ITEM

1.
1.1

TECHNICAL SPECIFICATIONS POWER GENERATOR


DESCRIPTION
YES
POWER PLANT
ENGINE
Diesel engine, turbo charged four-stroke, electronic
injection, normal operating speed 1,800 RPM, with
features and capabilities needed to drive the generator.
Electric start system 24 VDC
Maximum consumption: 26 gallons / hour @ 75% load
Electronic engine control
Double fuel filter
Preheater shirts: must be tank type, not accepted
immersion type.

1.2

The equipment should have elements of protection for


the following faults:
Low oil pressure or lubricating
High coolant temperature.
over-speed engine
Automatic shut-off for lack of fuel
Over-charging
Low coolant level
Low Power frequency
GENERATOR
4-pole synchronous generator brushless

1.3

Output voltage: 208/120 with minimum capacity


accessible neutral Standby: 625 Kva / 500Kw maximum
capacity 630 Kva
Harmonic distortion: less than 5% Voltage regulation:
maximum 2% Power factor: 0.8
Operating frequency: 60Hz
Three phases four wires should include PMG
CONTROL BOARD
The control board must meet the following
requirements:
The same brand of the power plant offered
Micro processing system
Possibility to connect a remote PC via Modbus protocol
The power plant must have a control board with the
following information:
Oil pressure
Cooling temperature
Battery voltage
Automatic startup control, shutdown and engine test
frequency
Current for each phase

NO

1.4

2.
2.1
2.1.1

Voltage lines and neutral


Hourmeter
RPM meter
Front panel lighting
Emergency stop button Fault History Emergency stop
button Fault History
OTHERS
The power plant should include the following
elements:
Battery
Pre heater shirts
Muffler low noise
Anti vibration dampers between generator and concrete
base
24v charger / battery 5 Amp
Breaker 2000 amps motorized totalizer
Operation Manuals
As built drawings
SPECIAL ACCOMMODATIONS
FUEL SYSTEM
LINE BETWEEN THE PLANT AND TANK
10 mts carbon steel pipe 3/4 "
The fuel line must meet the following characteristics:

2.1.2

2.1.3

2.1.4

Carbon Steel Pipe ASTM A53 API5L Schull 40 - A106 GB


Compressed sheet gaskets free of asbestos.
ASTM A193 Grade B7 screws.
ASTM A105 WNFR flanges, ANSI B16.5 CLASS 150.
NPT threaded connections
Supported with mechano fixer
LINE BETWEEN SPILLCONTAINER AND TANK
30 meters of carbon steel pipe 2 "
The fuel line must meet the following characteristics:
Carbon Steel Pipe ASTM A53 API5L Schull 40 - A106 GB
Compressed sheet gaskets free of asbestos.
ASTM A193 Grade B7 screws.
ASTM A105 WNFR flanges, ANSI B16.5 CLASS 150.
NPT threaded connections
Supported with mechano fixer
FUEL TANK
Tank with the following features:
Capacity: 500 gallons
Fabricated structural steel ASTM A36 caliber 3mm
Compliance with UL 142 and NFPA 30 standard (not
certified)
Filters required for proper operation.
Fuel Gauge
SPILL CONTAINER

2.1.4
The spill container shall be constructed of galvanized
sheet smooth, high quality 18 gauge also must meet the
following characteristics:
Pedestal type with a socket
Container anti spill.
OPW Universal Connection 2 ".
Metal supports to anchor in floor or wall.
Fully soldier.
Granulated material (Granon # 2) Spill permeability.
Welding according to AWS standards.
Polyester electrostatic painting outdoors.
The spill container must have the following
accessories:
Large handle arch.
Triangular plate with triangular key.
Connection with mini fuel drain valve fast anti spill.
Connecting fuel filling valve 2 "OPW.
The spill container must have the following boundary:

2.2

3.
4.

Flammability diamond.
Rombo health and radioactivity.
UN number (UN 1202)
No Smoking.
No cellphone.
Diesel tank filling cabinet, power plant
EXHAUST SYSTEM
The exhaust system shall consist of:
Thermal insulation for the silencer 8 "mineral wool with
12m exhaust pipe 8 "sheet ASTM A36, together with 4.5
12 meters of thermal insulation exhaust pipe 8 "mineral
25 meters of carbon steel pipe to find out about 8
Specify the optimum delivery time.
Specify the guarantee offered.