Sl.

No: Room Name


1 Office (if Seeting Available)
2 Office (if Seeting Notavailable)

3
4
5
6
7
8

Lobby, Pre function, Lounge, Waiting/Secretary,


Exhibit open space (Occupied area)
Lobby (Non-Occupied area)
Conference/Meeting room
Restaurant, F & B
Pool, Spa
Gym / Fitness

9 Copy/print:
Heat Gain from copy m/c
Heat Gain from PC
Heat gain from Laptop's 1* 40 W
Total heat gain

10 Pantry
Heat gain from Fridge
Heat gain from water cooler
Heat gain from micro oven
Heat gain from coffee m/c
Heat gain from water heater
Total heat gain
Apply 50% diversity
Expected total heat gain

Equ. Load
150 W/ PC
30 W/Sq m

ASHRAE Fundamentals - Table 8

5 W/Sq m
(Considered as pre function)
Nil
5 W/Sq m
100 W/Sq m

550
150

W
W

700

310
310
1400
440
440
2900

W
W
W
W
W
W

1450

Note: Latent heat for coffee m/c 220 W

a
b
c
d
e

11 Auditorium: ~(to be check)


Heat Gain from PC
Heat gain from projector
Total heat gain

150
500
650

W
W

Auditorium: (AU)
Heat Gain from PC
Heat gain from projector
Total heat gain

150
2500
2650

W
W

12 Laundry (Big)

13 Residential Areas:
Living/Dining/Kitchen
Living/Dining
Kitchen
Bed room
Study

800 W
150 W
650 W
150 W
300 W

Laundry (F1)
UL2 SUITE

Meeting room ( For 8 people)

Nil
800W

Heat gain from CPU 1*100 W


Heat gain from projector 1* 500 W
Heat gain from Laptop's 8* 40 W
Total heat gain
B

=
=
=
=

Meeting room (For morther 10 seating)


Heat gain from CPU 1*100 W
Heat gain from projector 1* 500 W
Heat gain from Laptop's 32* 40 W
Heat gain from Laptop's 10* 40 W (consider 10
people for morther 10 seating)
Total heat gain

=
=
=
=
=

Seminar Room
Heat gain from CPU 1*100 W
Heat gain from projector 1* 500 W
Total heat gain

=
=
=

Class Room Room


Heat gain from CPU 1*100 W
Heat gain from projector 1* 500 W
Total heat gain

=
=
=

Other equipment plant:


14
15
16
17
18
19
20
21
22
23
24
25
26

IT Room/ Server Rm
xxxxxx
Security / ICT Riser Cupbodoard
Server UPS
Server Equipment room
Security / ICT UPS room
Security / ICT equipment / BMS room
Tank + Pump room
Main Telecom Room
Poer factor correction panels
Transformer room
MV Swith gear room
LV Swith room

1 kW/Sq m As per schedule received on 18.06.2013


2 kW
10 kW
150 kW
15 kW
70 kW
15 kW
30 kW
1500 W/panel
15 kW/Transformer
2 kw/RMU/VCB panel
100 w/Sq m

HOT KITCHEN
PREP AREA

300 w/Sq m
100 w/Sq m

ASHRAE Fundamentals - Table 8

(Considered as pre function)

ASHRAE Fundamentals - Table 9


ASHRAE Fundamentals - Table 8

CIBSE Guide A - Table 6.A2


Assumed Equivalent to fridge
CIBSE Guide A - Table 6.A2
CIBSE Guide A - Table 6.A2
Assumed Equivalent to coffee m/c

Consider as 1500 W

as per MEP Assumptions

ASHRAE Fundamentals - Table 8


BENQ Brand

ASHRAE Fundamentals - Table 8


as per Electrical input

100
500
320
920

W
W
W
W

ASHRAE Fundamentals - Table 8


BENQ Brand
ASHRAE Fundamentals - Table 8

100
500
0

W
W
W

ASHRAE Fundamentals - Table 8


BENQ Brand
ASHRAE Fundamentals - Table 8

400
1000

W
W

ASHRAE Fundamentals - Table 8

100
500
600

W
W
W

ASHRAE Fundamentals - Table 8


BENQ Brand

100
500
600

W
W
W

ASHRAE Fundamentals - Table 8


BENQ Brand

As per schedule received on 18.06.2013

U/VCB panel

Sl. No:
1
1
2
3

4
5
6
7

8
9

10
11
12
13
14

a)
b)
c)

Assumptions
Stairs to be Air-conditioned @ 26 deg C (Including Basement stairs) if separate space and consider 12.5 is the supply
General plant rooms & Elect Rooms to be Air-conditioned @ 30 deg C
IT room - Equ. Load: As per schedule sent by them
Lighting Assumed as 10 W/Sq m & ballast multiplier 1.00 (Residential Buildings)
Lighting Assumed as 12 W/Sq m & ballast multiplier 1.00 (Other Buildings)
Main Entrance Lobby: ___?____W/Sq m
Infiltration 0.5 ACH for Residential Buildings & 0.2 ACH for Other Buildings
Toilet to be Air-conditioned @ 26 deg C
Longitude = -51.57 deg E ?
5 lps/sq m Extract considered for Comercial laundry
2 ACH Extract considered for Residential laundry
S1 - Loundry location not available?
Glass Type VG1 - 4 to be comfirm
Tel Rm - 1 Kw/m2
1 people considered for all Electrical/lT/Tel room/Pantry/lift M/C control/PHE plant
room/basement lobby/ Common laundry for HAP calculation only. *(will show in FA
calculation for understanding)
5 deg temperature difference considered for Non A/C area (partition)
Chilled water plant room Equipment load = 25 W/ Sq m
Hot water plant room Equipment load = 5 kW
6 ACH considered for Ablution Extract

DD Stage:
Lift / Elevator control room equipment load = 2000W (Basement)
Basement Garbage room = 100 W for Latent load.
Basement store room = 100 W for Latent load.
Motorized Damper in Roof level

1)ERU Suply and return side (2 Nos)


2)FAHU (1 No)
3)Extract Fan for laundry (1 No)
d)

e)
f)

VFD Concept
ERU
EC (Apartment which serving FA from ERU)
EC (Common kitchen)
FAHU (Common kitchen & Common laundry)
EF (Common laundry & Garbage)
(KITCHEN EXTRACT)
F1 TO F6 VFD&MD
S1&S2 MD
S3 TO S6 NO MOTORISED DAMPER & NO VFD
Roof Stair to be A/C at roof level with separate unit or combined with nearst room
Electrical Room (GF, (typical floor))
Electrical Room ( Basement)
Roof (As per sp assement)
Electrical Room (Residential)
GF, (typical floor)

Basement
Roof (As per sp assement)
g)

h)

i)

Garbage room
Extract Rate
Dry Storage
Kitchen Preparation Area,
Pot Wash
Survery Area
Juice Bar
Pool Area
Pantry
Can wash/Dish wash/Pot wash
Office area occupancy
Pressure drop for Unit selection

j)

Academic Auditorium
AHU
ERU
General
AHU & FAHU
ERU

k)

Lift / Elevator (for No of FCU's & Location as per markup)


Equpment load per lift
Design Temperature
Supply Temperature
Occupancy per Lift

l)

hot kitchen areas


Kitchen preparation areas
Dishwash
Dining

Occupancy for preparation/pot wash area (heat gain 80/80 W)


Pot wash
m)

HOT KITCHEN-FCU
Supply temp
Design temp
HOT KITCHEN-FAHU
Off coil temp
PREPARATION AREA-FCU
Design Temp 27
Supply Temp

(if Room design temp is 15 deg C) Off coil temp is


PREPARATION AREA-FAHU
Off coil temp
n)

Carpark - Janitorial storage Extract rate


U1 MEP room Extract rate
S1 & S2 KITCHEN EXHAUST DUCT
S3 TO S6 KITCHEN EXHAUST DUCT
SYSTEM FOR S1 - S6 & F1 - F4
S1 & S2

ERU only No EC unit, Apartment kitchen extract to be connected to ERU through small shaft proposed in near to kitch
S3 to S6
ERU

1)ERU Suply and return side (2 Nos)


2)FAHU (1 No)
3)Extract Fan for laundry (1 No)

Clarified date
arate space and consider 12.5 is the supply air temp.
6/19/2013
8/3/2013
8/3/2013
8/3/2013

TO BE CONSIDER
YES
YES
NO
NO
NO

2 kW
3 kW
non Residential building
1 kW
Residential

3 kW
Residential
18 deg C

10 ACH
20ACH
15ACH
12ACH
1.5 l/s/sqm
2.4 l/s/sqm
1.5 l/s/sqm
10 ACH
10m2/person

500pa
250pa/250pa

750pa
1050pa/750pa

6500 W
28 deg C
15 deg C
NO
300 w/m2.
100 w/m2
50 w/m2
5 w/m2
2
50 w/m2

12.5 deg C
27 deg C

18/17 deg C

27 deg C
12.5 deg C

from DP tower-1

As per Jai instruction

8.5/8 deg C to 9/8.5 deg C

CP

15/14.5 deg C
7.5 l/s / m2
7.5 l/s / m2

consider as chemical store


consider as chemical store

FD in plan & scheme


NO FD in plan & scheme

hrough small shaft proposed in near to kitchen

Space:
U - Values
External wall
External wall (concrete wall)
Roof
Partition Wall
Floor partition
Glass (Exposed) - for Residential Building
Glass (Exposed) - for Other Building
Glass (partition)
Occupancy gain:
Office/Residential
Pantry/Kitchen/ Dining Areas
Laundry
Fitness center
Auditorium
Other specialized areas

0.28
1.47
0.26
1.48
1.79
2
2.2
5.7

W/ Sq m K
W/ Sq m K
W/ Sq m K
W/ Sq m K
W/ Sq m K
W/ Sq m K
W/ Sq m K
W/ Sq m K

Sensible
75 W
80 W
80 W
210 W
70 W

Lighting:
Residential Buildings
Other Buildings
Gym/Main lobby etc

Latent
55 W
80 W
140 W
315 W
35 W
Discuss

10
12

W/ Sq m
W/ Sq m
Discuss

Infiltration
Residential Buildings
Other Buildings

0.5
0.2

ACH
ACH

System data:

T-stat Setpoints:
T-stat Throttling range
Diversity factor
Design Supply Temp.
Coil Bypass factor
Fan type
Total Static
Fan overall efficiency
Chilled water Delta - T
Safety Factors:
Cooling sensible
Cooling latent
Duct System:
Duct heat gain
Duct leakage

FCU's
Discuss

AHU's
Discuss

1 deg K
12.5 deg C
0.12
Forward curved
200 Pa
60%
7 deg K

1 deg K
100%
12.5 deg C
0.12
Draw thru, Backward curved
1200 Pa
60%
7 deg K

10%
5%

10%
5%

2%
3%

Return Air Plenum:


Wall heat gain to plenum
Roof heat gain to plenum
Lighting heat gain to plenum

10%
70%
30%

(0.4 shading coefficient)


(0.4 shading coefficient)
(0.59 shading coefficient)

(Ballast Multiplier: 1)
(Ballast Multiplier: 1)
Discuss

FCU's
IT Rm (Basement)
Elect Rm & Other Plant Rms, Lift control rm ( BF & RF)
Other Areas
Combined areas( IT, Elect Rm, Corridoretc)
Stair
AHU's
AUDITORIUM

T-stat Setpoints:
22 deg C
30 deg C
24 deg C
24 deg C
26 deg C
24 deg C
23 deg C

Design Supply Temp.


12.5 deg C
15 deg C
12.5 deg C
12.5 deg C
12.5 deg C
Based on 50 % RH
18 deg C