Professional Documents
Culture Documents
Application Note
Contents
Contents
1
Symbol
Description
Equipment damage or loss of data possible.
Title
Description
Line Impedance
Line Length
Current
Range
Compliance
Voltage
01.6
02 km/01.5 miles
100 A
50 V
0.88
50 A
100 V
4.040
20 A
250 V
> 16
10 A
500 V
(Eq. 2-1)
or
Vest [V] = meas [A] 0.64 [/mile] 2 lline [miles]
(Eq. 2-2)
Caution: While the grounding switch at the near end of the power line is
open, the area around CP GB1 in the range of 5 m/15 ft and around CP CU1
in the range of 2 m/5 ft is a dangerous zone due to high-voltage and
mechanical hazards. Do not enter the dangerous zone. Keep the
grounding switch open for a time as short as possible.
Caution: If you see or hear anything uncommon in the test equipment, for
example noise of electrical discharge or lightening of surge arrestors,
close the grounding switch before touching the measurement setup.
Figure 2-1:
Wiring the
Measurement Setup
Connection using
grounding sets on site
L3/C L2/B L1/A
8. Ground CPC 100 using a cable of at least 6 mm2 cross-section close to the
position of the operator.
9. Connect CP CU1 with CPC 100 as shown in Figure 2-1: "Wiring the
Measurement Setup" above.
10.Mark the area around CP GB1 in the range of at least 5 m/15 ft and around
CP CU1 in the range of at least 2 m/5 ft as dangerous zone.
11.Open the grounding switch and read the voltmeter on the CP CU1s front
panel from outside of the dangerous zone.
Caution: If the voltmeters reading is
(Eq. 3-1)
Note: Z1 = Z L
the complex ratio of the zero-sequence impedance Z 0 and the positivesequence impedance Z 1 (see Figure 3-1: "Zero-Sequence Impedance
Definition" below)
Z0
k 0 = ----Z1
10
(Eq. 3-2)
RE
-----RL
(Eq. 3-3)
XE
-----XL
(Eq. 3-4)
where R E and X E are the real and imaginary parts respectively of the ground
impedance and R L and X L are the real and imaginary parts respectively of the
line impedance.
Figure 3-1:
Zero-Sequence
Impedance Definition
11
(Eq. 3-5)
The coupling factor can be presented in two versions. The following equation
shows the complex coupling factor kM.
ZM
k M = ------Z1
(Eq. 3-6)
In the two equations below, the real and imaginary components are split.
RM
XM
------- and ------RL
XL
12
(Eq. 3-7)
13
In the course of the k factor test procedure, the following measurements are
performed:
Figure 3-3:
Line-to-Line Impedance
Measurements
Far end
Overhead line
Near end
V1 AC
I AC
CPC 100
EXT. BOOSTER
14
I AC V1 AC I OUT
CP CU1
BOOSTER V SENSE
CP GB1
Far end
Overhead line
Near end
V1 AC
I AC
CPC 100
EXT. BOOSTER
I AC V1 AC I OUT
CP CU1
BOOSTER V SENSE
CP GB1
15
Short the three phases with the delivered three-lead cable as shown in
"Shorting the Phases" on page 17 of the CP CU1 Reference Manual V1.4.
Figure 3-5:
Zero-Sequence
Impedance
Measurement System II is in operation
Far end
Overhead line
Near end
V1 AC
I AC
CPC 100
EXT. BOOSTER
16
I AC V1 AC I OUT
CP CU1
BOOSTER V SENSE
CP GB1
Figure 3-6:
Zero-Sequence
Impedance
Measurement System II is off and
disconnected from the
ground on at least one
end
Far end
Overhead line
Near end
V1 AC
I AC
CPC 100
EXT. BOOSTER
I AC V1 AC I OUT
CP CU1
BOOSTER
V SENSE
CP GB1
17
Figure 3-7:
Zero-Sequence
Impedance
Measurement System II is off and
connected to the ground
on both ends
Far end
Overhead line
Near end
V1 AC
I AC
CPC 100
EXT. BOOSTER
I AC V1 AC I OUT
CP CU1
BOOSTER
V SENSE
CP GB1
18
4. If an overload of CPC 100 occurs, reduce the test current or set a lower
current range and run the test procedure once again.
Lower test currents at the two highest frequencies are recommended.
5. Save the test procedure as a file on CPC 100.
6. Download the test file from CPC 100 to the PC using CPC Explorer.
Load the test file into the Microsoft Excel template.
The measurement results are displayed.
19
Figure 3-8: "Measurement Results" on page 21). The measured overhead line
with the shortest distance between the lines L1 and L3 is shown in Figure
3-9: "Measured Overhead Line" on page 22.
Note: For each line of measurement results there is a separate overload
indication top right on the CPC 100s screen (or in the report) explained
below.
No overload indication means no overload during that step of the measurement
sequence.
Dotted overload indication means that there was an overload during that step of
the measurement sequence but not all the time.
Solid overload indication means a permanent overload during that step of the
measurement sequence.
3.4.1
20
Figure 3-8:
Measurement Results
Click the button "Load XML-File" to open the browse menu to load the desired
data to the template. Click "Print Report" to print the calculated data. Under
"Measurements", the results of the impedances of the nine conducted
21
L2
L1
L3
The L2-E measurement features the lowest X component because the line is
very close to the ground wire. The X component of the L3-E measurement is
decreased by a parallel system taking course close to L3 on the other side of the
22
(Eq. 3-8)
and hence
( Z0 Z1 )
Z E = ---------------------3
(Eq. 3-9)
23