AS- will appear first.
C) SIC 13 and 14 Nos. are not offered in 3P EDO and 3P MDO standard breakers.
2) For EF versions
The ref. no. 12, 13, 14, 15, 16, 17, 18, 19, 20, 21 are provided as
per customer requirement.
Aux
NO
12
CC
C11
NCT
41
14
CP
15
Closing
Preventer
42
16
Spring
Charging
Indication
17
Common
fault
Indication
52
18
Separate
fault
Indication
55
74
19
Shunt
trip
Indication
75
72
20
Under
voltage
Indication
71
Electrical
anti-pumping
21
Electrical
anti-pumping
SI, SO
GI, GO
G
i discrimination
i discrimination
As per order/requirement
13
U/V
Neutral
C.T. Release
82
MV
70
73
50
41
42
81
15
13
11
Ref no.
Main
Circuit
Load
CA-1
Internal Wiring
C6
ECD
(
(
(
(
(
(
(
(
SR18G+D
Only for DC
Internal Wiring
(
(
(
(
(
(
(
(
(
(
(
(
23
WIRING DIAGRAM
ACCESSORIES
Type
Data
Mounted in place of normal trip push button. With this, ACB can be locked
in trip condition. For interlocking, LTPBs are offered in the following
combinations:
l
4 different types of keys i.e. AA, BB, CC and DD suitable for 2 I/C & 1 B/C
schemes
Door
Racking
Interlock Interlock
Locking in
Isolated
Position
Mechanical Interlock
24
ACCESSORIES
Type
Data
C1
C2
AN1-Annunciator Module
C5
25
ACCESSORIES
Type
Shunt Release
Undervoltage Release
Closing Release
Auxiliary Contacts
Technical Data
Data
Type
Rated
Power Operation
of
Operational consumLimit
Release voltage
ption at
(Ue)
pick-up
EA1
240 AC
415 AC
800 VA
800 VA
10-130%
Ue
EA
24V DC
48V DC
110 DC
220 DC
32 W
125 W
45 W
30 W
65-130%
Ue
Parameter
Specification
Rated Operational
voltage (Ue)
Pick-up (V)
80% Ue
35-65% Ue
Consumption (VA)
Pick-up - 23 VA
Hold on - 10 VA
Watt loss
6W
Rated
Power
Range
operational
consumption
of
voltage
operation
(Ue)
Pick-up Hold-up
110V AC
240V AC
220V AC
320 VA
110V DC
220V DC
300 W
50 W
24V DC
350 W
50 W
50 VA
85-110%
Ue
Rated
operational
voltage
(Ue)
Power
consumption
240V AC
320 VA
Electrical
circuit
Voltage
(V)
Rated current
(A)
Resistive
24 to 415 AC
250V AC
16
1.2
Nonresistive
24 to 415 AC
250V AC
16
1.0 #
110V DC
220V DC
Range
of
operation
85-110%
Ue
154 W
26
OVERALL DIMENSIONS
Fixed Breakers
For 800A to 2500A 3P/4P C/H & 400A to 1600A 3P/4P S1
A
26
58
264
26
140 min
36 min
36 min
To Remove
Arc Chute
340 min
For Insulating Sheet
100 min
200 min
20 min
9
7
Door
Bezel
256
385
394
309
27
33
16
68.8
104
22
27
21
Earthing Terminal 30
16
230
35
301
20
D
54
2.6 min
2 Holes-6.3
405
86
10
Dimensions (mm)
Ratings
CN - CS
326
57
102
414
56
98
98
3P
482
83
154
4P
628
82
150
156
Rating
Type
400E -1250E
150
1600E
10
145
2000E
15
140
400/630A
S1
3P
800/1000A
C/H/S1
3P
1250/1600A
C/H/S1
3P
400/630A
S1
4P
800/1000A
C/H/S1
4P
1250/1600A
C/H/S1
4P
2000/2500A
C/H
2000/2500A
C/H
316+1.0
40 min
58
102
102
40 min
100 min
340 min
Insulator
20 min
56
23.5
385
4 Holes
12
X
227
286
325
32
20
22
20
137.5
179.5
27
216
298
402
21
OVERALL DIMENSIONS
Fixed Breakers
Terminal
3 Holes-13
2 Holes-13
30
30
15
15
12.5
25
50
25
25
50
100
2000/2500C/H
Terminal Connections
23.5
23.5
23.5
15
10
15
140
145
147
227
227
10
227
12 Holes-4
Hinge
305
101
332
A
11 min
363
112
112
325
112
Hinge
59
294
Door Cutout
5.5
15 min
Bezel
Note:
A = 89 for 4000C/3200D
A = 91 for other
fixed ACBs
28
OVERALL DIMENSIONS
Drawout Breakers
For 800A to 2500A C/H, 3200A H2/H1, 4000A H2/H, 400A to 3200A S1 3P/4P
For Metallic Components
75 Isolated Position
122
94.5
100 min
380 min
For Insulating Sheet
40 max
264
40 64.5
51 Test Position
200 min
Service Position
26
Door
Bezel
256
4
28
160
M 10
74
46
68.8
397.5
404
468
*5
6
17.5 min.
18.9 max.
8.9 min. 18
6
538
D
64.5
40
40
15
308.5
308.5
221.5
221.5
308.5
15
Terminal for
400/630/800/1000/1250
S1 & 800/1000C, 2000C,
2500S1
Terminal for
1250/1600/2500C/H
& 800/1000/200H,
1600/2000S1
Terminal for
for 3200S1
Dimensions (mm)
Ratings
CN - CS
400/630/800/1000A
C/H/S1
3P
2000A
S1
3P
1250/1600A
C/H/S1
3P
400/630/800/1000A
C/H/S1
4P
2000A
S1
4P
1250/1600A
C/H/S1
4P
2000/2500A
C/H
3P
2500/3200A
S1
3P
2000/2500A
C/H
4P
2500/3200A
S1
4P
3200A
H2/H1
3P
4000A
H2/H
3P
3200A
H2/H1
4P
4000A
H2/H
4P
60
15
25
10
65
399
97.5
102
487
96.5
98
98
555
123.5
154
701
122.5
150
156
701
148.5
202
909
151.5
202
202
308.5
221.5
245
221.5
20
Earthing Terminal
29
54
10
199.5
Terminal for
3200H2/H1
& 4000H2/H
OVERALL DIMENSIONS
Drawout Breakers
Flat Terminal Connections
63
50
100
25
25
30 30
38
8.5
8.5
8.5
2000C
160
106
33
33
20
106
12
25
33
12
12.5
67
43
62
38
67
70
50
6 Holes-14
43
6 Holes-14
17.5
20
6 Holes-14
25 25 25 25
25
33
10.2
6 Slots
8.5 x 9.5
58.4
38
4 Slots
8.5 x 9.5
58.4
38
4 slots
8.5 x 9.5
20
10.2
10.2
58.4
19
12.5
6 Holes- 14
2500S1
3200S1
124
20 max
264
100 min
96.5
26
46
M 10
199.5
74
6
10
5
615
17.5 min
18.9 max.
8.9 min. 18
28
160
467
404
102
Isolated Position
51 Test Position
Service
Position
200 min
20
8 Holes-14
245
217
160
D
25
25
25
25
25
17.5
6 Holes-14
63
28
17.5
42
40
43.5
25
Terminal Connections
4000C
54
Earthing Terminal
67
15
15
Dimensions (mm)
E
711
155.5
200
4000C
4P
913
156.5
200
5000A/6300A
3P
913
187.5
269
5000A/6300A
4P
1182
187.5
269
Terminal for
4000A C
256
3P
368
A
4000C
256
Ratings
356
64.5
50
Terminal Connections
5000C/6300C
12.5
683
50
40
Terminal for
5000/6300A C
Note : All Dimensions are in mm.
30
OVERALL DIMENSIONS
Mounting Details
For Horizontal Mounting of all Draw-out Breakers
For 400A to 3200A C/H/ S1 3P/4P 3200 H2/H1, 4000 H2/H 3P/4P
107.5
367.5
10 Holes-11
40
24
*G
Ratings
Front
24
64.1
20
37
481
10 Holes-11
Type
G
(mm)
800A - 1600A
3P
C/H
280.3
400A - 2000A
3P
S1
280.3
800A - 1600A
4P
C/H
368.3
400A - 2000A
4P
S1
368.3
2000/2500A
3P
C/H
436.3
2000/2500A
4P
C/H
582.3
2500/3200A
3P
S1
436.3
2500/3200A
4P
S1
582.3
3200A
3P
H2/H1
582.3
3200A
4P
H2/H1
790.3
4000A
3P
H2/H
582.3
4000A
4P
H2/H
790.3
5000/6300A
3P
863
5000/6300A
4P
1132
25
Ratings CN-CS
Dimensions
25
3200D/4000C
711
3200D/4000C
913
5000C/6300C
913
5000C/6300C
1182
50
108.5
184.5
305
332
Hinge
199
450
412
224
Hinge
20.5 min
294
5 min
Door Cutout
Note: For 4000A C 3P/4P, 5000C/6300C 3P/4P ACB, A = 81.5
For other Drawout Breakers A = 79.5
31
5.5
Base of
Cradle
Door Drilling
for Bezel Fixing Plan
Bezel
OVERALL DIMENSIONS
Terminals
Horizontal Terminals
Rear Side
80
80
15
221.5
308.5
15
10
80
10
80
1250 - 1600C/H
& 800/1000H
4 Holes-14
12.5
20
160
100
16.5
25
6 Holes-14
25 25 25
15
63
16.5
50
25
12.5
2500C/H
& 2000H
12.5
3 Holes-14
12.5
2 Holes-14
2000C
33 33
800 - 1000C
30
12.5
25
12
43
Vertical Terminals
V
U
4 Holes- T
Top
M N
308.5
221.5
387.5
40
Rear View
Side View
Ratings
400-1250 S1 & 800-1000 C
1600-2000 S1 & 1250-1600 C/H
800-1000 H
2000 C
2500 S1/ C/H
2000 H
3200 S1
10.2
38
20
25
29.2
65
95
10
58.4
20
40
20
25
29.2
65
95
10
80
20
40
20
40
29.2
22.5
14
80
110
15
80
20
40
20
40
33.5
7.5
14
80
110
15
80
30
60
20
40
33.5
7.5
14
105
100
15
120
Note : 1) All Dimensions are in mm. 2) Consult us for other Terminal Orientations.
32
OVERALL DIMENSIONS
Terminals
Vertical Terminals 3200 H2/H1, 4000 H2/H
6 Holes - T
Top
P
R
221.5
308.5
387.5
M NN
S
60.0
Side View
Rear View
The dimensions for 3200 H2/H1 and 4000 H2/H are as under:
Ratings
3200 H2/H1, 4000A H2/H
33
30
50
45
40
29.5
95
14
80
140
15
160
Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.
Registered Office: L&T House, N. M. Marg, Ballard Estate, Mumbai 400 001, INDIA
SP 50437 R5