You are on page 1of 383

DEHNguard M ...

CI 275 (FM)
No additional backup fuse required due to arrester
backup fuse integrated in the protection module
Prewired, modular surge arrester for 230/400 V
systems consisting of a base part and plug-in
protection modules
See page 69

DEHNguard M YPV SCI ... FM


Prewired, modular surge arrester for use in photovoltaic systems consisting of a base part and plug-in
protection modules
Combined disconnection and short-circuiting device
with safe electrical isolation in the protection module
prevents fire damage due to d.c. arcs
See page 104

Surge Protection

DEHNguard S CI 275 (FM)


No additional backup fuse required due to arrester
backup fuse integrated in the protection module
Universal surge arrester consisting of a base part
and a plug-in protection module with integrated
backup fuse
See page 75

BITZDUCTOR XTU ML4 (2) BD 0-180


New combined lightning current and surge arrester
with actiVsense technology
Automatically detects the operating voltage of the
wanted signal
Optimally adjusts the voltage protection level to the
signal voltage currently applied
See page 179

BXT ML4 BE C 12
BXT combined lightning current and surge arrester
module with LifeCheck for protecting 2 pairs
Specifically coordinated with applications with diode
circuit at the input, current loops (TTY) and optocoupler inputs
See page 191

BXT ML2 B 180


TYPE 1 lightning current arrester module,
with LifeCheck monitoring system
Two-pole device with direct shield earthing
Suitable for almost all applications

See page 195

BXT ML2 BD HF EX 6
BXT surge arrester module with LifeCheck for use in
hazardous areas
For protecting one pair of intrinsically safe circuits
and RS485 bus systems
Self-capacitance and self-inductance negligibly small
See page 316

DRC LC M3+ Test Device


For fast testing of LifeCheck-equipped SPDs
Handheld device, easy transport and operation
With database function for the documentation
of results

See page 362

Catalogue 2010/2011

DEHNguard M ... 150/320/385/440 (FM)

Coordinated, spark-gap-based lightning current arrester with a discharge capacity up to 25 kA (10/350 s)


No tripping of 32 A gL/gG fuses up to short-circuit
currents of 50 kArms

Prewired, modular surge arrester consisting of a base


part and plug-in protection modules
New models with a max. continuous operating voltage
of 150 V, 320 V, 385 V and 440 V

See page 49

See page 76

DEHNbloc M 1 320 (FM)

DK 25 Feed-Through Terminal

Coordinated, spark-gap-based lightning current arrester with a max. continuous operating voltage of 320 V
and a discharge capacity up to 25 kA (10/350 s)
No tripping of 32 A gL/gG fuses up to short-circuit
currents of 50 kArms

For changing the wiring level


Supports lightning-impulse-current-conform
installation of SPD combinations

See page 46 (47)

See page 145

DEHNguard S VA (FM)

IGA 10 V2 IP54

Universal surge arrester consisting of a base part and


a plug-in protection module
Leakage-current-free series connection of a varistor
and a spark gap in the plug-in protection module

Enclosure for the installation of surge arresters,


tested with lightning impulse currents
Degree of protection of IP54
Sealable

See page 146

See page 112

BXT ML2 BD DL S 15

BITZDUCTOR VT ALD 36

BXT combined lightning current and surge arrester


module with LifeCheck monitoring system
Specifically coordinated with the requirements for
Dupline buses
Terminals for direct and indirect shield earthing

Energy coordinated combined lightning current and


surge arrester
For protecting earth-free d.c. supply systems up to
nominal currents of 4 A
Low voltage protection level, suitable for sensitive
terminal equipment

See page 198

See page 223

NET PRO 10X TC1 RST

DEHNgate DGA LG 7 16 X

Compact and cost-effective protective board with 10


RJ45 ports for the protection of telecommunications
systems
Input equipped with cage spring terminals which can
be removed as a block for easy line measuring
Integrated protection against power crossing

Coaxial surge arrester for HF technology


For multi-frequency applications with d.c. supply system
Optionally available with self-extinguishing gas discharge capsule up to nominal currents of 2.5 A
Maximum transmission and PIM performance

See page 252

See page 276

EG NET PRO 10X 19

DEHNpipe DPI CD HF EXD 5 M

19 (482.6 mm) stainless steel enclosure for installation into distribution cabinets
For up to 5 NET PRO 10X TC1 RST protective boards
Compact in design, protection of up to 50 ports over
a vertical module

Flameproof surge arrester for use in hazardous areas


For protecting measuring circuits and bus systems
Easy installation on field devices with a spare cable
gland

See page 252

See page 309

EG NET PRO 10X 3HE

DEHNpipe DPI CD EXD 230 24 M (N)

Stainless steel enclosure, 3 vertical modules for installation in 19 (482.6 mm) distribution cabinets
For NET PRO 10X TC1 RST protective boards
Ideally suited for small-sized distribution boards

Dual surge protection for 230 V power supply systems


and data interfaces
Easy installation on field devices with a spare cable
gland
Approved for hazardous areas due to flameproof
enclosure

See page 252

See page 310

Pipe Clamp for Use in hazardous Areas


for Diameters from 26.9 mm to 500 mm
For installation in potentially explosive atmospheres
(hazardous zones 1 and 2 as well as 21 and 22)
Tested according to explosion group IIB
Considerably reduced installation time
See page 351

DPRO 230 LAN100


Dual surge protection for power supply systems and
LAN interfaces
Gigabit Ethernet protection (1000 Base-T) with an
elegant design

See page 341

New Products

DEHNbloc Maxi NH00 255

Contents

100 th Anniversary of DEHN.


DEHN Worldwide.
DEHN Safety according to Specification.

Surge protection for


Power Supply Systems
SPDs for low-voltage installations and equipment
Contents

2
8
10

15
17

Surge protection for


Information Technology Systems

153

SPDs for IT installations and equipment


Contents

155

Surge protection for


Power Supply and Information Technology Systems 337
Combined adapters

Lightning Equipotential Bonding


Isolating spark gaps and components

343

Measuring and Test Devices

359

General information
Index

367
372

Valid from 1st April 2010


This catalogue replaces the Surge Protection Main Catalogue published in 2008. We reserve the right to introduce changes
in performance, dimensions and material in the course of technical progress. The figures shown are without obligation.
Misprints, errors and alterations excepted.
Reproduction in any form whatsoever is forbidden without our authorisation.
Publication No. DS570/E/2010

...from a workshop to an
industrial enterprise

100th Anniversary of DEHN.

In our great-grandparents time


electricity was by no means a
matter of course. In the early
20th century sufficient illumination used to be a luxury and a
privilege of the upper class.
Electricity was at best available
in large cities but rarely in rural
areas. The first long-distance
transmission of alternating current took place in 1891.
At that time Oskar von Miller
succeeded in transporting electrical energy for the first time
over a distance of 176 kilometres from Lauffen / Neckar to
Frankfurt / Main via a highvoltage power line (20 kV).
This marked the breakthrough
of the transmission of alternating current and was a significant step forward. But it was
still a long way to go before
the total population was efficiently and reliably supplied
with electricity. It was only in
the early 1920s that electricity
was made accessible to many
small towns for the first time.
During this eventful time, Hans
Dehn founded his electrical
installation company in Nuremberg on 21st January 1910.

1910

1918
Hans Dehn quite early deals with lightning protection. His first patent in this field is granted
in 1918.

On 21st January 1910 the electrician Hans Dehn


laid the foundation for todays company when
registering an electrical installation business in
Nuremberg.
Since electric current had to be transported to the
consumer, building installation and particularly
the construction of overhead lines were the main
fields of activity for DEHN electricians under the
management of Hans Dehn.

1923
1921

Now, many years later, and yet


within a comparatively short
period of time, which was characterised like no other by the
changeful history of Germany
and its people, success and setback, war, reconstruction and
economic crisis, DEHN celebrated its 100th anniversary on
21st January 2010.

Apart from overhead line


construction and building
installation, the installation of lightning protection systems on buildings is an integral part of
our business activities. Hans Dehn also starts to
develop and manufacture lightning protection
and earthing components.

1933

Starting as a small electrical


installation company, DEHN
became a globally operating
family-owned company.
The following pages show
some milestones in the companys history of 100 years.
After the first successful business years, a subsidiary is opened in Neumarkt i.d.Opf. located
about 45 km southeast of Nuremberg to
advance electrification in Upper Palatinate.
2

The company grows year after year and Hans


Dehns sons Walter and Willy become partners.
From now on, the family-owned company operates under the name of DEHN + SHNE. In
1941 the youngest son Richard becomes a
partner.

1939 1945

1952
In the post-war period, business
begins to pick up again:
DEHN + SHNE presents lightning protection and earthing
products at the Hanover trade
fair for the first time. The
increasing market demand
requires a further extension of
the production facilities in
Neumarkt.

The third product field besides


lightning and surge protection safety equipment - is launched.
The ball pin patented for DEHN
+ SHNE in 1953 significantly
influences the state of the art.

The Second World War inevitably slows down


business development. The premises in Nuremberg and Neumarkt are considerably damaged
during the war. Highly motivated, the family
starts reconstruction.
The starting point for post-war activities in
Neumarkt was a warehouse built in the last
months of the war near Hans-Dehn-Strae
where our head office is located today.

1953
DEHN seizes the opportunity to market its
products abroad: Austria becomes the first
exporting country.

1948

1954
The decision to build
a hot dip galvanising
plant in Neumarkt
paves the way for
the extension of the
subsidiary to a production site.

Due to our technical expert


knowledge and entrepreneurial
vision, we are the worlds first
manufacturer to realise that
external lightning protection
has to be combined with internal lightning protection.
The first generation of surge
protective devices is launched.
3

1956
The KS connector is developed to reliably connect
circular conductors to flat
profiles.

1984
The first lightning current carrying surge
arrester enters the market: VGA 280/4, also
known as DEHNventil. It globally becomes a
synonym for a new generation of surge
arresters. DEHN + SHNE captures a leading
position in the sector of surge protection.

1958
The pioneering innovation of the separable
earth rod considerably complements the range
of earthing components and is still in great
demand today.
DEHN + SHNE becomes well-known in the
field of earthing technology.

1986
The success story of surge protection starts
with VM 280, the worlds first arrester with a
modular width of 17.5 mm.

The universal MV clamp from our lightning


protection portfolio is launched.

1988
Foundation of DESITEK A/S in Denmark. It is
the first of todays 10 sales companies in foreign countries.

1970 1980
The product range is continuously complemented, especially in the field of surge protection.
New protective devices such as VA 280 and
BLITZDUCTOR are presented on the market.
Switzerland DEHN + SHNE participates in the
1990 InELVATEC
AG, which has been distributing DEHN
products on the Swiss market for several years.

1991

1996

Development and implementation of the master


plan DEHN 2000.
A milestone in the companys history:
DEHN+SHNE prepares for the future.
National and international success requires comprehensive restructuring, reorganisation and
reorientation.

The new energy-coordinated Yellow/Line


arrester family for the protection of data technology and automation systems, including the
key product BLITZDUCTOR CT, is another milestone of our research and development.

The positive development in Spain requires new


distribution channels. DEHN IBERICA S.A. is founded in co-operation with our long-standing partner.

1992

1993

1998

The new energy-coordinated Red/Line arrester family for low-voltage consumers


installations is launched.
Surge protective devices such as DEHNport and DEHNguard start their story of
success.
Red/Line becomes the general term for all protective devices for use in power
supply systems.

Foundation of DEHN & FILS in Strasbourg, later


renamed in DEHN FRANCE S.a.r.l.

1999
In this year DEHN + SHNE is ready to make
the leap to America. DEHN Inc. is founded.
DEHN POLSKA Sp. z o.o. is founded in Warsaw
to serve the Polish market more efficiently.

In co-operation with our long-time partner on the Italian


market DEHN ITALIA S.p.A. is founded in Bozen.

2000
After almost 50 years on the Austrian market, a
subsidiary is founded, DEHN AUSTRIA GmbH.

1994
To intensify our activities in England DEHN (UK)
Ltd. is founded near Manchester.
5

2002

2004

The successful DEHNventil has a strong successor: The new DEHNventil.


It is a perfect all-in-one solution with complete
devices for all system configurations
(TN-C, TN-S, TT).

50 years of surge protection by


DEHN + SHNE.
In 1954 only few believed in the
success of surge protection.
Today surge protective devices
are an essential part of electrical
installations.

Moreover, the master plan is continued:


Move into new production facilities for surge
protective devices.

2005
DEHN Surge Protection
(Shanghai) Co.Ltd is founded in
Shanghai to service the Chinese
market, which has been worked
by an agent since 1992.

2003
The HVI conductor is a milestone in external
lightning protection.
The separation distance can be easily maintained even in case of challenging architectural
design by using the new, high-voltage-resistant
down conductor.

2006
Safe and functional arresters with a unique design. The new Red/Line and
Yellow/Line product families are presented on international trade fairs in Hanover
and Frankfurt.

Completion of the new administration building


on Hans-Dehn-Strae.

In 2006 DEHN + SHNE was the first company


to obtain VdS certification for surge protective
devices.

2007

2009
Evolution of safety DEHNguard
SCI is a surge protective device
for PV systems which combines
effective surge protection with
the protection of persons and
fire protection.

Completion of a new three-storey production


facility. It stands for a further big step forward
in the scope of the master plan and provides
the company with more space for production.

DEHN + SHNE
proves for the first
time absence of
ignition sparks
when lightning
current flows
through a pipe
clamp. The newly
developed pipe clamp for hazardous areas can
be installed in potentially explosive areas with
little effort.

BLITZDUCTOR XTU is the first


arrester to automatically adjust its
nominal voltage. It does not have
a specified nominal voltage and
can thus be used for any voltage
in the range from 0 to 180 V d.c.
thanks to actiVsense technology.

2008
The new space-saving DEHNrecord MCM XT
condition monitoring system acts like an early
warning system generating a fault message
even in the event of imminent arrester overload.
Thus faults can be identified in advance and
precise status messages support maintenance
staff in diagnosing these faults.

2010
On 21st January 2010 DEHN + SHNE celebrates its 100th anniversary a time
for joy, pride and review.
During our history of 100 years, showing and pioneering new ways in the field of
lightning protection has always been a major concern.
We provide protection against lightning, surges and possible hazards of electricity
a triumvirate of safety.
Lightning protection
Surge protection
Safety equipment
DEHN your safety is our concern.
www.dehn.de

DEHN Worldwide.

Algeria
Argentina
Australia
Austria
Belgium
Belize
Bolivia
Brazil
Bulgaria
Canada
Cap Verde
Chile
China
Columbia
Costa Rica
Croatia
Cuba
Czech Republic
Denmark
El Salvador
Estonia
F.Y.R.O.M
Finland
France
Great Britain
Greece
Guatemala
Honduras
Hungary
Iceland
India
Iran
Ireland
Israel
Italy
Japan
Latvia
Lebanon
Lithuania
Luxembourg
Malaysia
Mauritius
Mexico
8

Netherlands
New Zealand
Nicaragua
Nigeria
Norway
Oman
Pakistan
Panama
Peru
Poland
Portugal
Romania
Russia
Saudi Arabia
Serbia
Singapore
Slovakia
Slovenia
South Africa
Spain
Sri Lanka
Sweden
Switzerland
Syria
Taiwan
Thailand
Turkey
Uganda
United Arab Emirates
USA
Venezuela
We shall be pleased to name you
the right contact person of our
subsidiaries or representatives.
Please contact our Export
Department under
Tel. +49 9181 906 462
Fax +49 9181 906 444
or send an e-mail to
export@dehn.de

DEHN Safety according to Specification.


Lightning Protection Zones Concept
Failures of technical systems and installations are very unpleasant
for the operators. These require faultless operation from the
equipment both under normal conditions and in case of thunderstorms. Loss reports of insurance companies show clearly that
there is a backlog demand both in the private (Fig. 1) and commercial sector (Fig. 2). A comprehensive protection concept
would help to achieve this aim.
The Lightning Protection Zones Concept enables designers, constructors and operators to plan, perform and control protection
measures. All relevant devices, installations and systems are thus
reliably protected and furthermore with economically acceptable
efforts.

22.9 %
Negligence

Fig. 1:

Theft
Vandalism
27.1 %

Fire
4.6 %

Water
5.6 %

15.3 %
Others

0.8 %
Elemental

23.7 %
Surges
(lightning discharges
switching operations)

In case of a close or direct lightning strike, the surges (Fig. 3:


Case 1a) are caused by a voltage drop at the impulse earthing
resistance and the resulting potential rise of the structure towards
the distant surroundings. This is the maximum load on electrical
installations in structures.
The characteristic parameters of flowing impulse currents (peak
value, rate of current rise, load, specific energy) can be described
with the impulse-current wave form 10/350 s (Fig. 4) and are
defined in international, European and national standards as test
currents for components and devices for protection against direct
lightning strokes.
In addition to the voltage drop at the impulse earthing resistance,
surges arise in the electrical building installation and the systems
connected to it and equipment due to the induction effect of the
electromagnetic lightning field (Fig 3: Case 1b).
The power of these induced surges and the resulting impulse currents is considerably lower than the power of a direct lightning
impulse current and is therefore only described with the impulse
current wave 8/20 s (Fig. 4). Components and equipment, which
do not have to conduct currents from direct lightning strokes, are
therefore tested with impulse currents of 8/20 s.

Protection philosophy

Causes of damage to electronic equipment,


Analysis of 7370 damage claims
(Ref.: Wrttemberigsche Versicherung AG)

Distant strokes are lightning strokes from a distance to the object


to be protected, lightning strokes into the medium voltage overhead line network or into its immediate surroundings or lightning
discharges from cloud to cloud (Fig. 3: Cases 2a, 2b and 2c).

Others
41 %

In analogy to induced surges, the effects of distant lightning strokes on the electrical system of a structure are controlled by devices and components, which are designed accordingly for impulse
current wave 8/20 s.
Surges due to switching operations (SEMP) are caused by e.g.
14 %
Unknown

45 %
Lightning/Surges

Fig. 2: Average damage causes during the last years


(Ref.: Gesamtverband der Deutschen Versicherungswirtschaft e.V.)

switching off inductive loads


(e.g. transformers, coils, motors),
ignition and interruption of electric arcs
(e.g. arc welding device),
tripping of fuses.

Sources of interference
Surges arising due to thunderstorms are caused by direct or close
lightning strokes or distant lightning strokes (Fig. 3).
Direct or close lightning strokes are strokes into the lightning protection system of a structure, into its immediate surroundings or
into the conductive systems entering the structure (e.g. low-voltage power supply, telecommunications lines and control lines...).
Due to their amplitudes and energy loads, the arising impulse currents and impulse voltages as well as the corresponding electromagnetic field (LEMP) represent a special risk for the system to
be protected.

10

The effects of switching operations in electrical installations of


structures can also be simulated with impulse currents of wave
form 8/20 s for testing purposes.

Direct/Close lightning strike:


Lightning strike into the external lightning
1 protection system, process framework
(in industrial installations), cables etc.
1a Voltage drop at the impulse earthing
resistance Rst

2b
2a

1b Induced voltage in loops

20 kV

L1
L2
L3
PEN

2c

Distant lightning strike


Strike into medium volta2a ge overhead lines
Surge travelling waves on
2b overhead lines due to
cloud-to-cloud lightning
2c Fields of the lightning
channel

1b

Rst
1a
low voltage power
supply system

IT system

Fig. 3:

Causes of surges in case of lightning discharges

(kA)
Wave form [s]
imax [kA]
Q [As]
W/R [J/]
Standard

100 kA
i

80 kA

10/350
100
50
2.5 106
IEC 62305-1

8/20
5
0.1
0.4 103
EN 61000-4-5

60 kA

50 kA
40 kA
20 kA

2
200 s

Fig. 4:

350 s

Test impulse current for


lightning current arresters

600 s

800 s

1000 s
t

(s)

Test impulse current for


surge arresters

spatial shield
terminal device

downconductor
system

l.v. power
supply system
foundation earth electrode
IT system
steel reinforcement
Lightning equipotential bonding
Lightning current arrester (SPD Type 1)

Lightning equipotential bonding


Lightning current arrester

Lightning electromagnetic pulse

Local equipotential bonding


Surge arrester (SPD Type 2, SPD Type 3)

Local equipotential bonding


Surge arrester

Switching electromagnetic pulse

Fig. 5:

In correspondence with the requirements and loads on


surge protective devices with respect to their installation
sites, these are classified as lightning current arresters,
surge arresters and combined lightning current and
surge arresters.
The highest requirements for the discharge capacity are
made on lightning current and combined lightning current and surge arresters used for the transition from
Lightning Protection Zone 0A to 1 or 0A to 2.
These SPDs must be able to conduct partial lightning
currents (wave form 10/350 s) several times without
destruction in order to prevent the penetration of
destructive partial lightning currents into the electrical
installation of a building.
At the boundary from LPZ 0B to 1 or downstream of the
lightning current arrester at the boundary from LPZ 1 to
2 and higher, surge arresters are used for protection
against surges. Their function is to further reduce both
the residual loads of the upstream protection levels and
limit the induced or own surges.

air-termination system

ventilation

To ensure continuous availability of complex power supply and IT systems even in case of a direct lightning
effect, further measures for surge protection of electrical
and electronic installations are necessary based on a
building lightning protection system. Taking all causes of
surges into consideration is very important. For this purpose, the Lightning Protection Zones Concept of IEC
62305-4 is applied (Fig. 5).
A structure is subdivided in different risk zones. These
zones help to define the necessary devices and components for lightning and surge protection.
Part of an EMC-conform lightning protection zones concept is an external lightning protection system (including
air-termination system, down-conductor system, earthing), equipotential bonding, spatial shielding and surge
protection for the power supply systems and IT systems.
The lightning protection zones have to be defined
according to Table 1.

Lightning
protection zone

EMC-based lightning protection zones concept

The aforementioned lightning and surge protective


measures at the boundaries of the lightning protection
zones apply to both power supply systems and IT systems to the same extent.
All measures described in the EMC-conform Lightning
Protection Zones Concept help to achieve a permanent
system availability of a modern infrastructure.

LEMP protection of structures with electrical and electronic systems


according to IEC 62305-4
Lightning Protection Zone

Description

LPZ 0A Threat by direct lightning strokes, impulse currents up to complete lightning


currents and the entire lightning field.
LPZ 0B Protected against direct lightning strokes. Threat by impulse currents up to
partial lightning currents and the entire lightning field.
LPZ 1

Impulse currents are further limited by current distribution and SPDs situated
at the zone boundaries. The lightning field is mostly attenuated by spatial
shielding.

LPZ 2

Impulse currents are further limited by current distribution and SPDs situated
at the zone boundaries. The lightning field is mostly attenuated by spatial
shielding.

Table 1: Definition of lightning protection zones (LPZ)


11

DEHN Technical Definitions.


Surge Protective Devices (SPD)
Surge protective devices are items of equipment
whose basic components are voltage-controlled
resistors (varistors, suppressor diodes) and/or
spark gaps (discharge paths). The function of
surge protective devices is to protect other electrical equipment and installations against impermissibly high surges and/or to establish the
equipotential bonding.
Surge protective devices are classified
a) according to their application in
Surge protective devices for power supply systems and equipment
for nominal voltage ranges up to 1000 V
according to EN 61643-1:2001 as SPD Types
1/2/3
according to IEC 61643-1:1998-02 as SPDs
Class I / II / III
Surge protective devices for IT systems
and equipment
for protection of modern electronic systems in
telecommunications and signal-processing networks with nominal voltages up to 1000 V a.c.
(root-mean-square value (rms)) and 1500 V
d.c. against indirect and direct effects of lightning strokes and other transients.
according to IEC 61643-21:2000 + Corrigendum:2001, EN 61643-21:2001 and DIN VDE
0845 Part 3-1.
Isolating spark gaps for earth-termination systems or for equipotential bonding
b) according to their impulse current discharge capacity and their protective effect
in
Lightning current arresters /
Coordinated lightning current arresters
for interference due to direct or close lightning strokes for protection of installations
and equipment (for use at the boundaries of
Lightning Protection Zones (LPZ) 0A and 1).
Surge arresters
for distant lightning strokes, switching overvoltages as well as electrostatic discharges
for protection of installations, equipment and
terminal devices (for use at the boundaries
downstream of LPZ 0B).
Combined lightning current and surge
arresters
for interference due to direct or close lightning strokes for protection of installations,
equipment and terminal devices (for use at
the boundaries between LPZ 0A and 1 as well
as 0A and 2).
12

Technical data of surge protective devices


The technical data of surge protective devices
comprise information defining the application
conditions upon
application
(e.g. installation, mains conditions,
temperature)
performance in case of interference
(e.g. impulse current discharge capacity,
follow current extinguishing capability,
voltage protection level, response time)
performance during operation
(e.g. nominal current, attenuation,
insulation resistance)
performance in case of failure
(e.g. backup fuse, disconnection device,
fail-safe)
Categories according to IEC 61643-21: 2001
(DIN VDE 0845 Part 3-1)
For testing the current carrying capability and
voltage limitation under influences of impulses,
a variety of impulse voltages and impulse currents is described in IEC 61643-21:2001 (DIN
VDE 0845 Part 3-1). They are sorted in Table 3
and provide preferred values. In table 2 of IEC
61643-22 (DIN VDE 0845-3-2) the source of
transients is assigned to the different impulse
categories according to the coupling mechanism.
Category C2 includes inductive couplings
(surges), category D1 galvanic couplings (lightning currents). The relevant category is specified
in the technical data.
Cut-off frequency fG
defines the frequency-dependent performance
of an SPD. Cut-off frequencies are frequencies
causing an insertion loss (aE) of 3 dB under certain test conditions (see EN 61643-21:2001).
If no other value is indicated, the frequency
value refers to a 50
system.

DEHN + SHNE surge protective devices


exceed the values indicated in the categories.
The explicit value for the impulse current carrying capability is therefore indicated by the
stated nominal discharge current (8/20 s) and
lightning impulse current (10/350 s).
Combined impulse UOC
is generated by a hybrid generator (1.2/50 s,
8/20 s) with a virtual impedance of 2 . The
open-circuit voltage of this generator is defined as UOC. UOC is especially indicated for
SPDs Type 3.
Degree of protection
The degree of protection (IP) corresponds to
the subdivision into degrees of protection in
accordance with DIN EN 60529 (VDE 0470
Part 1).
Disconnecting time ta
is the time passing until the automatic disconnection from power supply of the electrical
circuit or equipment to be protected in case of
a failure. The disconnecting time is an application-specific value resulting from the intensity
of the fault current flowing and the characteristics of the protective device.

system availability, SPDs should therefore be


subject to systematic tests. LifeCheck allows
for quick and easy SPD testing (refer also to
page 177).
Lightning impulse current Iimp
is a standardised impulse current curve, with a
wave form of 10/350 s. Its parameters (peak
value, charge, specific power) simulate the
loads of natural lightning currents.
Lightning current and combined lightning
current and surge arresters must be capable of
discharging such lightning impulse currents
several times without consequential destruction of the equipment.
Mains-side overcurrent protection /
Backup fuse
is an overcurrent protective device (e.g. fuse or
circuit breaker), which is installed outside of
the surge arrester on the supply side to interrupt the power-frequency follow currents, if
the breaking capacity of the surge protective
device is exceeded.

Disconnection capacity / Follow current


extinguishing capability Ifi
The disconnection capacity is the uninterfered
(prospective) rms value of the mains follow
current, which can automatically be extinguished by the surge protective device at presence of UC. It can be proven in the scope of an
operating duty test according to EN 61643-11.

Max. continuous operating voltage UC


is the root mean square (rms) value of the
maximum voltage, which may be applied to
the correspondingly marked terminals of the
surge protective device during operation. It is
the maximum voltage on the SPD in the
defined non-conductive state, which ensures
that this state is regained after response and
discharge.
The value of UC shall be chosen in accordance
with the nominal voltage of the system to be
protected and the requirements of the installation provisions (IEC 60364-5-534).

Frequency range
characterises the transmission band or letthrough frequency of an SPD according to
the described attenuation characteristics.

Max. discharge current Imax


is the maximum peak value of the impulse current (8/20 s), which can be safely discharged
by the device.

Insertion loss
With an indicated frequency, the insertion loss
of a surge protective device is defined by the
relation of the voltage value at the installation
site before and after installing the SPD.
If no other value is indicated, the value refers
to a 50 system.

Max. transmission capacity


defines the maximum RF capacity which can
be transmitted via a coaxial surge protective
device without interfering with the protective
component.

LifeCheck
Repeated discharges with values beyond the
specifications of the device may overload SPDs
used in IT systems. In order to ensure a high

Nominal discharge current In


is the peak value of an impulse current (wave
form 8/20 s), which the surge protective
device is rated for according to a certain test
programme.

13

Nominal load current (nominal current) IL


is the highest permissible operating current,
which may be permanently conducted via the
correspondingly marked terminals.

Shield attenuation
Relation of the power fed into a coaxial cable to
the power radiated through the cable from the
phase conductor.

Nominal voltage UN
corresponds to the nominal voltage of the system to be protected. The nominal voltage is
often indicated for surge protective devices used
in IT installations for type designation purposes.
For a.c. voltages it is indicated as rms value.

Short-circuit withstand capability


is the value of the prospective power-frequency
short-circuit current controlled by the surge protective device if it is supplied with an upstream
backup fuse.

N-PE surge arresters


are surge protective devices exclusively designed
for installation between the N and PE conductor.
Operating temperature range TU
indicates the range in which the devices can be
used. For devices without self-heating, it is equal
to the ambient temperature range. The temperature rise of devices with self-heating must not
exceed the maximum value indicated.
Protective circuit
Protective circuits are multi-stage, cascaded protective devices. The individual protection stages
can consist of discharge paths, varistors, semiconductor elements. The energy coordination of
the individual protection stages is performed
with decoupling elements.
Protective conductor current IPE
is the current flowing through the PE connection
when the surge protective device is connected to
the maximum continuous operating voltage UC,
corresponding to the installation instructions
and without load-side consumers.
Response time tA
Response times generally characterise the
response performance of the individual protection elements used in surge protective devices
(refer also to page 371).
Depending on the steepness du/dt of the impulse voltage or di/dt of the impulse current, the
response times can change within certain limits.
Return loss
indicates for high-frequency applications, how
many rates of the forward wave are reflected
at the protective device (transition point).
It is a direct measure for rating the adjustment
of the protective device to the surge impedance
of the system.
Series impedance
is the impedance in the direction of the signal
flow between input and output of the SPD.
14

SPD class (Yellow / Line)


All DEHN surge arresters for use in IT systems
are assigned a Yellow/Line SPD Class and are
marked correspondingly with a symbol in the
technical data sheet and on the rating plate
(refer also to page 151).
Thermal disconnector
Surge protective devices for use in power supply
systems, which are supplied with voltage-controlled resistors (varistors), mostly have an integrated disconnection device, which isolates the
surge protective device from mains in case of
overloads and indicates this operating state.
The disconnector reacts to the joule heat
generated by an overloaded varistor and disconnects the surge protective device from mains, if
a certain temperature is exceeded.
The disconnection device is designed to disconnect the overloaded surge protective device in
time to avoid a fire hazard. It is not designed to
ensure the protective measure of protection
against indirect contact.
The function of these thermal disconnectors can
be tested by simulated overloads/ageing of the
SPD.
Voltage protection level Up
The voltage protection level of a surge protective
device is the maximum instantaneous value of
the voltage on the terminals of a surge protective device, determined from the standardised
individual tests for
Lightning impulse sparkover voltage
1.2/50 s (100%)
Response voltage for a steepness of 1 kV/s
Residual voltage for nominal discharge
current Ures
The voltage protection level characterises the
capability of a surge protective device to limit
surges to a residual level. If used in power supply systems, the voltage protection level defines
the location of use by the overvoltage category
according to DIN VDE 0110-1:2003-11 (DIN EN
60664-1, IEC 60664-1). For surge protective
devices designed for protection of IT systems,
the voltage protection level has to be adapted
to the immunity of the equipment to be protected (IEC 61000-4-5: 2001-12).

Surge protection for

POWER SUPPLY SYSTEMS


SPDs for low-voltage installations and equipment

www.dehn.de

15

16

www.dehn.de

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

POWER SUPPLY SYSTEMS

Lightning Current Arresters Type 1

Accessories

CONTENTS

Easy choice

Combined SPDs Type 1

Surge Arresters
Type 3

18

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current Arresters Type 1 N-PE Lightning Current

31

45

63

Arresters Type 1

Surge Arresters Type 2

Surge Arresters Type 3

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

69

119

145
Accessories

Measuring and Test Devices

www.dehn.de

365

17

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS

Easy Choice
Arrangement I

Arrangement II

Arrangement III

SPD Type 3
(Surge arrester)

SPD Type 3
(Surge arrester)

SPD Type 3
(Surge arrester)

1 x DFL M 255
Part No. 924 396
for flush-mounted systems

1 x STC 230
Part No. 924 350
for existing socket outlets

Socket Outlet

L1 L2 L3 N PE

S-Schutz

DEHNflex

Cable leng

1 x DSA 230 LA
for cable ducts

th 5 m

Part No. 924 370

16 A

1 x DG M TNS 275

PE

Part No. 952 400

DG MOD 275

PE

with remote signalling contact:


1 x DG M TNS 275 FM
Part No. 952 405

SPD Type 2
(Surge arrester)

Cable length 15 m

DEHNguard

DG MOD 275

DEHNguard

L3

DG MOD 275

DG MOD 275

DEHNguard

DEHNguard

L2

indication of interference

L1

DG MOD 275

DEHNguard

DG MOD 275

DEHNguard

L3

DG MOD 275

DEHNguard

L2

DG MOD 275

L1

Subdistribution Board

125 A 1

DEHNguard

125 A 1

SPD Type 2
(Surge arrester)

DEHNventil
Directly coordinated to
Red/Line SPDs Type 2 and 3
without additional cable length.

DEHNbloc M
Coordinated to DEHNguard
without additional cable length.

For serial connection please see also page 21

L3

L3

N/PEN

N/PEN

EBB

1 x DB 3 255 H

Part No. 900 120

alt. 3 x DB 1 255 H
1 x MVS 1 6

Part No. 900 222


Part No. 900 815

N/PE(N)

3 x DB M 1 255 FM
1 x MVS 1 6
alt. 3 x DB M 1 255
1 x MVS 1 6

DB M 1 255 FM

DEHNbloc

DB M 1 255 FM

DEHNbloc

DEHNbloc

DB M 1 255 FM

N/PE(N)

N/PE(N)

Part No. 961 125


Part No. 900 815
Part No. 961 120
Part No. 900 815

L2

L2

L3

1 x DV M TNC 255
alt. 1 x DV M TNC 255 FM
also available as
1 x DV M TNS 255
alt. 1 x DV M TNS 255 FM

L3

DV MOD 255

L2

DEHNbloc DB 3 255 H

L1

DEHNventil

L2

L1

DV MOD 255

L1

L/N

DEHNventil

L1

L/N

indication of interference

L/N

PEN

Main Distribution Board

315 A 1

315 A 1

DV MOD 255

315 A 1

SPD Type 1
(Combined lightning current
and surge arrester)

SPD Type 1
(Coordinated lightning
current arrester)

DEHNventil

SPD Type 1
(Lightning current arrester)

Part No. 951 300


Part No. 951 305
Part No. 951 400
Part No. 951 405

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

L1 L2 L3 PEN

TN systems: Office Building Separation of the PEN in the main distribution board
18

www.dehn.de

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


L1 L2 L3 N PE

Easy Choice

Arrangement I

Arrangement II

Arrangement III

SPD Type 3
(Surge arrester)

SPD Type 3
(Surge arrester)

SPD Type 3
(Surge arrester)

Socket Outlet

Combined SPDs
Type 1

Part No. 924 342

th 5 m

PROTECTOR

1 x NSM PRO EW

Cable leng

berspannungsschutz

SFL-Protector

1 x DPRO 230 F
1 x DPRO 230

Part No. 909 240


Part No. 909 230

1 x SFL PRO

Part No. 912 260

16 A

Part No. 952 300

DG MOD 275

DEHNguard

DG MOD 275

DEHNguard

DEHNguard

DG MOD 275

PEN

1 x DG M TNC 275

L3

indication of interference

L2

DG MOD 275

L1

L3

DG MOD 275

DEHNguard

L2

DG MOD 275

DEHNguard

L1

Subdistribution Board

125 A 1

DEHNguard

125 A 1

PEN

with remote signalling contact:


1 x DG M TNC 275 FM
Part No. 952 305

SPD Type 2
(Surge arrester)

SPD Type 2
(Surge arrester)

Cable length 15 m

DEHNbloc M
Coordinated to DEHNguard
without additional cable length.

DEHNventil
Directly coordinated to
Red/Line SPDs Type 2 and 3
without additional cable length.

315 A 1

L3

L3

N/PEN

N/PEN

EBB

1 x DB 3 255 H

Part No. 900 120

alt. 3 x DB 1 255 H
1 x MVS 1 6

Part No. 900 222


Part No. 900 815

DB M 1 255 FM

DEHNbloc

DEHNbloc

N/PE(N)

3 x DB M 1 255 FM
1 x MVS 1 6
alt. 3 x DB M 1 255
1 x MVS 1 6

DB M 1 255 FM

DEHNbloc

DB M 1 255 FM

N/PE(N)

N/PE(N)

Part No. 961 125


Part No. 900 815
Part No. 961 120
Part No. 900 815

L2

L2

L3

1 x DV M TNC 255

L3

DEHNventil

L2

DEHNbloc DB 3 255 H

L1

DV MOD 255

L2

L1

L/N

DEHNventil

L1

L/N

indication of interference

L/N

DV MOD 255

315 A 1

L1

SPD Type 1
(Combined lightning current
and surge arrester)

DEHNventil

315 A 1

SPD Type 1
(Coordinated lightning
current arrester)

DV MOD 255

SPD Type 1
(Lightning current arrester)

PEN

Main Distribution Board

For serial connection please see also page 21

Part No. 951 300

alt. 1 x DV M TNC 255 FM Part No. 951 305

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

L1 L2 L3 PEN

TN systems: Example: Office Building Separation of the PEN in the subdistribution board

www.dehn.de

19

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS

Easy Choice
Arrangement I

L1 L2 L3 N PE

Arrangement II

SPD Type 3
(Surge arrester)

SPD Type 3
(Surge arrester)

25 A also
permissible
without NF 10

3A 1

Arrangement III
25 A 1

SPD Type 3
(Surge arrester)

10 A 1
3 9 4
L1
9 9
IN

NETZFILTER

SPS

SPS
OUT / FM
L

OUT
9 9

N N

1 9 2

1 x SPS PRO

Cable leng

th 5 m

Part No. 912 253

1 x DR M 2P 255 FM
1 x NF 10

L2

L3

Part No. 953 205


Part No. 912 254

DEHNrail

L1

L2

L3

electronic
equipment

DR M 4P 255 FM

DEHNrail

DR M 2P 255 FM

function

indication of interference

99 / IN
DEHN SPD
SPS PRO

1 x DR M 4P 255 FM Part No. 953 405


alt. 1 x DR M 4P 255
Part No. 953 400

Switchgear / Machine

Combined SPDs
Type 1

32 A

3 x V NH00 280

Part No. 900 261

DG MOD 275

DEHNguard

L3

DG MOD 275

V NH
V NH00 280
DEHNguard

V NH
V NH00 280

L2

DG MOD 275

V NH
V NH00 280

DEHNguard

L1

Subdistribution Board

125 A 1

PEN

1 x DG M TNC 275
Part No. 952 300
or with remote signalling contact:
1 x DG M TNC 275 FM
Part No. 952 305

SPD Type 2
(Surge arrester)

SPD Type 2
(Surge arrester)

DEHNventil
Directly coordinated to
Red/Line SPDs Type 2 and 3
without additional cable length.

DEHNbloc M
Coordinated to DEHNguard
without additional cable length.

For serial connection please see also page 21

315 A 1

3 x DBM NH00 255


EBB

L1 L2 L3 PEN

Part No. 900 255

3 x DB M 1 255 FM
1 x MVS 1 6
alt. 3 x DB M 1 255
1 x MVS 1 6

Part No. 961 125


Part No. 900 815
Part No. 961 120
Part No. 900 815

L3

PEN

DV MOD 255

L3

DEHNventil

L2

DV MOD 255

L2

DEHNventil

DEHNbloc

N/PE(N)

L1

indication of interference

N/PE(N)

indication of interference

N/PE(N)

DB M 1 255 FM

DBM NH00 255

DB M 1 255 FM

DEHNbloc Maxi

DBM NH00 255

L1

L/N

DEHNbloc

DEHNbloc Maxi

DBM NH00 255

DEHNbloc

DEHNbloc Maxi

L/N

DB M 1 255 FM

L/N

DV MOD 255

315 A 1

315 A 1

SPD Type 1
(Combined lightning current
and surge arrester)

Main Distribution Board

SPD Type 1
(Coordinated lightning
current arrester)

DEHNventil

SPD Type 1
(Coordinated lightning
current arrester)

1 x DV M TNC 255 FM Part No. 951 305


alt. 1 x DV M TNC 255

Part No. 951 300

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.
2) Without separate backup fuse in case of earth-fault- and short-circuit-proof installation.

TN systems: Example: Industry Separation of the PEN in the subdistribution board


20

www.dehn.de

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


L1 L2 L3 N PE

Easy Choice

SPD Type 3
(Surge arrester)

heating

DR M 2P 255 FM

DEHNrail

1 9 2

Cable leng

th 5 m

1 x DR M 2P 255

PROTECTOR

Heating Control

SPD Type 3
(Surge arrester)

1 x DPRO 230
1 x DPRO 230 F
1 x SFL PRO

Part No. 953 200

Part No. 909 230


Part No. 909 240
Part No. 912 260

Socket Outlet

Combined SPDs
Type 1

KW h

SPD Type 1
(Combined lightning current
and surge arrester)

PEN
L1

DEHNventil ZP
DV ZP TNC 255

L2

1 x DV ZP TNC 255

L3
9

Part No. 900 390

also available for 5-wire systems


1 x DV ZP TT 255
Part No. 900 391

PEN

315 A

Note:
As an alternative, surge arresters can also be
used downstream of meter panels
(e.g. DG M TNC 275
Part No. 952 300),
if no
lightning protection system,
electrical power supply by the service entry mast,
antenna of the roof
is available.

Central Main and


Subdistribution Board

16 A

EBB

L1 L2 L3 PEN

TN systems: Example: Single-family house

SPD Type 3
(Surge arrester)

Heating Control

SPD Type 3
(Surge arrester)

heating

DR M 2P 255 FM

DEHNrail

1 9 2

Cable leng

th 5 m

1 x DR M 2P 255

Socket Outlet

L1 L2 L3 N PE

DEHNflex

Part No. 953 200

1 x DFL M 255

Part No. 924 396

16 A

SPD Type 1
(Combined lightning current
and surge arrester)
L3

25 A

DV MOD NPE
50

DV MOD 255

DEHNventil

DEHNventil

DV MOD 255

DEHNventil

DV MOD 255

L2

DEHNventil

L1

PE

1 x DV M TT 255

Part No. 951 310

Note:
As an alternative, surge arresters can also be
used downstream of meter panels
(e.g. DG M TT 275
Part No. 952 310),
if no
lightning protection system,
electrical power supply by the service entry mast,
antenna of the roof
is available.

Central Main and


Subdistribution Board

RCD

EBB

L1 L2 L3 N

TT system: Example: Single-family house

www.dehn.de

21

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS

Easy Choice
Arrangement I

Arrangement II

Arrangement III

SPD Type 3
(Surge arrester)

SPD Type 3
(Surge arrester)

SPD Type 3
(Surge arrester)

1 x DFL M 255
Part No. 924 396
for flush-mounted systems

1 x STC 230
Part No. 924 350
for existing socket outlets

Socket Outlet

L1 L2 L3 N PE

S-Schutz

DEHNflex

Cable leng

th 5 m

1 x DSA 230 LA
for cable ducts

Part No. 924 370

16 A

RCD

Part No. 952 310

indication of interference

PE

DG MOD NPE

DG MOD 275

DEHNguard

L3

DEHNguard

DEHNguard

L2

DG MOD 275

DEHNguard

DG MOD NPE

DEHNguard

1 x DG M TT 275

L1

DG MOD 275

DG MOD 275

DG MOD 275

L3

DEHNguard

L2

DEHNguard

DEHNguard

L1

Subdistribution Board

125 A 1

DG MOD 275

125 A 1

PE

with remote signalling contact:


1 x DG M TT 275 FM
Part No. 952 315

SPD Type 2
(Surge arrester)

SPD Type 2
(Surge arrester)

DEHNbloc M
Coordinated to DEHNguard
without additional cable length.

Cable length 15 m

DEHNventil
Directly coordinated to
Red/Line SPDs Type 2 and 3
without additional cable length.

SPD Type 1
(Lightning current arrester)
315 A 1

315 A 1

315 A 1

L/N

L3

L/N

L1

L2

L2

L3

L3

DEHNventil

DV MOD NPE 50

DEHNventil

DV MOD 255

DEHNventil

DV MOD 255

DEHNventil

DV MOD 255

DEHNgap

DGP M 255

DB M 1 255

DEHNbloc

N/PEN

N/PE(N)

EBB

L1

DGP BN 255
DK25

Feed-Through
Terminal

N/PEN

DB 3 255 H
DB 1 255 H
DGP BN 255
DK 25
MVS 1 2

PE

DEHNgap B/n

DEHNbloc DB 3 255 H

1x
alt. 3 x
1x
1x
1x

L/N

L3

DB M 1 255

L2

DEHNbloc

L2

DEHNbloc

L1

DB M 1 255

L1

SPD Type 1
(Combined lightning current
and surge arrester)

SPD Type 1
(Coordinated lightning
current arrester)

Part No. 900 120


Part No. 900 222
Part No. 900 132
Part No. 952 699
Part No. 900 617

N/PE(N)

N/PE(N)

PE

Main Distribution Board

For serial connection please see also page 21

indication of interference
3 x DB M 1 255
1 x DGP M 255
1 x MVS 1 8

Part No. 961 120


Part No. 961 101
Part No. 900 611

1 x DV M TT 255 FM
alt. 1 x DV M TT 255

Part No. 951 315


Part No. 951 310

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

L1 L2 L3 N

TT systems: Example: Office Building


22

www.dehn.de

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS

Easy Choice

Arrangement I

L1 L2 L3 N PE

Arrangement II

SPD Type 3
(Surge arrester)

25 A also
permissible
without NF 10

3A 1

Arrangement III

SPD Type 3
(Surge arrester)

SPD Type 3
(Surge arrester)

25 A 1

10 A 1
3 9 4
L1
N

NETZFILTER

SPS

SPS
OUT / FM
L

OUT
9 9

N N

1 9 2

Cable leng

th 5 m

1 x SPS PRO

Part No. 912 253

1 x DR M 2P 255 FM
1 x NF 10

L2

L3

Part No. 953 205


Part No. 912 254

L1

L2

L3

electronic
equipment

DR M 4P 255 FM

9 9
IN

DEHNrail

DR M 2P 255 FM

DEHNrail

function

indication of interference

99 / IN
DEHN SPD
SPS PRO

1 x DR M 4P 255 FM Part No. 953 405


alt. 1 x DR M 4P 255
Part No. 953 400

Switchgear / Machine

Combined SPDs
Type 1

32 A

RCD

1 x DG M TT 275

PE

Part No. 952 310

DG MOD NPE

DEHNguard

DEHNguard

L3

DG MOD 275

DEHNguard

DEHNguard

DG MOD NPE

L2

DG MOD 275

L1

indication of interference

DEHNguard

DEHNguard

DG MOD 275

DEHNguard

L3

DG MOD 275

DEHNguard

L2

DG MOD 275

L1

Subdistribution Board

125 A 1

DG MOD 275

125 A 1

PE

with remote signalling contact:


1 x DG M TT 275 FM
Part No. 952 315

SPD Type 2
(Surge arrester)

SPD Type 2
(Surge arrester)

DEHNventil
Directly coordinated to
Red/Line SPDs Type 2 and 3
without additional cable length.

DEHNbloc M
Coordinated to DEHNguard
without additional cable length.

Cable length 15 m

SPD Type 1
(Coordinated lightning
current arrester)

SPD Type 1
(Combined lightning current
and surge arrester)
315 A 1

N/PE(N)

DEHNventil

L3

DV MOD NPE 50

L3

DEHNventil

L2

DV MOD 255

L2

DEHNventil

L1

DEHNventil

DEHNgap

DGP M 255 FM

DB M 1 255 FM

N/PE(N)

L1

indication of interference

N/PE(N)

PE

DEHNbloc

DEHNgap B NH
DGP B NH00 N 255

DEHNbloc

DEHNbloc NH
DB NH00 255 H

L/N

DB M 1 255 FM

DEHNbloc NH
DB NH00 255 H

DEHNbloc

DEHNbloc NH
DB NH00 255 H

L/N

DB M 1 255 FM

L/N

DV MOD 255

315 A 1

315 A 1

DV MOD 255

SPD Type 1
(Lightning current arrester)

PE

Main Distribution Board

For serial connection please see also page 21

indication of interference
EBB

3 x DB NH00 255 H
1 x DGP B NH00 N 255

Part No. 900 273


Part No. 900 269

3 x DB M 1 255 FM
1 x DGP M 255 FM
1 x MVS 1 8

Part No. 961 125


Part No. 961 105
Part No. 900 611

1 x DV M TT 255 FM
alt. 1 x DV M TT 255

Part No. 951 315


Part No. 951 310

1) Only required, if a fuse of the same or a lower nominal value is not already provided in the upstream power supply.

L1 L2 L3 N

TT systems: Example: Industry

www.dehn.de

23

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

POWER SUPPLY SYSTEMS

Easy Choice
PE

SPD Type 2
(Surge arrester)

125 A

indication of interference

DG S 440 FM

DEHNguard

DG S 440 FM

DEHNguard

DG S 440 FM

DEHNguard

100 A aM

3 x DG S 440 FM
1 x MVS 1 3

Part No. 952 095


Part No. 900 615

DEHNguard

DEHNguard

DEHNguard

DG 1000 FM

DG 1000 FM

DG 1000 FM

3 x DG 1000 FM
1 x EB DG 1000 1 3

SPD Type 1
(Coordinated lightning
current arrester)

Part No. 950 112


Part No. 900 411

SPD Type 1
(Coordinated lightning
current arrester)

250 A

250 A

3 x DBM 1 440 FM
1 x EB DG 1000 1 3

Part No. 961 145


Part No. 900 411

alt. 3 x DBM 1 440


1 x EB DG 1000 1 3

Part No. 961 140


Part No. 900 411

L1 L2 L3 PEN

TN systems: Industry TN-C 400/690 V

N/PEN

EBB

L1 L2 L3

3 x DBM 1 760 FM
1 x EB DG 1000 1 3

N/PEN

DEHNbloc
Maxi

DBM 1 760 FM

DEHNbloc
Maxi

N/PEN

indication of interference

N/PEN

DEHNbloc
Maxi

440 FM
DBM 1 760

DEHNbloc
Maxi

DBM 1 440 FM

N/PEN

indication of interference

N/PEN

DEHNbloc
Maxi

DEHNbloc
Maxi

DBM 1 440 FM

24

indication of interference

L1 L2 L3

SPD Type 2
(Surge arrester)

DBM 1 760 FM

L1 L2 L3 PEN

EBB

Accessories

DBM 1 760 FM

Combined SPDs
Type 1

Part No. 961 175


Part No. 900 411

PE

IT systems: Industry IT 690 V, without integrated neutral conductor

www.dehn.de

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS

Easy Choice
L1 L2 L3 N PE

L1 L2 L3 N PE

PE

with remote signalling contact:


1 x DG M TT CI 275 FM Part No. 952 327

SPD Type 1
(Coordinated lightning
current arrester)

alt. 3 x DB M 1 255
1 x MVS 1 6

315 A 1

N/PE(N)

N/PE(N)

N/PE(N)

DEHNgap

DGP M 255

DB M 1 255

PE

DEHNbloc

DB M 1 255

L/N

DEHNbloc

L/N

DEHNbloc

L/N

DB M 1 255

DB M 1 255 FM

N/PE(N)

indication of interference

N/PE(N)

DEHNbloc

DB M 1 255 FM

L/N

DEHNbloc

DEHNbloc

DB M 1 255 FM

L/N

Main Distribution Board

SPD Type 1
(Coordinated lightning
current arrester)

Subdistribution Board

DG MOD NPE

DEHNguard

DEHNguard

DG MOD CI
275

DG MOD CI
275

DEHNguard

DEHNbloc M
Coordinated to DEHNguard
without additional cable length.

3 x DB M 1 255 FM
1 x MVS 1 6

www.dehn.de

DEHNbloc M
Coordinated to DEHNguard
without additional cable length.

N/PE(N)

TN systems

L3

SPD Type 2
(Surge arrester)

L/N

L1 L2 L3 PEN
IK 25 kA

L2

SPD Type 2
(Surge arrester)

315 A 1

EBB

L1

Main Distribution Board

with remote signalling contact:


1 x DG M TNS CI 275 FM Part No. 952 406

1 x DFL M 255
Part No. 924 396
for flush-mounted systems

RCD

indication of interference

PE

DEHNflex

Subdistribution Board

DG MOD 275

indication of interference

DEHNguard

DG MOD CI
275

L3

DEHNguard

DEHNguard

DG MOD CI
275

L2

DG MOD CI
275

DEHNguard

L1

th 5 m

16 A

1 x DFL M 255
Part No. 924 396
for flush-mounted systems

16 A

Cable leng

DEHNguard

th 5 m

DG MOD CI
275

Socket Outlet

DEHNflex

Cable leng

Socket Outlet

SPD Type 3
(Surge arrester)

SPD Type 3
(Surge arrester)

Part No. 961 125


Part No. 900 815
EBB

Part No. 961 120


Part No. 900 815

1) Only required, if a fuse of the same or a


lower nominal value is not already
provided in the upstream power supply.

L1 L2 L3 N
IK 25 kA

3 x DB M 1 255
1 x DGP M 255
1 x MVS 1 8

Part No. 961 120


Part No. 961 101
Part No. 900 611

1) Only required, if a fuse of the same or a


lower nominal value is not already
provided in the upstream power supply.

TT systems

25

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

Easy Choice of SPDs for Use in Photovoltaic Systems


d.c. arresters
1

Modular surge arrester as complete unit for use in


photovoltaic systems
DG M YPV SCI 600
DG M YPV SCI 600 FM

Part No. 952 511


Part No. 952 516

DG M YPV SCI 1000


DG M YPV SCI 1000 FM

Part No. 952 510


Part No. 952 515

DG M YPV SCI 1200


DG M YPV SCI 1200 FM

Part No. 952 512


Part No. 952 517

max. PV voltage

unearthed / functionally earthed

up to 600 V d.c.

Part No. 952 511 (952 516)

up to 1000 V d.c.

Part No. 952 510 (952 515)

up to 1200 V d.c.

Part No. 952 512 (952 517)

Type 1 combined lightning current


and surge arrester for use in photovoltaic systems

DLM PV 1000 Part No. 900 330

a.c. arresters
2

Modular surge arrester for use in single-phase


230 V TN power supply systems
DG M TN 275
DG M TN 275 FM

26

Part No. 952 200


Part No. 952 205

Modular surge arrester for use in single-phase


230 V TT power supply systems
DG M TT 2P 275
DG M TT 2P 275 FM

Part No. 952 110


Part No. 952 115

Multipole combined lightning current and surge


arrester for use in three-phase power supply systems
DV M TNC 255
DV M TNC 255 FM

Part No. 951 300


Part No. 951 305

DV M TNS 255
DV M TNS 255 FM

Part No. 951 400


Part No. 951 405

DV M TT 255
DV M TT 255 FM

Part No. 951 310


Part No. 951 315

Modular combined lightning current and surge


arrester for use in single-phase TN power supply
systems
DV M TN 255
DV M TN 255 FM

Part No. 951 200


Part No. 951 205

Modular combined lightning current and surge


arrester for use in single-phase TT and TN-S power
supply systems
DV M TT 2P 255
DV M TT 2P 255 FM

Part No. 951 110


Part No. 951 115

Modular multipole surge arrester for use in threephase power supply systems
DG M TNC 275
DG M TNC 275 FM

Part No. 952 300


Part No. 952 305

DG M TNS 275
DG M TNS 275 FM

Part No. 952 400


Part No. 952 405

DG M TT 275
DG M TT 275 FM

Part No. 952 310


Part No. 952 315

www.dehn.de

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

Easy Choice of SPDs for Use in Photovoltaic Systems


PV system on a building with external lightning protection system.
a) if the separation distance s is observed

separation
distance OK

b) if the separation distance s is not observed

<s

separation
distance
not OK

<s

<s
s

6 2
a.c.
output

~
=

meter/
distribution board
power supply

3 4

5
~

a.c.
output

d.c. input

d.c. input

meter/
distribution board

kWh kWh

power supply

SEB

kWh kWh

SEB

PV system on a building without external lightning protection system.


c)

6 2
~

a.c.
output

meter/
distribution board
power supply

d.c. input

6
kWh kWh

SEB

Equipotential bonding
For lightning and surge protection reasons, it is strongly recommended to
connect the PV frame as follows to the equipotential bonding system:
Defined connection with at least 16 mm2 copper at the PV frame (b).
Defined connection with at least 6 mm2 copper at the PV frame
(a + c).
Electrically conductive connection of the PV frames has to be ensured.
The earth conductor is connected to the main earthing busbar of the
building on ground level.
The earth conductor has to be installed in parallel and in close proximity to the d.c. and a.c. cables / lines and accessory.

www.dehn.de

27

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS

Power Supply Systems Worldwide

International system configurations* according to IEC 60364-1 (DIN VDE 0100-100)


TN-S system

TN-C system

L1
L2
L3

L1
L2
L3
PE
N

PEN

RB

RB

TN-C system 230 / 400 V

TN-C-S system 230 / 400 V

L1
L2
L3

L1
L2
L3

N
PE

L1
L2
L3

PE

PE
RB

RB

TN-S system 230 / 400 V

RA

RA

TT system 230 / 400 V

IT system 230 V, 400 V, 500 V, 690 V

Further system configurations* used worldwide

L1

N
G

N
L2
G

single-phase; 3 conductors
(1 Ph, 2 W + G)
110 V
120 V
220 V
240 V

single-phase; 4 conductors
Split Phase or Edison
(1 Ph, 3 W + G)
120 V / 240 V

L1

L1

L2
L3
G

L2
L3
G

L1

L1

N
L2
L3
G

L2
L3
G

L2
L3
N
G

3-phase; 4 conductors

3-phase; 5 conductors

(3 Ph Y, 3 W + G)
480 V

(3 Ph Y, 4 W + G)
120 V / 208 V
277 V / 480 V

100 V
N

single-phase; 2 conductors

single-phase; 2 conductors

(1 Ph, 2 W)
200 V

(1 Ph, 2 W)
100 V

R
200 V

200 V

200 V

S
T

100 V

200 V

single-phase; 3 conductors
(1 Ph, 3 W)
100 V / 200 V

R
100 V

R
200 V

3-phase; 5 conductors
Delta Highleg
(3 Ph , 4 W + G)
120 V / 240 V

200 V

3-phase; 4 conductors
Delta Grounded Corner
(3 Ph , 3 W + G)
240 V
480 V

3-phase; 4 conductors
Delta Ungrounded
(3 Ph , 3 W + G)
240 V
480 V

L1

3-phase; 3 conductors
(3 Ph, 3 W)
200 V

200 V

200 V

100 V

N
100 V

3-phase;
single-phase;
+
3 conductors
3 conductors
100 V / 200 V; 200 V

* System according to earth connection (according to DIN VDE 0100-100)


28

www.dehn.de

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

POWER SUPPLY SYSTEMS


Discontinued Products
Part No.
Type
Combined SPDs Type 1
900 370
DV 2P TT 255
900 371

DV 2P TN 255

900 373

DV TNC 255

900 374

DV TNS 255

900 375

DV TT 255

Cross-reference

Alternatives
Part No.
Type

951 110
951 115
951 200
951 205
951 300
951 305
951 400
951 405
951 310
951 315

DV M TT 2P 255
DV M TT 2P 255 FM
DV M TN 255
DV M TN 255 FM
DV M TNC 255
DV M TNC 255 FM
DV M TNS 255
DV M TNS 255 FM
DV M TT 255
DV M TT 255 FM

Coordinated Lightning Current Arresters Type 1


900 015
DBM 1 135
961 110
DB M 1 150
961 115
DB M 1 150 FM
900 016
DBM 1 320
961 130
DB M 1 320
961 135
DB M 1 320 FM
900 025
DBM 1 255
961 120
DB M 1 255
900 026
DBM 1 255 L
961 125
DB M 1 255 FM
900 044
DBM 440
961 140
DBM 1 440
961 145
DBM 1 440 FM
900 055
DGPM 255
961 101
DGP M 255
961 105
DGP M 255 FM
Lightning Current Arresters Type 1
900 100
DP 255
961 120
900 222
900 101
DP 440
961 140
900 159
900 110
DB 3 255
900 120
900 111
DB 1 255
900 222
900 260
DB NH00 255
900 273
Surge Arresters Type 2
900 133
DGP C T 255

www.dehn.de

900 265
900 266
900 506
900 507
900 508
900 509
900 510
900 516
900 517

V NH1 3
VA NH1 3
DG TN 230
DG TN 230 FM
DG TT 230
DG TT 230 FM
DG TNC 230 400
DG IT 500
DG Y PV 1000

900 520
900 530
900 540
900 546
900 547

DG TT 230 400
DG TNS 230 400
DG TNC 230 400 FM
DG IT 500 FM
DG Y PV 1000 FM

900 550
900 560
900 600
900 601
900 602
900 603
900 604
900 605
900 607
900 620
900 621
900 622
900 623
900 624

DG TT 230 400 FM
DG TNS 230 400 FM
DG 275
DG 600
DG 385
DG 150
DG 75
DG 320
DG 440
DG 275 FM
DG 600 FM
DG 385 FM
DG 150 FM
DG 75 FM

952 030
952 035
900 270
900 271
952 200
952 205
952 110
952 115
952 300
952 302
952 510
952 511
2x 950 500
952 310
952 400
952 305
952 307
952 515
952 516
2x 950 505
952 315
952 405
952 070
952 076
952 074
952 072
952 071
952 073
952 075
952 090
952 096
952 094
952 092
952 091

Accessories

DB M 1 255
DB 1 255 H
DBM 1 440
DB 1 440
DB 3 255 H
DB 1 255 H
DB NH00 255 H
DGP C S
DGP C S FM
V NH1 280
VA NH1 280
DG M TN 275
DG M TN 275 FM
DG M TT 2P 275
DG M TT 2P 275 FM
DG M TNC 275
DG M WE 600
DG M YPV SCI 1000
DG M YPV SCI 600
2x DG PV 500 SCP
DG M TT 275
DG M TNS 275
DG M TNC 275 FM
DG M WE 600 FM
DG M YPV SCI 1000 FM
DG M YPV SCI 600 FM
2x DG PV 500 SCP FM
DG M TT 275 FM
DG M TNS 275 FM
DG S 275
DG S 600
DG S 385
DG S 150
DG S 75
DG S 320
DG S 440
DG S 275 FM
DG S 600 FM
DG S 385 FM
DG S 150 FM
DG S 75 FM

or
or
or
or
or

or
or

or
or

or
or

or

Discontinued Products
Part No.
Type

Alternatives
Part No.
Type

900 625
900 627
900 641
900 650
900 651
900 652
900 653
900 654
900 655
900 659
900 667
900 680
900 681
900 682
900 683
900 684
900 685
900 689
900 691
900 692
901 000

DG 320 FM
DG 440 FM
DG T 385
DG T 275
DG T 600
DG T 320
DG T 150
DG T 75
DG T 440
DG T 275 VA
DG T 75 VA
DG T 275 FM
DG T 600 FM
DG T 320 FM
DG T 150 FM
DG T 75 FM
DG T 440 FM
DG T 275 VA FM
DG T 385 FM
DG T 75 VA FM
VAV 1000

DG S 320 FM
DG S 440 FM
DG S 385
DG S 275
DG S 600
DG S 320
DG S 150
DG S 75
DG S 440
DG S 275 VA
DG S 75 VA
DG S 275 FM
DG S 600 FM
DG S 320 FM
DG S 150 FM
DG S 75 FM
DG S 440 FM
DG S 275 VA FM
DG S 385 FM
DG S 75 VA FM
DG 1000
DG 1000 FM

902 375
902 376
902 385
902 386
950 220
950 225

VA NH00 280 3 IG FM
VA NH00 280 4 IG FM
VA NH00 280 3 IG
VA NH00 280 4 IG
DG T 48
DG T 48 FM

952 093
952 095
952 074
952 070
952 076
952 073
952 072
952 071
952 075
952 082
952 080
952 090
952 096
952 093
952 092
952 091
952 095
952 087
952 094
952 085
950 102
950 112

952 078
952 098
953 205
953 200
953 209
953 204
953 208
953 203
953 207
953 202
953 206
953 201
953 405
953 400
909 240
909 230

DR M 2P 255 FM
DR M 2P 255
DR M 2P 150 FM
DR M 2P 150
DR M 2P 75 FM
DR M 2P 75
DR M 2P 60 FM
DR M 2P 60
DR M 2P 30 FM
DR M 2P 30
DR M 4P 255 FM
DR M 4P 255
DPRO 230 F
DPRO 230

Mains Connection Boxes


900 964
NAK 63A 4
900 965
NAK 63A 3
900 966
NAK 35A 4
900 967
NAK 35A 3+1
900 968
NAK 35A 3
900 969
NAK 63A 3+1
902 492
NAK TAB 3
902 493
NAK TAB 3+1
902 494
NAK TAB 4

951 400
951 300
951 400
951 310
951 300
951 310
900 390
900 391
900 391

DV M TNS 255
DV M TNC 255
DV M TNS 255
DV M TT 255
DV M TNC 255
DV M TT 255
DV ZP TNC 255
DV ZP TT 255
DV ZP TT 255

Accessories
900 309
IGA 10 IP54
902 480
IGA 10 IP55
900 121
DBR 35
900 122
DBR 63
900 699
DK 35

902 315
902 315

952 699

IGA 10 V2 IP54
IGA 10 V2 IP54

DK 25

Isolating Spark Gaps


923 070
EXFS C1
923 071
EXFS C1 KU

923 100
923 101

EXFS 100
EXFS 100 KU

Surge Arresters Type 3


901 100
DR 230 FML
901 101

DR 120 FML

901 102

DR 60 FML

901 103

DR 48 FML

901 104

DR 24 FML

901 130

DR 230 3N FML

909 820
909 821

SF PRO
S PRO

or

DG S 48
DG S 48 FM
or
or
or
or
or
or

29

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS

30

www.dehn.de

Lightning Current
Arresters Type 1

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNventil modular
Multipole modular combined lightning current and
surge arrester
Prewired spark-gap-based combined lightning
current and surge arrester, consisting of a base
part and plug-in protection modules
Maximum system availability due to RADAX
Flow follow current limitation
No tripping of 20 A gL/gG fuses up to short-circuit currents of 50 kArms
Discharge capacity up to 100 kA (10/350 s)
Protection of terminal devices
Operating state/fault indication by indicator
flag in the inspection window
Easy replacement of protection modules without tools due to module locking system with
module release button

For protecting low-voltage consumers installations against surges and


even direct lightning strikes. For installation in conformity with the lightning protection zones concept at the boundaries from 0A 2.

Vibration- and shock-tested according to EN


60068-2

DEHNventil M TNC 255: Modular combined lightning current and surge arrester for use in TN-C systems
DEHNventil M TNS 255: Modular combined lightning current and surge arrester for use in TN-S systems
DEHNventil M TT 255:
Modular combined lightning current and surge arrester for use in TT and TN-S systems
(3+1 circuit)
DEHNventil M TN 255: Modular combined lightning current and surge arrester for use in single-phase TN systems
DEHNventil M TT 2P 255: Modular combined lightning current and surge arrester for use in single-phase TT and TN systems
(1+1 circuit)
DEHNventil M ... FM:
With remote signalling contact for monitoring device (floating changeover contact)
With their functional Red/Line design, the devices of the modular
DEHNventil family combine safety and innovation. Designed for all-inone installation, the SPDs integrate lightning equipotential bonding and
protection against surges in a single device. This function is particularly of
advantage in compact electrical installations. The design of the SPDs
according to energy coordination criteria even allows protection of terminal devices if they are close to the consumers ( ) 5 m). With their lightning current discharge capacity up to 100 000 A, the SPDs ensure high
availability of the electrical installation to be protected. Even for expanded electrical installations, the modular DEHNventil devices offer various
application possibilities. Red/Line surge arresters installed at the boundaries of the individual lightning protection zones are already energy-coordinated with DEHNventil devices. By using encapsulated creepage discharge spark gaps, combined with a compact design, DEHNventil units
are well suited for use in switchgear installations or distribution boards.
A special feature of the new modular DEHNventil family is its functional
design. The module release button is a key element. It ensures reliable fixation of the protection module to keep the safe connection to the base
part even in case of maximum loads. If protection modules have to be
replaced, the module is released without tools and can be removed easily. The devices incorporate double terminals which are suitable for all conductors, allowing series connection in a space- and cost-effective way
according to IEC 60364-5-53 requirements for nominal currents up to
125 A. For connecting further DIN rail mounted devices, busbars of type

www.dehn.de

MVS 3 8 6 and MVS 4 11 8 can be


used. The right DEHNventil devices
can be easily chosen according to
the system configuration of the
low-voltage consumers installation and type designation of the
device.
The patented RADAX Flow technology ensures follow current limitation and extinction as well as maximum system availability of electrical installations to be protected. Even in case of short-circuit currents as
high as 50 kArms, mains follow currents are reduced in such a way that
there is a selectivity to lower fuse values, i.e. upstream fuses will not trip
due to arising mains follow currents.
The operating state/fault indication of each protective circuit immediately provides information on the operating state of the surge arrester even
if no operating current is present. Apart from the standard green and red
indicator, DEHNventil M ... FM devices feature a three-pole terminal for
remote signalling. With their floating changeover contact, the remote signal can be used as a break or make contact according to the particular circuit concept.

31

Combined SPDs Type 1

Combined SPDs
Type 1

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNventil modular
DEHNventil M TNC (FM)

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1

Combined SPDs Type 1

L1

L1

L2

L2

L3

951 300
TNC 255
951 305
TNC 255 FM

L3
DV M TNC 255
951 300
DV M TNC 255 FM
951 305

12
11
14

PEN

Basic circuit diagram DV M TNC 255 FM

Dimension drawing DV M TNC 255 (FM)

DV M TNC 255 (FM): Modular combined lightning current and surge arrester for protecting TN-C
systems against surges
DV M TNC 255
SPD according to EN 61643-11 / ... IEC 61643-1
Type 1 / Class I
Energy-coordinated protection effect with
regard to the terminal equipment
Type 1 + Type 2
Energy-coordinated protection effect with
regard to the terminal equipment ( ) 5m)
Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN
230 / 400 V
Max. continuous operating a.c. voltage UC
255 V
Lightning impulse current (10/350 s) [L1+L2+L3-PEN] Itotal
75 kA
Lightning impulse current (10/350 s) [L-PEN] Iimp
25 kA
Nominal discharge current (8/20 s) In
25 / 75 kA
Voltage protection level UP
) 1.5 kV
Follow current extinguishing capability a.c. Ifi
50 kArms
Follow current limitation/Selectivity
no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA
) 100 ns
Max. backup fuse (L) up to IK = 50 kArms
315 A gL/gG
Max. backup fuse (L) for IK > 50 kArms
200 A gL/gG
Max. backup fuse (L-L)
125 A gL/gG
Temporary overvoltage (TOV) UT
440 V / 5 sec.
TOV characteristics
withstand
Operating temperature range [parallel]/[continuity] TU
-40C...+80C / -40C...+60C
Operating state/fault indication
green / red
Cross-sectional area (L1, L1, L2, L2, L3, L3, PEN, 9) min.
10 mm2 solid/flexible
Cross-sectional area (L1, L2, L3, PEN) max.
50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L1, L2, L3, 9) max.
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

DV M TNC 255 FM
Type 1 / Class I
Type 1 + Type 2
Type 1 + Type 2 + Type 3
230 / 400 V
255 V
75 kA
25 kA
25 / 75 kA
) 1.5 kV
50 kArms
no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
withstand
-40C...+80C / -40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
6 mods., DIN 43880
KEMA, VDE, UL, VdS

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
6 mods., DIN 43880
KEMA, VDE, UL, VdS
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DV M TNC 255
951 300
1 pc(s).

DV M TNC 255 FM
951 305
1 pc(s).

Accessory part for DEHNventil modular


951 001
255

DV MOD 255
951 001

32

DV MOD

Spark-gap-based protection module


Type
DV MOD 255

PU
pc(s).
1

Part
No.
951 001

www.dehn.de

DV M
DV M

Combined SPDs
Type 1

951 400
255
951 405
255 FM

DV M TNS
DV M TNS

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNventil modular
DEHNventil M TNS (FM)

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1
L1

L2

L2

L3

L3

Combined SPDs Type 1

L1
DV M TNS 255
951 400
DV M TNS 255 FM
951 405

12
11
14

PE

Dimension drawing DV M TNS 255 (FM)

Basic circuit diagram DV M TNS 255 FM

DV M TNS 255 (FM): Modular combined lightning current and surge arrester for protecting TN-S
systems against surges
DV M TNS 255

DV M TNS 255 FM

SPD according to EN 61643-11 / ... IEC 61643-1


Type 1 / Class I
Energy-coordinated protection effect with
regard to the terminal equipment
Type 1 + Type 2
Energy-coordinated protection effect with
regard to the terminal equipment ( ) 5m)
Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN
230 / 400 V
Max. continuous operating a.c. voltage UC
255 V
Lightning impulse current (10/350 s) [L1+L2+L3+N-PE] Itotal
100 kA
Lightning impulse current (10/350 s) [L, N-PE] Iimp
25 kA
Nominal discharge current (8/20 s) In
25 / 100 kA
Voltage protection level [L-PE]/[N-PE] UP
) 1.5 kV / ) 1.5 kV
Follow current extinguishing capability a.c. Ifi
50 kArms
Follow current limitation/Selectivity
no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA
) 100 ns
Max. backup fuse (L) up to IK = 50 kArms
315 A gL/gG
Max. backup fuse (L) for IK > 50 kArms
200 A gL/gG
Max. backup fuse (L-L)
125 A gL/gG
Temporary overvoltage (TOV) [L-N] UT
440 V / 5 sec.
TOV characteristics
withstand
Operating temperature range [parallel]/[continuity] TU
-40C...+80C / -40C...+60C
Operating state/fault indication
green / red
Cross-sectional area (L1, L1, L2, L2, L3, L3, N, N, PE, 9) min.
10 mm2 solid/flexible
Cross-sectional area (L1, L2, L3, N, PE) max.
50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L1, L2, L3, N, 9) max.
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

Type 1 / Class I
Type 1 + Type 2
Type 1 + Type 2 + Type 3
230 / 400 V
255 V
100 kA
25 kA
25 / 100 kA
) 1.5 kV / ) 1.5 kV
50 kArms
no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
withstand
-40C...+80C / -40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
8 mods., DIN 43880
KEMA, VDE, UL, VdS

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
8 mods., DIN 43880
KEMA, VDE, UL, VdS
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DV M TNS 255
951 400
1 pc(s).

DV M TNS 255 FM
951 405
1 pc(s).

Accessory part for DEHNventil modular


Spark-gap-based protection module
951 001
255

Type
DV MOD 255
DV MOD 255
Ableiter-Schutzmodul

www.dehn.de

DV MOD

Kombi951 001

PU
pc(s).
1

Part
No.
951 001

33

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNventil modular
DEHNventil M TT (FM)

Accessories

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1
L1

Combined SPDs Type 1

Surge Arresters
Type 3

L1

L2

L3

L2

L3

951 310
255
951 315
255 FM

N
DV M TT 255
951 310
DV M TT 255 FM
951 315

12
11
14

NPE

PE

Basic circuit diagram DV M TT 255 FM

Dimension drawing DV M TT 255 (FM)

DV M TT 255 (FM): Modular combined lightning current and surge arrester for protecting TT and
TN-S systems (3+1 circuit) against surges
DV M TT 255

DV M TT 255 FM

SPD according to EN 61643-11 / ... IEC 61643-1


Type 1 / Class I
Energy-coordinated protection effect with
regard to the terminal equipment
Type 1 + Type 2
Energy-coordinated protection effect with
regard to the terminal equipment ( ) 5m)
Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN
230 / 400 V
Max. continuous operating a.c. voltage UC
255 V
Lightning impulse current (10/350 s) [L1+L2+L3+N-PE] Itotal
100 kA
Lightning impulse current (10/350 s) [L-N]/[N-PE] Iimp
25 / 100 kA
Nominal discharge current (8/20 s) In
25 / 100 kA
Voltage protection level [L-N]/[N-PE] UP
) 1.5 kV / ) 1.5 kV
Follow current extinguishing capability [L-N]/[N-PE] Ifi
50 kArms / 100 Arms
Follow current limitation/Selectivity
no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA
) 100 ns
Max. backup fuse (L) up to IK = 50 kArms
315 A gL/gG
Max. backup fuse (L) for IK > 50 kArms
200 A gL/gG
Max. backup fuse (L-L)
125 A gL/gG
Temporary overvoltage (TOV) [L-N] UT
440 V / 5 sec.
Temporary overvoltage (TOV) [N-PE] UT
1200 V / 200 ms
TOV characteristics
withstand
Operating temperature range [parallel]/[continuity] TU
-40C...+80C / -40C...+60C
Operating state/fault indication
green / red
Cross-sectional area (L1, L1, L2, L2, L3, L3, N, N, PE, 9) min.
10 mm2 solid/flexible
Cross-sectional area (L1, L2, L3, N, PE) max.
50 mm2 stranded/35 mm2 flexible
Cross-sectional area (L1, L2, L3, N, 9) max.
35 mm2 stranded/25 mm2 flexible
For mounting on
35 mm DIN rail acc. to EN 60715
Enclosure material
thermoplastic, red, UL 94 V-0
Degree of protection
IP 20
Capacity
8 mods., DIN 43880
Approvals, Certifications
KEMA, VDE, UL, VdS
Type of remote signalling contact

Switching capacity a.c.

Switching capacity d.c.

Cross-sectional area for remote signalling terminals

Ordering information
Type
Part No.
Packing unit

DV MOD 255
Ableiter-Schutzmodul

34

DV MOD

Kombi951 001

Type 1 + Type 2 + Type 3


230 / 400 V
255 V
100 kA
25 / 100 kA
25 / 100 kA
) 1.5 kV / ) 1.5 kV
50 kArms / 100 Arms
no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C / -40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
8 mods., DIN 43880
KEMA, VDE, UL, VdS
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DV M TT 255 FM

951 310
1 pc(s).

951 315
1 pc(s).

Accessory part for DEHNventil modular

Spark-gap-based protection module


Type
DV MOD 255

Type 1 + Type 2

DV M TT 255

Accessory part for DEHNventil modular


951 001
255

Type 1 / Class I

951 050
951 100

PU
pc(s).
1

Part
No.
951 001

DV MOD NPE 50
951 050
DV MOD NPE 100
951 100

DV MOD NPE 50
DV MOD NPE 100

N-PE spark-gap-based protection module


Type
DV MOD NPE 100

PU
pc(s).
1

Part
No.
951 100

www.dehn.de

DV M TT
DV M TT

Combined SPDs
Type 1

951 200
255
951 205
255 FM

DV M TN
DV M TN

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNventil modular
DEHNventil M TN (FM)

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1
N

Combined SPDs Type 1

L
DV M TN 255
951 200
DV M TN 255 FM
951 205

12
11
14

PE

Dimension drawing DV M TN 255 (FM)

Basic circuit diagram DV M TN 255 FM

DV M TN 255 (FM): Modular combined lightning current and surge arrester for protecting singlephase TN systems against surges

SPD according to EN 61643-11 / ... IEC 61643-1


Energy-coordinated protection effect with
regard to the terminal equipment
Energy-coordinated protection effect with
regard to the terminal equipment ( ) 5m)
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) [L+N-PE] Itotal
Lightning impulse current (10/350 s) [L, N-PE] Iimp
Nominal discharge current (8/20 s) In
Voltage protection level [L-PE]/[N-PE] UP
Follow current extinguishing capability a.c. Ifi
Follow current limitation/Selectivity
Response time tA
Max. backup fuse (L) up to IK = 50 kArms
Max. backup fuse (L) for IK > 50 kArms
Max. backup fuse (L-L)
Temporary overvoltage (TOV) [L-N] UT
TOV characteristics
Operating temperature range [parallel]/[continuity] TU
Operating state/fault indication
Cross-sectional area (L, L, N, N, PE, 9) min.
Cross-sectional area (L, N, PE) max.
Cross-sectional area (L, N, 9) max.
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

DV M TN 255

DV M TN 255 FM

Type 1 / Class I

Type 1 / Class I

Type 1 + Type 2

Type 1 + Type 2

Type 1 + Type 2 + Type 3


230 V
255 V
50 kA
25 kA
25 / 50 kA
) 1.5 kV / ) 1.5 kV
50 kArms
no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
withstand
-40C...+80C / -40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA, VDE, UL, VdS

Type 1 + Type 2 + Type 3


230 V
255 V
50 kA
25 kA
25 / 50 kA
) 1.5 kV / ) 1.5 kV
50 kArms
no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
withstand
-40C...+80C / -40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA, VDE, UL, VdS
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DV M TN 255
951 200

DV M TN 255 FM
951 205

1 pc(s).

1 pc(s).

Accessory part for DEHNventil modular


Spark-gap-based protection module
951 001
255

Type
DV MOD 255
DV MOD 255
Ableiter-Schutzmodul

www.dehn.de

DV MOD

Kombi951 001

PU
pc(s).
1

Part
No.
951 001

35

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNventil modular
DEHNventil M TT 2P (FM)

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1

Combined SPDs Type 1

951 110
2P 255
951 115
2P 255 FM

N
DV M TT 2P 255
951 110
DV M TT 2P 255 FM
951 115

12
11
14

NPE

PE

Basic circuit diagram DV M TT 2P 255 FM

Dimension drawing DV M TT 2P 255 (FM)

DV M TT 2P 255 (FM): Modular combined lightning current and surge arrester for protecting
single-phase TT and TN systems (1+1 circuit) against surges

SPD according to EN 61643-11 / ... IEC 61643-1


Energy-coordinated protection effect with
regard to the terminal equipment
Energy-coordinated protection effect with
regard to the terminal equipment ( ) 5m)
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) [L+N-PE] Itotal
Lightning impulse current (10/350 s) [L-N]/[N-PE] Iimp
Nominal discharge current (8/20 s) In
Voltage protection level [L-N]/[N-PE] UP
Follow current extinguishing capability [L-N]/[N-PE] Ifi
Follow current limitation/Selectivity
Response time tA
Max. backup fuse (L) up to IK = 50 kArms
Max. backup fuse (L) for IK > 50 kArms
Max. backup fuse (L-L)
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [N-PE] UT
TOV characteristics
Operating temperature range [parallel]/[continuity] TU
Operating state/fault indication
Cross-sectional area (L, L, N, N, PE, 9) min.
Cross-sectional area (L, N, PE) max.
Cross-sectional area (L, N, 9) max.
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals

DV M TT 2P 255

DV M TT 2P 255 FM

Type 1 / Class I

Type 1 / Class I

Type 1 + Type 2

Type 1 + Type 2

Type 1 + Type 2 + Type 3


230 V
255 V
50 kA
25 / 50 kA
25 / 50 kA
) 1.5 kV / ) 1.5 kV
50 kArms / 100 Arms
no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C / -40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94-V-0
IP 20
4 mods., DIN 43880
KEMA, VDE, UL, VdS

Type 1 + Type 2 + Type 3


230 V
255 V
50 kA
25 / 50 kA
25 / 50 kA
) 1.5 kV / ) 1.5 kV
50 kArms / 100 Arms
no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C / -40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94-V-0
IP 20
4 mods., DIN 43880
KEMA, VDE, UL, VdS
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DV M TT 2P 255

DV M TT 2P 255 FM

951 110
1 pc(s).

951 115
1 pc(s).

Ordering information
Type
Part No.
Packing unit

Accessory part for DEHNventil modular


951 001
255

DV MOD 255
Ableiter-Schutzmodul

36

DV MOD

Kombi951 001

Accessory part for DEHNventil modular

Spark-gap-based protection module


Type
DV MOD 255

PU
pc(s).
1

Part
No.
951 001

951 050

DV MOD NPE 50

DV MOD NPE 50
Ableiter-Schutzmodul N-PE 50 kA

Kombi951 050

N-PE spark-gap-based protection module


Type
DV MOD NPE 50

PU
pc(s).
1

Part
No.
951 050

www.dehn.de

DV M TT
DV M TT

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

Protection Module for DEHNventil modular

High discharge capacity due to powerful creepage discharge spark gap


Maximum system availability due to RADAX
Flow follow current limitation
With module release button for replacing protection modules without tools
Operating state/fault indication by green/red
indicator flag in the inspection window
The plug-in protection module can be replaced
without the need to de-energise and without
removing the cover plate of the distribution
board

For protecting low-voltage consumers installations against surges and


even direct lightning strikes. For installation in conformity with the lightning protection zones concept at the boundaries from 0A 2.

DV MOD 255:
Spark-gap-based protection module
DV MOD NPE 50: 50 kA N-PE spark-gap-based protection module
DV MOD NPE 100: 100 kA N-PE spark-gap-based protection module

The spark-gap-based protection modules of the modular DEHNventil


series combine safety and innovation. Apart from the encapsulated
RADAX Flow spark gap technology, the compact protection components
incorporate the complete monitoring circuit for controlling the energy
flow of the spark gap, monitoring device and operating state/fault indicator.

The module locking device ensures safe fixation of the protection modules
in the base part. The protection modules are easily removed without the
use of tools by simply pressing the module release button.

The mechanical coding of the protection module prevents unintended


interchanging of the N-PE protection modules with the spark-gap-based
module for the phase conductors.

www.dehn.de

37

Combined SPDs Type 1

SPD Type 1 according to EN 61643-11


SPD Class I according to IEC 61643-1

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Accessories

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1

Combined SPDs Type 1

Protection Module for DEHNventil modular


Spark-gap-based protection module

Surge Arresters
Type 3

951 001
255

DV MOD

DV MOD 255
951 001

Basic circuit diagram DV MOD 255

Dimension drawing DV MOD 255

DV MOD 255: Spark-gap-based protection module

DV MOD 255
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Follow current extinguishing capability [L-N] a.c. Ifi
Follow current limitation/Selectivity
Ordering information
Type
Part No.
Packing unit

255 V
25 kA
50 kArms
no tripping of a 20 A gL/gG fuse up to 50 kArms (prosp.)

DV MOD 255
951 001
1 pc(s).

951 050
NPE 50
951 100
NPE 100

N-PE spark-gap-based protection module

DV MOD NPE 50
951 050
DV MOD NPE 100
951 100

NPE

Basic circuit diagram DV MOD NPE ...

Dimension drawing DV MOD NPE ...

DV MOD NPE 50: 50 kA N-PE spark-gap-based protection module


DV MOD NPE 100: 100 kA N-PE spark-gap-based protection module

Max. continuous operating a.c. voltage UC


Lightning impulse current (10/350 s) Iimp
Follow current extinguishing capability [N-PE] a.c. Ifi
Ordering information
Type
Part No.
Packing unit

38

DV MOD NPE 50

DV MOD NPE 100

255 V
50 kA
100 Arms

255 V
100 kA
100 Arms

DV MOD NPE 50
951 050

DV MOD NPE 100


951 100

1 pc(s).

1 pc(s).

www.dehn.de

DV MOD
DV MOD

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNventil ZP
Multipole combined lightning current and
surge arrester for primary power systems

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

Combined lightning current and surge arrester based on RADAX


Flow spark gap technology
Fully compliant with all requirements of the national VDN*
Directive on the use of SPDs upstream of the meter
Quick and easy installation by snapping the SPD onto 40 mm busbar systems
Test for correct operation by pressing the button with light indicator
No tripping of fuses from 32 A gL/gG up to short-circuit currents
of 25 kArms
Discharge capacity up to 100 kA (10/350 s)
Protection of terminal equipment
Maximum system availability

For protecting low-voltage consumers installations against surges and even direct lightning
strikes. For installation in conformity with the
lightning protection zones concept at the
boundaries from 0A 2.

DEHNventil ZP TNC 255: Three-pole combined lightning current and surge


arrester for TN-C systems for use in primary power systems
DEHNventil ZP TT 255: Four-pole combined lightning current and surge
arrester for TT and TN-S systems for use in primary
power systems

The DEHNventil ZP combined lightning current


and surge arrester is specifically designed for
connection to busbar panels of supply meters. It
can be snapped directly onto the busbar system
without the need for tools. Its reduced size
leaves enough space for connecting cables from
the service entrance box (SEB), even if three
selective main circuit breakers are installed.
The operating state of the SPD is indicated by a
light indicator which is controlled by a button.
Both with this kind of operating state control
and due to its design as a spark-gap-based SPD,
the DEHNventil ZP device has no leakage and
operating currents.
The RADAX Flow spark gap technology allows
the required selectivity for follow currents even
for small-sized fuses in the service entrance
box. Unwanted interruptions of the power supply due to tripping of main fuses are thus avoided.
The dimensioning of the parameters as well as
the complete concept of the device are fully
compliant with all requirements of the new
German VDN* Directive on the use of surge protective devices in primary power systems.
* VDN ... Verband der Netzbetreiber VDN e. V. at BDEW
[Association of German network operators]

www.dehn.de

39

Combined SPDs Type 1

Combined SPDs
Type 1

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNventil ZP
DEHNventil ZP TNC

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1

Combined SPDs Type 1

PEN

900 390
TNC 255

DV ZP TNC 255
900 390

L1

&

L2

L3

PEN

Basic circuit diagram DV ZP TNC 255

Dimension drawing DV ZP TNC 255

DV ZP TNC 255: Combined lightning current and surge arrester for TN-C systems for use in primary
power systems (3-0 circuit)

DV ZP TNC 255
SPD according to EN 61643-11
Type 1
SPD according to IEC 61643-1
Class I
Energy-coordinated protection effect with regard to the terminal equipment
Type 1 + Type 2
Energy-coordinated protection effect with regard to the terminal equipment ( ) 5m)
Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN
230 / 400 V
Max. continuous operating a.c. voltage UC
255 V
Lightning impulse current (10/350 s) [L1+L2+L3-PEN] Itotal
75 kA
Lightning impulse current (10/350 s) [L-PEN] Iimp
25 kA
Nominal discharge current (8/20 s) In
25 / 75 kA
Voltage protection level UP
) 1.5 kV
Follow current extinguishing capability a.c. Ifi
25 kArms
Follow current limitation/Selectivity
no tripping of a 32 A gL/gG fuse up to 25 kArms (prosp.)
Response time tA
) 100 ns
Max. backup fuse up to I = 25 kArms
315 A gL/gG
Max. backup fuse for IK > 25 kArms
200 A gL/gG
Temporary overvoltage (TOV) UT
335 V / 5 sec.
TOV characteristics
withstand
Operating temperature range TU
Function control
Cross-sectional area (PEN, 9)
For mounting on
Enclosure material
Degree of protection
Capacity
Certifications, Approvals
Ordering information
Type
Part No.
Packing unit

40

-40C...+80C
button with light indicator
10-35 mm2 flexible/50 mm2 stranded
40 mm busbar system
thermoplastic, red, UL 94 V-0
IP 20
3 mods., DIN 43880
VDE

DV ZP TNC 255
900 390
1 pc(s).

www.dehn.de

DV ZP

Combined SPDs
Type 1

DV ZP TT

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNventil ZP
DEHNventil ZP TT

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1
N

DV ZP TT 255
900 391

Combined SPDs Type 1

900 391
255

Lightning Current
Arresters Type 1

L1
L2

&

L3

PE*
* in case of existing
PE busbar
PE

Dimension drawing DV ZP TT 255

Basic circuit diagram DV ZP TT 255

DV ZP TT 255: Combined lightning current and surge arrester for TT and TN-S systems for use in
primary power systems (3+1 circuit)

DV ZP TT 255
SPD according to EN 61643-11
Type 1
SPD according to IEC 61643-1
Class I
Energy-coordinated protection effect with regard to the terminal equipment
Type 1 + Type 2
Energy-coordinated protection effect with regard to the terminal equipment ( ) 5m)
Type 1 + Type 2 + Type 3
Nominal a.c. voltage UN
230 / 400 V
Max. continuous operating a.c. voltage UC
255 V
Lightning impulse current (10/350 s) [L1+L2+L3+N-PE] Iimp
100 kA
Lightning impulse current (10/350 s) [L-N] Iimp
25 kA
Lightning impulse current (10/350 s) [N-PE] Iimp
100 kA
Nominal discharge current (8/20 s) In
25 / 100 kA
Voltage protection level [L-N] UP
) 1.5 kV
Voltage protection level [N-PE] UP
) 1.5 kV
Follow current extinguishing capability [L-N] a.c. Ifi
25 kArms
Follow current extinguishing capability [N-PE] a.c. Ifi
100 Arms
Follow current limitation/Selectivity
no tripping of a 32 A gL/gG fuse up to 25 kArms (prosp.)
Response time tA
) 100 ns
Max. backup fuse up to I = 25 kArms
315 A gL/gG
Max. backup fuse for IK > 25 kArms
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [N-PE] UT
TOV characteristics
Operating temperature range TU
Function control
Cross-sectional area (PE, 9)
For mounting on
Enclosure material
Degree of protection
Capacity
Certifications, Approvals
Ordering information
Type
Part No.
Packing unit

www.dehn.de

200 A gL/gG
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
button with light indicator
10-35 mm2 flexible/50 mm2 stranded
40 mm busbar system
thermoplastic, red, UL 94 V-0
IP 20
3 mods., DIN 43880
VDE

DV ZP TT 255
900 391
1 pc(s).

41

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Combined SPDs Type 1

DEHNlimit PV 1000
Type 1 combined lightning current and
surge arrester for use in photovoltaic systems

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1
SPD Type 1 classification according to EN 61643-11
SPD Class I classification according to IEC 61643-1

Prewired combined lightning current and surge


arrester for use in photovoltaic generator circuits
For use in photovoltaic installations up to
1000 V UCPV
High lightning current discharge capacity due
to approved spark gap technology
Maximum system availability due to spark gap
technology with d.c. current extinction

For protecting photovoltaic inverters against surges and even direct lightning strikes. For use in accordance with IEC 60364-7-712:2002-05
(Installation of photovoltaic power supply systems).

DEHNlimit PV 1000: Combined lightning current and surge arrester for use in photovoltaic power supply systems up to
1000 V d.c.
The combined lightning current and surge arrester of type DEHNlimit PV
1000 was specifically developed for use in photovoltaic power supply systems. The approved encapsulated creepage discharge spark gap technology allows reliable protection of photovoltaic generators and inverters
even in the event of direct lightning impulse currents. It is the voltage protection level of DEHNlimit PV 1000 and reduction of the impulse time due
to the spark gap technology that allow for coordination of the SPD with
the equipment to be protected.

42

The d.c. extinction by the spark gap is a unique feature of DEHNlimit PV


1000. Potential short-circuit currents up to 100 A caused by a tripping
spark gap are interrupted within only a fraction of a second in case of a
photovoltaic voltage up to 1000 V d.c.
The combination of lightning current carrying capability, protection capability and follow current extinction provides maximum availability of the
PV system protected by DEHNlimit PV 1000.

www.dehn.de

900 330
1000

DLM PV

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNlimit PV 1000
DEHNlimit PV 1000

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1
L+

Combined SPDs Type 1

Combined SPDs
Type 1

DLM PV 1000
900 330

d.c.

control

bypass

(8 mods.)

Dimension drawing DLM PV 1000

Basic circuit diagram DLM PV 1000

DLM PV 1000: Combined lightning current and surge arrester for use in photovoltaic power
supply systems up to 1000 V d.c.

DLM PV 1000

www.dehn.de

SPD classification according to EN 61643-11


SPD classification according to IEC 61643-1
Max. PV voltage [UCPV ] of the PV generator
Max. continuous operating d.c. voltage Umax dc
Min. continuous operating d.c. voltage Umin dc
Follow current extinguishing capability d.c. Ifi dc
Nominal discharge current (8/20 s) In
Lightning impulse current (10/350 s) [L+/L- -> PE] Iimp
Lightning impulse current (10/350 s) [L+ -> L-] Iimp
Voltage protection level [L+ -> L-] Up
Voltage protection level [(L+/L-) -> PE] Up
Operating current IIN dc
Response time [L+ -> L-] tA
Protective conductor current IPE
Operating temperature range Tu
Cross-sectional area (min.)
Cross-sectional area (max.)

Type 1
Class I
1000 V
1000 V
100 V
100 A
100 kA
50 kA
25 kA
) 3.3 kV
) 4 kV
) 5 mA
) 20 ns
) 1 A
-40C...+60C
10 mm2 solid/flexible
50 mm2 stranded/ 35 mm2 flexible

For mounting on
Enclosure material
Degree of protection
Capacity

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
8 mods., DIN 43880

Ordering information
Type
Part No.
Packing unit

DLM PV 1000
900 330
1 pc(s).

43

Combined SPDs
Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

Combined SPDs Type 1

POWER SUPPLY SYSTEMS


COMBINED SPDs TYPE 1

44

www.dehn.de

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

Surge Arresters
Type 3

Accessories

DEHNbloc M
Single-pole modular coordinated
lightning current arrester

Coordinated spark-gap-based lightning current


arrester consisting of a base part and plug-in
protection module

No tripping of 32 A gL/gG fuses up to short-circuit currents of 50 kArms


Discharge capacity up to 50 kA (10/350 s)
Directly coordinated with DEHNguard surge
protective devices without additional cable
length
Low voltage protection level
Operating state/fault indication by indicator
flag in the inspection window
For protecting low-voltage consumers installations against surges and
even direct lightning strikes. For installation in conformity with the lightning protection zones concept at the boundaries from 0A 1.

Easy replacement of protection modules without tools due to module locking system with
module release button

DEHNbloc M 1 ...:
Single-pole modular coordinated lightning current arrester with high follow current limitation
DEHNbloc M 1 ... FM: With remote signalling contact for the monitoring system (floating changeover contact)

The modular devices of the DEHNbloc M product family are coordinated


lightning current arresters with a functional design.
Energy coordination with Type 2 surge arresters of the DEHNguard family is ensured without additional cable lengths or decoupling coils. This is
one of the most important characteristics of the Red/Line product family.
The DEHNbloc M devices stand for performance and user friendliness in a
concise form. Their electrical parameters were rated for maximum requirements for lightning and surge protection systems. DEHNbloc M is the ideal
device for use in main distribution boards of low-voltage consumers
installations of a building. Equipped with the latest RADAX Flow spark
gap technology, the most important goal of DEHNbloc M is to ensure protection and availability of electrical installations.
Due to the unique follow current limitation and follow current extinction,
a follow current breaking selectivity is ensured even for small-sized fuses
in installations. DEHNbloc M is leakage-current-free and has a mechanical operating state indication, allowing the device to be installed even
upstream of meter panels in low-voltage consumers installations.
When installing this modular arrester, the user of DEHNbloc M has all
safety characteristics and features this design has to offer. The vibrationproof module locking system, for example, is unique. Shock or vibration

www.dehn.de

during transport or operation or


enormous mechanical impulse
loads resulting from discharges do
not affect the module locking system which ensures safe fixation
both for the base part and protection module. Nevertheless, the protection modules can be easily
replaced without tools by simply
pressing the user-friendly module
release button. In order to avoid
incorrect insertion by the installer
or user when replacing the modules, both the base part and protection
module are mechanically coded. DEHNbloc M devices incorporate double
terminals which are suitable for all conductors, allowing series connection
of the SPDs in a space- and cost-saving way according to IEC 60364-5-53
requirements for nominal currents up to 125 A.
The operating state/fault indication of DEHNbloc M immediately provides
information on the availability of the device even if no operating current
is present. Apart from the standard red and green indicator, DEHNbloc M
... FM devices have an additional remote signalling output. With their
floating changeover contact, the remote signal can be used as a break or
make contact according to the particular circuit concept.

45

Lightn. Curr. Arr. Type 1

Maximum system availability due to RADAX


Flow follow current limitation

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

DEHNbloc M
DEHNbloc M 1 ...

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1

961 110
150
961 120
255
961 130
320

L/N
DB M 1 150
961 110
DB M 1 255
961 120
DB M 1 320
961 130

Lightn. Curr. Arr. Type 1

(2 mods.)

N/PE(N)

Basic circuit diagram DB M 1 ...

Dimension drawing DB M 1 ...

DB M 1 ...: Single-pole, modular, coordinated lightning current arrester with high follow current
limitation

SPD according to EN 61643-11


SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Follow current limitation/Selectivity
Response time tA
Max. backup fuse (L) up to IK = 50 kArms (ta ) 0.2 s)
Max. backup fuse (L) up to IK = 50 kArms (ta ) 5 s)
Max. backup fuse (L) for IK > 50 kArms
Max. backup fuse (L-L)
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range (parallel connection) TUP
Operating temperature range (series connection) TUS
Operating state/fault indication
Cross-sectional area (L/N, L/N, N/PE (N)) min.
Cross-sectional area (L/N, N/PE(N)) max.
Cross-sectional area (L/N) max.
For mounting on
Enclosure material
Degree of protection
Capacity
Test standards
Ordering information
Type
Part No.
Packing unit

DB M 1 150

DB M 1 255

DB M 1 320

Type 1
Class I
150 V
35 kA
35 kA
1.5 kV
50 kArms
no tripping of a 32 A gL/gG
fuse up to 50 kArms (prosp.)
) 100 ns
500 A gL/gG
315 A gL/gG
200 A gL/gG
125 A gL/gG
200 V / 5 sec.
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880

Type 1
Class I
255 V
50 kA
50 kA
2.5 kV
50 kArms
no tripping of a 32 A gL/gG
fuse up to 50 kArms (prosp.)
) 100 ns
500 A gL/gG
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
VDE, KEMA

Type 1
Class I
320 V
25 kA
25 kA
2.5 kV
50 kArms
no tripping of a 32 A gL/gG
fuse up to 50 kArms (prosp.)
) 100 ns
315 A gL/gG
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880

DB M 1 150
961 110
1 pc(s).

DB M 1 255
961 120
1 pc(s).

DB M 1 320
961 130
W
E
N
1 pc(s).

Accessory Part for DEHNbloc M


961 001
MOD 150
961 002
MOD 255
961 003
MOD 320

DB M MOD 150
961 001
DB M MOD 255
961 002
DB M MOD 320
961 003

46

DB M
DB M

DB M spark-gap-based protection module

DB M

Type
DB M MOD 150
DB M MOD 255
DB M MOD 320

PU
pc(s).
1
1
1

Part
No.
961 001
961 002
961 003

www.dehn.de

DB M 1
DB M 1
DB M 1

Combined
Arresters Type 1

961 115
150 FM
961 125
255 FM
961 135
320 FM

DB M 1
DB M 1
DB M 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNbloc M
DEHNbloc M 1 ... FM

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1
L/N

DB M 1 150 FM
961 115
DB M 1 255 FM
961 125
DB M 1 320 FM
961 135

12
11
14

Lightn. Curr. Arr. Type 1

(2 mods.)

N/PE(N)

Dimension drawing DB M 1 ... FM

Basic circuit diagram DB M 1 ... FM

DB M 1 ... FM: Single-pole, modular, coordinated lightning current arrester with high follow current limitation; with remote signalling contact for the monitoring system (floating
changeover contact)

SPD according to EN 61643-11


SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Follow current limitation/Selectivity
Response time tA
Max. backup fuse (L) up to IK = 50 kArms (ta ) 0.2 s)
Max. backup fuse (L) up to IK = 50 kArms (ta ) 5 s)
Max. backup fuse (L) for IK > 50 kArms
Max. backup fuse (L-L)
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range (parallel connection) TUP
Operating temperature range (series connection) TUS
Operating state/fault indication
Cross-sectional area (L/N, L/N, N/PE (N)) min.
Cross-sectional area (L/N, N/PE(N)) max.
Cross-sectional area (L/N) max.
For mounting on
Enclosure material
Degree of protection
Capacity
Test standards
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

DB M 1 150 FM

DB M 1 255 FM

DB M 1 320 FM

Type 1
Class I
150 V
35 kA
35 kA
1.5 kV
50 kArms
no tripping of a 32 A gL/gG
fuse up to 50 kArms (prosp.)
) 100 ns
500 A gL/gG
315 A gL/gG
200 A gL/gG
125 A gL/gG
200 V / 5 sec.
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880

changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Type 1
Class I
255 V
50 kA
50 kA
2.5 kV
50 kArms
no tripping of a 32 A gL/gG
fuse up to 50 kArms (prosp.)
) 100 ns
500 A gL/gG
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
VDE, KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

Type 1
Class I
320 V
25 kA
25 kA
2.5 kV
50 kArms
no tripping of a 32 A gL/gG
fuse up to 50 kArms (prosp.)
) 100 ns
315 A gL/gG
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880

changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

max. 1.5 mm2 solid/flexible

max. 1.5 mm2 solid/flexible

max. 1.5 mm2 solid/flexible

DB M 1 150 FM
961 115
1 pc(s).

DB M 1 255 FM
961 125
1 pc(s).

DB M 1 320 FM
961 135 NEW
1 pc(s).

Accessory Part for DEHNbloc M


DB M spark-gap-based protection module
961 001
MOD 150
961 002
MOD 255
961 003
MOD 320

DB M
DB M
DB M

Type
DB M MOD 150
DB M MOD 255
DB M MOD 320
DB M MOD 150
fr DB M, 150 V
DB M MOD 255
fr DB M, 255 V
DB M MOD 320
fr DB M, 320 V

www.dehn.de

S-Modul
961 001
S-Modul
961 002
S-Modul
961 003

PU
pc(s).
1
1
1

Part
No.
961 001
961 002
961 003

47

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Protection Module for DEHNbloc M

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

High discharge capacity due to powerful creepage discharge spark gap

Lightn. Curr. Arr. Type 1

Maximum system availability due to RADAX


Flow follow current limitation
With module release button for replacing protection modules without tools
Operating state / fault indication by green / red
indicator flag in the inspection window
The plug-in protection module can be replaced
without the need to de-energise and removing
the vertical cover

DB M MOD ...:

Spark-gap-based mains protection module

The spark-gap-based protection modules for DEHNbloc M devices provide


the complete protective circuit including RADAX Flow spark gap and
monitoring circuit for controlling the energy flow.
The spark gap monitoring system and operating state and fault indication
are also integrated in the protection module.

For protecting low-voltage consumers installations against surges and


even direct lightning strikes. For installation in conformity with the lightning protection zones concept at the boundaries from 0A 1.
In order to avoid incorrect insertion when replacing the protection modules, every protection module is mechanically coded.
Like with all modular protective devices, protection modules are easily
replaced without tools by simply pressing the module release button.
961 001
MOD 150
961 002
MOD 255
961 003
MOD 320

DB M MOD 150
961 001
DB M MOD 255
961 002
DB M MOD 320
961 003

Basic circuit diagram DB M MOD ...

Dimension drawing DB M MOD ...

DB M MOD ...: Spark-gap-based mains protection module

Max. continuous operating a.c. voltage UC


Lightning impulse current (10/350 s) Iimp
Follow current extinguishing capability a.c. Ifi
Follow current limitation/Selectivity
Ordering information
Type
Part No.
Packing unit

48

DB M MOD 150

DB M MOD 255

DB M MOD 320

150 V
35 kA
50 kArms

255 V
50 kA
50 kArms
no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)

320 V
25 kA
50 kArms

DB M MOD 150
961 001
1 pc(s).

DB M MOD 255
961 002
1 pc(s).

DB M MOD 320
961 003
NEW
1 pc(s).

www.dehn.de

DB M
DB M
DB M

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


DEHNbloc Maxi
LIGHTNING CURRENT ARRESTERS TYPE 1 Coordinated lightning current arrester
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

Encapsulated RADAX Flow spark gap with high


follow current limitation
No tripping of 32 A gL/gG fuses up to short-circuit currents of 50 kArms
Directly coordinated with DEHNguard ... or V(A)
NH ... surge protective devices without additional cable length
NH00 versions
Low voltage protection level

For protecting low voltage consumers installations against surges and


even direct lightning strikes. For installation in conformity with the lightning protection zones concept at the boundaries from 0A 1.

DBM NH00 255: Coordinated single-pole lightning current arrester in NH design size 00 with high follow current limitation
for UC = 255 V

The coordinated DEHNbloc Maxi ... lightning current arrester adapts to


every kind of application. Be it in exposed locations or harsh industrial
environments: DEHNbloc Maxi ... always offers the adequate solution. The
single-pole device is coordinated with the approved DEHNguard or V(A)
NH surge arresters of the Red/Line family. Independent of cable lengths
and without the need for additional decoupling coils, the surge protection
concept can be individually adapted to all operating conditions of the
installation.
DEHNbloc Maxi uses the patented technologies of encapsulated creepage
discharge spark gaps and RADAX Flow follow current limitation. There is
no need for installers to worry about safety distances from busbars or
equipment. This arrangement also eliminates the risk of tripped backup
fuses resulting from the lack of selectivity between the protective device
and any overcurrent protection systems that may be in place, ensuring the
highest possible system availability.
DEHNbloc Maxi NH00 255 was specifically designed for use in industrial
distribution boards and supply systems and can be easily installed in size
00 NH fuse holders or NH disconnectors in a compact and space-saving
way.

www.dehn.de

49

Lightn. Curr. Arr. Type 1

High discharge capacity of lightning currents

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

DEHNbloc Maxi
DEHNbloc Maxi NH00 255

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1

Lightn. Curr. Arr. Type 1

NEW

900 255

DBM NH00 255


900 255

Basic circuit diagram DBM NH00 255

Dimension drawing DBM NH00 255

DBM NH00 255: Coordinated single-pole lightning current arrester in NH design, size 00, with
high follow current limitation for UC = 255 V

DBM NH00 255


SPD according to EN 61643-11
SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Follow current limitation / Selectivity
Response time tA
Max. backup fuse (L) up to IK = 50 kArms
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range (parallel connection) TUP
For mounting on
Enclosure material
Degree of protection
Ordering information
Type
Part No.
Packing unit

50

Type 1
Class I
255 V
25 kA
25 kA
) 2.5 kV
50 kArms
no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
315 A gL/gG
440 V / 5 sec.
withstand
-40C...+80C
NH fuse holder size 00
thermoplastic, red, UL 94 V-0
IPX4W

DBM NH00 255


900 255
1 pc(s).

www.dehn.de

DBM NH00 255

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


DEHNbloc Maxi 440 / 760
LIGHTNING CURRENT ARRESTERS TYPE 1 Coordinated lightning current arrester
SPD Type 1 according to EN 61643-11
for nominal voltages 400 V and 690 V
SPD Class I according to IEC 61643-1
Encapsulated non-exhausting spark gap

Directly coordinated with DEHNguard surge


protective devices without additional cable
length
Operating state/fault indication by indicator
flag in window

For protecting low-voltage consumers installations against surges and


even direct lightning strikes. For installation in conformity with the lightning protection zones concept at the boundaries from 0A 1.

DEHNbloc Maxi 1 440:

Coordinated single-pole lightning current arrester with high follow current limitation for
UC = 440 V
DEHNbloc Maxi 1 440 FM: With remote signalling contact for the monitoring system (floating changeover contact)
DEHNbloc Maxi 1 760 FM: Coordinated single-pole lightning current arrester with high follow current limitation for
UC = 760 V; with remote signalling contact for the monitoring system (floating changeover contact)

The coordinated DEHNbloc Maxi 440 and 760 lightning current arresters
were specifically designed for higher system voltages.
This allows to reliably protect a variety of industrial applications against
direct and indirect lightning currents.
Be it in a wind turbine or isolated low-voltage installation of an industrial enterprise, DEHNbloc Maxi devices excellently meet all requirements.

devices even if no operating current is present. Apart from the standard


visual green and red indication, DEHNbloc Maxi 1 ... FM features a threepole remote signalling terminal. With its floating changeover contact, the
remote signal can be used as a break or make contact according to the
particular circuit concept.

Both the design of the protective circuit and the enclosure specifically
designed for this type of devices are particularly adapted to high system
voltages.
The core of the coordinated DEHNbloc Maxi 440 and 760 lightning current arresters is the approved RADAX Flow technology. Their capability of
considerably limiting mains-frequency follow currents and extinguishing
them within a matter of milliseconds places these devices in a special
position.
The patented RADAX Flow follow current limitation allows a follow current breaking selectivity, even for small-sized fuses in installations.
Its capability to discharge lightning currents without damage and to suppress mains follow currents without tripping of upstream overcurrent protective devices ensures high availability of electrical installations.
The operating state/fault indication of the coordinated lightning current
arresters immediately provides information on the availability of the

www.dehn.de

51

Lightn. Curr. Arr. Type 1

High follow current extinguishing capability


and follow current limitation due to RADAX
Flow technology

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

DEHNbloc Maxi 440 / 760


DEHNbloc Maxi 1 440 (FM)

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1
L

961 140
961 145

L
DBM 1 440
961 140
DBM 1 440 FM
961 145

12
11
14

Lightn. Curr. Arr. Type 1

( 2 mods.)

N/PEN

Basic circuit diagram DBM 1 440 FM

Dimension drawing DBM 1 440 FM

DBM 1 440 (FM): Coordinated, single-pole lightning current arrester with high follow current limitation for UC = 440 V

DBM 1 440

DBM 1 440 FM

Type 1
Class I
440 V

Type 1
Class I
440 V

35 kA
35 kA
) 2.5 kV
50 kArms
no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
500 A gL/gG
250 A gL/gG
160 A gL/gG
125 A gL/gG
690 V / 5 sec.
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880

35 kA
35 kA
) 2.5 kV
50 kArms
no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
500 A gL/gG
250 A gL/gG
160 A gL/gG
125 A gL/gG
690 V / 5 sec.
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DBM 1 440
961 140
1 pc(s).

DBM 1 440 FM
961 145
1 pc(s).

SPD according to EN 61643-11


SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Follow current limitation / Selectivity
Response time tA
Max. backup fuse (L) up to IK = 50 kArms (ta ) 0.2 s)
Max. backup fuse (L) up to IK = 50 kArms (ta ) 5 s)
Max. backup fuse (L) for IK > 50 kArms
Max. backup fuse (L-L)
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range (parallel connection) TUP
Operating temperature range (series connection) TUS
Operating state/fault indication
Cross-sectional area (L, L, N/PEN) min.
Cross-sectional area (L, N/PEN) max.
Cross-sectional area (L) max.
For mounting on
Enclosure material
Degree of protection
Capacity
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

Accessory Part for DEHNbloc Maxi 440 / 760


EB DG, 3-pole, single-phase

Accessory Part for DEHNbloc Maxi 440 / 760


900 411
1000 1 3

EB DG

Earthing clip for earth-side jumpering of e.g. 3 Type 1 SPDs in a 2module enclosure with multifunctional terminal
EB DG 1000 1 3
900 411

Type
EB DG 1000 1 3

52

Dimension
34 x 112 x 3 mm

Terminal
up to 25 mm2

PU
pc(s).
1

Part
No.
900 411

Earthing Clip, 4-pole, single-phase

900 417

EB 1 4 9

Earthing clip for earth-side jumpering of e.g. 4 Type 1 SPDs in a 2module enclosure with multifunctional terminal
EB 1 4 9
900 417

Type
EB 1 4 9

Dimension
34 x 148 x 3 mm

Terminal
up to 25 mm2

PU
pc(s).
1

Part
No.
900 417

www.dehn.de

DBM 1 440
DBM 1 440 FM

Combined
Arresters Type 1

961 175

DBM 1 760 FM

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNbloc Maxi 440 / 760


DEHNbloc Maxi 1 760 FM

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1
L

DBM 1 760 FM
961 175

12
11
14
9

( 2 mods.)

Dimension drawing DBM 1 760 FM

Lightn. Curr. Arr. Type 1

Basic circuit diagram DBM 1 760 FM

DBM 1 760 FM: Single-pole, coordinated lightning current arrester with high follow current
limitation for UC = 760 V

DBM 1 760 FM
SPD according to EN 61643-11
SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC

Type 1
Class I
760 V

Lightning impulse current (10/350 s) Iimp


Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Follow current limitation / Selectivity
Response time tA
Max. backup fuse (L) up to IK = 25 kArms (ta ) 5 s)
Max. backup fuse (L) up to IK > 25 kArms
Max. backup fuse (L-L)
Short-circuit withstand capability for max. mains-side overcurrent protection
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range (parallel connection) TUP
Operating temperature range (series connection) TUS
Operating state/fault indication
Cross-sectional area (L, L, 9) min.
Cross-sectional area (L, 9) max.
Cross-sectional area (L) max.
For mounting on
Enclosure material
Degree of protection
Capacity
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals

25 kA
25 kA
) 4 kV
25 kArms
no tripping of a 32 A gL/gG fuse up to 25 kArms (prosp.)
) 100 ns
250 A gL/gG
100 A gL/gG
125 A gL/gG
25 kArms
1000 V / 5 sec.
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

Ordering information
Type
Part No.
Packing unit

DBM 1 760 FM
961 175
1 pc(s).

Accessory Part for DEHNbloc Maxi 440 / 760


Earthing Clip, 4-pole, single-phase
Earthing clip for earth-side jumpering of e.g. 4 Type 1 SPDs in a 2module enclosure with multifunctional terminal
Type
EB 1 4 9

www.dehn.de

Dimension
34 x 148 x 3 mm

Terminal
up to 25 mm2

PU
pc(s).
1

Part
No.
900 417

Accessory Part for DEHNbloc Maxi 440 / 760


900 411
1000 1 3

EB DG

EB DG 1000 1 3
Erdungsbgel 1-phasig, 3-polig, 8 TE

900 411

EB DG, 3-pole, single-phase


Earthing clip for earth-side jumpering of e.g. 3 Type 1 SPDs in a 2module enclosure with multifunctional terminal
Type
EB DG 1000 1 3

Dimension
34 x 112 x 3 mm

Terminal
up to 25 mm2

PU
pc(s).
1

900 417

EB 1 4 9

EB 1 4 9
Erdungsbgel 1-phasig, 4-polig, 9 TE

900 417

Part
No.
900 411

53

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

DEHNbloc Maxi S
Coordinated lightning
current arrester for busbars

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

Combination of spark gap and integrated backup fuse


For mounting directly onto PEN/N busbars

Lightn. Curr. Arr. Type 1

Low voltage protection level UP


(80 cm connecting cable included)

) 2.5 kV

Directly coordinated with DEHNguard surge


protective device without additional cable
length
Short-circuit withstand capability of 100 kArms
(220 kApeak)
High follow current extinguishing capability
and follow current limitation due to RADAX
Flow technology
High lightning current discharge capacity
With optical-fibre interface for monitoring the
SPD

For protecting low voltage consumers installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0A 1.

DEHNbloc Maxi 1 255 S: Coordinated lightning current arrester with integrated backup fuse for busbars
DEHNbloc Maxi S allows to better integrate surge protective devices into
application environments of a low-voltage switchgear installation or distribution board.
Due to its unique mechanical design, the coordinated DEHNbloc Maxi S
lightning current arrester can be mounted directly onto the PEN/N busbar
of a switchgear installation without requiring additional adapters.
With the backup fuse integrated into the device, no further separate backup fuses need to be installed.
Installing the DEHNbloc Maxi S devices directly into the terminal panel of
the switchgear installation upstream of the circuit breaker ensures short
cable lengths of the SPDs and a low voltage protection level for the installation.
With a discharge capacity of 25 kA (10/350 s) DEHNbloc Maxi S fulfils
the most stringent requirements of national and international lightning
protection standards for all three-phase current applications in TN and TT
systems.
For 3+1 circuits, DEHNgap Maxi S provides a powerful creepage discharge spark gap with a discharge capacity of 100 kA (10/350 s).

*)

DEHbloc Maxi S
DBM 1 255 S

DEHNbloc Maxi S also features the patented RADAX Flow follow current
limitation thus allowing selectivity, even for small-sized fuses.
The capability of conducting lightning impulse currents without damage
and suppressing mains follow currents without tripping upstream overcurrent protective devices ensures the availability of the switchgear
installation in case of a lightning strike and considerably reduces the risk
of arc formation in the installation.
Combined with the DEHNsignal remote signalling system, the availability
of DEHNbloc Maxi S devices can be monitored at any time.
An optical fibre transmission to the DEHNsignal E 3 receiver module,
which is easy to perform, ensures
safe electrical isolation between
the power circuit and the remote
signalling circuit.

main circuit bre

main circuit bre

aker

**) DEHNgap Maxi S


DGPM 1 255 S

aker

optical fibre

L1

L2

L3

LWL DSI plastic


max. 6 m

**)
N busbar

*)

*)

without
wire
jumper
S/N

*)

L1

L2

L3

LWL DSI plastice


max. 6 m

*) DEHbloc Maxi S
DBM 1 255 S

*)

*)

with
wire
jumper
S/N

*)

N L
(PEN)

PEN busbar
N' N L

N' N L

DEHNgap Maxi S
DGPM 1 255 S

PE busbar

power supply
230 V~

equipoten

tial bond
ing

!
All three optical fibres
must be connected!

Application in a TT / TN-S system

54

TN-C
DSI E 3
power supply

optical fibr

TT / TN-S
DSI E 3
power supply

F
L max. 16 A gl/gG
(C 16 A)
N

equipoten

tial bond
ing

All three optical fibres


must be connected!

power

L 230 V~supply
N max. 16 A gl/g
G
(C 16 A)

Application in a TN-C system

www.dehn.de

Combined
Arresters Type 1

900 220

DBM 1 255 S

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNbloc Maxi S
DEHNbloc Maxi 1 255 S

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1

DBM 1 255 S
900 220

optical fibre

Dimension drawing DBM 1 255 S

DBM 1 255 S:

Lightn. Curr. Arr. Type 1

N/PEN

Basic circuit diagram DBM 1 255 S

Coordinated single-pole lightning current arrester with integrated backup fuse for
busbars

DBM 1 255 S
SPD according to EN 61643-11
SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Follow current limitation / Selectivity
Response time tA
Short-circuit withstand capability
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range TU
For mounting on
Connection type
Enclosure material
Dimension (W x H x D)

Type 1
Class I
255 V
25 kA
25 kA
) 2.5 kV (includes 80 cm connecting cable)
50 kArms
no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
100 kArms (220 kApeak)
335 V / 5 sec.
withstand
-40C...+80C
PEN / N busbar min. 35 mm2
cable lug min. 35 mm2/max. 50 mm2
thermoplastic, red, UL 94 V-0
72 x 89 x 100 mm

Operating state indication

by optical fibres via DSI E 3

Ordering information
Type
Part No.
Packing unit

DBM 1 255 S
900 220
1 pc(s).

Accessory Part for DEHNbloc Maxi S

Accessory Part for DEHNbloc Maxi S


LWL ST DSI

DEHNsignal E 3

Plug for plastic optical fibres

DSI E 3: Receiver module for optical fibre transmission for selective


operating state indication / centralised fault indication of 3 coordinated DEHNbloc Maxi S and, if required, DEHNgap Maxi S lightning current arresters in 5-conductor systems

910 641
DSI

LWL ST DSI
Optical Fibre

LWL ST

910 631

Plug for
910 641

DSI E 3
910 631

Type
LWL ST DSI

PU
pc(s).
1

Diameter
2.2 mm

Part
No.
910 641

Type
DSI E 3

LWL DSI 18M


910 642
18M

DSI E 3

LWL DSI

PU
pc(s).
1

Part
No.
910 631

18 metres of plastic optical fibre, preferably for use with DEHNbloc


Maxi S
LWL DSI 18M
910 642

Type
LWL DSI 18M

www.dehn.de

Diameter
2.2 mm

Length
18 m

PU
pc(s).
1

Part
No.
910 642

55

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

DEHNsignal
Remote signalling and receiver module

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


ACCESSORIES FOR SPDs TYPE 1
EN 61010-1; EN 61010-1/A2

Operating state indication of the surge protective device connected to it


Indication of phase failures

Lightn. Curr. Arr. Type 1

Floating changeover contact


Selective operating state indication
Centralised fault indication

Receiver module for optical fibre transmission for DEHNbloc Maxi S and
DEHNgap Maxi S protective devices with floating changeover contact.

DEHNsignal E 3: Receiver module for optical fibre transmission for selective operating state indication / centralised fault
indication of three coordinated lightning current arresters of type DEHNbloc Maxi S and DEHNgap Maxi S,
if any, in 5-conductor systems
The receiver module for optical fibre transmission of type
DEHNsignal E 3 transmits
remote signals of DEHNbloc
Maxi S and DEHNgap Maxi S
surge protective devices.
The receiver module for optical fibre transmission of type
DEHNsignal E 3 is particularly adapted to the place of
installation of the coordinated DEHNbloc Maxi S and
DEHNgap Maxi S surge protective devices.
The receiver module for optical fibre transmission is able
to telemonitor three DEHNbloc Maxi S SPDs and, if
required, the N-PE protective
circuit via optical fibre cables.

56

Considering the special installation environment of the surge protective


devices in a switchgear installation, communication via optical fibre cable
between the protective devices and the DEHNsignal E 3 receiver module
is a considerable benefit in terms of safety.
The readiness for operation of the individual SPDs is transmitted to the
DEHNsignal E 3 receiver module in the form of a visual signal via EMCsafe plastic optical fibre cables. The visual signals are evaluated in the
DEHNsignal E 3 receiver module and are converted into an electrical signal. The signal of the operating states can be directly read out at the
DEHNsignal E 3 receiver module or is provided via a floating changeover
contact. The DEHNsignal E 3 receiver module features a green indicator
lamp to check its operating state. In addition to the function indication,
the three indicator lamps of the selective operating state indication show
that the assigned protective devices are ready for operation. The receiver
module indicates if a protective device of a phase fails. The surge protective devices and the DEHNsignal E 3 receiver module are easily connected via optical fibre cable by using the accessory parts described.

www.dehn.de

Combined
Arresters Type 1

DSI E 3

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

POWER SUPPLY SYSTEMS


ACCESSORIES FOR SPDs TYPE 1

DEHNsignal
DEHNsignal E 3

DSI E 3
910 631

red

L1

red

L2

red

L3

LWL 1
LWL 2
LWL 3

L
S

Accessories

signal
evaluation

green

12
14

N
S

11
Note:
Change of contacts in case of present
voltage and optical fibre signal!

Dimension drawing DSI E 3

Lightn. Curr. Arr. Type 1

910 631

Lightning Current
Arresters Type 1

Basic circuit diagram DSI E 3

DSI E 3: Receiver module for optical fibre transmission for selective operating state indication /
centralised fault indication of 3 coordinated DEHNbloc Maxi S and, if required, DEHNgap
Maxi S lightning current arresters in 5-conductor systems

DSI E 3
Supply a.c. voltage UN
Power input P
Backup fuse for supply voltage
Operating temperature range
Signal input
Operating state indication
Selective operating state indication
For mounting on
Enclosure material
Degree of protection
Capacity
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area
Max. distance with LWL DSI 18M
Test standards

230 V
< 550 mW
16 A gL/gG or C 16 A
-40C...+80C
3x via optical fibre plug-in system (LWL ST DSI)
green LED
3 x red LEDs (L1, L2, L3)
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
1.5 mods., DIN 43880
floating changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
min. 0.5 mm2 solid/flexible; max. 4 mm2 solid/flexible
6m
EN 61010-1:1993 and EN 61010-1/A2:1995

Ordering information
Type
Part No.
Packing unit

DSI E 3
910 631
1 pc(s).

Accessory Part for DEHNsignal

Accessory Part for DEHNsignal

LWL ST DSI
910 641
DSI

LWL DSI 18M

LWL ST

910 642
18M

Plug for plastic optical fibres


LWL ST DSI
Optical Fibre

Type
LWL ST DSI

www.dehn.de

Plug for
910 641

Diameter
2.2 mm

PU
pc(s).
1

Part
No.
910 641

LWL DSI

18 metres of plastic optical fibre, preferably for use with DEHNbloc


Maxi S
LWL DSI 18M
910 642

Type
LWL DSI 18M

Diameter
2.2 mm

Length
18 m

PU
pc(s).
1

Part
No.
910 642

57

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

DEHNbloc
Lightning current arrester

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1
SPD Type 1 according to EN 61643-11
SPD Class I according to IEC 61643-1

Encapsulated, non-exhausting creepage discharge spark gap

Lightn. Curr. Arr. Type 1

DEHNbloc ... H: RADAX Flow spark gap technology with high follow current limitation
Energy-coordinated within the Red/Line product family
High insulation resistance allows installation
even upstream of meter panels
Multifunctional terminal for connecting conductors and busbars
Single-pole and three-pole version (lightning
impulse currents up to 100 kA according to the
system configuration)
NH00 version also available
For protecting low voltage consumers installations against surges and
even direct lightning strikes. For installation in conformity with the lightning protection zones concept at the boundaries from 0A 1.

DEHNbloc 1 255 H:
DEHNbloc 3 255 H:
DEHNbloc NH00 H:
DEHNbloc 1 440:

Single-pole lightning current arrester with high follow current limitation


Three-pole lightning current arrester with high follow current limitation
Lightning current arrester, NH 00 design, with high follow current limitation
Single-pole lightning current arrester for UC = 440 V

The spark gaps of the DEHNbloc lightning current arresters allow for a
compact structure of low-voltage distribution boards. Using pressurised
encapsulated creepage discharge spark gaps, safety distances from electrical busbars and special flameproof enclosures are not required.

But the concept of the DEHNbloc H family also stands out due to other
product features: With its phase-side and earth-side double terminals, the
single-pole device of type DEHNbloc 1 255 H offers a wide range of application possibilities.

With a lightning current discharge capacity up to 50 kA (10/350 s) per


pole, DEHNbloc devices fulfil the most stringent requirements of national
and international lightning protection and application standards.

DEHNbloc incorporates double terminals which are suitable for all conductors, allowing a series connection of three-pole DEHNbloc 3 255 H
SPDs in a space- and cost-saving way according to IEC 60364-5-53
requirements for nominal currents up to 125 A.

The consistent development of the integration concept has made the


DEHNbloc devices even more powerful: With the product designation
DEHNbloc ... H, the groundbreaking RADAX Flow spark gap technology
for follow current extinction and follow current limitation was integrated
into the DEHNbloc family.
The RADAX Flow technology prevents operational interruptions caused by
tripping conductor protection due to responding SPDs. In times where all
systems increasingly depend on a functioning electrical infrastructure, this
is an indispensable product feature. Due to the patented RADAX Flow
principle, even the amplitudes of short circuits in installations up to 50
kArms can be limited to approx. 500 A and extinguished after approx. 5 ms.
This performance allows a breaking selectivity of the SPD even in case of
small-sized fuses.

For application with other DIN rail mounted devices, multifunctional terminals are ideally suited for providing connection for conductors and busbars.
DEHNbloc NH00 255 H was
especially developed for use
in industrial distribution
boards and in power supply
systems. It can be installed
into size 00 NH fuse holders
or NH disconnectors according to the particular system.
DEHNbloc 1 440 is suitable
for rated voltages of 440 V.

DB NH00 255 H in a busbar connection


panel of a meter system

58

www.dehn.de

Combined
Arresters Type 1

DB 1 255 H
DEHNbloc/1
DB 3 255 H
DEHNbloc/3

DB 1 255
DB 3 255

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

L1

Accessories

DEHNbloc
DEHNbloc ... 255 H

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1

900 222

Surge Arresters
Type 3

L2

L3

900 120

N/PEN

N/PEN N/PEN

Dimension drawing DB 1 255 H / DB 3 255 H

Lightn. Curr. Arr. Type 1

900 222
H
900 120
H

Lightning Current
Arresters Type 1

Basic circuit diagram DB 1 255 H / DB 3 255 H

DB ... 255 H: Single-pole and three-pole lightning current arrester with high follow current limitation

DB 1 255 H
SPD according to EN 61643-11
Type 1
SPD according to IEC 61643-1
Class I
Nominal a.c. voltage UN
230 V
Max. continuous operating a.c. voltage UC
255 V
Lightning impulse current (10/350 s) Iimp
50 kA
Lightning impulse current (10/350 s) [L-N/PEN] Iimp

Lightning impulse current (10/350 s) [L1+L2+L3-N/PEN] Itotal

Nominal discharge current (8/20 s) In


50 kA
Voltage protection level UP
) 4 kV
Follow current extinguishing capability a.c. Ifi
50 kArms
Follow current limitation / Selectivity
no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
Response time tA
) 100 ns
Max. backup fuse up to IK = 50 kArms (ta ) 0.2 s)
500 A gL/gG
Max. backup fuse up to IK = 50 kArms (ta ) 5 s)
315 A gL/gG
Max. backup fuse for IK > 50 kArms
200 A gL/gG
Max. backup fuse (L-L)
125 A gL/gG
Temporary overvoltage (TOV) UT
335 V / 5 sec.
TOV characteristics
Operating temperature range (parallel connection) TUP
Operating temperature range (series connection) TUS
Cross-sectional area (L, L, N/PEN, N/PEN) min.
Cross-sectional area (L, N/PEN) max.
Cross-sectional area (L, N/PEN) max.
Cross-sectional area (L1, L1, L2, L2, L3, L3, N/PEN, N/PEN)
Cross-sectional area (L1, L2, L3, N/PEN)
Cross-sectional area (L1, L2, L3, N/PEN)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

DB 3 255 H
Type 1
Class I
230/400 V
255 V

50 kA
100 kA
50 / 100 kA
) 4 kV
50 kArms
no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
500 A gL/gG
315 A gL/gG
200 A gL/gG
125 A gL/gG
335 V / 5 sec.

withstand
-40C...+80C
-40C...+60C
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA

withstand
-40C...+80C
-40C...+60C

10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
6 mods., DIN 43880
KEMA

DB 1 255 H
900 222
1 pc(s).

DB 3 255 H
900 120
1 pc(s).

59

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

DEHNbloc
DEHNbloc NH00 255 H

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1

900 273

Lightn. Curr. Arr. Type 1

DB NH00 255 H
900 273

Basic circuit diagram DB NH00 255 H

Dimension drawing DB NH00 255 H

DB NH00 255 H: Single-pole lightning current arrester in NH design, size 00, with high follow current limitation

DB NH00 255 H
SPD according to EN 61643-11
SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Follow current limitation / Selectivity
Response time tA
Max. backup fuse up to IK = 50 kArms (ta ) 0.2 s)
Max. backup fuse up to IK = 50 kArms (ta ) 5 s)
Max. backup fuse for IK > 50 kArms
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range TU
For mounting on
Enclosure material

Type 1
Class I
255 V
25 kA
25 kA
) 4 kV
50 kArms
no tripping of a 32 A gL/gG fuse up to 50 kArms (prosp.)
) 100 ns
315 A gL/gG
200 A gL/gG
125 A gL/gG
440 V / 5 sec.
withstand
-40C...+80C
NH fuse holder, size 00
thermoplastic, red, UL 94 V-0

Degree of protection

IPX4W

Ordering information
Type
Part No.
Packing unit

DB NH00 255 H
900 273
1 pc(s).

60

www.dehn.de

DB NH00 255 H

Combined
Arresters Type 1

DB 1 440

DB 1 440
900 159

DEHNbloc/1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

DEHNbloc
DEHNbloc 1 440

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1

Dimension drawing DB 1 440

Accessories

Lightn. Curr. Arr. Type 1

900 159

Lightning Current
Arresters Type 1

Basic circuit diagram DB 1 440

DB 1 440: Single-pole lightning current arrester with high discharge capacity for UC = 440 V

DB 1 440
SPD according to EN 61643-11
SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for max. mains-side overcurrent protection
Temporary overvoltage (TOV) TN system UT
Temporary overvoltage (TOV) IT system UT
TOV characteristics
Operating temperature range TU
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on

www.dehn.de

Type 1
Class I
440 V
50 kA
50 kA
) 4 kV
1.5 kArms
) 100 ns
160 A gL/gG
50 kArms
580 V / 5 sec.
1200 V + U0 / 200 ms
withstand
-40C...+80C
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm DIN rail acc. to EN 60715

Enclosure material
Degree of protection
Capacity

thermoplastic, red, UL 94 V-0


IP 20
2 mods., DIN 43880

Ordering information
Type
Part No.
Packing unit

DB 1 440
900 159
1 pc(s).

61

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

Lightn. Curr. Arr. Type 1

POWER SUPPLY SYSTEMS


LIGHTNING CURRENT ARRESTERS TYPE 1

62

www.dehn.de

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

POWER SUPPLY SYSTEMS


N-PE LIGHTNING CURRENT ARRESTERS

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNgap
N-PE lightning current arrester

SPD Type 1 according to EN 61643-11


SPD Class 1 according to IEC 61643-1

Discharge capacity up to 100 kA (10/350 s)


Total current arrester specifically designed for
installation in 3+1 and 1+1 circuits of TT
systems according to IEC 60364-5-53 between
neutral conductor N and protective earth conductor PE
Creepage discharge spark gap technology

N-PE Arresters Type 1

DEHNgap M model available with operating


state/fault indication in the inspection window

For protecting low voltage consumers installations against surges and


even direct lightning strikes. For installation in conformity with the lightning protection zones concept at the boundaries from 0A 1 with 3+1 circuits.

DEHNgap M 255 (FM): Coordinated, single-pole, modular N-PE lightning current arrester
DEHNgap Maxi 1 255 S: Coordinated, single-pole N-PE lightning current arrester for busbars
DEHNgap BN 255:
Single-pole N-PE lightning current arrester
DEHNgap B NH00 N 255: Single-pole N-PE lightning current arrester in NH design
DEHNgap Maxi 440 (FM): Coordinated, single-pole N-PE lightning current arrester for UC = 440 V a.c.
Being total current arresters between neutral and protective conductors
in TT systems, the single-pole N-PE lightning current arresters DEHNgap
M, DEHNgap Maxi, DEHNgap Maxi S, DEHNgap BN and DEHNgap B NH
are designed to meet the requirements for the protection of persons and
material assets in 3+1 circuits. The creepage discharge spark gaps were
specifically developed to meet this challenge. With a discharge capacity
up to 100 kA (10/350 s) they fulfil the highest requirements specified in
national and international lightning protection standards. The leakagecurrent-free spark gap design allows the devices to be used upstream of
the meter according to national regulations (e.g. German VDN Directive).
Being coordinated N-PE lightning current arresters, DEHNgap M,
DEHNgap Maxi and DEHNgap Maxi S are different from other total current arresters. Due to their response performance, they can be coordinated directly with N-PE surge arresters of the DEHNguard M family and
DEHNgap S surge arresters without additional decoupling coil. If lightning
current and surge arresters have to be installed together at one site, no
additional DEHNgap S is required thanks to the low voltage protection
levels of DEHNgap M and DEHNgap Maxi.
The design and installation of DEHNgap Maxi S are adapted to the special characteristics of low voltage switchgear installations and entirely
complement the application of DEHNbloc Maxi S.
DEHNgap B NH was specifically developed for industrial plants as well as
for supply systems. This SPD can be easily integrated into existing size 00
NH fuse holders. The multifunctional terminals of the DIN rail mounted
devices DEHNgap M, DEHNgap Maxi and DEHNgap BN are suitable for

www.dehn.de

connecting conductors
and busbars, allowing
wiring with other DIN
rail mounted terminals.
The functional Red/Line
design of DEHNgap M
offers many features for
safe and easy handling.
The mechanical operating state and fault indication, for example,
stands for fulfilling the high safety requirements, just like the module locking device which is unique for use with surge arresters. It fixes the protection modules and the base part of the device firmly in place. Neither vibration nor shock during transport nor the enormous electromagnetic forces
of lightning discharge can loosen the protection modules. Nevertheless,
they can be easily replaced without tools by pressing the user-friendly
module release button of the protection module. Each protection module
is mechanically coded to avoid incorrect insertion by the installer or user.
Apart from the standard visual indication of DEHNgap M, DEHNgap M ...
FM features a three-pole remote signalling terminal. With its floating
changeover contact, the remote signal can be used as a break or make
contact according to the particular circuit concept.

63

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNgap
DEHNgap M 255 (FM)

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


N-PE LIGHTNING CURRENT ARRESTERS

961 101
255
961 105
255 FM

PE
PE

12
11
14

NPE

DGP M 255
961 101
DGP M 255 FM
961 105

(2 mods.)

Basic circuit diagram DGP M 255 FM

Dimension drawing DGP M 255 FM

N-PE Arresters Type 1

DGP M 255 (FM): Single-pole, modular, coordinated N-PE lightning current arrester for UC = 255 V;
also available with remote signalling contact for the monitoring system (floating
changeover contact)

SPD according to EN 61643-11


SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Response time tA
Temporary overvoltage (TOV)
TOV characteristics
Operating temperature range (parallel connection) TUP
Operating temperature range (series connection) TUS
Operating state/fault indication
Cross-sectional area (N, PE, 9) min.
Cross-sectional area (N, PE) max.
Cross-sectional area (9) max.
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

DGP M 255

DGP M 255 FM

Type 1
Class I
255 V
100 kA
100 kA
) 1.5 kV
100 Arms
) 100 ns
1200 V / 200 ms
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715

Type 1
Class I
255 V
100 kA
100 kA
) 1.5 kV
100 Arms
) 100 ns
1200 V / 200 ms
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715

thermoplastic, red, UL 94 V-0


IP 20
2 mods., DIN 43880
VDE, KEMA

thermoplastic, red, UL 94 V-0


IP 20
2 mods., DIN 43880
VDE, KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DGP M 255
961 101
1 pc(s).

DGP M 255 FM
961 105
1 pc(s).

Accessory Part for DEHNgap


961 010
MOD 255

DGP M MOD 255


961 010

DGP M

DGP M 100 kA N-PE spark-gap-based protection


module
DGP M MOD ...: 100 kA N-PE spark-gap-based protection module for
use with all modular DEHNgap M devices
Type
DGP M MOD 255

64

PU
pc(s).
1

Part
No.
961 010

www.dehn.de

DGP M
DGP M

Combined
Arresters Type 1

900 050

DGPM 1 255 S

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNgap
DEHNgap Maxi 1 255 S

POWER SUPPLY SYSTEMS


N-PE LIGHTNING CURRENT ARRESTERS
PE

DGPM 1 255 S
900 050

NPE

S
(DSI E 3)

N/PEN

Dimension drawing DGPM 1 255 S

Basic circuit diagram DGPM 1 255 S

N-PE Arresters Type 1

DGPM 1 255 S: Coordinated single-pole N-PE lightning current arrester for busbars

DGPM 1 255 S
SPD according to EN 61643-11
SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Response time tA
Temporary overvoltage (TOV)
TOV characteristics
Operating temperature range TU
For mounting on
Connection
Operating state control
Connection for DSI E 3 (S) min.
Connection for DSI E 3 (S) max.
Enclosure material

www.dehn.de

Type 1
Class I
255 V
100 kA
100 kA
) 2.5 kV (includes 80 cm connecting cable)
100 Arms
) 100 ns
1200 V / 200 ms
withstand
-40C...+80C
N busbar min. 35 mm2
via cable lug min. 35 mm2/max. 50 mm2
via DEHNsignal DSI E 3
1 mm2 solid/flexible
2.5 mm2 solid/flexible
thermoplastic, red, UL 94 V-0

Dimension (W x H x D)

72 x 89 x 100 mm

Ordering information
Type
Part No.
Packing unit

DGPM 1 255 S
900 050
1 pc(s).

65

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

DEHNgap
DEHNgap BN 255

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


N-PE LIGHTNING CURRENT ARRESTERS

Basic circuit diagram DGP BN 255

900 132
255

DGP BN

DGP BN 255
B/n

DEHNgap
900 132

Dimension drawing DGP BN 255

N-PE Arresters Type 1

DGP BN 255: Single-pole N-PE lightning current arrester

DGP BN 255
SPD according to EN 61643-11
SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Response time tA
Temporary overvoltage (TOV)
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Ordering information
Type
Part No.
Packing unit

66

Type 1
Class I
255 V
100 kA
100 kA
) 4 kV
100 Arms
) 100 ns
1200 V / 200 ms
withstand
-40C...+80C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880

DGP BN 255
900 132
1 pc(s).

www.dehn.de

Combined
Arresters Type 1

900 269
NH00 N 255

DGP B

DGP B NH00 N 255


B/NH/n

DEHNgap
900 269

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

POWER SUPPLY SYSTEMS


N-PE LIGHTNING CURRENT ARRESTERS

Dimension drawing DGP B NH00 N 255

Surge Arresters
Type 3

Accessories

DEHNgap
DEHNgap B NH00

Basic circuit diagram DGP B NH00 N 255

N-PE Arresters Type 1

DGP B NH00 N 255: Single-pole N-PE lightning current arrester, NH design, size 00

DGP B NH00 N 255


SPD according to EN 61643-11
SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Response time tA
Temporary overvoltage (TOV)
TOV characteristics
Operating temperature range TU
For mounting on
Enclosure material
Ordering information
Type
Part No.
Packing unit

www.dehn.de

Type 1
Class I
255 V
50 kA
50 kA
) 4 kV
100 Arms
) 100 ns
1200 V / 200 ms
withstand
-40C...+80C
NH fuse holder, size 00
thermoplastic, red, UL 94 V-0

DGP B NH00 N 255


900 269
1 pc(s).

67

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNgap
DEHNgap Maxi 440 (FM)

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


N-PE LIGHTNING CURRENT ARRESTERS
PE

PE

961 160
440
961 165
440 FM

DGPM 440
961 160
DGPM 440 FM
961 165

12
11
14
N

( 2 mods.)

Basic circuit diagram DGPM 440 FM

Dimension drawing DGPM 440

N-PE Arresters Type 1

DGPM 440 (FM): Coordinated, single-pole N-PE lightning current arrester for UC = 440 V

SPD according to EN 61643-11


SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Lightning impulse current (10/350 s) Iimp
Nominal discharge current (8/20 s) In
Voltage protection level UP
Follow current extinguishing capability a.c. Ifi
Response time tA
Temporary overvoltage (TOV)
TOV characteristics
Operating temperature range (parallel connection) TUP
Operating temperature range (series connection) TUS
Operating state/fault indication
Cross-sectional area (N, PE, 9) min.
Cross-sectional area (N, PE) max.
Cross-sectional area (9) max.
For mounting on
Enclosure material
Degree of protection
Capacity
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

68

DGPM 440

DGPM 440 FM

Type 1
Class I
440 V
100 kA
100 kA
) 2.5 kV
100 Arms
) 100 ns
1200 V / 200 ms
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715

Type 1
Class I
440 V
100 kA
100 kA
) 2.5 kV
100 Arms
) 100 ns
1200 V / 200 ms
withstand
-40C...+80C
-40C...+60C
green / red
10 mm2 solid/flexible
50 mm2 stranded/35 mm2 flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715

thermoplastic, red, UL 94 V-0


IP 20
2 mods., DIN 43880

thermoplastic, red, UL 94 V-0


IP 20
2 mods., DIN 43880
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DGPM 440
961 160
1 pc(s).

DGPM 440 FM
961 165
1 pc(s).

www.dehn.de

DGPM
DGPM

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard modular CI
Modular surge arrester
with integrated backup fuse
Arrester backup fuse integrated in the protection module
Prewired complete unit consisting of a base
part and plug-in protection modules
Energy coordination within the Red/Line product family
High discharge capacity
High reliability due to Thermo Dynamic
Control SPD monitoring device
Easy replacement of protection modules without tools due to module locking system with
module release button

Surge Arresters Type 2

For protecting low-voltage consumers installations against surges. For


use in conformity with the lightning protection zones concept at the
boundaries from 0B 1 and higher.

DEHNguard M TNC CI 275: modular surge arrester with integrated backup fuse for TN-C systems
DEHNguard M TNS CI 275: with integrated backup fuse for TN-S systems
DEHNguard M TT CI 275:
with integrated backup fuse for TT and TN-S systems (3+1 circuits)
DEHNguard M TN CI 275: with integrated backup fuse for 230 V TN systems
DEHNguard M TT 2P CI 275: with integrated backup fuse for 230 V TT and TN systems (1+1 circuits)
DEHNguard S CI 275:
single-pole, modular surge arrester with integrated backup fuse
DEHNguard M ... CI 275 FM: with remote signalling contact for the monitoring device (floating changeover contact)
The modular surge arresters of the DEHNguard M ... CI family with their
functional Red/Line design combine short-circuit protection and surge
protection in a single protection module. This sets new standards for userfriendly surge and short-circuit protection.
The protective circuit with the arrester backup fuse integrated in the protection module and the heavy-duty zinc oxide varistor in combination
with the dual Thermo Dynamic Control monitoring device offer the advantage of easy installation and minimum space requirements.
Due to the integrated arrester backup fuse the user does not have to
worry about arrester-specific dimensioning requirements such as backup
protection in case of short-circuits and impulse current carrying capacity.
The user has the possibility to implement space-saving surge protection
measures in installations up to short-circuit currents of 25 kArms which
cover all functions specified in the IEC 60364-5-53 installation standard.
All circuits including the N-PE circuit feature an operating state indication
required in accordance with the IEC 60364-5-53 standard.
The Thermo Dynamic Control monitoring device does not only evaluate
the surface temperature of the heavy-duty varistor but also the intensity
of the discharge current. The mechanical visual indication with green and
red flags, which is free of operating currents, shows if every protective circuit is ready for operation. The visual indication indicates the activation of
the Thermo Dynamic Control monitoring device and the integrated
arrester backup fuse.

www.dehn.de

Apart from the mechanical operating state/fault indication, the ...FM version of the DEHNguard M ...CI devices features a three-pole remote signalling terminal. With its floating changeover contact, the remote signal
can be used as break or make contact according to the particular circuit
concept.
All benefits of the modular design of the DEHNguard M family were completely integrated into the new DEHNguard M ... CI family.
The system-configuration-specific product designation as well as the
Thermo Dynamic Control monitoring device reflect the high safety
requirements.
The unique module locking system prevents the protection modules from
becoming loose due to shock during transport or due to the enormous
forces of discharge. Nevertheless, the protection modules can be easily
replaced without tools, the need to de-energise and removing the cover
of the distribution board by simply pressing the user-friendly module
release button of the protection modules. To prevent incorrect insertion by
the installer or user, every protective circuit of the multipole and singlepole SPDs and every protection module is mechanically coded.
The surge arresters of the mutlipole modular DEHNguard M ... CI family
feature multifunctional terminals on a standardised spacing of 1 module
for connecting conductors and busbars, allowing easy wiring with other
DIN rail mounted devices. Thus, a variety of applications can be easily connected in series in accordance with IEC 60364-5-53 for optimal protection.

69

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


DEHNguard modular with integrated backup fuse
SURGE ARRESTERS TYPE 2
DEHNguard M TNC CI 275 (FM)
L1

NEW

L2

952 304
952 309

L3
DG M TNC CI 275
952 304
DG M TNC CI 275 FM
952 309

12
11
14

PEN

Basic circuit diagram DG M TNC CI 275 FM

Dimension drawing DG M TNC CI 275 FM

Surge Arresters Type 2

DG M TNC CI 275 (FM): Modular surge arrester with integrated backup fuses for TN-C systems

DG M TNC CI 275

DG M TNC CI 275 FM

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Voltage protection level at 5 kA UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)

Type 2
Class II
230/400 V
275 V
12.5 kA
25 kA
) 1.5 kV
) 1 kV
) 25 ns
not required
25 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

Type 2
Class II
230/400 V
275 V
12.5 kA
25 kA
) 1.5 kV
) 1 kV
) 25 ns
not required
25 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
3 mods., DIN 43880
KEMA

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
3 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG M TNC CI 275
952 304
1 pc(s).

DG M TNC CI 275 FM
952 309
1 pc(s).

Ordering information
Type
Part No.
Packing unit

Accessory Part for DEHNguard modular with integrated backup fuse


NEW

Varistor-based protection module for


DEHNguard M CI

952 020
CI 275

DG MOD

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 comprising a varistor connected in series with the integrated backup fuse
DG MOD CI 275
952 020

Type
DG MOD CI 275

70

PU
pc(s).
1

Part
No.
952 020

www.dehn.de

DG M TNC CI 275
DG M TNC CI 275 FM

Combined
Arresters Type 1

DG M TNS CI 275
DG M TNS CI 275 FM

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


DEHNguard modular with integrated backup fuse
SURGE ARRESTERS TYPE 2
DEHNguard M TNS CI 275 (FM)
L1

L2

L3

PE

NEW

DG M TNS CI 275
952 401
DG M TNS CI 275 FM
952 406

12
11
14

Dimension drawing DG M TNS CI 275 FM

Basic circuit diagram DG M TNS CI 275 FM

DG M TNS CI 275 (FM): Modular surge arrester with integrated backup fuses for TN-S systems

DG M TNS CI 275

DG M TNS CI 275 FM

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Voltage protection level at 5 kA UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)

Type 2
Class II
230/400 V
275 V
12.5 kA
25 kA
) 1.5 kV
) 1 kV
) 25 ns
not required
25 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

Type 2
Class II
230/400 V
275 V
12.5 kA
25 kA
) 1.5 kV
) 1 kV
) 25 ns
not required
25 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG M TNS CI 275
952 401
1 pc(s).

DG M TNS CI 275 FM
952 406
1 pc(s).

Ordering information
Type
Part No.
Packing unit

Accessory Part for DEHNguard modular with integrated backup fuse


Varistor-based protection module for N-PE circuits
952 010
275

DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
DG MOD 275
952 010

Type
DG MOD 275

www.dehn.de

PU
pc(s).
1

Part
No.
952 010

Surge Arresters Type 2

952 401
952 406

Lightning Current
Arresters Type 1

Accessory Part for DEHNguard modular with integrated backup fuse


Varistor-based protection module for
DEHNguard M CI

952 020
CI 275

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 comprising a varistor connected in series with the integrated backup fuse

DG MOD CI 275
952 020

Type
DG MOD CI 275

PU
pc(s).
1

DG MOD

NEW

Part
No.
952 020

71

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


DEHNguard modular with integrated backup fuse
SURGE ARRESTERS TYPE 2
DEHNguard M TT CI 275 (FM)
L1

NEW

L2

L3

952 322
952 327

N
DG M TT CI 275
952 322
DG M TT CI 275 FM
952 327

12
11
14

PE

Basic circuit diagram DG M TT CI 275 FM

Dimension drawing DG M TT CI 275 FM

Surge Arresters Type 2

DG M TT CI 275 (FM): Modular surge arrester with integrated backup fuses for TT and TN-S systems (3+1 circuits)
DG M TT CI 275

DG M TT CI 275 FM

Type 2 / Class II
230/400 V
275 V
255 V
12.5 kA
20 kA
25 kA
40 kA
12 kA
) 1.5 kV
) 1 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
not required
25 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

Type 2 / Class II
230/400 V
275 V
255 V
12.5 kA
20 kA
25 kA
40 kA
12 kA
) 1.5 kV
) 1 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
not required
25 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG M TT CI 275
952 322
1 pc(s).

DG M TT CI 275 FM
952 327
1 pc(s).

SPD according to EN 61643-11 / ... IEC 61643-1


Nominal a.c. voltage UN
Max. continuous operating a.c. voltage [L-N] UC
Max. continuous operating a.c. voltage [N-PE] UC
Nominal discharge current (8/20 s) [L-N] In
Nominal discharge current (8/20 s) [N-PE] In
Max. discharge current (8/20 s) [L-N] Imax
Max. discharge current (8/20 s) [N-PE] Imax
Lightning impulse current (10/350 s) [N-PE] Iimp
Voltage protection level [L-N] UP
Voltage protection level [L-N] at 5 kA UP
Voltage protection level [N-PE] UP
Follow current extinguishing capability [N-PE] Ifi
Response time [L-N] tA
Response time [N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [N-PE] UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

Accessory Part for DEHNguard modular with integrated backup fuse


NEW

Varistor-based protection module for


DEHNguard M CI

DG MOD

Accessory Part for DEHNguard modular with integrated backup fuse


N-PE spark-gap-based protection module for
DEHNguard M TT ...
952 050
NPE

DG MOD

DG MOD NPE
952 050

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 comprising a varistor connected in series with the integrated backup fuse
DG MOD CI 275
952 020

Type
DG MOD CI 275

72

952 020
CI 275

PU
pc(s).
1

Part
No.
952 020

DG MOD NPE: N-PE spark-gap-based protection module for two- and


four-pole DEHNguard DG M TT ... surge arresters
Type
DG MOD NPE

PU
pc(s).
1

Part
No.
952 050
www.dehn.de

DG M TT CI 275
DG M TT CI 275 FM

Combined
Arresters Type 1

DG M TN CI 275
DG M TN CI 275 FM

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


DEHNguard modular with integrated backup fuse
SURGE ARRESTERS TYPE 2
DEHNguard M TN CI 275 (FM)
L

PE

NEW

DG M TN CI 275
952 173
DG M TN CI 275 FM
952 178

12
11
14

Dimension drawing DG M TN CI 275 FM

Basic circuit diagram DG M TN CI 275 FM

DG M TN CI 275 (FM): Modular surge arrester with integrated backup fuse for single-phase
230 V TN systems

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Voltage protection level at 5 kA UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact

DG M TN CI 275

DG M TN CI 275 FM

Type 2
Class II
230 V
275 V
12.5 kA
25 kA
) 1.5 kV
) 1 kV
) 25 ns
not required
25 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA

Type 2
Class II
230 V
275 V
12.5 kA
25 kA
) 1.5 kV
) 1 kV
) 25 ns
not required
25 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA
changeover contact

250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG M TN CI 275
952 173
1 pc(s).

DG M TN CI 275 FM
952 178
1 pc(s).

Switching capacity a.c.


Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

Accessory Part for DEHNguard modular with integrated backup fuse


Varistor-based protection module for N-PE circuits
952 010
275

DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
DG MOD 275
fr DG M und DG S, 275 V

Type
DG MOD 275

www.dehn.de

S-Modul
952 010

PU
pc(s).
1

Part
No.
952 010

Surge Arresters Type 2

952 173
952 178

Lightning Current
Arresters Type 1

Accessory Part for DEHNguard modular with integrated backup fuse


Varistor-based protection module for
DEHNguard M CI

952 020
CI 275

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 comprising a varistor connected in series with the integrated backup fuse
Type
DG MOD CI 275

PU
pc(s).
1

DG MOD

NEW

DG MOD CI 275
952 020

Part
No.
952 020

73

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


DEHNguard modular with integrated backup fuse
SURGE ARRESTERS TYPE 2
DEHNguard M TT 2P CI 275 (FM)
L

NEW

952 171
952 176

N
DG M TT 2P CI 275
952 171
DG M TT 2P CI 275 FM
952 176

12
11
14

PE

Basic circuit diagram DG M TT 2P CI 275 FM

Dimension drawing DG M TT 2P CI 275 FM

Surge Arresters Type 2

DG M TT 2P CI 275 (FM): Modular surge arrester with integrated backup fuse for single-phase
230 V TT and TN systems (1+1 circuits)
DG M TT 2P CI 275

DG M TT 2P CI 275 FM

Type 2 / Class II
230 V
275 V
255 V
12.5 kA
20 kA
25 kA
40 kA
12 kA
) 1.5 kV
) 1 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
not required
25 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

Type 2 / Class II
230 V
275 V
255 V
12.5 kA
20 kA
25 kA
40 kA
12 kA
) 1.5 kV
) 1 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
not required
25 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG M TT 2P CI 275
952 171
1 pc(s).

DG M TT 2P CI 275 FM
952 176
1 pc(s).

SPD according to EN 61643-11 / ... IEC 61643-1


Nominal a.c. voltage UN
Max. continuous operating a.c. voltage [L-N] UC
Max. continuous operating a.c. voltage [N-PE] UC
Nominal discharge current (8/20 s) [L-N] In
Nominal discharge current (8/20 s) [N-PE] In
Max. discharge current (8/20 s) [L-N] Imax
Max. discharge current (8/20 s) [N-PE] Imax
Lightning impulse current (10/350 s) [N-PE] Iimp
Voltage protection level [L-N] UP
Voltage protection level [L-N] at 5 kA UP
Voltage protection level [N-PE] UP
Follow current extinguishing capability [N-PE] Ifi
Response time [L-N] tA
Response time [N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [N-PE] UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

Accessory Part for DEHNguard modular with integrated backup fuse


NEW

Varistor-based protection module for


DEHNguard M CI

952 020
CI 275

DG MOD

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 comprising a varistor connected in series with the integrated backup fuse
DG MOD CI 275
952 020

Type
DG MOD CI 275

74

PU
pc(s).
1

Part
No.
952 020

Accessory Part for DEHNguard modular with integrated backup fuse


N-PE spark-gap-based protection module for
DEHNguard M TT ...
952 050
NPE

DG MOD

DG MOD NPE
N-PE fr DG M TT

S-Modul
952 050

DG MOD NPE: N-PE spark-gap-based protection module for two- and


four-pole DEHNguard DG M TT ... surge arresters
Type
DG MOD NPE

PU
pc(s).
1

Part
No.
952 050
www.dehn.de

DG M TT 2P CI 275
DG M TT 2P CI 275 FM

Combined
Arresters Type 1

DG S CI 275
DG S CI 275 FM

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


DEHNguard modular with integrated backup fuse
SURGE ARRESTERS TYPE 2
DEHNguard S CI 275 (FM)
NEW

DG S CI 275
952 079
DG S CI 275 FM
952 099

12
11
14

Dimension drawing DG S CI 275 FM

Basic circuit diagram DG S CI 275 FM

DG S CI 275 (FM): Single-pole, pluggable surge arrester consisting of a base part and plug-in protection module; with integrated backup fuse; optionally available with floating
remote signalling contact

SPD according to EN 61643-11


SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Voltage protection level at 5 kA UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

DG S CI 275

DG S CI 275 FM

Type 2
Class II
275 V
12.5 kA
25 kA
) 1.5 kV
) 1 kV
) 25 ns
not required
25 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715

Type 2
Class II
275 V
12.5 kA
25 kA
) 1.5 kV
) 1 kV
) 25 ns
not required
25 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715

thermoplastic, red, UL 94 V-0


IP 20
1 mod., DIN 43880
KEMA

thermoplastic, red, UL 94 V-0


IP 20
1 mod., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG S CI 275
952 079
1 pc(s).

DG S CI 275 FM
952 099
1 pc(s).

Surge Arresters Type 2

952 079
952 099

Lightning Current
Arresters Type 1

Accessory Part for DEHNguard modular with integrated backup fuse


Varistor-based protection module for
DEHNguard M CI

952 020
CI 275

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 comprising a varistor connected in series with the integrated backup fuse

DG MOD CI 275
952 020

Type
DG MOD CI 275

www.dehn.de

PU
pc(s).
1

DG MOD

NEW

Part
No.
952 020

75

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

DEHNguard modular
Multipole, modular surge arrester

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

Prewired complete unit consisting of a base


part and plug-in protection modules
Energy coordination within the Red/Line product family
High discharge capacity due to heavy-duty zinc
oxide varistors/spark gaps
High reliability due to Thermo Dynamic
Control SPD monitoring device
Easy replacement of protection modules due to
module locking system with module release
button
Vibration- and shock-tested according to EN
60068-2

Surge Arresters Type 2

For protecting low-voltage consumers installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0B 1 and higher.

DEHNguard M TNC ...:


DEHNguard M TNS ...:
DEHNguard M TT ...:
DEHNguard M TN ...:
DEHNguard M TT 2P ...:
DEHNguard M WE ...:
DEHNguard M ... FM:

Modular surge arrester for use in TN-C systems


Modular surge arrester for use in TN-S systems
Modular surge arrester for use in TT and TN-S systems (3+1 circuit)
Modular surge arrester for use in single-phase TN systems
Modular surge arrester for use in single-phase TT and TN systems (1+1 circuit)
Modular surge arrester especially for use in wind turbines
With remote signalling contact for the monitoring device (floating changeover contact)

The modular DEHNguard M ... surge arresters with their functional


Red/Line family design set new standards in terms of safety and userfriendliness. The approved protective circuit with heavy-duty zinc oxide
varistors in combination with the dual Thermo Dynamic Control monitoring device characterise the DEHNguard technology.
Many features of the device show that both safe surge protection and
reliability of the devices are the key element of the new modular
DEHNguard. The application-oriented product designation, which makes
the choice of the adequate devices considerably easier, as well as the
module locking device, which is unique for use with surge protective
devices, stand for fulfilling stringent safety requirements. It fixes the protection modules and the base part of the device firmly in place. Neither
vibration during transport nor the enormous electromagnetic forces of
discharge can loosen the protection modules. Nevertheless, they can be
easily replaced without tools by simply pressing the user-friendly module
release button of the protection modules. In order to avoid incorrect insertion by the installer or user when replacing the modules, each protective
circuit of the multipole surge arresters and each protection module are
mechanically coded.

76

The dual Thermo Dynamic Control monitoring device was not only developed on the basis of national and international product standards, but it
also stands for experience of decades in the international use of surge
protective devices and considers many fields of application where SPDs
might be damaged. Like with all DEHN surge arresters with Thermo
Dynamic Control, evaluation is based on the intensity of the discharge
current and the surface temperature of the heavy-duty varistor. The green
and red indicator shows if each protective circuit is ready for operation.
Apart from this standard visual indication, DEHNguard M ... FM devices
feature a three-pole terminal for remote signalling.
With their floating changeover contact, the remote signal can be used as
a make or break contract according to the particular circuit concept. The
surge arresters of the multipole modular DEHNguard M family feature
multifunctional terminals on a standardised spacing of 1 module for the
connection of conductors
and busbars, allowing
easy wiring with other
DIN rail mounted devices.
Thus a variety of applications can be connected in
series according to IEC
60364-5-53 for optimal
protection.

www.dehn.de

Combined
Arresters Type 1

952 313
952 300
952 314
952 303

DG M TNC 150
DG M TNC 275
DG M TNC 385
DG M TNC 440

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard modular
DEHNguard M TNC ...

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
L1

L2

L3

PEN

DG M TNC 150
952 313
DG M TNC 275
952 300
DG M TNC 385
952 314
DG M TNC 440
952 303

Dimension drawing DG M TNC ...

Basic circuit diagram DG M TNC ...

DG M TNC 150
SPD according to EN 61643-11
Type 2
SPD according to IEC 61643-1
Class II
Nominal a.c. voltage UN
120/240 V
Max. continuous operating a.c. voltage UC
150 V
Nominal discharge current (8/20 s) In
15 kA
Max. discharge current (8/20 s) Imax
40 kA
Voltage protection level UP
) 0.7 kV
Voltage protection level at 5 kA UP
) 0.55 kV
Response time tA
) 25 ns
Max. mains-side overcurrent protection
125 A gL/gG
Short-circuit withstand capability
for max. mains-side overcurrent protection
50 kArms
Temporary overvoltage (TOV) UT
175 V / 5 sec.
TOV characteristics
withstand
Operating temperature range TU
-40C...+80C
Operating state/fault indication
green / red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

DG M TNC 275

DG M TNC 385

DG M TNC 440

Type 2
Class II
230/400 V
275 V
20 kA
40 kA
) 1.25 kV
) 1 kV
) 25 ns
125 A gL/gG

Type 2
Class II
230/400 V
385 V
20 kA
40 kA
) 1.75 kV
) 1.35 kV
) 25 ns
125 A gL/gG

Type 2
Class II
400/690 V
440 V
20 kA
40 kA
) 2 kV
) 1.7 kV
) 25 ns
125 A gL/gG

50 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

25 kArms
385 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

25 kArms
580 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

Surge Arresters Type 2

DG M TNC ... : Modular surge arrester for TN-C systems

35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
thermoplastic, red, UL 94 V-0
thermoplastic, red, UL 94 V-0
thermoplastic, red, UL 94 V-0
IP 20
IP 20
IP 20
IP 20
3 mods., DIN 43880
3 mods., DIN 43880
3 mods., DIN 43880
3 mods., DIN 43880

KEMA, VDE, UL, VdS

DG M TNC 150
952 313 NEW
1 pc(s).

DG M TNC 275
952 300
1 pc(s).

DG M TNC 385
952 314 NEW
1 pc(s).

DG M TNC 440
952 303
1 pc(s).

Accessory Part for DEHNguard modular


Varistor-based protection module
952 012
150
952 010
275
952 013
320
952 014
385
952 015
440

DG MOD
DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
952 015

Type
DG MOD 150
DG MOD 275
DG MOD 385
DG MOD 440

www.dehn.de

DG MOD

PU
pc(s).
1
1
1
1

Part
No.
952 012
952 010
952 014
952 015

77

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNguard modular
DEHNguard M TNC ... FM

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
L1

L2

952 318
952 305
952 319
952 308

L3
DG M TNC 150 FM
952 318
DG M TNC 275 FM
952 305
DG M TNC 385 FM
952 319
DG M TNC 440 FM
952 308

12
11
14

PEN

Basic circuit diagram DG M TNC ... FM

Dimension drawing DG M TNC ... FM

DG M TNC ... FM: Modular surge arrester for TN-C systems; with floating remote signalling contact

Surge Arresters Type 2

DG M TNC 150 FM
SPD according to EN 61643-11
Type 2
SPD according to IEC 61643-1
Class II
Nominal a.c. voltage UN
120/240 V
Max. continuous operating a.c. voltage UC
150 V
Nominal discharge current (8/20 s) In
15 kA
Max. discharge current (8/20 s) Imax
40 kA
Voltage protection level UP
) 0.7 kV
Voltage protection level at 5 kA UP
) 0.55 kV
Response time tA
) 25 ns
Max. mains-side overcurrent protection
125 A gL/gG
Short-circuit withstand capability
for max. mains-side overcurrent protection
50 kArms
Temporary overvoltage (TOV) UT
175 V / 5 sec.
TOV characteristics
withstand
Operating temperature range TU
-40C...+80C
Operating state/fault indication
green / red
Cross-sectional area (min.)
1.5 mm2 solid/flexible

DG M TNC 275 FM

DG M TNC 385 FM

DG M TNC 440 FM

Type 2
Class II
230/400 V
275 V
20 kA
40 kA
) 1.25 kV
) 1 kV
) 25 ns
125 A gL/gG

Type 2
Class II
230/400 V
385 V
20 kA
40 kA
) 1.75 kV
) 1.35 kV
) 25 ns
125 A gL/gG

Type 2
Class II
400/690 V
440 V
20 kA
40 kA
) 2 kV
) 1.7 kV
) 25 ns
125 A gL/gG

50 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

25 kArms
385 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

25 kArms
580 V / 5 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

Cross-sectional area (max.)


35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible 35 mm2 stranded/25 mm2 flexible
For mounting on
35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Enclosure material
thermoplastic, red, UL 94 V-0
thermoplastic, red, UL 94 V-0
thermoplastic, red, UL 94 V-0
thermoplastic, red, UL 94 V-0
Degree of protection
IP 20
IP 20
IP 20
IP 20
Capacity
3 mods., DIN 43880
3 mods., DIN 43880
3 mods., DIN 43880
3 mods., DIN 43880
Approvals, Certifications

KEMA, VDE, UL, VdS

Type of remote signalling contact


changeover contact
changeover contact
changeover contact
changeover contact
Switching capacity a.c.
250 V/0.5 A
250 V/0.5 A
250 V/0.5 A
250 V/0.5 A
Switching capacity d.c.
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals
max. 1.5 mm2 solid/flexible
Ordering information
Type
Part No.
Packing unit

DG M TNC 150 FM
NEW 952 318
1 pc(s).

DG M TNC 275 FM
952 305
1 pc(s).

DG M TNC 385 FM
E
N W 952 319
1 pc(s).

DG M TNC 440 FM
952 308
1 pc(s).

Accessory Part for DEHNguard modular


952 012
150
952 010
275
952 013
320
952 014
385
952 015
440
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
952 015

78

DG MOD
DG MOD

Varistor-based protection module

DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
Type
DG MOD 150
DG MOD 275
DG MOD 385
DG MOD 440

PU
pc(s).
1
1
1
1

Part
No.
952 012
952 010
952 014
952 015

www.dehn.de

DG M TNC 150 FM
DG M TNC 275 FM
DG M TNC 385 FM
DG M TNC 440 FM

Combined
Arresters Type 1

952 403
952 400
952 404

DG M TNS 150
DG M TNS 275
DG M TNS 385

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard modular
DEHNguard M TNS ...

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
L1

L2

L3

PE

DG M TNS 150
952 403
DG M TNS 275
952 400
DG M TNS 385
952 404

Dimension drawing DG M TNS ...

Basic circuit diagram DG M TNS ...

DG M TNS ... : Modular surge arrester for TN-S systems

Cross-sectional area (max.)


For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

DG M TNS 150

DG M TNS 275

DG M TNS 385

Type 2
Class II
120/240 V
150 V
15 kA
40 kA
) 0.7 kV
) 0.55 kV
) 25 ns
125 A gL/gG

Type 2
Class II
230/400 V
275 V
20 kA
40 kA
) 1.25 kV
) 1 kV
) 25 ns
125 A gL/gG

Type 2
Class II
230/400 V
385 V
20 kA
40 kA
) 1.75 kV
) 1.35 kV
) 25 ns
125 A gL/gG

50 kArms
175 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

50 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

25 kArms
385 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA, UL

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA, VDE, UL, VdS

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA, UL

DG M TNS 150
952 403 NEW
1 pc(s).

DG M TNS 275
952 400
1 pc(s).

Surge Arresters Type 2

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Voltage protection level at 5 kA UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
for max. mains-side overcurrent protection
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)

DG M TNS 385
952 404 NEW
1 pc(s).

Accessory Part for DEHNguard modular


Varistor-based protection module
952 012
150
952 010
275
952 013
320
952 014
385
952 015
440

DG MOD
DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
952 015

Type
DG MOD 150
DG MOD 275
DG MOD 385

www.dehn.de

DG MOD

PU
pc(s).
1
1
1

Part
No.
952 012
952 010
952 014

79

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNguard modular
DEHNguard M TNS ... FM

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
L1

L2

L3

952 408
952 405
952 409

N
DG M TNS 150 FM
952 408
DG M TNS 275 FM
952 405
DG M TNS 385 FM
952 409

12
11
14

PE

Basic circuit diagram DG M TNS ... FM

Dimension drawing DG M TNS ... FM

DG M TNS ... FM: Modular surge arrester for TN-S systems; with floating remote signalling contact

DG M TNS 150 FM

DG M TNS 275 FM

DG M TNS 385 FM

Type 2
Class II
120/240 V

Type 2
Class II
230/400 V

Type 2
Class II
230/400 V

150 V
15 kA
40 kA
) 0.7 kV
) 0.55 kV
) 25 ns
125 A gL/gG

275 V
20 kA
40 kA
) 1.25 kV
) 1 kV
) 25 ns
125 A gL/gG

385 V
20 kA
40 kA
) 1.75 kV
) 1.35 kV
) 25 ns
125 A gL/gG

50 kArms
175 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA, UL
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

50 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA, VDE, UL, VdS
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

25 kArms
385 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA, UL
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

Surge Arresters Type 2

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Voltage protection level at 5 kA UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
for max. mains-side overcurrent protection
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

DG M TNS 150 FM
952 408
NEW
1 pc(s).

DG M TNS 275 FM
952 405
1 pc(s).

DG M TNS 385 FM
952 409
NEW
1 pc(s).

Accessory Part for DEHNguard modular


952 012
150
952 010
275
952 013
320
952 014
385
952 015
440
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
952 015

80

DG MOD
DG MOD

Varistor-based protection module

DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
Type
DG MOD 150
DG MOD 275
DG MOD 385

PU
pc(s).
1
1
1

Part
No.
952 012
952 010
952 014

www.dehn.de

DG M TNS 150 FM
DG M TNS 275 FM
DG M TNS 385 FM

Combined
Arresters Type 1

DG M TT 275
DG M TT 320
DG M TT 385

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard modular
DEHNguard M TT ...

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
L1

DG M TT 275
952 310
DG M TT 320
952 320
DG M TT 385
952 311

Dimension drawing DG M TT ...

L2

L3

PE

Basic circuit diagram DG M TT ...

DG M TT ... : Modular surge arrester for TT and TN-S systems (3+1 circuits)

DG M TT 275

DG M TT 320

DG M TT 385

Type 2
Class II
230/400 V

Type 2
Class II
230/400 V

Type 2
Class II
230/400 V

275 V
255 V
20 kA
40 kA
12 kA
) 1.25 kV
) 1 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

320 V
255 V
20 kA
40 kA
12 kA
) 1.5 kV
) 1.2 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

385 V
255 V
20 kA
40 kA
12 kA
) 1.75 kV
) 1.35 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

50 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA, VDE, UL, VdS

25 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA

25 kArms
385 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage [L-N] UC
Max. continuous operating a.c. voltage [N-PE] UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Lightning impulse current (10/350 s) [N-PE] Iimp
Voltage protection level [L-N] UP
Voltage protection level [L-N] at 5 kA UP
Voltage protection level [N-PE] UP
Follow current extinguishing capability [N-PE] Ifi
Response time [L-N] tA
Response time [N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
for max. mains-side overcurrent protection
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [N-PE] UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

DG M TT 275
952 310
1 pc(s).

Accessory Part for DEHNguard modular


DG MOD

DG MOD NPE: N-PE spark-gap-based protection module for two- and


four-pole DEHNguard DG M TT ... surge arresters
DG MOD NPE
952 050

Type
DG MOD NPE

www.dehn.de

PU
pc(s).
1

DG M TT 385
952 311 NE
W
1 pc(s).

Accessory Part for DEHNguard modular

N-PE spark-gap-based protection module for


DEHNguard M TT ...
952 050
NPE

DG M TT 320
952 320 NEW
1 pc(s).

Surge Arresters Type 2

952 310
952 320
952 311

Lightning Current
Arresters Type 1

Part
No.
952 050

Varistor-based protection module


952 012
150
952 010
275
952 013
320
952 014
385
952 015
440

DG MOD
DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
952 015

Type
DG MOD 275
DG MOD 320
DG MOD 385

DG MOD

PU
pc(s).
1
1
1

Part
No.
952 010
952 013
952 014

81

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNguard modular
DEHNguard M TT ... FM

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
L1

L2

L3

952 315
952 325
952 316

N
DG M TT 275 FM
952 315
DG M TT 320 FM
952 325
DG M TT 385 FM
952 316

12
11
14

PE

Basic circuit diagram DG M TT ... FM

Dimension drawing DG M TT ... FM

Surge Arresters Type 2

DG M TT ... FM: Modular surge arrester for TT and TN-S systems (3+1 circuits); with floating
remote signalling contact

SPD according to EN 61643-11 / ... IEC 61643-1


Nominal a.c. voltage UN
Max. continuous operating a.c. voltage [L-N] UC
Max. continuous operating a.c. voltage [N-PE] UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Lightning impulse current (10/350 s) [N-PE] Iimp
Voltage protection level [L-N] UP
Voltage protection level [L-N] at 5 kA UP
Voltage protection level [N-PE] UP
Follow current extinguishing capability [N-PE] Ifi
Response time [L-N] tA
Response time [N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
for max. mains-side overcurrent protection
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [N-PE] UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals

DG M TT 275 FM

DG M TT 320 FM

DG M TT 385 FM

Type 2 / Class II
230/400 V
275 V
255 V
20 kA
40 kA
12 kA
) 1.25 kV
) 1 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

Type 2 / Class II
230/400 V
320 V
255 V
20 kA
40 kA
12 kA
) 1.5 kV
) 1.2 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

Type 2 / Class II
230/400 V
385 V
255 V
20 kA
40 kA
12 kA
) 1.75 kV
) 1.35 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

50 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

25 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

25 kArms
385 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA, VDE, UL, VdS
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

Ordering information
Type
Part No.
Packing unit

DG M TT 275 FM
952 315
1 pc(s).

Accessory Part for DEHNguard modular


952 012
150
952 010
275
952 013
320
952 014
385
952 015
440
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
952 015

82

DG MOD
DG MOD

DG M TT 320 FM
E
N W 952 325
1 pc(s).

Accessory Part for DEHNguard modular

Varistor-based protection module

952 050
NPE

DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
Type
DG MOD 275
DG MOD 320
DG MOD 385

DG M TT 385 FM
952 316
W
NE
1 pc(s).

PU
pc(s).
1
1
1

Part
No.
952 010
952 013
952 014

DG MOD NPE
952 050

DG MOD

N-PE spark-gap-based protection module for


DEHNguard M TT ...
DG MOD NPE: N-PE spark-gap-based protection module for two- and
four-pole DEHNguard DG M TT ... surge arresters
Type
DG MOD NPE

PU
pc(s).
1

Part
No.
952 050

www.dehn.de

DG M TT 275 FM
DG M TT 320 FM
DG M TT 385 FM

Combined
Arresters Type 1

952 201
952 200

DG M TN 150
DG M TN 275

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard modular
DEHNguard M TN ...

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
L

PE

DG M TN 150
952 201
DG M TN 275
952 200

Dimension drawing DG M TN ...

Basic circuit diagram DG M TN ...

DG M TN ... : Modular surge arrester for single-phase TN systems


DG M TN 150

DG M TN 275

Ordering information
Type
Part No.
Packing unit

Type 2
Class II
230 V
275 V
20 kA
40 kA
) 1.25 kV
) 1 kV
) 25 ns
125 A gL/gG
50 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA, VDE, UL, VdS

DG M TN 150
952 201 NEW

Surge Arresters Type 2

SPD according to EN 61643-11


Type 2
SPD according to IEC 61643-1
Class II
Nominal a.c. voltage UN
120 V
Max. continuous operating a.c. voltage UC
150 V
Nominal discharge current (8/20 s) In
15 kA
Max. discharge current (8/20 s) Imax
40 kA
Voltage protection level UP
) 0.7 kV
Voltage protection level at 5 kA UP
) 0.55 kV
Response time tA
) 25 ns
Max. mains-side overcurrent protection
125 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 50 kArms
Temporary overvoltage (TOV) UT
175 V / 5 sec.
TOV characteristics
withstand
Operating temperature range TU
-40C...+80C
Operating state/fault indication
green / red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
Cross-sectional area (max.)
35 mm2 stranded/25 mm2 flexible
For mounting on
35 mm DIN rail acc. to EN 60715
Enclosure material
thermoplastic, red, UL 94 V-0
Degree of protection
IP 20
Capacity
2 mods., DIN 43880
Approvals, Certifications

DG M TN 275
952 200

1 pc(s).

1 pc(s).

Accessory Part for DEHNguard modular


Varistor-based protection module
952 010
275
952 012
150
952 013
320
952 014
385
952 015
440

DG MOD

DG MOD 275
fr DG M und DG S, 275 V
DG MOD 150
fr DG M und DG S, 150 V
DG MOD 320
fr DG M und DG S, 320 V
DG MOD 385
fr DG M und DG S, 385 V
DG MOD 440
fr DG M und DG S, 440 V

S-Modul
952 010
S-Modul
952 012
S-Modul
952 013
S-Modul
952 014
S-Modul
952 015

DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
Type
DG MOD 150
DG MOD 275

www.dehn.de

DG MOD

PU
pc(s).
1
1

Part
No.
952 012
952 010

83

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNguard modular
DEHNguard M TN ... FM

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
L

952 206
952 205

N
DG M TN 150 FM
952 206
DG M TN 275 FM
952 205

12
11
14

PE

Basic circuit diagram DG M TN ... FM

Dimension drawing DG M TN ... FM

DG M TN ... FM: Modular surge arrester for single-phase TN systems; with floating remote signalling contact

Surge Arresters Type 2

DG M TN 150 FM
SPD according to EN 61643-11
Type 2
SPD according to IEC 61643-1
Class II
Nominal a.c. voltage UN
120 V
Max. continuous operating a.c. voltage UC
150 V
Nominal discharge current (8/20 s) In
15 kA
Max. discharge current (8/20 s) Imax
40 kA
Voltage protection level UP
) 0.7 kV
Voltage protection level at 5 kA UP
) 0.55 kV
Response time tA
) 25 ns
Max. mains-side overcurrent protection
125 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 50 kArms
Temporary overvoltage (TOV) UT
175 V / 5 sec.
TOV characteristics
withstand
Operating temperature range TU
-40C...+80C
Operating state/fault indication
green / red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
Cross-sectional area (max.)
35 mm2 stranded/25 mm2 flexible
For mounting on
35 mm DIN rail acc. to EN 60715
Enclosure material
thermoplastic, red, UL 94 V-0
Degree of protection
IP 20
Capacity
2 mods., DIN 43880
Approvals, Certifications

Type of remote signalling contact


changeover contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals

250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

Ordering information
Type
Part No.
Packing unit

DG M TN 150 FM
E
N W 952 206
1 pc(s).

DG M TN 275 FM
Type 2
Class II
230 V
275 V
20 kA
40 kA
) 1.25 kV
) 1 kV
) 25 ns
125 A gL/gG
50 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA, VDE, UL, VdS
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG M TN 275 FM
952 205
1 pc(s).

Accessory Part for DEHNguard modular

84

952 010
275
952 012
150
952 013
320
952 014
385
952 015
440

DG MOD

DG MOD 275
fr DG M und DG S, 275 V
DG MOD 150
fr DG M und DG S, 150 V
DG MOD 320
fr DG M und DG S, 320 V
DG MOD 385
fr DG M und DG S, 385 V
DG MOD 440
fr DG M und DG S, 440 V

S-Modul
952 010
S-Modul
952 012
S-Modul
952 013
S-Modul
952 014
S-Modul
952 015

DG MOD

Varistor-based protection module

DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
Type
DG MOD 150
DG MOD 275

PU
pc(s).
1
1

Part
No.
952 012
952 010

www.dehn.de

DG M TN 150 FM
DG M TN 275 FM

Combined
Arresters Type 1

952 110
952 130
952 111

DG M TT 2P 275
DG M TT 2P 320
DG M TT 2P 385

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard modular
DEHNguard M TT 2P ...

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
L

PE

DG M TT 2P 275
952 110
DG M TT 2P 320
952 130
DG M TT 2P 385
952 111

Dimension drawing DG M TT 2P ...

Basic circuit diagram DG M TT 2P ...

DG M TT 2P ... : Modular surge arrester for single-phase TT and TN systems (1+1 circuits)
DG M TT 2P 320

DG M TT 2P 385

Type 2
Class II
230 V
275 V
255 V
20 kA
40 kA
12 kA
) 1.25 kV
) 1 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

Type 2
Class II
230 V
320 V
255 V
20 kA
40 kA
12 kA
) 1.5 kV
) 1.2 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

Type 2
Class II
230 V
385 V
255 V
20 kA
40 kA
12 kA
) 1.75 kV
) 1.35 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

50 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

25 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

25 kArms
385 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA, VDE, UL, VdS

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA

35 mm2 stranded/25 mm2 flexible


35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage [L-N] UC
Max. continuous operating a.c. voltage [N-PE] UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Lightning impulse current (10/350 s) [N-PE] Iimp
Voltage protection level [L-N] UP
Voltage protection level [L-N] at 5 kA UP
Voltage protection level [N-PE] UP
Follow current extinguishing capability [N-PE] Ifi
Response time [L-N] tA
Response time [N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
for max. mains-side overcurrent protection
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [N-PE] UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

DG M TT 2P 275
952 110
1 pc(s).

Accessory Part for DEHNguard modular


DG MOD

DG MOD NPE: N-PE spark-gap-based protection module for two- and


four-pole DEHNguard DG M TT ... surge arresters
DG MOD NPE
952 050

Type
DG MOD NPE

www.dehn.de

PU
pc(s).
1

DG M TT 2P 385
952 111 NEW

1 pc(s).

1 pc(s).

Accessory Part for DEHNguard modular

N-PE spark-gap-based protection module for


DEHNguard M TT ...
952 050
NPE

DG M TT 2P 320
952 130 NEW

Surge Arresters Type 2

DG M TT 2P 275

Part
No.
952 050

Varistor-based protection module


952 010
275
952 012
150
952 013
320
952 014
385
952 015
440

DG MOD

DG MOD 275
fr DG M und DG S, 275 V
DG MOD 150
fr DG M und DG S, 150 V
DG MOD 320
fr DG M und DG S, 320 V
DG MOD 385
fr DG M und DG S, 385 V
DG MOD 440
fr DG M und DG S, 440 V

S-Modul
952 010
S-Modul
952 012
S-Modul
952 013
S-Modul
952 014
S-Modul
952 015

DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
Typ
DG MOD 275
DG MOD 320
DG MOD 385

DG MOD

VPE
Stk.
1
1
1

Art.-Nr.
952 010
952 013
952 014

85

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNguard modular
DEHNguard M TT 2P ... FM

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
L

952 115
952 135
952 116

N
DG M TT 2P 275 FM
952 115
DG M TT 2P 320 FM
952 135
DG M TT 2P 385 FM
952 116

12
11
14

PE

Basic circuit diagram DG M TT 2P ... FM

Dimension drawing DG M TT 2P ... FM

Surge Arresters Type 2

DG M TT 2P ... FM: Modular surge arrester for single-phase TT and TN systems (1+1 circuit);
with floating remote signalling contact

SPD according to EN 61643-11 / ... IEC 61643-1


Nominal a.c. voltage UN
Max. continuous operating a.c. voltage [L-N] UC
Max. continuous operating a.c. voltage [N-PE] UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Lightning impulse current (10/350 s) [N-PE] Iimp
Voltage protection level [L-N] UP
Voltage protection level [L-N] at 5 kA UP
Voltage protection level [N-PE] UP
Follow current extinguishing capability [N-PE] Ifi
Response time [L-N] tA
Response time [N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
for max. mains-side overcurrent protection
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [N-PE] UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals

DG M TT 2P 275 FM

DG M TT 2P 320 FM

DG M TT 2P 385 FM

Type 2 / Class II
230 V
275 V
255 V
20 kA
40 kA
12 kA
) 1.25 kV
) 1 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

Type 2 / Class II
230 V
320 V
255 V
20 kA
40 kA
12 kA
) 1.5 kV
) 1.2 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

Type 2 / Class II
230 V
385 V
255 V
20 kA
40 kA
12 kA
) 1.75 kV
) 1.35 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
125 A gL/gG

50 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

25 kArms
335 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

25 kArms
385 V / 5 sec.
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA, VDE, UL, VdS
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

Ordering information
Type
Part No.
Packing unit

DG M TT 2P 275 FM
952 115
1 pc(s).

Accessory Part for DEHNguard modular

86

952 010
275
952 012
150
952 013
320
952 014
385
952 015
440

DG MOD

DG MOD 275
fr DG M und DG S, 275 V
DG MOD 150
fr DG M und DG S, 150 V
DG MOD 320
fr DG M und DG S, 320 V
DG MOD 385
fr DG M und DG S, 385 V
DG MOD 440
fr DG M und DG S, 440 V

S-Modul
952 010
S-Modul
952 012
S-Modul
952 013
S-Modul
952 014
S-Modul
952 015

DG MOD

DG M TT 2P 320 FM
NEW 952 135
1 pc(s).

Accessory Part for DEHNguard modular

Varistor-based protection module

952 050
NPE

DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
Typ
DG MOD 275
DG MOD 320
DG MOD 385

DG M TT 2P 385 FM
NEW 952 116
1 pc(s).

VPE
Stk.
1
1
1

Art.-Nr.
952 010
952 013
952 014

DG MOD NPE
952 050

DG MOD

N-PE spark-gap-based protection module for


DEHNguard M TT ...
DG MOD NPE: N-PE spark-gap-based protection module for two- and
four-pole DEHNguard DG M TT ... surge arresters
Type
DG MOD NPE

PU
pc(s).
1

Part
No.
952 050

www.dehn.de

DG M TT 2P 275 FM
DG M TT 2P 320 FM
DG M TT 2P 385 FM

Combined
Arresters Type 1

952 302
952 307

DG M WE 600
DG M WE 600 FM

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard modular
DEHNguard M WE ... (FM)

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
L1

L2

L3

PEN

DG M WE 600
952 302
DG M WE 600 FM
952 307

12
11
14

Dimension drawing DG M WE ... FM

Basic circuit diagram DG M WE ... FM

DG M WE ... (FM): Three-pole modular surge arrester for use in wind turbines with a rated voltage
of the varistor Umov = 750 V a.c.; FM version with floating remote signalling
contact

SPD according to EN 61643-11


Type 2
SPD according to IEC 61643-1
Class II
Nominal a.c. voltage UN
600 V
Max. continuous operating a.c. voltage UC
600 V
Rated voltage of varistor Umov
750 V
Nominal discharge current (8/20 s) In
15 kA
Max. discharge current (8/20 s) Imax
25 kA
Voltage protection level UP
) 3 kV
Voltage protection level at 5 kA UP
) 2.5 kV
Response time tA
) 25 ns
Max. mains-side overcurrent protection
100 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 25 kArms
Temporary overvoltage (TOV) UT
900 V / 5 sec.
TOV characteristics
withstand
Operating temperature range TU
-40C...+80C
Operating state/fault indication
green / red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
Cross-sectional area (max.)
35 mm2 stranded/25 mm2 flexible
For mounting on
35 mm DIN rail acc. to EN 60715
Enclosure material
thermoplastic, red, UL 94 V-0
Degree of protection
IP 20
Capacity
3 mods., DIN 43880
Approvals, Certifications
KEMA, UL, VdS
Type of remote signalling contact

Switching capacity a.c.

Switching capacity d.c.

Cross-sectional area for remote signalling terminals

Ordering information
Type
Part No.
Packing unit

DG M WE 600
952 302
1 pc(s).

DG M WE 600 FM
Type 2
Class II
600 V
600 V
750 V
15 kA
25 kA
) 3 kV
) 2.5 kV
) 25 ns
100 A gL/gG
25 kArms
900 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
3 mods., DIN 43880
KEMA, UL, VdS
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

Surge Arresters Type 2

DG M WE 600

DG M WE 600 FM
952 307
1 pc(s).

Accessory Part for DEHNguard modular


Varistor-based protection module for DEHNguard
M (S) WE

952 017
750

DG MOD

DG MOD 750
952 017

DG MOD 750: Varistor-based protection module for DEHNguard M WE


... and DEHNguard S WE ... surge arresters with a rated varistor voltage
Umov = 750 V a.c.
Type
DG MOD 750

www.dehn.de

PU
pc(s).
1

Part
No.
952 017

87

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

DEHNguard S / DEHNguard S FM
Single-pole, pluggable surge arrester

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

Multi-purpose surge arrester consisting of a


base element and plug-in protection module
High discharge capacity due to heavy-duty zinc
oxide varistor
High reliability due to Thermo Dynamic
Control SPD monitoring device
Energy coordination within the Red/Line product family
Narrow (modular) design acc. to DIN 43880
Multifunctional terminals for connecting conductors and busbars
Easy replacement of protection modules due to
module locking system with module release
button

Surge Arresters Type 2

Vibration- and shock-tested according to EN


60068-2

For protecting low-voltage consumers installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0B 1 and higher.

DEHNguard S ...:
Pluggable surge arrester consisting of a base part and plug-in protection module
DEHNguard S ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

The universal features are characteristic of the single-pole devices of the


DEHNguard S product family. Be it as a single device or in combination
with other devices DEHNguard S surge arresters always provide the
right protective circuit. The modern Red/Line family design and its universal features ensure safety and user-friendliness. The module release button and the approved Thermo Dynamic Control SPD monitoring device
with dual tripping performance characterise the devices of the
DEHNguard S series.
Experience of decades in the international use of surge arresters has further improved the latest DEHNguard generation compared to the previous
types.

Like with all DEHNguard surge arresters, the users of DEHNguard S can
rely on the dual Thermo Dynamic Control SPD monitoring device. This
ensures maximum reliability of the devices, even under unfavourable
environmental conditions. The green and red indicator shows if
DEHNguard S is ready for operation. Apart from the standard visual indicator, DEHNguard S ... FM features a three-pole terminal for remote signalling. With its floating changeover contact, the remote signal can be
used as a break or make contact according to the particular circuit concept. The multifunctional terminals of DEHNguard S surge arresters are
suitable for connecting conductors and busbars, allowing an easy connection to other DIN rail mounted devices. Series connection according to IEC
60364-5-53 for optimal protection is therefore possible for a wide range
of applications.

The module locking system, which is unique for use with surge protective
devices, fixes the protection module and the base part firmly in place.
Neither vibration during transport nor the enormous electromagnetic
forces of discharge can loosen this connection. Nevertheless, the modules
can be easily replaced without tools by simply pressing the user-friendly
module release button of the protection modules.
In order to avoid incorrect insertion by the installer or user when replacing the protection modules, every base part and protection module is
mechanically coded by the manufacturer.

88

www.dehn.de

Combined
Arresters Type 1

952 078
952 071
952 072
952 070
952 073
952 074
952 075
952 076

DG S 48
DG S 75
DG S 150
DG S 275
DG S 320
DG S 385
DG S 440
DG S 600

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard S / DEHNguard S FM
DEHNguard S ...

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

DG S 48
952 078
DG S 75
952 071
DG S 150
952 072
DG S 275
952 070
DG S 320
952 073
DG S 385
952 074
DG S 440
952 075
DG S 600
952 076

Dimension drawing DG S ...

Basic circuit diagram DG S ...

DG S 48
SPD according to EN 61643-11
Type 2
SPD according to IEC 61643-1
Class II
Max. continuous operat. a.c. volt. UC 48 V
Max. continuous operat. d.c. volt. UC 60 V
Nominal discharge current (8/20 s) In 10 kA
Max. discharge current (8/20 s) Imax 25 kA
Voltage protection level UP
) 0.3 kV
Voltage protection level at 5 kA UP ) 0.25 kV
Response time tA
) 25 ns
Max. mains-side overcurrent protection 125 A gL/gG
Short-circuit withstand capability for max.
mains-side overcurrent protection
50 kArms
Temporary overvoltage (TOV) UT
70 V / 5 sec.
TOV characteristics
withstand
Operating temperature range TU -40C...+80C
Operating state/fault indication
green / red
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
IP 20
Capacity
Approvals, Certifications

DG S 75

DG S 150

DG S 275

DG S 320

DG S 385

DG S 440

DG S 600

Type 2
Class II
75 V
100 V
10 kA
40 kA
) 0.4 kV
) 0.35 kV
) 25 ns
125 A gL/gG

Type 2
Class II
150 V
200 V
15 kA
40 kA
) 0.7 kV
) 0.55 kV
) 25 ns
125 A gL/gG

Type 2
Class II
275 V
350 V
20 kA
40 kA
) 1.25 kV
) 1 kV
) 25 ns
125 A gL/gG

Type 2
Class II
320 V
420 V
20 kA
40 kA
) 1.5 kV
) 1.2 kV
) 25 ns
125 A gL/gG

Type 2
Class II
385 V
500 V
20 kA
40 kA
) 1.75 kV
) 1.35 kV
) 25 ns
125 A gL/gG

Type 2
Class II
440 V
585 V
20 kA
40 kA
) 2 kV
) 1.7 kV
) 25 ns
125 A gL/gG

Type 2
Class II
600 V
600 V
15 kA
30 kA
) 2.5 kV
) 2 kV
) 25 ns
100 A gL/gG

50 kArms
90 V / 5 sec.
withstand
-40C...+80C
green / red

50 kArms
175 V / 5 sec.
withstand
-40C...+80C
green / red

50 kArms
25 kArms
335 V / 5 sec.
335 V / 5 sec.
withstand
withstand
-40C...+80C
-40C...+80C
green / red
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
IP 20
IP 20
1 mod., DIN 43880
KEMA, VDE,
KEMA, VDE,
KEMA, VDE,

25 kArms
385 V / 5 sec.
withstand
-40C...+80C
green / red

25 kArms
580 V / 5 sec.
withstand
-40C...+80C
green / red

25 kArms
600 V / 5 sec.
withstand
-40C...+80C
green / red

IP 20

IP 20

IP 20

KEMA, VDE,

KEMA, VDE,

KEMA, VDE,

UL, CSA

UL, VdS, CSA

UL, VdS, CSA

UL, VdS, CSA

UL, VdS, CSA

UL, VdS, CSA

UL, VdS, CSA

DG S 75
952 071
1 pc(s).

DG S 150
952 072
1 pc(s).

DG S 275
952 070
1 pc(s).

DG S 320
952 073
1 pc(s).

DG S 385
952 074
1 pc(s).

DG S 440
952 075
1 pc(s).

DG S 600
952 076
1 pc(s).

IP 20
KEMA, VDE,

Surge Arresters Type 2

DG S ...: Single-pole, pluggable surge arrester consisting of a base part and plug-in protection
module

Ordering information
Type
Part No.
Packing unit

DG S 48
952 078
1 pc(s).

Accessory Part for DEHNguard S / DEHNguard S FM


Varistor-based protection module
952 018
48
952 011
75
952 012
150
952 010
275
952 013
320
952 014
385
DG
952MOD
015 48
952
440 018
DG
952MOD
016 75
952
600 011
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
952 015
DG MOD 600
952 016

DG MOD
DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
Type
DG MOD 48
DG MOD 75
DG MOD 150
DG MOD 275
DG MOD 320
DG MOD 385
DG MOD 440
DG MOD 600

www.dehn.de

DG MOD
DG MOD
DG MOD
DG MOD

PU
pc(s).
1
1
1
1
1
1
1
1

Part
No.
952 018
952 011
952 012
952 010
952 013
952 014
952 015
952 016

89

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNguard S / DEHNguard S FM
DEHNguard S ... FM

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

952 098
FM
952 091
FM
952 092
FM
952 090
FM
952 093
FM
952 094
FM
952 095
FM
952 096
FM

DG S 48 FM
952 098
DG S 75 FM
952 091
DG S 150 FM
952 092
DG S 275 FM
952 090
DG S 320 FM
952 093
DG S 385 FM
952 094
DG S 440 FM
952 095
DG S 600 FM
952 096

12
11
14

Basic circuit diagram DG S ... FM

Dimension drawing DG S ... FM

DG S ... FM: Single-pole, pluggable surge arrester consisting of a base part and plug-in protection
module; with floating remote signalling contact

Surge Arresters Type 2

DG S 48 FM
SPD according to EN 61643-11
Type 2
SPD according to IEC 61643-1
Class II
Max. continuous operat. a.c. volt. UC 48 V
Max. continuous operat. d.c. volt. UC 60 V
Nominal discharge current (8/20 s) In 10 kA
Max. discharge current (8/20 s) Imax 25 kA
Voltage protection level UP
) 0.3 kV
Voltage protection level at 5 kA UP ) 0.25 kV
Response time tA
) 25 ns
Max. mains-side overcurrent protection 125 A gL/gG
Short-circuit withstand capability for max.
mains-side overcurrent protection
50 kArms
Temporary overvoltage (TOV) UT
70 V / 5 sec.
TOV characteristics
withstand
Operating temperature range TU -40C...+80C
Operating state/fault indication
green / red
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
IP 20
Capacity
Approvals, Certifications

DG S 75 FM

DG S 150 FM DG S 275 FM DG S 320 FM DG S 385 FM DG S 440 FM DG S 600 FM

Type 2
Class II
75 V
100 V
10 kA
40 kA
) 0.4 kV
) 0.35 kV
) 25 ns
125 A gL/gG

Type 2
Class II
150 V
200 V
15 kA
40 kA
) 0.7 kV
) 0.55 kV
) 25 ns
125 A gL/gG

50 kArms
90 V / 5 sec.
withstand
-40C...+80C
green / red

50 kArms
175 V / 5 sec.
withstand
-40C...+80C
green / red

Type 2
Class II
385 V
500 V
20 kA
40 kA
) 1.75 kV
) 1.35 kV
) 25 ns
125 A gL/gG

Type 2
Class II
440 V
585 V
20 kA
40 kA
) 2 kV
) 1.7 kV
) 25 ns
125 A gL/gG

Type 2
Class II
600 V
600 V
15 kA
30 kA
) 2.5 kV
) 2 kV
) 25 ns
100 A gL/gG

50 kArms
25 kArms
335 V / 5 sec.
335 V / 5 sec.
withstand
withstand
-40C...+80C
-40C...+80C
green / red
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
IP 20
IP 20
1 mod., DIN 43880
KEMA, VDE,
KEMA, VDE,
KEMA, VDE,

25 kArms
385 V / 5 sec.
withstand
-40C...+80C
green / red

25 kArms
580 V / 5 sec.
withstand
-40C...+80C
green / red

25 kArms
600 V / 5 sec.
withstand
-40C...+80C
green / red

IP 20

IP 20

IP 20

KEMA, VDE,

KEMA, VDE,

KEMA, VDE,

UL, VdS, CSA

UL, VdS, CSA

UL, VdS, CSA

UL, VdS, CSA

Type of remote signalling contact


Switching capacity a.c.
250 V/0.5 A
250 V/0.5 A
Switching capacity d.c.
Cross-sectional area for remote signalling terminals

UL, VdS, CSA


UL, VdS, CSA
changeover contact
250 V/0.5 A
250 V/0.5 A
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

250 V/0.5 A

250 V/0.5 A

250 V/0.5 A

Ordering information
Type
Part No.
Packing unit

DG S 150 FM
952 092
1 pc(s).

DG S 385 FM
952 094
1 pc(s).

DG S 440 FM
952 095
1 pc(s).

DG S 600 FM
952 096
1 pc(s).

IP 20
KEMA, VDE,
UL, CSA

952 018
48
952 011
75
952 012
150
952 010
275
952 013
320
952 014
385
DG
952MOD
015 48
952
440 018
DG
952MOD
016 75
952
600 011
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
952 015
DG MOD 600
952 016

90

DG MOD
DG MOD

DG S 48 FM
952 098
1 pc(s).

DG S 75 FM
952 091
1 pc(s).

Type 2
Class II
275 V
350 V
20 kA
40 kA
) 1.25 kV
) 1 kV
) 25 ns
125 A gL/gG

DG S 275 FM
952 090
1 pc(s).

Type 2
Class II
320 V
420 V
20 kA
40 kA
) 1.5 kV
) 1.2 kV
) 25 ns
125 A gL/gG

DG S 320 FM
952 093
1 pc(s).

Varistor-based protection module

DG MOD
DG MOD
DG MOD
DG MOD
DG MOD
DG MOD

DG MOD ...: Varistor-based protection module for DEHNguard M ... and


DEHNguard S ... surge arresters
Type
DG MOD 48
DG MOD 75
DG MOD 150
DG MOD 275
DG MOD 320
DG MOD 385
DG MOD 440
DG MOD 600

PU
pc(s).
1
1
1
1
1
1
1
1

Part
No.
952 018
952 011
952 012
952 010
952 013
952 014
952 015
952 016

www.dehn.de

DG S 48
DG S 75
DG S 150
DG S 275
DG S 320
DG S 385
DG S 440
DG S 600

Combined
Arresters Type 1

952 077
600
952 097
600 FM

DG S WE
DG S WE

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard S / DEHNguard S FM
DEHNguard S WE 600 (FM)

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

DG S WE 600
952 077
DG S WE 600 FM
952 097

12
11
14

Dimension drawing DG S WE 600 FM

Basic circuit diagram DG S WE 600 FM

DG S WE 600 (FM): Single-pole, pluggable surge arrester with a rated varistor voltage Umov = 750 V
a.c., consisting of base part and plug-in protection module; FM version with
floating remote signalling contact

DG S WE 600

DG S WE 600 FM

For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

Type 2
Class II
600 V
750 V
15 kA
25 kA
) 3 kV
) 2.5 kV
) 25 ns
100 A gL/gG
25 kArms
900 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
1 mod., DIN 43880
UL, CSA

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
1 mod., DIN 43880
UL, CSA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG S WE 600
952 077
1 pc(s).

DG S WE 600 FM
952 097
1 pc(s).

Surge Arresters Type 2

SPD according to EN 61643-11


Type 2
SPD according to IEC 61643-1
Class II
Max. continuous operating a.c. voltage UC
600 V
Rated varistor voltage a.c. Umov
750 V
Nominal discharge current (8/20 s) In
15 kA
Max. discharge current (8/20 s) Imax
25 kA
Voltage protection level UP
) 3 kV
Voltage protection level at 5 kA UP
) 2.5 kV
Response time tA
) 25 ns
Max. mains-side overcurrent protection
100 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 25 kArms
Temporary overvoltage (TOV) UT
900 V / 5 sec.
TOV characteristics
withstand
Operating temperature range TU
-40C...+80C
Operating state/fault indication
green / red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
Cross-sectional area (max.)
35 mm2 stranded/25 mm2 flexible

Accessory Part for DEHNguard S / DEHNguard S FM


Varistor-based protection module for
DEHNguard M (S) WE
952 017
750

DG MOD

DG MOD 750: Varistor-based protection module for DEHNguard M WE


... and DEHNguard S WE ... with a rated varistor voltage Umov = 750 V
a.c.
DG MOD 750
952 017

Type
DG MOD 750

www.dehn.de

PU
pc(s).
1

Part
No.
952 017

91

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

DEHNgap C S
N-PE surge arrester

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

Specifically designed for use in 3+1 and


1+1 circuits of TT systems acc. to IEC 603645-53 between neutral conductor N and protective earth conductor PE
High discharge capacity
Two-part unit consisting of a base part and
spark-gap-based plug-in protection module
Energy coordination within the Red/Line product family
Operating state/fault indication by indicator
flag in the inspection window
With remote signalling contact for SPD monitoring device

Surge Arresters Type 2

Easy replacement of protection modules without tools due to module release button
Vibration- and shock-tested according to EN
60068-2

For protecting low-voltage consumers installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0B 1 and higher.

DEHNgap C S:
N-PE surge arrester consisting of a base part and plug-in protection module
DEHNgap C S FM: With remote signalling contact for monitoring device (floating changeover contact)

The N-PE surge arrester DEHNgap C S ideally complements the single-pole


DEHNguard S surge protective devices. Being a total current arrester
between neutral conductor and protective conductor in TT systems, its
function is to ensure that the requirements for protection of persons and
material assets in so-called 3+1 and 1+1 circuits are fulfilled.

Monitoring of the arrester temperature and an integrated disconnector,


which is connected in series to the surge arrester, further increase the
safety of DEHNgap C S.

With the modern Red/Line design, DEHNgap C S provides safety and performance just like the DEHNguard S devices. The module locking system,
which is unique for use with surge protective devices, combines the sparkgap-based module and base part to a powerful unit. Neither vibration
during transport nor the enormous electromagnetic forces of discharge
can loosen the protection module. Nevertheless, the protection modules
can be easily replaced without tools by simply pressing the module
release button of the protection module. The mechanical coding at the
protection module and base part prevents incorrect insertion by the
installer or user.

Apart from the standard visual indicator, DEHNgap C S ... FM incorporates


a three-pole terminal for remote signalling. With its floating changeover
contact, the remote signal can be used as a break or make contact according to the particular circuit concept. The N-PE surge arrester DEHNgap C
S features multifunctional terminals for connection of conductors and
busbars, allowing easy wiring with other DIN rail mounted devices. Series
connection according to IEC 60364-5-53 for optimal protection is therefore possible for a wide range of applications.

92

The green and red indicator shows if DEHNgap C S is ready for operation.

www.dehn.de

Combined
Arresters Type 1

952 030
952 035
FM

DGP C S
DGP C S

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNgap C S
DEHNgap C S (FM)

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

DGP C S
952 030
DGP C S FM
952 035

12
11
14

Dimension drawing DGP C S FM

Basic circuit diagram DGP C S FM

SPD according to EN 61643-11


SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Follow current extinguishing capability Ifi
Lightning impulse current (10/350 s) Iimp
Voltage protection level UP
Response time tA
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

DGP C S

DGP C S FM

Type 2
Class II
255 V
20 kA
40 kA
100 Arms
12 kA
) 1.5 kV
) 100 ns
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0

Type 2
Class II
255 V
20 kA
40 kA
100 Arms
12 kA
) 1.5 kV
) 100 ns
1200 V / 200 ms
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0

IP 20
1 mod., DIN 43880
KEMA, VDE, UL, VdS

IP 20
1 mod., DIN 43880
KEMA, VDE, UL, VdS
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DGP C S
952 030
1 pc(s).

DGP C S FM
952 035
1 pc(s).

Surge Arresters Type 2

DGP C S (FM): N-PE surge arrester; FM version with floating remote signalling contact

Accessory Part for DEHNgap C S


N-PE spark-gap-based protection module for
DEHNgap C S
952 060
MOD

DGP C

DGP C MOD: N-PE spark-gap-based protection module for single-pole


N-PE surge arresters of type DEHNgap DGP C S ...
DGP C MOD
952 060

Type
DGP C MOD

www.dehn.de

PU
pc(s).
1

Part
No.
952 060

93

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Protection Module
for DEHNguard M, ... S and DEHNgap C S

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

High discharge capacity due to heavy-duty zinc


oxide varistors/spark gaps
High reliability due to Thermo Dynamic
Control SPD monitoring device
Energy coordination within the Red/Line product family
Operating state/fault indication by indicator
flag in the inspection window
Easy replacement of protection modules without tools by module locking system with module release button
The plug-in protection module can be replaced
without the need to de-energise and without
removing the cover plate of the distribution
board

Surge Arresters Type 2

Vibration- and shock-tested according to EN


60068-2

For protecting low-voltage consumers installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0B 1 and higher.

DEHNguard MOD ...:


DEHNguard MOD 750:
DEHNguard MOD NPE:

Varistor-based protection module for DEHNguard M ... and DEHNguard S


Varistor-based protection module for DEHNguard M WE 600 and DEHNguard S WE 600
N-PE spark-gap-based protection module for two- and four-pole DEHNguard M TT ... surge
arresters
DEHNgap C MOD:
N-PE spark-gap-based protection module for single-pole DEHNgap C S ... N-PE surge arresters
DEHNguard MOD CI 275: Varistor-based protection module for DEHNguard M CI
DEHNguard MOD ... VA:
Varistor- and spark-gap-based protection module for DEHNguard S ... VA
DEHNguard MOD PV SCI ...: Varistor-based protection module for DEHNguard M YPV SCI

The varistor- and spark-gap-based protection modules of the DEHNguard


M, DEHNguard S and DEHNgap C S devices distinguish themselves
through their outstanding performance and sophistication.
The compact protection modules include the complete protective circuit
as well as the monitoring device and disconnector.
The green flag in the window indicates if the protection modules are
ready for operation.

94

In order to avoid incorrect insertion by the installer or user when replacing the modules, all protection modules are mechanically coded. The protection modules can be easily replaced without tools by simply pressing
the user-friendly module release button.

www.dehn.de

Combined
Arresters Type 1

952 018
48
952 011
75
952 012
150
952 010
275
952 013
320
952 014
385
952 015
440
952 016
600

DG MOD
DG MOD
DG MOD
DG MOD
DG MOD

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

Prot. Mod. f. DEHNguard M, ... S and DEHNgap C S


Varistor-based protection module

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

DG MOD
DG MOD
DG MOD

DG MOD 48
952 018
DG MOD 75
952 011
DG MOD 150
952 012
DG MOD 275
952 010
DG MOD 320
952 013
DG MOD 385
952 014
DG MOD 440
952 015
DG MOD 600
952 016

Dimension drawing DG MOD varistor-based


protection module

Basic circuit diagram DG MOD varistor-based


protection module

DG MOD ...: Varistor-based protection module for DEHNguard M ... and DEHNguard S ... surge
arresters
DG MOD 48
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Max. continuous op. a.c. voltage UC
Max. continuous op. d.c. voltage UC

10 kA
25 kA
48 V
60 V

10 kA
40 kA
75 V
100 V

15 kA
40 kA
150 V
200 V

20 kA
40 kA
275 V
350 V

20 kA
40 kA
320 V
420 V

20 kA
40 kA
385 V
500 V

20 kA
40 kA
440 V
585 V

15 kA
30 kA
600 V
600 V

DG MOD 48
952 018
1 pc(s).

DG MOD 75
952 011
1 pc(s).

DG MOD 150
952 012
1 pc(s).

DG MOD 275
952 010
1 pc(s).

DG MOD 320
952 013
1 pc(s).

DG MOD 385
952 014
1 pc(s).

DG MOD 440
952 015
1 pc(s).

DG MOD 600
952 016
1 pc(s).
Surge Arresters Type 2

Ordering information
Type
Part No.
Packing unit

DG MOD 75 DG MOD 150 DG MOD 275 DG MOD 320 DG MOD 385 DG MOD 440 DG MOD 600

952 017
750

DG MOD

Varistor-based protection module for DEHNguard M (S) WE

DG MOD 750
952 017

Dimension drawing DG MOD 750 varistor-based


protection module

Basic circuit diagram DG MOD 750 varistor-based


protection module

DG MOD 750: Varistor-based protection module for DEHNguard M WE ... and DEHNguard S WE ...
surge arresters with a rated varistor voltage Umov = 750 V a.c.
DG MOD 750
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Max. continuous operating a.c. voltage UC
Max. continuous operating d.c. voltage UC
Rated varistor voltage Umov
Ordering information
Type
Part No.
Packing unit

www.dehn.de

15 kA
25 kA
600 V
600 V
750 V

DG MOD 750
952 017
1 pc(s).

95

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Prot. Mod. f. DEHNguard M, ... S and DEHNgap C S


N-PE spark-gap-based protection module
for DEHNguard M TT ...

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

952 050
NPE

DG MOD

DG MOD NPE
952 050

Basic circuit diagram DG MOD NPE

Dimension drawing DG MOD NPE

DG MOD NPE: N-PE spark-gap-based protection module for two- and four-pole DEHNguard DG M
TT ... surge arresters

DG MOD NPE
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Max. continuous operating a.c. voltage UC

DG MOD NPE
952 050
1 pc(s).

Surge Arresters Type 2

Ordering information
Type
Part No.
Packing unit

20 kA
40 kA
255 V

952 060
MOD

N-PE spark-gap-based protection module for DEHNgap C S

DGP C MOD
952 060

Basic circuit diagram DGP C MOD

Dimension drawing DGP C MOD

DGP C MOD: N-PE spark-gap-based protection module for single-pole N-PE surge arresters of
type DEHNgap DGP C S ...

DGP C MOD
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Max. continuous operating a.c. voltage UC
Ordering information
Type
Part No.
Packing unit

96

20 kA
40 kA
255 V

DGP C MOD
952 060
1 pc(s).

www.dehn.de

DGP C

Combined
Arresters Type 1

952 053
952 051
952 054

DG MOD PV SCI 300


DG MOD PV SCI 500
DG MOD PV SCI 600

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

Prot. Mod. f. DEHNguard M, ... S and DEHNgap C S


Varistor-based protection module
for DEHNguard M YPV SCI

DG MOD PV SCI 300


952 053
DG MOD PV SCI 500
952 051
DG MOD PV SCI 600
952 054

Dimension drawing DG MOD PV SCI

Basic circuit diagram DG MOD PV SCI

DG MOD PV SCI ...: Protection module for DEHNguard M YPV SCI ... comprising a varistor connected in parallel with a short-circuiting device with integrated back-up fuse

Nominal discharge current (8/20 s) In


Max. discharge current (8/20 s) Imax
Max. continuous operating d.c. voltage UC

DG MOD PV SCI 500

DG MOD PV SCI 600

12.5 kA
25 kA
300 V

12.5 kA
25 kA
500 V

12.5 kA
25 kA
600 V

DG MOD PV SCI 300


952 053
1 pc(s).

DG MOD PV SCI 500


952 051
1 pc(s).

DG MOD PV SCI 600


952 054
1 pc(s).
Surge Arresters Type 2

Ordering information
Type
Part No.
Packing unit

DG MOD PV SCI 300

952 025
952 027
952 029

DG MOD 75 VA
DG MOD 275 VA
DG MOD 385 VA

Varistor-and spark-gap-based protection module for DEHNguard S ... VA

DG MOD 75 VA
952 025
DG MOD 275 VA
952 027
DG MOD 385 VA
952 029

Dimension drawing DG MOD ... VA

Basic circuit diagram DG S ... VA

DG MOD ... VA: Protection module for DEHNguard S ... VA comprising a varistor connected in
series with a spark gap

Nominal discharge current (8/20 s) In


Max. discharge current (8/20 s) Imax
Max. continuous operating a.c. voltage UC
Max. continuous operating d.c. voltage UC
Ordering information
Type
Part No.
Packing unit

www.dehn.de

DG MOD 75 VA

DG MOD 275 VA

DG MOD 385 VA

10 kA
20 kA
75 V
100 V

10 kA
20 kA
275 V
350 V

10 kA
20 kA
385 V
500 V

DG MOD 75 VA
952 025
1 pc(s).

DG MOD 275 VA
952 027
1 pc(s).

DG MOD 385 VA
952 029
1 pc(s).

97

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Prot. Mod. f. DEHNguard M, ... S and DEHNgap C S


Varistor-based protection module
for DEHNguard M CI

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

952 020

DG MOD CI 275
952 020

Basic circuit diagram DG MOD CI 275

Dimension drawing DG MOD CI 275

DG MOD CI 275: Protection module for DEHNguard M ... CI 275 comprising a varistor connected
in series with the integrated backup fuse

DG MOD CI 275

Surge Arresters Type 2

Nominal discharge current (8/20 s) In


Max. discharge current (8/20 s) Imax
Max. continuous operating a.c. voltage UC
Ordering information
Type
Part No.
Packing unit

98

12.5 kA
25 kA
275 V

DG MOD CI 275
952 020
1 pc(s).

www.dehn.de

DG MOD CI 275

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard ... H LI
Multipole surge arrester with
Pro-Active Thermo Control
Prewired complete unit for standard system
configurations consisting of a base part and
plug-in protection modules
Clear operating state indication due to 3-stage
visual service life indicator <GREEN-YELLOWRED> with linked remote signalling function
Pro-Active Thermo Control SPD monitoring
device
Recommends the user to replace the protection
module <YELLOW> before the SPD is threatened by overloads
Energy coordination within the Red/Line product family

DEHNguard TNC H LI:


DEHNguard TNS H LI:
DEHNguard TT H LI:
DEHNguard T H LI:

Surge Arresters Type 2

For protecting low-voltage consumers installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0B 1 and higher.

Multipole surge arrester with service life indicator for use in TN-C systems
Multipole surge arrester with service life indicator for use in TN-S systems
Multipole surge arrester with service life indicator for use in TT and TN-S systems (3+1 circuit)
Single-pole surge arrester with service life indicator

The single-pole and multipole surge arresters of the DEHNguard ... H LI


family provide maximum safety and user-friendliness and set new standards in surge protection.
With the Pro-Active Thermo Control concept, they are the first intelligent surge arresters to warn the user of failures of the surge protection
system in due time. With this technique, this new SPD monitoring device
meets the steadily increasing requirements on the availability of electrical
systems in industrial, commercial and domestic environments. The 3-stage
visual indicator along with a floating changeover contact for remote signalling always informs the user on the operating state of the SPD. If there
is a risk that the varistor might be irreversibly damaged due to an
increased energy load, the user is informed by the yellow indicator and
the remote signalling function that the surge protection module should be
replaced before the installation is unprotected!
Like the well-known multipole DEHNguard family, the application-based
type designation makes the choice of products of the prewired complete
units considerably easier. Less installation errors and saving of installation
work at the same time are unbeatable advantages for the customer. Both

the triple monitoring device of each circuit with Pro-Active Thermo


Control and the coding of the pluggable protection modules characterise
the maximum degree of safety of the devices. Damage caused by incorrect subsequent insertion by the installer or the user is very unlikely.
With DEHNguard T H LI, the user is also provided with a single-pole device
for universal use.
All types of DEHNguard ... H LI feature a three-pole terminal for remote
signalling. With their floating changeover contact, the remote signal can
be used as a make or break contact according to the particular
circuit concept. All surge arresters
of the DEHNguard ... H LI family
incorporate multifunctional terminals for the connection of conductors and busbars, allowing
easy wiring with other DIN rail
mounted devices.

Yellow indicator flag: Replacement of


the protection module recommended

www.dehn.de

99

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNguard ... H LI
DEHNguard TNC H LI

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
PEN

950 160
H230 400 LI

DG TNC H230 400 LI


950 160

12
11
14

L1

L2

L3

Basic circuit diagram DG TNC H230 400 LI

Dimension drawing DG TNC H230 400 LI

DG TNC H LI: Multipole surge arrester for use in TN-C systems with Pro-Active Thermo Control
SPD monitoring device with 3-stage visual indicator.

Surge Arresters Type 2

DG TNC H230 400 LI


SPD according to EN 61643-11
SPD according to IEC 61643-1
Nominal a.c. voltage
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Voltage protection level at 5 kA UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for max. mains-side overcurrent protection
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range
Indication of disconnector
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals

Type 2
Class II
230/400 V
275 V
20 kA
65 kA
) 1.25 kV
) 1 kV
) 25 ns
160 A gL/gG
20 kArms
335 V / 5 sec.
withstand
-40C...+55C
green-yellow-red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
3 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

Ordering information
Type
Part No.
Packing unit

DG TNC H230 400 LI


950 160
1 pc(s).

Accessory Part for DEHNguard ... H LI


Varistor-based protection module with Pro-Active
Thermo Control
950 130
950 131

Type
T H 275 LI

100

PU
pc(s).
1
T H 275 LI
950 130
T H 385 LI
950 131

T H 275 LI
T H 385 LI

Part
No.
950 130

www.dehn.de

DG TNC

Combined
Arresters Type 1

DG TNS

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard ... H LI
DEHNguard TNS H LI

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
PE

DG TNS H230 400 LI


950 170

12
11
14

L1

Dimension drawing DG TNS H230 400 LI

L2

L3

Basic circuit diagram DG TNS H 230 400 LI

DG TNS H LI: Multipole surge arrester for use in TN-S systems with Pro-Active Thermo Control
SPD monitoring device with 3-stage visual indicator

DG TNS H230 400 LI


SPD according to EN 61643-11
SPD according to IEC 61643-1
Nominal a.c. voltage
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Voltage protection level at 5 kA UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for max. mains-side overcurrent protection
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range
Indication of disconnector
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

Type 2
Class II
230/400 V
275 V
20 kA
65 kA
) 1.25 kV
) 1 kV
) 25 ns
160 A gL/gG
20 kArms
335 V / 5 sec.
withstand
-40C...+55C
green-yellow-red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

Surge Arresters Type 2

950 170
H230 400 LI

Lightning Current
Arresters Type 1

DG TNS H230 400 LI


950 170
1 pc(s).

Accessory Part for DEHNguard ... H LI


Varistor-based protection module with Pro-Active
Thermo Control
Type
T H 275 LI

www.dehn.de

PU
pc(s).
1

Part
No.
950 130

950 130
950 131

T H 275 LI
T H 385 LI

T H 275 LI
950 130
T H 385 LI
950 131

101

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNguard ... H LI
DEHNguard TT H LI

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
PE

950 150
H230 400 LI
950 151
H230 400 LI385

DG TT H230 400 LI
950 150
DG TT H230 400 LI385
950 151

12
11
14

L1

L2

L3

Basic circuit diagram DG TT H230 400 LI

Dimension drawing DG TT H230 400 LI

DG TT H LI: Multipole surge arrester with Pro-Active Thermo Control SPD monitoring device
with 3-stage visual indicator for use in TT and TN-S systems (3+1 circuit)
DG TT H230 400 LI

DG TT H230 400 LI385

Type 2
Class II
230/400 V
275 V

Type 2
Class II
230/400 V
385 V

Surge Arresters Type 2

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage
Max. continuous operating a.c. voltage [L-N]

Max. continuous operating a.c. voltage [N-PE]


255 V
Max. discharge current (8/20 s) [L-N] Imax
65 kA
Max. discharge current (8/20 s) [N-PE]
65 kA
Lightning impulse current (10/350 s) [N-PE]
12 kA
Voltage protection level [L-N]
) 1.25 kV
Voltage protection level [L-N] at 5 kA
) 1 kV
Voltage protection level [N-PE]
) 1.5 kV
Follow current extinguishing capability [N-PE]
100 Arms
Response time [L-N]
) 25 ns
Response time [N-PE]
) 100 ns
Max. mains-side overcurrent protection
160 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 20 kArms
TOV characteristics
withstand
Temporary overvoltage (TOV) [L-N]
335 V / 5 sec.
Temporary overvoltage (TOV) [N-PE]
1200 V / 200 ms
Operating temperature range
-40C...+55C
Indication of disconnector
green-yellow-red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
Cross-sectional area (max.)
35 mm2 stranded/25 mm2 flexible
For mounting on
35 mm DIN rail acc. to EN 60715
Enclosure material
thermoplastic, red, UL 94 V-0
Degree of protection
IP 20
Capacity
4 mods., DIN 43880
Approvals, Certifications
KEMA
Type of remote signalling contact
changeover contact
Switching capacity a.c.
250 V/0.5 A
Switching capacity d.c.
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals
max. 1.5 mm2 solid/flexible
Ordering information
Type
Part No.
Packing unit

DG TT H230 400 LI
950 150
1 pc(s).

Accessory Part for DEHNguard ... H LI


Varistor-based protection module with Pro-Active
Thermo Control

102

DG TT H230 400 LI385


950 151
1 pc(s).

Accessory Part for DEHNguard ... H LI


950 130
950 131

Type
T H 275 LI
T H 385 LI

255 V
65 kA
65 kA
12 kA
) 1.75 kV
) 1.35 kV
) 1.5 kV
100 Arms
) 25 ns
) 100 ns
160 A gL/gG
20 kArms
withstand
385 V / 5 sec.
1200 V / 200 ms
-40C...+55C
green-yellow-red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
4 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

PU
pc(s).
1
1
T H 275 LI
950 130
T H 385 LI
950 131

T H 275 LI
T H 385 LI

Part
No.
950 130
950 131

900 216

T C H 255
900 216

T C H 255

N-PE spark-gap-based protection module


Type
T C H 255

PU
pc(s).
1

Part
No.
900 216

www.dehn.de

DG TT
DG TT

Combined
Arresters Type 1

950 120
275 LI
950 121
385 LI

DG T H
DG T H

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard ... H LI
DEHNguard T H LI

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

DG T H 275 LI
950 120
DG T H 385 LI
950 121

12
11
14

Dimension drawing DG T H ... LI

Basic circuit diagram DG T H ... LI

DG T H LI: Single-pole, pluggable surge arrester with Pro-Active Thermo Control SPD monitoring device with 3-stage visual indicator
DG T H 385 LI

Type 2
Class II
230 V
275 V

Type 2
Class II
230 V
385 V

Nominal discharge current (8/20 s) In


20 kA
Max. discharge current (8/20 s) Imax
65 kA
Voltage protection level UP
) 1.25 kV
Voltage protection level at 5 kA UP
) 1 kV
Response time tA
) 25 ns
Max. mains-side overcurrent protection
160 A gL/gG
Short-circuit withstand capability for max. mains-side overcurrent protection 20 kArms
Temporary overvoltage (TOV) UT
335 V / 5 sec.
TOV characteristics
withstand
Operating temperature range
-40C...+55C
Indication of disconnector
green-yellow-red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
Cross-sectional area (max.)
35 mm2 stranded/25 mm2 flexible
For mounting on
35 mm DIN rail acc. to EN 60715
Enclosure material
thermoplastic, red, UL 94 V-0
Degree of protection
IP 20
Capacity
1 mods., DIN 43880
Approvals, Certifications
KEMA
Type of remote signalling contact
changeover contact
Switching capacity a.c.
250 V/0.5 A
Switching capacity d.c.
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
Cross-sectional area for remote signalling terminals
max. 1.5 mm2 solid/flexible
Ordering information
Type
Part No.
Packing unit

20 kA
65 kA
) 1.75 kV
) 1.35 kV
) 25 ns
160 A gL/gG
20 kArms
385 V / 5 sec.
withstand
-40C...+55C
green-yellow-red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
1 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG T H 275 LI
950 120
1 pc(s).

Surge Arresters Type 2

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage
Max. continuous operating a.c. voltage UC

DG T H 275 LI

DG T H 385 LI
950 121
1 pc(s).

Accessory Part for DEHNguard ... H LI


Varistor-based protection module with Pro-Active
Thermo Control
Type
T H 275 LI
T H 385 LI

www.dehn.de

PU
pc(s).
1
1

Part
No.
950 130
950 131

950 130
950 131

T H 275 LI
T H 385 LI

T H 275 LI
950 130
T H 385 LI
950 131

103

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


DEHNguard M YPV SCI ... (FM)
Multipole arrester for use in photovoltaic systems SURGE ARRESTERS TYPE 2
SPD Type 2 classification according to EN 61643-11
with three-step d.c. switching device
SPD Class II classification according to IEC 61643-1
Prewired modular complete unit for use in photovoltaic systems consisting of a base part and
plug-in protection modules
Combined disconnection and short-circuiting
device with safe electrical isolation in the protection module prevents fire damage due to
d.c. arcs
Approved fault-resistant Y circuit prevents
damage to the surge protective devices in case
of insulation faults in the generator circuit
Safe replacement of protection modules without arc formation due to integrated d.c. fuse
Suitable for all PV systems in accordance with
IEC 60364-7-712

Surge Arresters Type 2

For protecting low-voltage consumers installations against surges. For


use in accordance with IEC 60364-7-712:2002-05 (installation of photovoltaic power supply systems)

DEHNguard M YPV SCI 600:

Multipole, modular surge arrester with three-step d.c. switching device; for use in photovoltaic systems up to 600 V
DEHNguard M YPV SCI 1000: For photovoltaic systems up to 1000 V
DEHNguard M YPV SCI 1200: For photovoltaic systems up to 1200 V
DEHNguard M YPV SCI ... FM: With remote signalling contact for a monitoring device (floating changeover contact)
The modular surge arresters of type DEHNguard M YPV SCI ... (FM) were
specifically designed for protecting equipment in photovoltaic systems.
The innovative three-step d.c. switching device makes these arresters
especially safe so that they fulfil the requirements for modern photovoltaic systems.
The application features of the modular Red/Line family design are similarly unique as the three-step d.c. switching device. The module locking
system firmly fixes the protection modules in the base part of the arrester.
Neither shock nor vibration nor the enormous forces of discharge affect
the safe connection to the protection module. Nevertheless, the protection modules can be easily replaced without tools by simply pressing the
user-friendly module release button of the protection modules. Every protective circuit of the DEHNguard M YPV SCI ... (FM) and every protection
module is mechanically coded to avoid incorrect insertion by the installer
or user.
To fulfil the specific requirements for photovoltaic systems, the approved
safety philosophies of the fault-resistant Y circuit consisting of three protective circuits of the varistor and the combined disconnection and shortcircuiting device were integrated in a single device.
This synergy reduces the probability of an arrester failure in case of operating and fault states which have to be considered in photovoltaic systems. This ensures that the arrester is protected in case of overload without presenting a fire risk to the system. Even in case of voltages up to
1200 V d.c. an arc, which is likely to occur in the surge protective device
if a conventional disconnection device is activated, is extinguished immediately and without risk. Fire protection is the top priority of the
DEHNguard M YPV SCI ... (FM) arrester. A fuse particularly developed for

photovoltaic systems was integrated into the short-circuit path to ensure


safe electrical isolation in case of a faulty surge protection module, allowing de-energised replacement of the protection module without arc formation in case of a faulty surge protection module. This unique design
combines surge protection, fire protection and the protection of persons.
DEHNguard M YPV SCI ... (FM) can be used in all low-, medium- and highperformance photovoltaic systems without backup fuse due to this innovative and unique design.
The green and red indicator flags show if every protective circuit is ready
for operation. Apart from this standard visual indication, DEHNguard M
YPV SCI ... (FM) arresters also feature a three-pole terminal for remote
signalling. With their floating changeover contact, the remote signal can
be used as make or break contact according to the particular circuit concept. Like all surge arresters of the modular DEHNguard M family,
DEHNguard M YPV SCI ... (FM) arresters incorporate multifunctional terminals on a standardised spacing of 1 module for connecting conductors
and busbars, allowing easy wiring with other DIN rail mounted devices.
Switching stages:
Original state

SCI

104

1.
Response of the
disconnection device

SCI

2.
Arc extinction

SCI

3.
Safe electrical
isolation

SCI

www.dehn.de

Combined
Arresters Type 1

DG M YPV SCI 600


DG M YPV SCI 1000
DG M YPV SCI 1200

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DC+/
DG M YPV SCI 600
952 511
DG M YPV SCI 1000
952 510
DG M YPV SCI 1200
952 512
9

Accessories

DEHNguard M YPV SCI ... (FM)


DEHNguard M YPV SCI ...

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

DC+/

Surge Arresters
Type 3

NEW

DC/+

DC/+

Dimension drawing DG M YPV SCI ...

Basic circuit diagram DG M YPV SCI ...

DG M YPV SCI ...: Multipole, modular surge arrester with three-step d.c. switching device for use
in PV systems.

DG M YPV SCI 600

DG M YPV SCI 1000

DG M YPV SCI 1200

Type 2
Class II
) 1000 V
500 V
40 kA
12.5 kA
25 kA
) 4 kV
) 3.5 kV
) 25 ns
-40C...+80C
30 kA / 1000 V d.c.
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0

Type 2
Class II
) 1200 V
600 V
30 kA
12.5 kA
25 kA
) 4.5 kV
) 4 kV
) 25 ns
-40C...+80C
30 kA / 1200 V d.c.
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0

IP 20
3 mod(s)., DIN 43880
UL

IP 20
3 mod(s)., DIN 43880
UL

IP 20
3 mod(s)., DIN 43880

DG M YPV SCI 600


952 511
1 pc(s).

DG M YPV SCI 1000


952 510
1 pc(s).

DG M YPV SCI 1200


952 512
1 pc(s).

SPD classification according to EN 61643-11


Type 2
SPD classification according to IEC 61643-1
Class II
Max. PV voltage UCPV
) 600 V
Max. continuous operating d.c. voltage [(DC+/DC-) > PE] UC
300 V
Total discharge current (8/20 s) Itotal
40 kA
Nominal discharge current (8/20 s) [(DC+/DC-) > PE] In
12.5 kA
Max. discharge current (8/20 s) [(DC+/DC-) > PE] Imax
25 kA
Voltage protection level UP
) 2.5 kV
Voltage protection level at 5 kA UP
) 2 kV
Response time tA
) 25 ns
Operating temperature range TU
-40C...+80C
Breaking capacity of the integrated fuse
30 kA / 1000 V d.c.
Operating state/fault indication
green / red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
Cross-sectional area (max.)
35 mm2 stranded/25 mm2 flexible
For mounting on
35 mm DIN rail acc. to EN 60715
Enclosure material
thermoplastic, red, UL 94 V-0
Degree of protection
Capacity
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

Accessory Part for DEHNguard M YPV SCI ... (FM)


Varistor-based protection module
952 010
275
952 015
440
952 016
600

Type
DG MOD 275
DG MOD 440
DG MOD 600
DG MOD 275
952 010
DG MOD 440
952 015
DG MOD 600
952 016

www.dehn.de

Accessory Part for DEHNguard M YPV SCI ... (FM)


Varistor-based protection module for M YPV SCI

DG MOD
DG MOD
DG MOD

PU
pc(s).
1
1
1

Part
No.
952 010
952 015
952 016

952 053
PV SCI 300
952 051
PV SCI 500
952 054
PV SCI 600

DG MOD
DG MOD
DG MOD

DG MOD PV SCI ...: Protection module for DEHNguard M YPV SCI ...
comprising a varistor connected in parallel with a short-circuiting
device with integrated back-up fuse
DG MOD PV SCI 300
952 053
DG MOD PV SCI 500
952 051
DG MOD PV SCI 600
952 054

Type
DG MOD PV SCI 300
DG MOD PV SCI 500
DG MOD PV SCI 600

PU
pc(s).
1
1
1

Part
No.
952 053
952 051
952 054

105

Surge Arresters Type 2

952 511
952 510
952 512

Lightning Current
Arresters Type 1

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNguard M YPV SCI ... (FM)


DEHNguard M YPV SCI ... FM

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

NEW

DC+/

DC/+
DC+/

952 516
952 515
952 517

DG M YPV SCI 600 FM


952 516
DG M YPV SCI 1000 FM
952 515
DG M YPV SCI 1200 FM
952 517

DC/+

12
11
14

Basic circuit diagram DG M YPV SCI ... FM

DG M YPV SCI ... FM:

Multipole, modular surge arrester with three-step d.c. switching device for
use in PV systems with remote signalling contact (floating changeover
contact).

Surge Arresters Type 2

DG M YPV SCI 600 FM

DG M YPV SCI 1000 FM

DG M YPV SCI 1200 FM

Type 2
Class II
) 1000 V
500 V
40 kA
12.5 kA
25 kA
) 4 kV
) 3.5 kV
) 25 ns
-40C...+80C
30 kA / 1000 V d.c.
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0

Type 2
Class II
) 1200 V
600 V
30 kA
12.5 kA
25 kA
) 4.5 kV
) 4 kV
) 25 ns
-40C...+80C
30 kA / 1200 V d.c.
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0

IP 20
3 mod(s)., DIN 43880
UL
changeover contact
250 V/0.1 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

IP 20
3 mod(s)., DIN 43880
UL
changeover contact
250 V/0.1 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

IP 20
3 mod(s)., DIN 43880

changeover contact
250 V/0.1 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG M YPV SCI 600 FM


952 516
1 pc(s).

DG M YPV SCI 1000 FM


952 515
1 pc(s).

DG M YPV SCI 1200 FM


952 517
1 pc(s).

SPD classification according to EN 61643-11


Type 2
SPD classification according to IEC 61643-1
Class II
Max. PV voltage UCPV
) 600 V
Max. continuous operating d.c. voltage [(DC+/DC-) > PE] UC
300 V
Total discharge current (8/20 s) Itotal
40 kA
Nominal discharge current (8/20 s) [(DC+/DC-) > PE] In
12.5 kA
Max. discharge current (8/20 s) [(DC+/DC-) > PE] Imax
25 kA
Voltage protection level UP
) 2.5 kV
Voltage protection level at 5 kA UP
) 2 kV
Response time tA
) 25 ns
Operating temperature range TU
-40C...+80C
Breaking capacity of the integrated fuse
30 kA / 1000 V d.c.
Operating state/fault indication
green / red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
Cross-sectional area (max.)
35 mm2 stranded/25 mm2 flexible
For mounting on
35 mm DIN rail acc. to EN 60715
Enclosure material
thermoplastic, red, UL 94 V-0
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
a.c. switching capacity
d.c. switching capacity
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

Accessory Part for DEHNguard M YPV SCI ... (FM)


952 053
PV SCI 300
952 051
PV SCI 500
952 054
PV SCI 600

DG MOD PV SCI 300


952 053
DG MOD PV SCI 500
952 051
DG MOD PV SCI 600
952 054

DG MOD
DG MOD

106

Accessory Part for DEHNguard M YPV SCI ... (FM)

Varistor-based protection module for M YPV SCI

DG MOD

DG MOD PV SCI ...: Protection module for DEHNguard M YPV SCI ...
comprising a varistor connected in parallel with a short-circuiting
device with integrated back-up fuse
Type
DG MOD PV SCI 300
DG MOD PV SCI 500
DG MOD PV SCI 600

Dimension drawing DG M YPV SCI ... FM

PU
pc(s).
1
1
1

Part
No.
952 053
952 051
952 054

952 010
275
952 015
440
952 016
600

DG MOD 275
952 010
DG MOD 440
952 015
DG MOD 600
952 016

DG MOD
DG MOD

Varistor-based protection module

DG MOD

Type
DG MOD 275
DG MOD 440
DG MOD 600

PU
pc(s).
1
1
1

Part
No.
952 010
952 015
952 016

www.dehn.de

DG M YPV SCI 600 FM


DG M YPV SCI 1000 FM
DG M YPV SCI 1200 FM

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
SPD Type 2 classification according to EN 61643-11
SPD Class II classification according to IEC 61643-1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard PV ... SCP (FM)


Single-pole arrester for use in
photovoltaic systems with short-circuiting device
For use in all types of PV systems in accordance
with IEC 60364-7-712
High discharge capacity due to heavy-duty zinc
oxide varistor
No fire risk in case of overload due to combined disconnection and short-circuiting device
Continuous current carrying capacity of the
short-circuiting device of 80 A d.c.
Indication of overload by red flag in the inspection window and remote signalling function

DG PV ... SCP:

Single-pole surge arrester with combined disconnection and short-circuiting device for use in photovoltaic
generator circuits
DG PV ... SCP FM: With remote signalling contact for the monitoring device (floating changeover contact)
Single-pole surge arresters of type DEHNguard PV ... SCP (FM) are specifically designed for use in photovoltaic power supply systems.
Even the external design of the surge arresters (width of 2 modules) is
completely adapted to the safety requirements of modern photovoltaic
systems with their high system voltages.

Apart from the standard green and red indication, DEHNguard PV ... SCP FM devices feature a three-pole remote signalling terminal.
With their floating changeover contact, the
remote signal can be used as a break or make
contact according to the particular circuit
concept.

The approved dual Thermo Dynamic Control monitoring and disconnection device of the DEHNguard PV ... SCP (FM) Type 2 surge arresters was
combined with an additional short-circuiting device. This two-step d.c.
switching device ensures safe operation, even in case of overloaded
devices, e.g. due to an insulation fault in the photovoltaic generator circuit, without presenting a fire risk to the installation. The combined disconnection and short-circuiting device is capable of conducting the indicated short-circuit current independently until the PV installation is maintained.

Switching stages:
Original state

SCP

www.dehn.de

1.
Response of the
disconnection device

SCP

2.
Arc extinction

SCP

107

Surge Arresters Type 2

For protecting photovoltaic installations against surges. For use in accordance with IEC 60364-7-712:2002-05 (Installation of photovoltaic power
supply systems).

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNguard PV ... SCP (FM)


DEHNguard PV ... SCP

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

950 500
950 501
950 502

DG PV 500 SCP
950 500
DG PV 700 SCP
950 501
DG PV 1200 SCP
950 502

Basic circuit diagram DG PV ... SCP

Dimension drawing DG PV ... SCP

DG PV ... SCP: Single-pole surge arrester with combined disconnection and short-circuiting device
for use in photovoltaic generator circuits

DG PV 500 SCP

Surge Arresters Type 2

DG PV 700 SCP

DG PV 1200 SCP

SPD classification according to EN 61643-11


Type 2
SPD classification according to IEC 61643-1
Class II
PV voltage of earth-free PV systems (2 x DG PV ...) UCPV
) 1000 V
PV voltage of functionally earthed PV systems (thin film) UCPV
) 500 V
Max. continuous operating d.c. voltage UC
500 V
Nominal discharge current (8/20 s) In
20 kA
Max. discharge current (8/20 s) Imax
30 kA
Voltage protection level for In UP
) 2 kV
Voltage protection level at 5 kA UP
) 1.7 kV
Response time tA
) 25 ns
Permanent short-circuit withstand capability IK
80 A d.c.
Reverse current withstand capability Ipmax
50 kA / 5 ms
Max. protection of the main d.c. line at the inverter
315 A gR
Operating temperature range TU
-40C...+65C
Operating state/fault indication
green / red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
Cross-sectional area (max.)
35 mm2 stranded/25 mm2 flexible

Type 2
Class II
) 1400 V
) 700 V
700 V
15 kA
30 kA
) 2.5 kV
) 2 kV
) 25 ns
80 A d.c.
50 kA / 5 ms
315 A gR
-40C...+65C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

Type 2
Class II
) 1400 V
) 1200 V
1200 V
15 kA
30 kA
) 4.2 kV
) 3.5 kV
) 25 ns
80 A d.c.
50 kA / 5 ms
315 A gR
-40C...+65C
green/red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

For mounting on
Enclosure material
Degree of protection
Capacity

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880

Ordering information
Type
Part No.
Packing unit

DG PV 500 SCP
950 500
1 pc(s).

DG PV 700 SCP
950 501
1 pc(s).

DG PV 1200 SCP
950 502
1 pc(s).

108

www.dehn.de

DG PV 500 SCP
DG PV 700 SCP
DG PV 1200 SCP

Combined
Arresters Type 1

950 505
950 506
950 507

DG PV 500 SCP FM
DG PV 700 SCP FM
DG PV 1200 SCP FM

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard PV ... SCP (FM)


DEHNguard PV ... SCP FM

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

DG PV 500 SCP FM
950 505
DG PV 700 SCP FM
950 506
DG PV 1200 SCP FM
950 507

12
11
14

Dimension drawing DG PV ... SCP FM

Basic circuit diagram DG PV ... SCP FM

DG PV 500 SCP FM

DG PV 700 SCP FM

DG PV 1200 SCP FM

Type 2
Class II
) 1400 V
) 700 V
700 V
15 kA
30 kA
) 2.5 kV
) 2 kV
) 25 ns
80 A d.c.
50 kA / 5 ms
315 A gR
-40C...+65C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

Type 2
Class II
) 1400 V
) 1200 V
1200 V
15 kA
30 kA
) 4.2 kV
) 3.5 kV
) 25 ns
80 A d.c.
50 kA / 5 ms
315 A gR
-40C...+65C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG PV 500 SCP FM
950 505
1 pc(s).

DG PV 700 SCP FM
950 506
1 pc(s).

DG PV 1200 SCP FM
950 507
1 pc(s).

SPD classification according to EN 61643-11


Type 2
SPD classification according to IEC 61643-1
Class II
PV voltage of earth-free PV systems (2 x DG PV ...) UCPV
) 1000 V
PV voltage of functionally earthed PV systems (thin film) UCPV
) 500 V
Max. continuous operating d.c. voltage UC
500 V
Nominal discharge current (8/20 s) In
20 kA
Max. discharge current (8/20 s) Imax
30 kA
Voltage protection level for In UP
) 2 kV
Voltage protection level at 5 kA UP
) 1.7 kV
Response time tA
) 25 ns
Permanent short-circuit withstand capability IK
80 A d.c.
Reverse current withstand capability Ipmax
50 kA / 5 ms
Max. protection of the main d.c. line at the inverter
315 A gR
Operating temperature range TU
-40C...+65C
Operating state/fault indication
green / red
Cross-sectional area (min.)
1.5 mm2 solid/flexible
Cross-sectional area (max.)
35 mm2 stranded/25 mm2 flexible
For mounting on
Enclosure material
Degree of protection
Capacity
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

www.dehn.de

109

Surge Arresters Type 2

DG PV ... SCP FM: Single-pole surge arrester with combined disconnection and short-circuiting
device for use in photovoltaic generator circuits; with floating remote signalling contact

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

DEHNguard 1000 (FM)


Single-pole, compact surge arrester

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

High discharge capacity due to heavy-duty zinc


oxide varistor
Quick response
High reliability due to Thermo Dynamic
Control disconnector
Fault indication by red indicator flag in the
inspection window
Specifically designed for high system voltages

Surge Arresters Type 2

For protecting low voltage consumers installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0B 1 and higher.

DEHNguard 1000: Single-pole, compact surge arrester with a rated voltage UC = 1000 V a.c.
DEHNguard ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

The compact and powerful DEHNguard ... 1000 (FM) surge arresters are
designed for rated voltages of 1000 V. These single-pole devices can be
used for a wide range of applications.
It is not only the flexibility that characterises the DEHNguard family, but
especially the striking performance parameters, setting trends worldwide:
High discharge capacity, low voltage protection level and dual Thermo
Dynamic Control monitoring and disconnection device stand for maximum reliability.

Especially the DEHN-specific Thermo Dynamic Control disconnector


ensures that the arresters change to a safe isolated operating state even
in case of extreme overload. Apart from the surface temperature of the
heavy-duty varistor, also the intensity of the discharge current is evaluated.
Also the external design of the device is completely adapted to the field
of application. DEHNguard 1000 (FM), with a width of 2 modules, entirely fulfils all mechanical requirements resulting from the high system voltages.
Apart from the standard green and red indication, DEHNguard ... FM features a three-pole terminal for remote signalling. With its floating
changeover contact, the remote signal can be used as a break or make
contact according to the particular circuit concept.
For earth-sided installation of DEHNguard (FM) devices, earthing brackets
of type EB DG 1000 1 3 and EB 1 4 9 can be used.

110

www.dehn.de

Combined
Arresters Type 1

950 102
950 112

DG 1000
DG 1000 FM

DG 1000
950 102
DG 1000 FM
950 112

DEHNguard FM, 1000 V

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard 1000 (FM)


DEHNguard 1000 (FM)

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

DEHNguard, 1000 V

12
11
14

Dimension drawing DG 1000 FM

Basic circuit diagram DG 1000 FM

SPD according to EN 61643-11


SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Max. continuous operating d.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level Up
Voltage protection level at 5 kA UP
Response time tA
Max. overcurrent protection
Max. overcurrent protection for U ) 690 V a.c.
Short-circuit withstand capability for max. backup fuse
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

Accessory Part for DEHNguard 1000 (FM)

DG 1000 FM

Type 2
Class II
1000 V
1000 V
15 kA
30 kA
) 4.2 kV
) 3.5 kV
) 25 ns
100 A aM
125 A gL/gG
25 kArms
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715

Type 2
Class II
1000 V
1000 V
15 kA
30 kA
) 4.2 kV
) 3.5 kV
) 25 ns
100 A aM
125 A gL/gG
25 kArms
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible
35 mm DIN rail acc. to EN 60715

thermoplastic, red, UL 94 V-0


IP 20
2 mods., DIN 43880

thermoplastic, red, UL 94 V-0


IP 20
2 mods., DIN 43880
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG 1000
950 102
1 pc(s).

DG 1000 FM
950 112
1 pc(s).

Accessory Part for DEHNguard 1000 (FM)

EB DG, 3-pole, single-phase

Earthing Clip, 4-pole, single-phase

Earthing clip for earth-side jumpering of 3 DEHNguard 1000 (FM) surge


arresters

Earthing clip for earth-side jumpering of 4 DEHNguard 1000 (FM) surge


arresters

900 411
1000 1 3

EB DG

900 417

EB DG 1000 1 3
900 411

Type
EB DG 1000 1 3

www.dehn.de

DG 1000

Dimension
34 x 112 x 3 mm

Terminal
up to 25 mm2

PU
pc(s).
1

Surge Arresters Type 2

DG 1000 (FM): Single-pole, compact surge arrester with a rated voltage UC = 1000 V a.c.; FM version with floating remote signalling contact

Part
No.
900 411

EB 1 4 9

EB 1 4 9
900 417

Type
EB 1 4 9

Dimension
34 x 148 x 3 mm

Terminal
up to 25 mm2

PU
pc(s).
1

Part
No.
900 417

111

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

DEHNguard S ... VA (FM)


Single-pole, pluggable varistor- and
spark-gap-based arrester

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2
SPD Type 2 according to EN 61643-11
SPD Class II according to IEC 61643-1

All-purpose surge arrester consisting of a base


part and plug-in protection module
Leakage-current-free series connection of a
varistor and a spark gap in the pluggable protection module
High reliability due to Thermo Dynamic
Control SPD monitoring device
Energy coordination within the Red/Line product family
Easy replacement of protection modules without tools due to module locking system with
module release button
Narrow (modular) design in accordance with
DIN 43880

Surge Arresters Type 2

Multifunctional terminal for connecting conductors and busbars

For protecting low-voltage consumers installations against overvoltage.


For installation in conformity with the lightning protection zones concept
at the boundaries from 0B 1 and higher.

DEHNguard S ... VA:

Modular, single-pole surge arrester with a varistor and a spark gap connected in series in the pluggable protection module
DEHNguard S ... VA FM: With remote signalling contact for the monitoring device (floating changeover contact)

The single-pole DEHNguard S ... VA surge arresters complement the tried


and tested DEHNguard product families. The special series connection of
a spark gap and a varistor module in the protection module opens up new
fields of application. It is advisable to use DEHNguard S ... VA devices e.g.
in systems with permanent insulation monitoring and in e.g. railroad systems for protecting the power supply of signal lines which have to be free
of leakage currents. DEHNguard S ... VA arresters are also suited for protecting power line communication applications.

Particularly the DEHN-specific Thermo Dynamic Control disconnection


device ensures that the arresters enter a safe, isolated state even in case
of extreme overload. For this purpose, the intensity of the discharge current is evaluated together with the surface temperature of the heavy-duty
varistor. In addition to the standard red and green indicator, the
DEHNguard S VA ... FM devices feature a three-pole remote signalling terminal. With their floating changeover contact, the remote signal can be
used as break or make contact according to the particular protection concept.

The multifunctional terminals allow almost unlimited flexibility in terms of


connection among one another, but also with other DIN rail mounted
devices in a distribution board. The DEHNguard S ... VA line is not only
characterised by flexibility. It are rather the distinctive performance
parameters which set standards worldwide:
A high discharge capacity, complete absence of leakage currents, a low
voltage protection level and the dual Thermo Dynamic Control monitoring
and disconnection device describe the high degree of reliability.

112

www.dehn.de

Combined
Arresters Type 1

DG S 75 VA
DG S 275 VA
DG S 385 VA

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNguard S ... VA (FM)


DEHNguard S VA

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

NEW

DG S 75 VA
952 080
DG S 275 VA
952 082
DG S 385 VA
952 084

Dimension drawing DG S ... VA

Basic circuit diagram DG S ... VA

DG S ... VA: Modular, single-pole surge arrester comprising a varistor and a spark gap connected
in series in the pluggable protection module

DG S 75 VA

DG S 275 VA

DG S 385 VA

Type 2
Class II
75 V
100 V
10 kA
20 kA
) 1.1 kV
) 100 ns
100 A gL/gG

Type 2
Class II
275 V
350 V
10 kA
20 kA
) 1.5 kV
) 100 ns
100 A gL/gG

Type 2
Class II
385 V
500 V
10 kA
20 kA
) 1.75 kV
) 100 ns
100 A gL/gG

25 kArms
75 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

25 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

25 kArms
385 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

For mounting on
Enclosure material
Degree of protection
Capacity

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
1 mod., DIN 43880

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
1 mod., DIN 43880

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
1 mod., DIN 43880

Ordering information
Type
Part No.
Packing unit

DG S 75 VA
952 080
1 pc(s).

DG S 275 VA
952 082
1 pc(s).

DG S 385 VA
952 084
1 pc(s).

SPD according to EN 61643-11


SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Max. continuous operating d.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Response time tA
Max. supply side overcurrent protection
Short-circuit withstand capability for
max. supply side overcurrent protection
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)

Accessory Part for DEHNguard S ... VA (FM)


Varistor-and spark-gap-based protection module
for DEHNguard S ... VA
952 025
75 VA
952 027
275 VA
952 029
385 VA

DG MOD
DG MOD
DG MOD

DG MOD ... VA: Protection module for DEHNguard S ... VA comprising a


varistor connected in series with a spark gap
DG MOD 75 VA
952 025
DG MOD 275 VA
952 027
DG MOD 385 VA
952 029

Type
DG MOD 75 VA
DG MOD 275 VA
DG MOD 385 VA

www.dehn.de

PU
pc(s).
1
1
1

Part
No.
952 025
952 027
952 029

NEW

113

Surge Arresters Type 2

952 080
952 082
952 084

Lightning Current
Arresters Type 1

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNguard S ... VA (FM)


DEHNguard S VA FM

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

NEW

952 085
952 087
952 089

DG S 75 VA FM
952 085
DG S 275 VA FM
952 087
DG S 385 VA FM
952 089

12
11
14

Basic circuit diagram DG S ... VA FM

Dimension drawing DG S ... VA FM

Surge Arresters Type 2

DG S ... VA FM: Modular, single-pole surge arrester with a varistor and a spark gap connected in
series in the pluggable protection module; with floating remote signalling contact

SPD according to EN 61643-11


SPD according to IEC 61643-1
Max. continuous operating a.c. voltage UC
Max. continuous operating d.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Response time tA
Max. supply side overcurrent protection
Short-circuit withstand capability for
max. supply side overcurrent protection
Temporary overvoltage (TOV) UT
TOV characteristics
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

DG S 75 VA FM

DG S 275 VA FM

DG S 385 VA FM

Type 2
Class II
75 V
100 V
10 kA
20 kA
) 1.1 kV
) 100 ns
100 A gL/gG

Type 2
Class II
275 V
350 V
10 kA
20 kA
) 1.5 kV
) 100 ns
100 A gL/gG

Type 2
Class II
385 V
500 V
10 kA
20 kA
) 1.75 kV
) 100 ns
100 A gL/gG

25 kArms
75 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

25 kArms
335 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

25 kArms
385 V / 5 sec.
withstand
-40C...+80C
green / red
1.5 mm2 solid/flexible
35 mm2 stranded/25 mm2 flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
1 mod., DIN 43880
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
1 mod., DIN 43880
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
1 mod., DIN 43880
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DG S 75 VA FM
952 085
1 pc(s).

DG S 275 VA FM
952 087
1 pc(s).

DG S 385 VA FM
952 089
1 pc(s).

Accessory Part for DEHNguard S ... VA (FM)


952 025
75 VA
952 027
275 VA
952 029
385 VA

NEW
DG MOD 75 VA
952 025
DG MOD 275 VA
952 027
DG MOD 385 VA
952 029

DG MOD
DG MOD
DG MOD

Varistor-and spark-gap-based protection module


for DEHNguard S ... VA
DG MOD ... VA: Protection module for DEHNguard S ... VA comprising a
varistor connected in series with a spark gap
Type
DG MOD 75 VA
DG MOD 275 VA
DG MOD 385 VA

114

PU
pc(s).
1
1
1

Part
No.
952 025
952 027
952 029

www.dehn.de

DG S 75 VA FM
DG S 275 VA FM
DG S 385 VA FM

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

V NH / VA NH
NH Surge arresters

SPD Type 2 according to EN 61643-11


SPD Class II according to IEC 61643-1

Surge arrester for use in size 00 and 1 NH fuse


holders
Zinc oxide varistor with monitoring device, disconnector and integrated backup fuse (VA NH
with additional spark gap connected in series)
Energy coordination within the Red/Line product family
Fault indication by tripping indicator

V(A) NH00 280:


Surge arrester for use in size 00 NH fuse holders
V(A) NH1 280:
Surge arrester for use in size 1 NH fuse holders
V(A) NH00 280 FM: With fault indicator for remote signalling; allows for use of NH fuse holders with microswitch (tripping
distance of fault indicator max. 7 mm)

The single-pole V NH and VA NH surge arresters show that surge protective devices do not necessarily have to be designed exclusively for DIN
rails or socket outlets. Being adapted to the conditions in industrial subcircuit distribution boards, V NH and VA NH devices are designed in the
form of an NH fuse holder. This allows for easy integration into busbar systems, as often applied in zones belonging to the operators of power supply systems or in industrial installations. Thus, the advantages of busbar
systems such as easy installation, less installation time and reduced
wiring also apply to surge protection. The idea of such a busbar system is
consistently continued with SPDs in NH design. V NH and VA NH surge
arresters can be installed and removed by means of a fuse switch disconnector and a fuse handle. This makes it considerably easier to measure the
isolation of the installation as the SPD does not have to be disconnected
any more.
Another considerable advantage of the V NH / VA NH family is the already integrated
backup fuse. If SPDs are
installed in an earth fault- and
short-circuit-proof way, this
considerably saves space and
costs in distribution boards. In

www.dehn.de

case of type VA NH, a spark gap was connected in series to the heavy-duty
zinc oxide varistor with thermal monitoring and disconnection device of
the V NH devices. VA NH devices provide reliable protection especially for
large-scale systems with permanent isolation control. Apart from the
standard visual indication by a fault indicator, V(A) NH ... FM devices provide a microswitch integrated into the NH fuse holder for remote signalling.

115

Surge Arresters Type 2

For protecting low voltage consumers installations against surges. For


installation in conformity with the lightning protection zones concept at
the boundaries from 0B 1 and higher. German patented design.

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

V NH / VA NH
V NH00 (FM)

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

Basic circuit diagram V NH00 (FM), V NH1

Dimension drawing
V NH1

900 261
280
900 263
280 FM

V NH00

V NH00 280
Surge Arrester, Size 00
V NH00 280 FM
Surge Arrester, Size 00

VNH
900 261
VNH FM
900 263

V NH00

Dimension drawing
V NH00 (FM)

V NH00 (FM): Surge arrester for use in size 00 NH fuse holders; optionally available with indicator
for remote signalling
V NH1:

Surge Arresters Type 2

SPD according to EN 61643-11 / ... IEC 61643-1


Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Voltage protection level at 5 kA UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
Temporary overvoltage (TOV) UT
TOV characteristics
Indication of the disconnector
Operating temperature range TU
For mounting on
Enclosure material
Degree of protection
Ordering information
Type
Part No.
Packing unit

Surge arrester for use in size 1 NH fuse holders


V NH00 280

V NH00 280 FM

Type 2 / Class II
280 V
15 kA

Type 2 / Class II
280 V
15 kA

30 kA
) 1.25 kV
) 1 kV
) 25 ns
not required
25 kArms
335 V / 5 sec.
withstand
red fault indicator
-40C...+80C
size 00 NH fuse holder
thermoplastic, red, UL 94 V-0
IPX4W

30 kA
) 1.25 kV
) 1 kV
) 25 ns
not required
25 kArms
335 V / 5 sec.
withstand
red fault indicator (tripping distance 7 mm)
-40C...+80C
size 00 NH fuse holder
thermoplastic, red, UL 94 V-0

V NH00 280
900 261
1 pc(s).

V NH00 280 FM
900 263
1 pc(s).

V NH1 280
SPD according to EN 61643-11 / ... IEC 61643-1
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Voltage protection level at 5 kA UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
Temporary overvoltage (TOV) UT
TOV characteristics
Indication of the disconnector
Operating temperature range TU
For mounting on
Enclosure material
Degree of protection
Ordering information
Type
Part No.
Packing unit
116

Type 2 / Class II
280 V
15 kA
30 kA
) 1.25 kV
) 1 kV
) 25 ns
not required
25 kArms
335 V / 5 sec.
withstand
red fault indicator
-40C...+80C
size 1 NH fuse holder
thermoplastic, red, UL 94 V-0
IPX4W

900 270
280

V NH1

V NH1 280
Surge Arrester, Size 1

VNH
900 270

V NH1 280
900 270
1 pc(s).
www.dehn.de

Combined
Arresters Type 1

900 262
280
900 264
280 FM

VA NH00

VA NH00 280
Surge Arrester, Size 00
VA NH00 280 FM
Surge Arrester, Size 00

VANH
900 262
VANH FM
900 264

VA NH00

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

Dimension drawing
VA NH00 (FM)

Dimension drawing
VA NH1

Surge Arresters
Type 3

Accessories

V NH / VA NH
VA NH00 (FM)

Basic circuit diagram VA NH00 (FM), V NH1

VA NH00 FM: Surge arrester with a varistor and a spark gap connected in series; for use in size 00
NH fuse holders, optionally available with indicator for remote signalling
Surge arrester with a varistor and a spark gap connected in series; for use in size 1
NH fuse holders

SPD according to EN 61643-11 / ... IEC 61643-1


Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
Temporary overvoltage (TOV) UT
TOV characteristics
Indication of the disconnector
Operating temperature range TU
For mounting on
Enclosure material
Degree of protection
Ordering information
Type
Part No.
Packing unit

VA NH00 280

VA NH00 280 FM

Type 2 / Class II
280 V
10 kA

Type 2 / Class II
280 V
10 kA

20 kA
) 1.5 kV
) 100 ns
not required
25 kArms
335 V / 5 sec.
withstand
red fault indicator
-40C...+80C
size 00 NH fuse holder
thermoplastic, red, UL 94 V-0
IPX4W

20 kA
) 1.5 kV
) 100 ns
not required
25 kArms
335 V / 5 sec.
withstand
red fault indicator (tripping distance 7 mm)
-40C...+80C
size 00 NH fuse holder
thermoplastic, red, UL 94 V-0
IPX4W

VA NH00 280
900 262
1 pc(s).

VA NH00 280 FM
900 264
1 pc(s).

Surge Arresters Type 2

VA NH1:

VA NH1 280

900 271
280

VA NH1 280
280, Size 1

VA NH1

VANH
900 271

SPD according to EN 61643-11 / ... IEC 61643-1


Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Max. discharge current (8/20 s) Imax
Voltage protection level UP
Response time tA
Max. mains-side overcurrent protection
Short-circuit withstand capability
Temporary overvoltage (TOV) UT
TOV characteristics
Indication of the disconnector
Operating temperature range TU
For mounting on
Enclosure material
Degree of protection
Ordering information
Type
Part No.
Packing unit

www.dehn.de

Type 2 / Class II
280 V
10 kA
20 kA
) 1.5 kV
) 100 ns
not required
25 kArms
335 V / 5 sec.
withstand
red fault indicator
-40C...+80C
size 1 NH fuse holder
thermoplastic, red, UL 94 V-0
IPX4W

VA NH1 280
900 271
1 pc(s).

117

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

Surge Arresters Type 2

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 2

118

www.dehn.de

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNrail modular
Two-pole, pluggable surge arrester

SPD Type 3 according to EN 61643-11


SPD Class III according to IEC 61643-1

Two-pole surge arrester consisting of a base


part and plug-in protection module
High discharge capacity due to heavy-duty zinc
oxide varistor/spark gap combination
Energy coordination within the Red/Line product family
Operating state/fault indication by indicator
flag in the inspection window
Narrow (modular) design according to DIN
43880
Easy replacement of protection modules due to
module locking system with module release
button
For protection of the power supply circuit of industrial electronics equipment against transient surges in switchboards. For installation according
to the lightning protection zones concept at the boundaries from 1 2
and higher.

Vibration- and shock-tested according to EN


60068-2

The modular devices of the DEHNrail M product family stand out due to
their high performance parameters and new straightforward Red/Line
design. The devices combine safety and user-friendliness in a single module. The low voltage protection level and comprehensive common and differential mode protection are ideally suited for the protection of terminal
devices in industrial electronic environments. The design of the devices
with input and output terminals for series connection and the protective
circuit designed for high load currents underline this concept.
Compact in design, DEHNrail M surge arresters feature a distinctive Y protection circuit and a combined SPD monitoring device and disconnection
mechanism.
The base part and protection module are coded thus preventing incorrect
insertion by the installer or user.

www.dehn.de

The new module locking system of the DEHNrail M product family is


unique for surge protective devices. It fixes the surge protection module
and the base part of the SPD firmly in place. Neither vibration during
transport nor the electromagnetic forces of discharge can loosen the connection.
If the protective circuit is overloaded despite of the powerful characteristics of the devices, the module release button allows quick replacement
of the protection modules without tools.
In addition to the standard green
and red indication, DEHNrail M ...
FM devices feature a three-pole
terminal for remote signalling. With
their floating changeover contact,
the remote signal can be used as a
break or make contact according to
the particular circuit concept.

119

Surge Arresters Type 3

DEHNrail M 2P ...:
Two-pole surge arrester consisting of a base element and plug-in protection module
DEHNrail M 2P ... FM: With remote signalling contact for the monitoring device (floating changeover contact)

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNrail modular
DEHNrail M 2P ...

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
1

953 201
30
953 202
60
953 203
75
953 204
150
953 200
255

DR M 2P 30
953 201
DR M 2P 60
953 202
DR M 2P 75
953 203
DR M 2P 150
953 204
DR M 2P 255
953 200

Basic circuit diagram DR M 2P ...

Dimension drawing DR M 2P ...

DR M 2P ...: Two-pole surge arrester consisting of a base element and plug-in protection module

Surge Arresters Type 3

DR M 2P 30
SPD according to EN 61643-11 / ... IEC 61643-1
Type 3 / Class III
Nominal a.c. voltage UN
24 V
Max. continuous operating a.c. voltage UC
30 V
Max. continuous operating d.c. voltage UC
30 V
Nominal load current a.c. IL
25 A
Nominal discharge current (8/20 s) In
1 kA
Total discharge current (8/20 s) [L+N-PE] Itotal
2 kA
Combined impulse UOC
2 kV
Combined impulse [L+N-PE] UOC total
4 kV
Voltage protection level [L-N] UP
) 180 V
Voltage protection level [L/N-PE] UP
) 630 V
Response time [L-N] tA
) 25 ns
Response time [L/N-PE] tA
) 100 ns
Max. mains-side overcurrent protection
25 A gL/gG or B 25 A
Short-circuit withstand capability for
mains-side overcurrent protection with 25 A gL/gG
6 kArms
Temporary overvoltage (TOV) [L-N] UT

Temporary overvoltage (TOV) [L/N-PE] UT

Temporary overvoltage (TOV) [L+N-PE] UT

Operating temperature range TU


-40C...+80C
Operating state/fault indication
green / red
Cross-sectional area (min.)
0.5 mm2 solid/flexible
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

IP 20
1 mod., DIN 43880

DR M 2P 60

DR M 2P 75

DR M 2P 150

DR M 2P 255

Type 3 / Class III


48 V
60 V
60 V
25 A
1 kA
2 kA
2 kV
4 kV
) 350 V
) 730 V
) 25 ns
) 100 ns
25 A gL/gG or B 25 A

Type 3 / Class III


60 V
75 V
75 V
25 A
2 kA
4 kA
4 kV
8 kV
) 400 V
) 730 V
) 25 ns
) 100 ns
25 A gL/gG or B 25 A

Type 3 / Class III


120 V
150 V
150 V
25 A
2 kA
4 kA
4 kV
8 kV
) 640 V
) 800 V
) 25 ns
) 100 ns
25 A gL/gG or B 25 A

Type 3 / Class III


230 V
255 V
255 V
25 A
3 kA
5 kA
6 kV
10 kV
) 1250 V
) 1500 V
) 25 ns
) 100 ns
25 A gL/gG or B 25 A

6 kArms
6 kArms

-40C...+80C
-40C...+80C
green / red
green / red
0.5 mm2 solid/flexible 0.5 mm2 solid/flexible
4 mm2 solid/2.5 mm2 flexible

6 kArms
335 V / 5 sec.
400 V / 5 sec.
1200 V + U0 / 200 ms
-40C...+80C
green / red
0.5 mm2 solid/flexible

6 kArms

-40C...+80C
green / red
0.5 mm2 solid/flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
IP 20
IP 20
1 mod., DIN 43880
1 mod., DIN 43880
1 mod., DIN 43880
KEMA, VDE, UL, VdS, CSA

DR M 2P 30
953 201
1 pc(s).

DR M 2P 60
953 202
1 pc(s).

DR M 2P 75
953 203
1 pc(s).

DR M 2P 150
953 204
1 pc(s).

IP 20
1 mod., DIN 43880

DR M 2P 255
953 200
1 pc(s).

Accessory Part for DEHNrail modular


953 011
30
953 012
60
953 013
75
953 014
150
953 010
255
DR MOD 30
953 011
DR MOD 60
953 012
DR MOD 75
953 013
DR MOD 150
953 014
DR MOD 255
953 010

120

DR MOD
DR MOD

Protection module for DEHNrail M 2P

DR MOD
DR MOD
DR MOD

DR MOD ...: Protection module with integrated Y protection circuit


Type
DR MOD 30
DR MOD 60
DR MOD 75
DR MOD 150
DR MOD 255

PU
pc(s).
1
1
1
1
1

Part
No.
953 011
953 012
953 013
953 014
953 010

www.dehn.de

DR M 2P
DR M 2P
DR M 2P
DR M 2P
DR M 2P

Combined
Arresters Type 1

DR M 2P
DR M 2P
DR M 2P
DR M 2P
DR M 2P

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNrail modular
DEHNrail M 2P ... FM

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3

DR M 2P 30 FM
953 206
DR M 2P 60 FM
953 207
DR M 2P 75 FM
953 208
DR M 2P 150 FM
953 209
DR M 2P 255 FM
953 205

12
11
14

Dimension drawing DR M 2P ... FM

Basic circuit diagram DR M 2P ... FM

DR M 2P ... FM: Two-pole surge arrester consisting of a base element and plug-in protection module; with floating remote signalling contact
DR M 2P 30 FM
SPD according to EN 61643-11 / ... IEC 61643-1
Type 3 / Class III
Nominal a.c. voltage UN
24 V
Max. continuous operating a.c. voltage UC
30 V
Max. continuous operating d.c. voltage UC
30 V
Nominal load current a.c. IL
25 A
Nominal discharge current (8/20 s) In
1 kA
Total discharge current (8/20 s) [L+N-PE] Itotal
2 kA
Combined impulse UOC
2 kV
Combined impulse [L+N-PE] UOC total
4 kV
Voltage protection level [L-N] UP
) 180 V
Voltage protection level [L/N-PE] UP
) 630 V
Response time [L-N] tA
) 25 ns
Response time [L/N-PE] tA
) 100 ns
Max. mains-side overcurrent protection
25 A gL/gG or B 25 A
Short-circuit withstand capability for
mains-side overcurrent protection with 25 A gL/gG
6 kArms
Temporary overvoltage (TOV) [L-N] UT

Temporary overvoltage (TOV) [L/N-PE] UT

Temporary overvoltage (TOV) [L+N-PE] UT

Operating temperature range TU


-40C...+80C
Operating state/fault indication
green / red
Cross-sectional area (min.)
0.5 mm2 solid/flexible
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
IP 20
Capacity
1 mod., DIN 43880
Approvals, Certifications
Type of remote signalling contact
changeover contact
Switching capacity a.c.
250 V/0.5 A
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

DR M 2P 30 FM
953 206
1 pc(s).

DR M 2P 60 FM

DR M 2P 75 FM

DR M 2P 150 FM

DR M 2P 255 FM

Type 3 / Class III


48 V
60 V
60 V
25 A
1 kA
2 kA
2 kV
4 kV
) 350 V
) 730 V
) 25 ns
) 100 ns
25 A gL/gG or B 25 A

Type 3 / Class III


60 V
75 V
75 V
25 A
2 kA
4 kA
4 kV
8 kV
) 400 V
) 730 V
) 25 ns
) 100 ns
25 A gL/gG or B 25 A

Type 3 / Class III


120 V
150 V
150 V
25 A
2 kA
4 kA
4 kV
8 kV
) 640 V
) 800 V
) 25 ns
) 100 ns
25 A gL/gG or B 25 A

Type 3 / Class III


230 V
255 V
255 V
25 A
3 kA
5 kA
6 kV
10 kV
) 1250 V
) 1500 V
) 25 ns
) 100 ns
25 A gL/gG or B 25 A

6 kArms
6 kArms

-40C...+80C
-40C...+80C
green / red
green / red
0.5 mm2 solid/flexible 0.5 mm2 solid/flexible
4 mm2 solid/2.5 mm2 flexible

6 kArms
335 V / 5 sec.
400 V / 5 sec.
1200 V + U0 / 200 ms
-40C...+80C
green / red
0.5 mm2 solid/flexible

6 kArms

-40C...+80C
green / red
0.5 mm2 solid/flexible

35 mm DIN rail acc. to EN 60715


thermoplastic, red, UL 94 V-0
IP 20
IP 20
IP 20
1 mod., DIN 43880
1 mod., DIN 43880
1 mod., DIN 43880
KEMA, VDE, UL, VdS, CSA
changeover contact
changeover contact
changeover contact
250 V/0.5 A
250 V/0.5 A
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DR M 2P 60 FM
953 207
1 pc(s).

DR M 2P 75 FM
953 208
1 pc(s).

DR M 2P 150 FM
953 209
1 pc(s).

Surge Arresters Type 3

953 206
30 FM
953 207
60 FM
953 208
75 FM
953 209
150 FM
953 205
255 FM

Lightning Current
Arresters Type 1

IP 20
1 mod., DIN 43880
changeover contact
250 V/0.5 A

DR M 2P 255 FM
953 205
1 pc(s).

Protection module for DEHNrail M 2P


953 011
30
953 012
60
953 013
75
953 014
150
953 010
255

DR MOD

DR MOD 30
DEHNrail, 2-polig, 30 V
DR MOD 60
DEHNrail, 2-polig, 60 V
DR MOD 75
DEHNrail, 2-polig, 75 V
DR MOD 150
DEHNrail, 2-polig, 150 V
DR MOD 255
DEHNrail, 2-polig, 255 V

S-Modul
953 011
S-Modul
953 012
S-Modul
953 013
S-Modul
953 014
S-Modul
953 010

DR MOD
DR MOD
DR MOD

DR MOD ...: Protection module with integrated Y protection circuit


Type
DR MOD 30
DR MOD 60
DR MOD 75
DR MOD 150
DR MOD 255
www.dehn.de

DR MOD

PU
pc(s).
1
1
1
1
1

Part
No.
953 011
953 012
953 013
953 014
953 010

121

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

DEHNrail modular, multipole


Four-pole, pluggable surge arrester

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

Four-pole surge arrester consisting of a base


element and plug-in protection module
High discharge capacity due to heavy-duty zinc
oxide varistor/spark gap combination
Energy coordination within the Red/Line product family
Operating state/fault indication by indicator
flag in the inspection window
Easy replacement of protection modules without the use of tools due to module locking system with module release button
Nominal load currents up to 25 A
Vibration- and shock-tested in accordance with
EN 60068-2
For protecting the power supply circuit of industrial electronics equipment
against transient surges in switchgear cabinets. For installation in conformity with the lightning protection zones concept at the boundaries
from 1 2 and higher.

Surge Arresters Type 3

DEHNrail M 4P ...:
Four-pole surge arrester consisting of a base element and plug-in protection module
DEHNrail M 4P ... FM: With remote signalling contact for the monitoring device (floating changeover contact)
The four-pole, modular DEHNrail M 4P ... (FM) surge arrester was specifically developed for protecting three-phase industrial electronics terminal
equipment. Adapted to this kind of environment, the SPD with the new
Red/Line design is suitable for 35 mm DIN rails. The low voltage protection level and the comprehensive common and differential mode protection are characteristic of DEHNrail M 4P ... (FM). In order to provide optimal low voltage protection levels for the terminal equipment to be protected, the device features input and output terminals for series connection. DEHNrail M 4P ... (FM) devices ideally adapt to the cable run
upstream of the terminal equipment therefore not requiring additional
terminal blocks for outgoing cables. The very compact design of DEHNrail
M 4P ... (FM) already incorporates the tried and tested disconnector. It disconnects an overloaded SPD circuit from the mains without interrupting
the supply circuit.

122

The base part and protection module of the device are coded thus preventing incorrect insertion by the installer or user.
The new module locking system of the DEHNrail M family is unique for
surge protective devices. It fixes the surge protection modules and the
base part of the SPD firmly in place. Neither vibrations during transport
nor the electrodynamic forces of discharge can loosen the connection.
If the protective circuits, which are rated for high load currents up to
25 A, are overloaded despite of the powerful characteristics of the device,
the protection modules can be easily replaced without tools by simply
pressing the module release button.
Apart from the standard green and red visual indication, DEHNrail M 4P
... FM devices feature a three-pole remote signalling terminal. With their
floating changeover contact, the remote signal can be used as a break or
make contact according to the particular circuit concept.

www.dehn.de

Combined
Arresters Type 1

953 400
255
953 405
255 FM

DR M 4P
DR M 4P

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNrail modular, multipole


DEHN rail M 4P ... (FM)

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
L1 L1

L2 L2

PE PE

N N

L3 L3

DR M 4P 255
953 400
DR M 4P 255 FM
953 405

12
11
14

Dimension drawing DR M 4P ... FM

Basic circuit diagram DR M 4P ... FM

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal load current a.c. IL
Nominal discharge current (8/20 s) In
Total discharge current (8/20 s) [L1+L2+L3+N-PE] Itotal
Combined impulse UOC
Combined impulse [L1+L2+L3+N-PE] UOC total
Voltage protection level [L-N] UP
Voltage protection level [L/N-PE] UP
Response time [L-N] tA
Response time [L/N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for
mains-side overcurrent protection with 25 A gL/gG
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [L/N-PE] UT
Temporary overvoltage (TOV) [N-PE] UT
Operating temperature range TU
Operating state/fault indication
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Approvals, Certifications
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

DR M 4P 255

DR M 4P 255 FM

Type 3
Class III
230/400 V
255/440 V

Type 3
Class III
230/400 V
255/440 V

25 A
3 kA
8 kA
6 kV
16 kV
) 1000 V
) 1500 V
) 25 ns
) 100 ns
25 A gL/gG or B 25 A

25 A
3 kA
8 kA
6 kV
16 kV
) 1000 V
) 1500 V
) 25 ns
) 100 ns
25 A gL/gG or B 25 A

6 kArms
335 V / 5 sec.
400 V / 5 sec.
1200 V / 200 ms
-40C...+80C
green / red
0.5 mm2 solid/flexible
4 mm2 stranded/2.5 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA

6 kArms
335 V / 5 sec.
400 V / 5 sec.
1200 V / 200 ms
-40C...+80C
green / red
0.5 mm2 solid/flexible
4 mm2 solid/2.5 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic, red, UL 94 V-0
IP 20
2 mods., DIN 43880
KEMA
changeover contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible

DR M 4P 255
953 400
1 pc(s).

DR M 4P 255 FM
953 405
1 pc(s).

Surge Arresters Type 3

DR M 4P ... (FM): Four-pole surge arrester consisting of a base element and plug-in protection
module; also available with floating remote signalling contact

Accessory Part for DEHNrail modular, multipole


Protection module for DEHNrail M 4P
953 020
4P 255

DR MOD

DR MOD 4P ...: 4-pole protection module with integrated protective


circuit
DR MOD 4P 255
953 020

Type
DR MOD 4P 255

www.dehn.de

PU
pc(s)
1

Part
No.
953 020

123

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Protection Module for DEHNrail modular


Plug-in protection module for SPDs Type 3

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

The plug-in protection module can be replaced


without the need to de-energise and without
removing the covering plate from the distribution board
Operating state and fault indication by indicator flag in the inspection window
Easy replacement of the protection modules
due to module locking system with module
release button

DEHNrail MOD ...:

For all types of two-pole DEHNrail M


2P ... surge arresters
DEHNrail MOD 4P...: For all types of four-pole DEHNrail M
4P ... surge arresters

For protection of the power supply circuit of industrial electronics equipment against surges in switchboards. For installation in conformity with
the lightning protection zones concept at the boundaries from 1 2 and
higher.

Protection module for DEHNrail M 2P


953 011
30
953 012
60
953 013
75
953 014
150
953 010
255

DR MOD ...: Protection module with integrated Y protection circuit

Surge Arresters Type 3

Basic circuit diagram


DR MOD protection module

Nominal discharge current (8/20 s) In


Total discharge current (8/20 s) [L+N-PE] Itotal
Max. continuous operating a.c. / d.c. voltage UC
Ordering information
Type
Part No.
Packing unit

Dimension drawing
DR MOD protection module

DR MOD 30

DR MOD 60

DR MOD 75

DR MOD 150

DR MOD 255

1 kA
2 kA
30 V

1 kA
2 kA
60 V

2 kA
4 kA
75 V

2 kA
4 kA
150 V

3 kA
5 kA
255 V

DR MOD 30
953 011
1 pc(s).

DR MOD 60
953 012
1 pc(s).

DR MOD 75
953 013
1 pc(s).

DR MOD 150
953 014
1 pc(s).

DR MOD 255
953 010
1 pc(s).

DR MOD
DR MOD
DR MOD
DR MOD
DR MOD

DR MOD 30
953 011
DR MOD 60
953 012
DR MOD 75
953 013
DR MOD 150
953 014
DR MOD 255
953 010

Protection module for DEHNrail M 4P


DR MOD 4P ...: Four-pole protection module with integrated protective
circuit

953 020
4P 255

Basic circuit diagram


Dimension drawing
DR MOD 4P protection module DR MOD 4P protection module

DR MOD 4P 255
953 020

DR MOD 4P 255
Nominal discharge current (8/20 s) In
Total discharge current (8/20 s) [L+N-PE] Itotal
Max. continuous operating a.c. / d.c. voltage UC
Ordering information
Type
Part No.
Packing unit

124

3 kA
8 kA
255 V

DR MOD 4P 255
953 020
1 pc(s).

www.dehn.de

DR MOD

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

Mains Filter
NF 10

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3

Protection of sensitive industrial electronics


equipment against balanced and unbalanced
high-frequency interferences
Completes surge protection,
e.g. DEHNrail M 2P 255
Easy installation on DIN rails in switchgears

The NF 10 mains filter is the ideal completion of surge protection for


industrial terminal equipment. Being a DIN rail mounted device, the mains
filter is ideally suited for installation downstream of surge protective
devices (e.g. DEHNrail M 2P 255). In addition to surge protection, this
ensures protection against balanced and unbalanced high-frequency
NF 10

NF 10
Filter 10 A

Mains
912 254

L1

L1

mains

SPD

N
PE

Dimension drawing NF 10

N
PE

Surge Arresters Type 3

912 254

interferences. The separate input and output terminals of the mains filter
ensure that an optimal protective effect of the device is provided for the
equipment to be protected. This also allows to meet electromagnetic compatibility requirements for constructing control systems and installations
which do not relate to surge protection.

Basic circuit diagram NF 10

NF 10: Mains filter for protection against balanced and unbalanced interferences
NF 10
Nominal a.c. voltage UN
Nominal load current a.c. IL
Nominal frequency fN
Discharge current (for UN)
Attenuation for f = 1 MHz, balanced
Attenuation for f = 1 MHz, unbalanced
Total circuit capacitance [L-N]
Total circuit capacitance [L (N)-PE]
Total circuit inductance
Backup fuse
Operating temperature range
Cross-sectional area
For mounting on
Enclosure material
Degree of protection
Dimension
Ordering information
Type
Part No.
Packing unit

www.dehn.de

230 V
10 A
50...60 Hz
) 3.5 mA
> 64 dB
> 69 dB
660 nF
66 nF
1.8 mH per line
10 A gL/gG
-25C...+40C
min. 2.5 mm2 stranded, max. 4 mm2 flexible
35 mm DIN rail acc. to EN 60715
thermoplastic GF (polycarbonate)
IP 20
110 x 45 x 75 mm

NF 10
912 254
1 pc(s).

125

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

SPS Protector
Two-pole surge arrester with filter

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

Combination of surge protection and filter


Surge protection with monitoring device and
disconnector
Interference suppressor filter for protecting
sensitive industrial electronics equipment
against balanced and unbalanced high-frequency interference
Installed into a shielded enclosure
Visual operating state indication (green) and
floating remote signalling contact (break contact) for fault indication
For protecting the power supply circuit of industrial electronics equipment
(e.g. programmable logic controls/PLCs) against surges and high-frequency interference voltages. For installation in conformity with the lightning
protection zones concept at the boundaries from 1 2 and higher.

Surge Arresters Type 3

SPS Protector: Two-pole surge arrester with interference suppressor filter

The SPS Protector combines surge protection and interference suppressor


filter in one compact device. This makes the device ideal for protecting
sensitive terminal equipment in industrial automation systems (e.g. programmable logic controls PLCs). The coordinated surge protection and
filter functions complement one another and prevent core saturation of
the filter in the event of high-energy transients. The separate input and
output terminals ensure that an optimal protective effect is provided for

126

the device to be protected. The metal enclosure of the SPS Protector


ensures that high-frequency interferences are discharged without interfering with other devices close to the installation. The compact design of the
SPS Protector already incorporates the approved disconnector. In case of
overload, it disconnects the SPD from the mains without interrupting the
supply circuit. Apart from the green light, standard SPS Protector devices
can also be used for remote signalling.

www.dehn.de

Combined
Arresters Type 1

912 253

SPS PRO

SPS PRO
Protector

SPS912 253

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

SPS Protector
SPS Protector

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
11

FM
12

L'

N'

PE

PE

Dimension drawing SPS PRO

Basic circuit diagram SPS PRO

SPS PRO: Surge arrester with interference suppressor filter

SPS PRO

Ordering information
Type
Part No.
Packing unit

www.dehn.de

Type 3
Class III
230 V
255 V
3A
3 kA
5 kA
6 kV
10 kV
) 0.8 kV
) 1.0 kV
) 25 ns
) 100 ns
6 kArms
green light off
green light
-10C...+40C
0.14 mm2 solid/stranded/flexible
2.5 mm2 solid/stranded/flexible
35 mm DIN rail acc. to EN 60715
aluminium, red powder coating
IP 20
7 mods., DIN 43880
break contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A
max. 1.5 mm2 solid/flexible
acc. to DIN VDE 0565 Part 3
* 73 dB
* 45 dB

Surge Arresters Type 3

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal load current a.c. IL
Nominal discharge current (8/20 s) In
Total discharge current (8/20 s) [L+N-PE] Itotal
Combined impulse UOC
Combined impulse [L+N-PE] UOC total
Voltage protection level [L-N] UP
Voltage protection level [L/N-PE] UP
Response time [L-N] tA
Response time [L/N-PE] tA
Short-circuit withstand capability for max. mains-side overcurrent protection
Fault indication
Operating state indication
Operating temperature range TU
Cross-sectional area (min.)
Cross-sectional area (max.)
For mounting on
Enclosure material
Degree of protection
Capacity
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Cross-sectional area for remote signalling terminals
Mains filter
Attenuation for f = 1 MHz, balanced
Attenuation for f = 1 MHz, unbalanced

SPS PRO
912 253
1 pc(s).

127

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNsafe
Surge arrester for use in cable ducts

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

Two-pole surge protective device for 230 V terminal devices


For use in flush-type boxes and cable ducts
Enhanced safety due to distinctive Y protection
circuit
Multiple visual operating state indication
Programmable acoustic function
Terminals for series connection
Independent from the design of socket outlets

For protecting electronic devices against surges. For installation into electrical installation systems, e.g. cable ducts or flush-type boxes. For installation in conformity with the lightning protection zones concept at the
boundaries from 1 2 anf higher.

Surge Arresters Type 3

DEHNsafe 230 LA: Surge protective device for use in cable ducts
The DEHNsafe surge arrester particularly stands out due to its flexible
application options. DEHNsafe is a two-pole surge protective device for
230 V terminal equipment which can be installed into cable ducts, but
also into flat flush-type boxes due to the minimal installation depth of
only 31 mm. DEHNsafe incorporates a monitoring device and a thermal
disconnector. In addition to a visual operating state indication, the device
features a programmable acoustic fault indication. With such an acoustic
signal, the fault indication can be programmed for three different operating states:
Acoustic fault indication,
Test function,

A triple TAE cover plate of any switch programme manufacturer can be used for covering
it. Thus, DEHNsafe adapts ideally to any socket
outlet design.
The two available terminals for L, N and PE allow
for series connection to ensure that the surge
protection is situated in parallel to the circuit to
be protected. If DEHNsafe surge arresters are
overloaded, the surge protective device does not necessarily interrupt the
circuit to be protected. DEHNsafe surge arresters feature a green and red
LED for visual indication of the protective device.

Muting of the acoustic signal.

128

www.dehn.de

Combined
Arresters Type 1

924 370
LA

DSA 230

DSA 230 LA
924 370

DEHNsafe

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNsafe
DEHNsafe

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3

Dimension drawing DSA 230 LA

PE

Basic circuit diagram DSA 230 LA

DSA 230 LA: Surge protective device for use in cable ducts and flush-type boxes
DSA 230 LA
Type 3
Class III
230 V
255 V
16 A
3 kA
5 kA
6 kV
10 kV
) 1.25 kV
) 1.5 kV
) 25 ns
) 100 ns
16 A gL/gG or B 16 A
6 kArms
335 V / 5 sec.
400 V / 5 sec.
1200 V + U0 / 200 ms
red light + acoustic signal
green light
function test / acoustic signal off
-25C...+40C
0.5 mm2 solid/stranded/flexible

2.5 mm2 solid/stranded/flexible


supporting ring (60 mm) for installing into switch boxes, depth of 40 mm
thermoplastic, grey, UL 94 V-2
IP 20
TAE

Cross-sectional area (max.)


For mounting on
Enclosure material
Degree of protection
Cover
Ordering information
Type
Part No.
Packing unit

DSA 230 LA
924 370
1 pc(s).

Accessory Part for DEHNsafe

Covering frame

Single unit, alpha exclusive

Single unit, alpha exclusive

ZAP STW
Covering Plate for DEHNsafe

Type
ZAP STW

www.dehn.de

Accessory Part for DEHNsafe

Central covering plate


924 329

Surge Arresters Type 3

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal load current IL
Nominal discharge current (8/20 s) In
Total discharge current (8/20 s) [L+N-PE] Itotal
Combined impulse UOC
Combined impulse [L+N-PE] UOC total
Voltage protection level [L-N] UP
Voltage protection level [L/N-PE] UP
Response time [L-N] tA
Response time [L/N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [L/N-PE] UT
Temporary overvoltage (TOV) [L+N-PE] UT
Fault indication
Operating state indication
Switch
Operating temperature range TU
Cross-sectional area (min.)

ZAP STW

924 328

Central
924 329

AR1 STW
Frame for DEHNsafe, studio white

Colour
studio white

PU
pc(s).
1

Part
No.
924 329

Type
AR1 STW

AR1 STW

Covering
924 328

Colour
studio white

PU
pc(s).
1

Part
No.
924 328

129

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

STC Module
Surge arrester for earthed socket outlets

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

Two-pole surge arrester with monitoring device


and disconnector
Enhanced safety due to distinctive Y protection
circuit
Acoustic fault indication
For installation in combination with standard
earthed socket outlets
Independent from the design of the socket outlets
Plastic supporting ring with latch for easy
installation on already mounted socket outlets
For protecting electronic devices against surges. For use with standard
earthed socket outlets. For installation in conformity with the lightning
protection zones concept at the boundaries from 1 2 and higher.

Surge Arresters Type 3

STC 230:

Snap-on module for standard earthed socket outlets

The popular STC surge protection module can be installed inconspicuously. Being a two-pole surge arrester, the module can be installed on the rear
side of standard earthed socket outlets. The STC surge protection module
thus adapts to every type of socket outlet. The plastic supporting ring with
latch allows easy installation even on already mounted socket outlets. In

130

addition to a thermal disconnector, the protective device features an


acoustic fault indication. As the surge protection module is installed in
parallel to the socket outlet, the power supply of the connected consumers remains uninterrupted, even if the surge arrester is overloaded.

www.dehn.de

Combined
Arresters Type 1

924 350

STC 230

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

STC Module
STC 230

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3

STC 230
924 350

approx. 127

approx. 117

Dimension drawing STC 230

PE

Basic circuit diagram STC 230

STC 230: Two-pole surge arrester for snapping onto earthed socket outlets

STC 230

Ordering information
Type
Part No.
Packing unit

www.dehn.de

Surge Arresters Type 3

SPD according to EN 61643-11


Type 3
SPD according to IEC 61643-1
Class III
Nominal a.c. voltage UN
230 V
Max. continuous operating a.c. voltage UC
255 V
Nominal discharge current (8/20 s) In
3 kA
Total discharge current (8/20 s) [L+N-PE] Itotal
5 kA
Combined impulse UOC
6 kV
Combined impulse [L+N-PE] UOC total
10 kV
Voltage protection level [L-N] UP
) 1.25 kV
Voltage protection level [L/N-PE] UP
) 1.5 kV
Response time [L-N] tA
) 25 ns
Response time [L/N-PE] tA
) 100 ns
Max. mains-side overcurrent protection
16 A gL/gG or B 16 A
Short circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG
6 kArms
Temporary overvoltage (TOV) [L-N] UT
335 V / 5 sec.
Temporary overvoltage (TOV) [L/N-PE] UT
400 V / 5 sec.
Temporary overvoltage (TOV) [L+N-PE] UT
1200 V + U0 / 200 ms
Fault indication
acoustic signal on
Operating temperature range TU
-25C...+40C
Terminal wires
1 mm2, length: 120 mm
For mounting on
common socket outlets with earth contact
Enclosure material
thermoplastic, red, UL 94 V-2
Degree of protection of installed device
IP 20
Dimension
53 x 53 x 32 mm
Indication of disconnector
acoustic signal on

STC 230
924 350
1 pc(s).

131

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNflex
Flexible protection of terminal equipment

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

Two-pole surge arrester with monitoring device


and disconnector
Enhanced safety due to distinctive Y protection
circuit
Acoustic fault indication
Compact design
For use in flush-mounted systems, cable ducts
and flush-type boxes

For protecting electronic equipment against surges. For installation into


electrical installation systems, e.g. flush-mounted systems, cable ducts
and flush-type boxes. German utility patent for DEHNflex A / ... D. For
installation in conformity with the lightning protection zones concept at
the boundaries from 1 2 and higher.

Surge Arresters Type 3

DEHNflex M:
DEHNflex A:
DEHNflex D:

More compact version; for use in cable duct systems and flush-mounted socket outlets
For use in any cable duct systems or flush-mounted socket outlets; with test function
Like DEHNflex A, but for series connection of several socket outlets

The name of the DEHNflex family refers to the nearly unlimited application possibilities of the devices. Being 2-pole surge arresters, the compact
modules are ideally suited for protecting electronic consumers in final circuits. The design was adapted to the most common installation locations,
i.e. cable ducts and flush-type boxes. DEHNflex devices show that small
and compact sizes do not necessarily mean low-capacity performance.

132

The distinctive Y protection circuit always ensures safety even if the phase
and neutral conductors cannot be identified. Apart from the powerful Y
circuit, the compact enclosure also incorporates a disconnector and an
acoustic fault indicator. In cable ducts, flush-mounted systems, branching
boxes or device tubs DEHNflex can always be installed in the right place
close to terminal equipment.

www.dehn.de

Combined
Arresters Type 1

924 396
255

DFL M

DFL M 255
M

DEHNflex
924 396

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

DEHNflex
DEHNflex M

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3

Dimension drawing DFL M

Accessories

PE

Basic circuit diagram DFL M

DFL M: Surge arrester for use in all types of installation systems for terminal equipment; compact
dimensions

DFL M 255

Ordering information
Type
Part No.
Packing unit

www.dehn.de

Type 3
Class III
230 V
255 V
1.5 kA
3 kA
3 kV
6 kV
) 1.25 kV
) 1.5 kV
) 25 ns
) 100 ns
32 A gL/gG or B 32 A
6 kArms
335 V / 5 sec.
400 V / 5 sec.
1200 V + U0 / 200 ms
acoustic signal on
-25C...+40C
1 mm2 , length: 120 mm
thermoplastic, red, UL 94 V-2
IP 20
30 x 50 x 11 mm

Surge Arresters Type 3

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Total discharge current (8/20 s) [L+N-PE] Itotal
Combined impulse UOC
Combined impulse [L+N-PE] UOC total
Voltage protection level [L-N] UP
Voltage protection level [L/N-PE] UP
Response time [L-N] tA
Response time [L/N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection with 32 A gL/gG
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [L/N-PE] UT
Temporary overvoltage (TOV) [L+N-PE] UT
Fault indication
Operating temperature range TU
Terminal wires
Enclosure material
Degree of protection of installed device
Dimension

DFL M 255
924 396
1 pc(s).

133

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNflex
DEHNflex A

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
L
N

924 389

DFL A 255

DFL A 255
A

DEHNflex
924 389

PE

Basic circuit diagram DFL A

Dimension drawing DFL A

DFL A: Surge arrester for use in all types of installation systems for terminal equipment; with test
function

Surge Arresters Type 3

DFL A 255
SPD according to EN 61643-11
SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Total discharge current (8/20 s) [L+N-PE] Itotal
Combined impulse UOC
Combined impulse [L+N-PE] UOC total
Voltage protection level [L-N] UP
Voltage protection level [L/N-PE] UP
Response time [L-N] tA
Response time [L/N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [L/N-PE] UT
Temporary overvoltage (TOV) [L+N-PE] UT
Fault indication
Operating temperature range TU
Terminal wires
Enclosure material
Degree of protection of installed device
Dimension
Ordering information
Type
Part No.
Packing unit

134

Type 3
Class III
230 V
255 V
3 kA
5 kA
6 kV
10 kV
) 1.25 kV
) 1.5 kV
) 25 ns
) 100 ns
16 A gL/gG or B 16 A
6 kArms
335 V / 5 sec.
400 V / 5 sec.
1200 V + U0 / 200 ms
acoustic signal on
-25C...+40C
1 mm2 , length: 120 mm
thermoplastic, red, UL 94 V-2
IP 20
36 x 62 x 19 mm

DFL A 255
924 389
1 pc(s).

www.dehn.de

Combined
Arresters Type 1

924 395

DFL D 255

DFL D 255
D

DEHNflex
924 395

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

DEHNflex
DEHNflex D

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
L
N

PE

Dimension drawing DFL D

Basic circuit diagram DFL D

DFL D: Surge arrester for use in all types of installation systems for terminal equipment; allows for
through-wiring; with test function

DFL D 255

Ordering information
Type
Part No.
Packing unit

www.dehn.de

Type 3
Class III
230 V
255 V
16 A
3 kA
5 kA
6 kV
10 kV
) 1.25 kV
) 1.5 kV
) 25 ns
) 100 ns
16 A gL/gG or B 16 A
6 kArms
335 V / 5 sec.
400 V / 5 sec.
1200 V + U0 / 200 ms
acoustic signal on
-25C...+40C
2.5 mm2 , length: 120 mm
thermoplastic, red, UL 94 V-2
IP 20
36 x 62 x 19 mm

Surge Arresters Type 3

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal load current a.c. IL
Nominal discharge current (8/20 s) In
Total discharge current (8/20 s) [L+N-PE] Itotal
Combined impulse UOC
Combined impulse [L+N-PE] UOC total
Voltage protection level [L-N] UP
Voltage protection level [L/N-PE] UP
Response time [L-N] tA
Response time [L/N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [L/N-PE] UT
Temporary overvoltage (TOV) [L+N-PE] UT
Fault indication
Operating temperature range TU
Terminal wires
Enclosure material
Degree of protection of installed device
Dimension

DFL D 255
924 395
1 pc(s).

135

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

NSM Protector
Surge protective socket outlet

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

Surge protection with monitoring device and


disconnector
Maximum safety due to distinctive Y protection
circuit
Visual operating state (green) and fault indication (red)
With supporting ring (dimension 60 mm) for
installation into switchboxes with a diameter of
60 mm and a depth of 40 mm

For protecting electronic equipment against surges. Earthed socket outlet


contact and surge protective circuit for installation into electrical installation systems. For installation according to the lightning protection zones
concept at the boundaries from 1 2 and higher. German utility patent.

Surge Arresters Type 3

NSM Protector: Earthed socket outlet with integrated surge protection


The devices of the NSM Protector family combine surge protection and
earthed socket outlet in one single device. The two-pole surge arresters
are specifically designed for protecting electronic consumers in final circuits. The very compact design of NSM Protector devices already includes
the approved disconnector. It isolates overloaded surge arresters without
interrupting the supply circuit. The low voltage protection level as well as
the comprehensive common and differential mode protection is typical of

136

the devices of the NSM Protector family. The distinctive Y protective circuit ensures safety even if the phase and neutral conductors in final circuits cannot be identified. The integrated disconnector makes a further
contribution to the safety of devices and installations. The standard green
and red LEDs inform the user on the present operating state of the surge
protective devices.

www.dehn.de

Combined
Arresters Type 1

924 335
TW
924 337
SI
924 339
AZ
924 342
EW

NSM PRO
NSM PRO
NSM PRO
NSM PRO

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Accessories

NSM Protector
NSM PRO

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
L/N

NSM PRO TW
Protector DELTA profile, titan white
NSM PRO SI
Protector DELTA profile, silver
NSM PRO AZ
Protector DELTA profile, anthracite
NSM PRO EW
Protector DELTA profile, studio white

Surge Arresters
Type 3

L/N

NSM924 335
NSM924 337
NSM924 339
NSM924 342

PE

Dimension drawing NSM PRO ...

Basic circuit diagram NSM PRO ...

NSM PRO ...: Surge protective socket outlet


NSM PRO TW

NSM PRO SI

NSM PRO AZ

NSM PRO EW

Enclosure material
Degree of protection
DELTA type

thermoplastic, UL 94 V-2
IP 20
profile, titanium white

thermoplastic, UL 94 V-2
IP 20
profile, silver

thermoplastic, UL 94 V-2
IP 20
profile, anthracite

thermoplastic, UL 94 V-2
IP 20
plus, studio white

Ordering information
Type
Part No.
Packing unit

NSM PRO TW
924 335
1 pc(s).

NSM PRO SI
924 337
1 pc(s).

NSM PRO AZ
924 339
1 pc(s).

NSM PRO EW
924 342
1 pc(s).

Surge Arresters Type 3

SPD according to EN 61643-11


Type 3
Type 3
Type 3
Type 3
SPD according to IEC 61643-1
Class III
Class III
Class III
Class III
Nominal a.c. voltage UN
230 V
230 V
230 V
230 V
Max. continuous operating a.c. voltage UC
255 V
255 V
255 V
255 V
Nominal discharge current (8/20 s) In
3 kA
3 kA
3 kA
3 kA
Total discharge current (8/20 s) [L+N-PE] Itotal
5 kA
5 kA
5 kA
5 kA
Combined impulse UOC
6 kV
6 kV
6 kV
6 kV
Combined impulse [L+N-PE] UOC total
10 kV
10 kV
10 kV
10 kV
Voltage protection level [L-N] UP
) 1.25 kV
) 1.25 kV
) 1.25 kV
) 1.25 kV
Voltage protection level [L/N-PE] UP
) 1.5 kV
) 1.5 kV
) 1.5 kV
) 1.5 kV
Response time [L-N] tA
) 25 ns
) 25 ns
) 25 ns
) 25 ns
Response time [L/N-PE] tA
) 100 ns
) 100 ns
) 100 ns
) 100 ns
Max. mains-side overcurrent protection
16 A gL/gG or B 16 A
16 A gL/gG or B 16 A
16 A gL/gG or B 16 A
16 A gL/gG or B 16 A
Short-circuit withstand capability for mains-side
overcurrent protection with 16 A gL/gG
6 kArms
6 kArms
6 kArms
6 kArms
Temporary overvoltage (TOV) [L-N] UT
335 V / 5 sec.
335 V / 5 sec.
335 V / 5 sec.
335 V / 5 sec.
Temporary overvoltage (TOV) [L/N-PE] UT
400 V / 5 sec.
400 V / 5 sec.
440 V / 5 sec.
400 V / 5 sec.
Temporary overvoltage (TOV) [L+N-PE] UT
1200 V + U0 / 200 ms
1200 V + U0 / 200 ms
1200 V + U0 / 200 ms
1200 V + U0 / 200 ms
Fault indication
red light
red light
red light
red light
Operating state indication
green light
green light
green light
green light
Operating temperature range TU
-25C...+40C
-25C...+40C
-25C...+40C
-25C...+40C
Cross-sectional area
screwless double terminals up to 2.5 mm2 each, also suitable for series connection
For mounting on
supporting ring (60 mm) for installation into switchboxes, depth of 32 mm

Accessory Part for NSM Protector


AR1 Covering Frame
924 336
924 338
924 340
924 343

AR1 TW
AR1 SI
AR1 AZ
AR1 EW

Single unit, suitable for NSM Protector


AR1 TW
Cover, single-piece, titan white
AR1 SI
Cover, single piece, silver
AR1 AZ
Cover, single piece, anthracite
AR1 EW
Cover, single piece, studio white

Type
AR1 TW
AR1 SI
AR1 AZ
AR1 EW

www.dehn.de

Protector
924 336
Protector
924 338
Protector
924 340
Protector
924 343

Profile
DELTA profile, titanium white
DELTA profile, silver
DELTA profile, anthracite
DELTA plus, studio white

PU
pc(s).
1
1
1
1

Part
No.
924 336
924 338
924 340
924 343

137

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNprotector
Surge protective adapter

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
Type 3 according to EN 61643-11
Class III according to EN 61643-1

Surge protection with monitoring device and


disconnector
Visual operating state (green) and fault indication (red)
Mains filter (DEHNpro 230 F-Protector only)
Enhanced safety due to distinctive Y protection
circuit

Adapters for protecting the power supply circuit of electronic devices


against transient overvoltages as well as high-frequency interference
voltages (DEHNpro 230 F-Protector). For installation in conformity with
the lightning protection zones concept at the boundaries from 1 2 and
higher.

Surge Arresters Type 3

DEHNpro 230: Protection for terminal devices


DEHNpro 230 F: Protection for terminal devices with mains filter
The surge protective adapters of the DEHNpro family provide surge protection for electronic consumers connected to final circuits. In the
DEHNpro 230 F-Protector, the powerful surge protective circuit of
DEHNpro 230 Protector was supplemented by an interference suppressor
filter with a balancing and unbalancing effect. This combination of surge
protection and filter prevents a core saturation of the filter in case of highenergy transients. The nominal current carrying capability of 16 A for
DEHNpro 230 and 10 A for 230 F-Protector allows flexible use of these

138

devices in final circuits. The distinctive Y protection circuit ensures protection even if the phase and neutral conductors in standard earthed socket
outlets cannot be identified. The integrated disconnector also contributes
to the safety of devices and installations. The standard green and red LEDs
inform the user on the operating state of the surge protective devices.
The modern design of DEHNpro devices and the use of high-quality materials ensure safety in a sophisticated appearance. The DEHNpro devices
thus ideally adapt to the environment. They create the right technical
ambience already at the socket outlet for connecting the latest communication and multimedia systems. The curved enclosure surfaces and the
smooth surface structure ensure that the DEHNpro devices will not lose
their original properties even after several years of application.

www.dehn.de

Combined
Arresters Type 1

DPRO 230

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Accessories

DEHNprotector
DPRO 230 Protector

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3

DPRO 230
909 230

Surge Arresters
Type 3

L/N

red
PE

green

L'/N'
PE
N'/L'

N/L

Dimension drawing DPRO 230

Basic circuit diagram DPRO 230

DPRO 230: Surge protective adapter

DPRO 230

DPRO 230 SE

Type 3
Class III
230 V
255 V
16 A
3 kA
5 kA
6 kV
10 kV
) 1.25 kV
) 1.5 kV
) 25 ns
) 100 ns
16 A gL/gG or B 16 A

Type 3
Class III
230 V
255 V
16 A
3 kA
5 kA
6 kV
10 kV
) 1.25 kV
) 1.5 kV
) 25 ns
) 100 ns
16 A gL/gG or B 16 A

6 kArms
335 V / 5 sec.

6 kArms
335 V / 5 sec.

Enclosure material
Degree of protection
Dimension

400 V / 5 sec.
1200 V + U0 / 200 ms
red LED
green LED
-25C...+40C
plug-in system with earth contact
according to DIN 49440 / DIN 49441
thermoplastic, pure white, UL 94 V-2
IP 20
128 x 71 x 40 mm

400 V / 5 sec.
1200 V + U0 / 200 ms
red LED
green LED
-25C...+40C
centre earthing contact system
according to CEE 7, standard sheet V
thermoplastic, pure white, UL 94 V-2
IP 20
128 x 71 x 40 mm

Ordering information
Type
Part No.
Packing unit

DPRO 230
909 230
1 pc(s).

DPRO 230 SE
909 235
1 pc(s).

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal load current a.c. IL
Nominal discharge current (8/20 s) In
Total discharge current (8/20 s) [L+N-PE] Itotal
Combined impulse UOC
Combined impulse [L+N-PE] UOC total
Voltage protection level [L-N] UP
Voltage protection level [L/N-PE] UP
Response time [L-N] tA
Response time [L/N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for
mains-side overcurrent protection with 16 A gL/gG
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [L/N-PE] UT
Temporary overvoltage (TOV) [L+N-PE] UT
Fault indication
Operating state indication
Operating temperature range TU
For mounting on

www.dehn.de

Surge Arresters Type 3

909 230

Lightning Current
Arresters Type 1

139

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

DEHNprotector
DPRO 230 F-Protector

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3

DPRO 230 F
909 240

L/N

red
PE

909 240
F

green

L'/N'
PE
N'/L'

N/L

Basic circuit diagram DPRO 230 F

Dimension drawing DPRO 230 F

Surge Arresters Type 3

DPRO 230 F: Surge protective adapter with integrated mains filter

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal load current a.c. IL
Nominal discharge current (8/20 s) In
Total discharge current (8/20 s) [L+N-PE] Itotal
Combined impulse UOC
Combined impulse [L+N-PE] UOC total
Voltage protection level [L-N] UP
Voltage protection level [L/N-PE] UP
Response time [L-N] tA
Response time [L/N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for
mains-side overcurrent protection with 16 A gL/gG
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [L/N-PE] UT
Temporary overvoltage (TOV) [L+N-PE] UT
Fault indication
Operating state indication
Operating temperature range TU
For mounting on
Enclosure material
Degree of protection
Dimension
Mains filter
Attenuation for f = 1 MHz, balanced
Attenuation for f = 1 MHz, unbalanced
Ordering information
Type
Part No.
Packing unit

140

DPRO 230 F

DPRO 230 SE F

Type 3
Class III
230 V
255 V
10 A
3 kA
5 kA
6 kV
10 kV
) 1.25 kV
) 1.5 kV
) 25 ns
) 100 ns
16 A gL/gG or B 16 A

Type 3
Class III
230 V
255 V
10 A
3 kA
5 kA
6 kV
10 kV
) 1.25 kV
) 1.5 kV
) 25 ns
) 100 ns
16 A gL/gG or B 16 A

6 kArms
335 V / 5 sec.

6 kArms
335 V / 5 sec.

400 V / 5 sec.
1200 V + U0 / 200 ms
red light
green light
-25C...+40C
plug-in system with earth contact
according to DIN 49440 / DIN 49441
thermoplastic, pure white, UL 94 V-2
IP 20
128 x 71 x 40 mm
acc. to DIN VDE 0565 Part 3
* 40 dB
* 30 dB

400 V / 5 sec.
1200 V + U0 / 200 ms
red light
green light
-25C...+40C
centre earthing contact system
according to CEE 7, standard sheet V
thermoplastic, pure white, UL 94 V-2
IP 20
128 x 71 x 40 mm
acc. to DIN VDE 0565 Part 3
* 40 dB
* 30 dB

DPRO 230 F
909 240
1 pc(s).

DPRO 230 SE F
909 245
1 pc(s).

www.dehn.de

DPRO 230

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SFL Protector
SURGE ARRESTERS TYPE 3 Surge protective multiple socket outlet with filter
SPD Type 3 according to EN 61643-11
SPD Class III according to IEC 61643-1

Surge protection with monitoring device and


disconnector
Interference suppressor filter
Enhanced safety due to distinctive Y protection
circuit
Mains switch with operating state indication
Visual fault indicator (red)

Multiple socket outlet for protecting the power supply circuit of electronic devices against transient surges as well as high-frequency interference
voltages. For installation in conformity with the lightning protection zones
concept at the boundaries from 1 2 and higher.

SFL Protector:

Surge protective multiple socket outlet with interference suppressor filter

quency interferences. With a nominal current carrying capability of 16 A,


the SFL Protector can be used flexibly in final electrical circuits. The distinctive Y protection circuit ensures protection even if the phase and neutral conductors in standard earthed socket outlets cannot be identified.
The standard green and red LEDs inform the user at a glance about the
present operating state of the surge protective device.
Surge Arresters Type 3

The SFL Protector compelements the wide range of Red/Line surge protective devices. The combination of surge protection and mains filter makes
the 5-fold socket outlet a powerful device for protecting electronic consumers in final electrical circuits. The coordinated functions of surge protection and filter complement one another and prevent a core saturation
of the filter in case of high-energy transients. The integrated mains filter
was optimised for protection against balanced and unbalanced high-fre-

www.dehn.de

141

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

SFL Protector
SFL PRO

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3

912 260

SFL PRO

SFL PRO
Protector

SFL912 260

L/N

PE

approx.

N/L

Basic circuit diagram SFL PRO

Dimension drawing SFL PRO

Surge Arresters Type 3

SFL PRO: Surge protective multiple socket outlet with mains filter

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal load current a.c. IL
Nominal discharge current (8/20 s) In
Total discharge current (8/20 s) [L+N-PE] Itotal
Combined impulse UOC
Combined impulse [L+N-PE] UOC total
Voltage protection level UP
Response time [L-N] tA
Response time [L/N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for
mains-side overcurrent protection with 16 A gL/gG
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [L/N-PE] UT
Temporary overvoltage (TOV) [L+N-PE] UT
Fault indication
Operating state indication
Operating temperature range TU
Connecting cable
Number of socket outlets
For mounting on
Enclosure material
Degree of protection
Dimension
Mains filter
Attenuation for f = 1 MHz, balanced
Attenuation for f = 1 MHz, unbalanced
Ordering information
Type
Part No.
Packing unit

142

SFL PRO

SFL PRO SE

Type 3
Class III
230 V
255 V
16 A
3 kA
5 kA
6 kV
10 kV
) 1.5 kV
) 25 ns
) 100 ns
16 A gL/gG or B 16 A

Type 3
Class III
230 V
255 V
16 A
3 kA
5 kA
6 kV
10 kV
) 1.5 kV
) 25 ns
) 100 ns
16 A gL/gG or B 16 A

1.5 kArms
335 V / 5 sec.
400 V / 5 sec.
1200 V + U0 / 200 ms
red light
green light
-25C...+40C
length: 200 cm
5
plug-in system with earth contact
according to DIN 49440 / DIN 49441
black/anthracite thermoplastic, UL 94 V-2
IP 20
513 x 55 x 47 mm
according to DIN VDE 0565 Part 3
* 54 dB
* 42 dB

1.5 kArms
335 V / 5 sec.
400 V / 5 sec.
1200 V + U0 / 200 ms
red light
green light
-25C...+40C
length: 200 cm
5
centre earthing contact system
according to CEE 7, standard sheet V
black/anthracite thermoplastic, UL 94 V-2
IP 20
513 x 55 x 47 mm
according to DIN VDE 0565 Part 3
* 54 dB
* 42 dB

SFL PRO
912 260
1 pc(s).

SFL PRO
912 261
1 pc(s).

www.dehn.de

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

VC 280 2
Compact protection for terminal equipment

SPD Type 3 according to EN 61643-11


SPD Class III according to IEC 61643-1

Two-pole surge arrester with monitoring device


and disconnector
Complete surge protective circuit for devices
with a.c. voltage power supply
Enhanced safety due to distinctive Y protection
circuit
Floating remote signalling contact (break contact) with test option for fault indication
For installation onto printed circuit boards

For protecting electronic equipment against surges. For installation into


the enclosure or directly into the device to be protected. For installation
in conformity with the lightning protection zones concept at the boundaries from 1 2 and higher. German utility patent.

Surge protective mains module for installation into the terminal device to be protected

Surge arresters of type VC 280 2 are small-sized, but still feature all
required characteristics. The two-pole module includes a distinctive Y protection circuit, monitoring device and disconnector as well as a floating
remote signalling contact ensuring maximum compact safety. The SPDs

www.dehn.de

even feature an integrated test option for testing the fault indicator.
VC 280 2 reliably protects electronic equipment against surges. The solder
pins allow the SPD to be installed directly onto the PCBs of the device to
be protected.

143

Surge Arresters Type 3

VC 280 2:

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

VC 280 2
VC 280 2

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


SURGE ARRESTERS TYPE 3
L/N

900 471

L/N
VC 280 2
Surge Protection Module, 2-pole

11
12

Basic circuit diagram VC 280 2

Dimension drawing VC 280 2

VC 280 2: Surge protective mains module for installation into terminal devices to be protected

Surge Arresters Type 3

VC 280 2
SPD according to EN 61643-11
SPD according to IEC 61643-1
Nominal a.c. voltage UN
Max. continuous operating a.c. voltage UC
Nominal discharge current (8/20 s) In
Total discharge current (8/20 s) [L+N-PE] Itotal
Combined impulse UOC
Combined impulse [L+N-PE] UOC total
Voltage protection level [L-N] UP
Voltage protection level [L/N-PE] UP
Response time [L-N] tA
Response time [L/N-PE] tA
Max. mains-side overcurrent protection
Short-circuit withstand capability for mains-side overcurrent protection with 16 A gL/gG
Temporary overvoltage (TOV) [L-N] UT
Temporary overvoltage (TOV) [L/N-PE] UT
Temporary overvoltage (TOV) [L+N-PE] UT
Fault indication
Operating temperature range UT
For mounting on
Enclosure material
Degree of protection
Dimension
Type of remote signalling contact
Switching capacity a.c.
Switching capacity d.c.
Ordering information
Type
Part No.
Packing unit

144

VC 280 2

Type 3
Class III
230 V
280 V
3 kA
5 kA
6 kV
10 kV
) 1.25 kV
) 1.5 kV
) 25 ns
) 100 ns
16 A gL/gG or B 16 A
6 kArms
335 V / 5 sec.
400 V / 5 sec.
1200 V + U0 / 200 ms
remote signalling contact
-25C...+40C
printed circuit board
thermoplastic, red, UL 94 V-2
IP 20
32 x 24 x 15 mm
break contact
250 V/0.5 A
250 V/0.1 A; 125 V/0.2 A; 75 V/0.5 A

VC 280 2
900 471
1 pc(s).

www.dehn.de

Mains
900 471

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

POWER SUPPLY SYSTEMS


ACCESSORIES

Surge Arresters
Type 3

Accessories

Wiring Accessories
DK 25 and STAK 2X16
DK 25 allows to change the wiring level
DK 25 supports lightning-impulse-current-conform installation of SPD combinations
STAK 2X16 allows to clamp cross sections that
are smaller than the defined minimum clamping cross section of the surge protective device
STAK 2X16 allows EMC-optimised series connection according to IEC 60364-5-53

952 699

EMC-optimised series connection of lightning current and surge arresters


according to IEC 60364-5-53 by means of STAK 2X16

DK 25

NEW

DK 25
952 699

Dimension drawing DK 25
900 589
2X16

DK 25

STAK 2X16

DK 25

STAK 2X16

500 V
100 A
100 A
100 kA
630 V
6 kV
-40C...+80C
min. 1.5 mm2 solid/flexible, max. 25 mm2 stranded/16 mm2 flexible
35 mm DIN rail according to EN 60715

thermoplastic, red, UL 94 V-0


IP 20
1 mod., DIN 43880

2x min. 1.5 mm2, max. 16 mm2

front (double terminal)

STAK

DK 25: Feed-through terminal for busbar wiring


STAK 2X16: Pin-shaped terminal

Nominal a.c./d.c. voltage UN


Nominal load current a.c. IL
Test current according to EN 60947-7-1
Lightning impulse current (10/350 s)
Rated insulation voltage Ui
Rated impulse withstand voltage Uimp
Operating temperature range TU
Cross-sectional area
For mounting on
Type of connection
Enclosure material
Degree of protection
Capacity
Ordering information
Type
Part No.
Packing unit

www.dehn.de

DK 25
952 699 NEW
1 pc(s).

Accessories

STAK 2X16
900 589

STAK 2X16
900 589
1 pc(s).

145

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Insulating Enclosure

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


ACCESSORIES

Enclosure for installing surge arresters tested


with lightning impulse currents

Application example: Modular DEHNventil M TNC in


IGA 10 V2 IP54 insulating enclosure

902 315

IGA 10 V2 IP54
NEW

IGA 10 V2 IP54
902 315

Accessories

Dimension drawing IGA 10 V2 IP54

IGA 10 V2 IP54: Insulating enclosure for the installation of max. 10 modules; with membrane
flange for 5 cables 7-30 mm EPDM and 3 mounted membrane openings M20
with lock nut; ideally suited for through-wiring
IGA 10 V2 IP54
Degree of protection
Tested with lightning currents
Type of cover
Colour of enclosure
Quantity of cable entries
Available installation space
Dimension (W x H x D)
Sealable
Ordering information
Type
Part No.
Packing unit

146

IP 54
3
Transparent cover
grey
1 x for cables 7...10 mm; 2x for cables 10...14 mm or 15...30 mm each; 3 x for cables 8...13 mm
10 mods., DIN 43880
200 x 300 x 132 mm
3

IGA 10 V2 IP54
902 315
1 pc(s).

www.dehn.de

IGA 10 V2 IP54

Combined
Arresters Type 1

902 471
IP54

IGA 12

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

POWER SUPPLY SYSTEMS


ACCESSORIES

Surge Arresters
Type 3

Accessories

Insulating Enclosure
IGA 12 IP54

IGA 12 IP54
902 471

Dimension drawing IGA 12 IP54

Integrated plug-in terminal technology


for PE and N conductors

IGA 12 IP54: Insulating enclosure for max. 12 modules, for non-exhausting SPDs
IGA 12 IP54
Degree of protection
Type of cover
Colour of enclosure
Cable entry
PE/N Quantity x Cross section
Available installation space
Dimension (W x H x D)
Ordering information
Type
Part No.
Packing unit
902 472
IP54

IP 54
transparent cover
grey, RAL 7035
integrated, elastic sealing membrane for entering cables
3 x 25 mm2, 12 x 4 mm2, Cu
12 mods., DIN 43880
295 x 333 x 129 mm

IGA 12 IP54
902 471
1 pc(s).

IGA 24

IGA 24 IP54

IGA 24 IP54
902 472

Integrated plug-in terminal technology


for PE and N conductors

Accessories

Dimension drawing IGA 24 IP54

IGA 24 IP54: Insulating enclosure for max. 2x 12 modules, for non-exhausting SPDs

IGA 24 IP54
Degree of protection
Type of cover
Colour of enclosure
Cable entry
PE/N Quantity x Cross section
Available installation space
Dimension (W x H x D)
Ordering information
Type
Part No.
Packing unit

www.dehn.de

IP 54
transparent cover
grey, RAL 7035
integrated, elastic sealing membrane for entering cables
6 x 25 mm2, 24 x 4 mm2, Cu
24 (2x 12) mods., DIN 43880
295 x 458 x 129 mm

IGA 24 IP54
902 472
1 pc(s).

147

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Insulating Enclosure
IGA 6 IP54

Surge Arresters
Type 3

Accessories

POWER SUPPLY SYSTEMS


ACCESSORIES

902 485
IP54

IGA 6 IP54
Enclosure 6 mods.

Dimension drawing IGA 6 IP54

IGA 6 IP54: Enclosure for non-exhausting SPDs for max. 6 modules


IGA 6 IP54
Degree of protection
Type of cover
Colour of enclosure
Quantity of cable entries
Available installation space
Dimension (W x H x D)
Sealable

IGA 6 IP54
902 485
1 pc(s).

Accessories

Ordering information
Type
Part No.
Packing unit

IP 54
transparent cover
grey
2 plug-in glands EST 21 for cables 9 ... 21 mm
6 mods., DIN 43880
165 x 255 x 115 mm
3

148

www.dehn.de

IGA 6

Insulating
902 485

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

Surge Arresters
Type 3

Accessories

Busbars / Modular Wiring System

POWER SUPPLY SYSTEMS


ACCESSORIES

Allows for compact connection of SPDs with one


another and to other DIN rail mounted devices

900 617

MVS 1 2

MVS 1 2
900 617

Single-phase unit
Number of contact studs
Max. installation width
Nominal cross section

3
2
2 mods.
16 mm2

Ordering information
Type
Part No.
Packing unit

MVS 1 2
900 617
1 pc(s).

MVS 1 3

900 615

MVS 1 3

MVS 1 3
900 615

900 610

MVS 1 4

MVS 1 4
single-phase, 4-pole

Busbar
900 610

Single-phase unit
Number of contact studs
Max. installation width
Nominal cross section

3
3
3 mods.
16 mm2

Ordering information
Type
Part No.
Packing unit

MVS 1 3
900 615
1 pc(s).

MVS 1 4
Single-phase unit
Number of contact studs
Max. installation width
Nominal cross section

3
4
4 mods.
16 mm2

Ordering information
Type
Part No.
Packing unit

MVS 1 4
900 610
1 pc(s).

MVS 1 6

900 815

Single-phase unit
Number of contact studs
Max. installation width
Nominal cross section

3
6
6 mods.
16 mm2

Ordering information
Type
Part No.
Packing unit

MVS 1 6
900 815
1 pc(s).

MVS 2-pole, single-phase

MVS 3-pole, single-phase

MVS 4-pole, single-phase

Accessories

MVS 1 2

MVS 6-pole, single-phase

MVS 1 6

MVS 1 6
900 815

www.dehn.de

149

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Busbars / Modular Wiring System


MVS 7-pole, single-phase

Accessories

POWER SUPPLY SYSTEMS


ACCESSORIES

Single-phase unit
Number of contact studs
Max. installation width
Nominal cross section

3
7
7 mods.
16 mm2

Ordering information
Type
Part No.
Packing unit

MVS 1 7
900 848
1 pc(s).

MVS 1 8
Single-phase unit
Number of contact studs
Max. installation width
Nominal cross section

3
8
8 mods.
16 mm2

Ordering information
Type
Part No.
Packing unit

MVS 1 8
900 611
1 pc(s).

MVS 57-pole, single-phase

MVS 1 57
Single-phase unit
Number of contact studs
Max. installation width
Nominal cross section

3
57
57 mods.
16 mm2

Ordering information
Type
Part No.

MVS 1 57
900 612

Packing unit

MVS 6-pole, three-phase

Accessories

Surge Arresters
Type 3

MVS 1 7

MVS 8-pole, single-phase

900 848

MVS 1 7

MVS 1 7
900 848

900 611

MVS 1 8

MVS 1 8
single-phase, 8-pole

Busbar
900 611

900 612

MVS 1 57

MVS 1 57
single-phase, 57-pole

Busbar
900 612

1 pc(s).

MVS 3 6
Three-phase unit
Number of contact studs
Max. installation width
Nominal cross section

3
6
6 mods.
16 mm2

Ordering information
Type
Part No.
Packing unit

MVS 3 6
900 595
1 pc(s).

MVS 6-pole, three-phase

900 595

MVS 3 6

MVS 3 6
phase, 6-pole

Busbar 3900 595

MVS 3 6 8
Three-phase unit
Number of contact studs
Max. installation width
Nominal cross section
Ordering information
Type
Part No.
Packing unit

150

Surge Arresters
Type 2

3
6
8 mods.
16 mm2

900 813
8

MVS 3 6 8
phase, 8-pole

MVS 3 6 8
900 813
1 pc(s).

www.dehn.de

MVS 3 6

Busbar 3900 813

Combined
Arresters Type 1

Lightning Current
Arresters Type 1

N-PE Lightning Current


Arresters Type 1

Surge Arresters
Type 2

POWER SUPPLY SYSTEMS


ACCESSORIES
900 814
11

MVS 4 8

MVS 4 8 11
phase, 11-pole

Busbar 4900 814

Ordering information
Type
Part No.
Packing unit

MVS 4 56

MVS 4 56
phase, 56-pole

Busbar 4900 614

Four-phase unit
Number of contact studs
Max. installation width
Nominal cross section

MVS 8-pole, four-phase

3
8
11 mods.
16 mm2

MVS 4 8 11
900 814
1 pc(s).

MVS 4 56
900 614

Accessories

Busbars / Modular Wiring System

MVS 4 8 11
Four-phase unit
Number of contact studs
Max. installation width
Nominal cross section

Surge Arresters
Type 3

MVS 56-pole, four-phase

3
56
56 mods.
16 mm2

Ordering information
MVS 4 56
900 614
1 pc(s).

EB DG 1000 1 3
900 411
1000 1 3

EB DG

EB DG 1000 1 3
900 411

Single-phase unit
Number of contact studs
Dimension
Terminal

3
3
34 x 112 x 3 mm
up to 25 mm2

Ordering information
Type
Part No.
Packing unit

EB DG 1000 1 3
900 411
1 pc(s).

EB 1 4 9
900 417
49

EB 1

EB 1 4 9
900 417

Single-phase unit
Number of contact studs
Dimension
Terminal
Ordering information
Type
Part No.
Packing unit

www.dehn.de

3
4
34 x 148 x 3 mm
up to 25 mm2

DG Earthing Clip, 3-pole,


single-phase

Earthing Clip, 4-pole,


single-phase
Accessories

Type
Part No.
Packing unit

EB 1 4 9
900 417
1 pc(s).

151

152

www.dehn.de

Surge protection for

INFORMATION
TECHNOLOGY SYSTEMS
SPDs for installations and equipment

www.dehn.de

153

Cross-reference
Discontinued Products
Part No.
Type

INFORMATION TECHNOLOGY SYSTEMS


Alternatives
Part No.
Type

Discontinued Products
Part No.
Type

Alternatives
Part No.
Type

Pluggable SPDs for DIN rail mounting


BLITZDUCTOR CT
BLITZDUCTOR XT

Pluggable SPDs for DIN rail mounting


BLITZDUCTOR CT
BLITZDUCTOR XT

919 506
919 310
919 320

BCT BAS
BCT MLC B 110
BCT MLC BE 5

919 522

BCT MOD ME 15

or

919 523

BCT MOD ME 24

919 321

BCT MLC BE 12

or

919 524

BCT MOD ME 30

919 322

BCT MLC BE 15

or

919 525

BCT MOD ME 48

919 323

BCT MLC BE 24

919 324

BCT MLC BE 30

919 325

BCT MLC BE 48

919 326
919 327
919 360
919 361
919 362
919 363
919 340

BCT MLC BE 60
BCT MLC BE 110
BCT MLC BE C 5
BCT MLC BE C 12
BCT MLC BE C 24
BCT MLC BE C 30
BCT MLC BD 5

919 526
919 527
919 560
919 561
919 562
919 563
919 540

BCT MOD ME 60
BCT MOD ME 110
BCT MOD ME C 5
BCT MOD ME C 12
BCT MOD ME C 24
BCT MOD ME C 30
BCT MOD MD 5

919 541

BCT MOD MD 12

919 542

BCT MOD MD 15

or

919 543

BCT MOD MD 24

919 341

BCT MLC BD 12

or

919 544

BCT MOD MD 30

919 342

BCT MLC BD 15

or

919 545

BCT MOD MD 48

919 343

BCT MLC BD 24

or

919 546
919 547

BCT MOD MD 60
BCT MOD MD 110

919 344

BCT MLC BD 30

919 345

BCT MLC BD 48

919 549
919 570

BCT MOD MD 250


BCT MOD MD HF 5

919 346
919 347

BCT MLC BD 60
BCT MLC BD 110

919 571

BCT MOD MD HFD 5

919 349
919 370

BCT MLC BD 250


BCT MLC BD HF 5

919 371

BCT MLC BD HFD 5

919 375
919 520

BCT MLC BD HFD 24


BCT MOD ME 5

919 575
919 552
919 589
919 502
919 504
919 505

BCT MOD MD HFD 24


BCT MOD MD TC N
BCT MOD MY 250
GDT 90
BCT MOD PTS
EKS BCT

920 222
920 322
920 224
920 324
920 224
920 324
920 225
920 325
920 326
920 327

920 362
920 364
920 364
920 240
920 340
920 242
920 342
920 242
920 342
920 244
920 344
920 244
920 344
920 245
920 345
920 346
920 247
920 347

920 270
920 370
920 271
920 371
920 375

920 389

920 309
920 308

919 508

EFK BCT

920 395

SAK BXT LR

919 521

BCT MOD ME 12

920 300
920 310
920 220
920 320
920 222
920 322
920 222
920 322
920 224
920 324
920 224
920 324
920 225
920 325
920 326
920 327

920 362
920 364
920 364
920 240
920 340
920 242
920 342
920 242
920 342
920 244
920 344
920 244
920 344
920 245
920 345
920 346
920 247
920 347

920 270
920 370
920 271
920 371
920 375
920 220
920 320
920 222
920 322

BXT BAS
BXT ML4 B 180
BXT ML2 BE S 5
BXT ML4 BE 5
BXT ML2 BE S 12
BXT ML4 BE 12
BXT ML2 BE S 12
BXT ML4 BE 12
BXT ML2 BE S 24
BXT ML4 BE 24
BXT ML2 BE S 24
BXT ML4 BE 24
BXT ML2 BE S 48
BXT ML4 BE 48
BXT ML4 BE 60
BXT ML4 BE 180
BXT ML4 BE C 12
BXT ML4 BE C 24
BXT ML4 BE C 24
BXT ML2 BD S 5
BXT ML4 BD 5
BXT ML2 BD S 12
BXT ML4 BD 12
BXT ML2 BD S 12
BXT ML4 BD 12
BXT ML2 BD S 24
BXT ML4 BD 24
BXT ML2 BD S 24
BXT ML4 BD 24
BXT ML2 BD S 48
BXT ML4 BD 48
BXT ML4 BD 60
BXT ML2 BD 180
BXT ML4 BD 180
BXT ML2 BE HFS 5
BXT ML4 BE HF 5
BXT ML2 BD HFS 5
BXT ML4 BD HF 5
BXT ML4 BD HF 24
BXT ML2 BE S 5
BXT ML4 BE 5
BXT ML2 BE S 12
BXT ML4 BE 12

or
or
or

or
or

or

or
or

or

BXT ML2 BE S 12
BXT ML4 BE 12
BXT ML2 BE S 24
BXT ML4 BE 24
BXT ML2 BE S 24
BXT ML4 BE 24
BXT ML2 BE S 48
BXT ML4 BE 48
BXT ML4 BE 60
BXT ML4 BE 180
BXT ML4 BE C 12
BXT ML4 BE C 24
BXT ML4 BE C 24
BXT ML2 BD S 5
BXT ML4 BD 5
BXT ML2 BD S 12
BXT ML4 BD 12
BXT ML2 BD S 12
BXT ML4 BD 12
BXT ML2 BD S 24
BXT ML4 BD 24
BXT ML2 BD S 24
BXT ML4 BD 24
BXT ML2 BD S 48
BXT ML4 BD 48
BXT ML4 BD 60
BXT ML2 BD 180
BXT ML4 BD 180
BXT ML2 BE HFS 5
BXT ML4 BE HF 5
BXT ML2 BD HFS 5
BXT ML4 BD HF 5
BXT ML4 BD HF 24

DGA F 1.6 5.6


DGA G N

SPDs for LSA technology


907 209
GDT 230 G3 FS
907 215
DPL 10 G3 110 FS

SPDs for terminal connection


924 271
DSM TC 1 SK
924 273
DSM TC DK SK

924 272

DSM TC 2 SK

Accessories for screwable SPDs


929 981
KV S M20 MS 13
929 985
KV M20 MS 8

SPDs for potentially explosive areas


919 507
BCT BAS EX
919 580
BCT MOD MD EX 24
919 581
BCT MOD MD EX 30
919 583
BCT MOD MD HFD EX 6

920 301
920 381
920 381
920 538

154

929 028

929 028

GDT 230 G3 FSD


DPL 10 G3 110 FSD
DPA M CAT6 RJ45S 48
DPA M CAT6 RJ45S 48
NET PRO TC 2
NET PRO TC 2 LSA
DLI TC 2 I

or

or
or
or
or
or
or

or

or
or

or

929 040
929 044

SPDs for RJ connection


929 027
DLI TC 1 I
929 029
DLI TC DK
929 080
DLI TC ECO

or

BXT M4 T
BXT M4 E

SPDs for coaxial connection


929 041
DGA G 1.6 5.6
929 058
DGA G N 3

SPDs for data cabinets 482.6 mm (19 inch)


929 067
NET PRO ISDN
929 100
929 068
NET PRO ISDN LSA
929 100
929 069
NET PRO TC 1
929 071
929 070
NET PRO TC 1 LSA
929 072

or

BXT ML4 MY 250

Accessories for compact SPDs for DIN rail mounting


919 885
KB 5 DCO RK

919 888
KB 8 DCO RK

907 217
907 216

or

BXT BAS EX
BXT ML4 BD EX 24
BXT ML4 BD EX 24
BXT ML2 BD HF EX 6

DLI TC 2 I

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS

CONTENTS

Easy choice according to Interface / Signal

156

Pluggable SPDs for DIN rail mounting

179

Compact SPDs for DIN rail mounting

209

SPDs for LSA technology

229
1

SPDs for data cabinets 482.6 mm (19 inch)

247

SPDs for RJ connection

253

SPDs for BT Jack connection

265

SPDs for coaxial connection

267

SPDs for D-Sub connection

281

SPDs for terminal connection

289

Screwable SPDs

297

SPDs for use in potentially explosive areas

301

Accessories for terminal block systems

325

Combined adapters

337

Measuring and test devices

359

155
www.dehn.de

Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS


Bus systems and measuring and control technology
Telecommunications, Telephony
Data networks
Antenna systems, Broadband systems,
Transmitting and receiving systems, Video systems

Page 156 165


Page 166 169
Page 170 171
Page 172 174

Bus systems and measuring and control technology


LifeCheck
Interface / Signal

For mounting on

Ex

Protected
Connection system
lines

SPD
class

TYPE

SPD

Part No.

Page

screw terminals

920 324 + 920 300

188

screw terminals

920 224 + 920 300

197

spring terminals

919 921

210

spring terminals

919 988

215

wires / terminals

929 921

293

screw terminals

920 344 + 920 300

189

screw terminals

920 244 + 920 300

196

spring terminals

919 941

211

screw terminals

918 407

220

wires / terminals

929 941

292

LSA

20

907 401
+ 907 498 + 907 442

232

3/4 conductor measuring

screw terminals

920 354 + 920 300

190

ADVANT

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

screw terminals

918 401

221

spring terminals

919 970

214

AS interface

vampire taps

925 013

293

Binary signals

screw terminals

920 320 327 + 920 300

188

screw terminals

920 220 225 + 920 300

197

spring terminals

919 920 923

210

spring terminals

919 987 990

215

907 401
+ 907 498 + 907 422

232

0-20 mA, 4-20 mA


(also with HART)
J

J
Joker
actiVsense

4-20 mA
(also with HART) acc.
to NAMUR recommendation NE 21 or acc. to
EN 61000-4-5, open-circuit
voltage 1 kV A-PG
J

J
Joker
actiVsense

156

Bitbus

LSA

20

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal


Bus systems and measuring and control technology
LifeCheck
Interface / Signal

For mounting on

BLN
(Building Level network)

CAN Bus
(data line only)
J

Ex

Protected
Connection system
lines

SPD
class

TYPE

SPD

Part No.

Page

screw terminals

920 342 + 920 300

189

screw terminals

920 242 + 920 300

196

screw terminals

920 345 + 920 300

189

screw terminals

920 245 + 920 300

198

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

907 401
+ 907 498 + 907 465

232

J
Joker
actiVsense

LSA

20

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

BNC

929 010

268

BNC

909 710 / 711

271

CP installations
Sensor circuit

screw terminals

918 421 / 405

226

Anode circuit

screw terminals

918 420 / 404

225

Data Highway Plus

screw terminals

920 342 + 920 300

189

screw terminals

920 242 + 920 300

196

spring terminals

919 940

214

d.c. power supply


+24/30 V d.c.

screw terminals

918 402

222

screw terminals

918 408

223

Delta Net Peer Bus

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

C Bus (Honeywell)
J

J
Joker
actiVsense

Control Net

J
Joker
actiVsense

Device Net
(data line only)
J

J
Joker
actiVsense

J
Joker
actiVsense

www.dehn.de

For further details please refer to page 174

157

Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS


Bus systems and measuring and control technology
LifeCheck
Interface / Signal

For mounting on

Dupline
J

Ex

Protected
Connection system
lines

SPD
class

TYPE

SPD

Part No.

Page

screw terminals

920 243 + 920 300

198

screw terminals

920 345 + 920 300

189

screw terminals

920 245 + 920 300

197

screw terminals

920 310 + 920 300

187

screw terminals

920 211 + 920 300

195

wires

925 001

293

LSA

20

907 401

232

screw terminals

920 327 + 920 300

188

spring terminals

919 923

210

907 401
+ 907 498 + 907 445

232

J
Joker
actiVsense

E-Bus (Honeywell)
J

J
Joker
actiVsense

EIB

Electroacoustic
system (ELA)

LSA

20

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

200

spring terminals

919 970

214

Ex(d) circuits
4-20 mA, NAMUR,
HART, PROFIBUS-PA, FF

wires

929 962 / 964

308

Ex (i) circuits

screw terminals

920 381 + 920 301

314

screw terminals

920 538 + 920 301

316

spring terminals

919 960

323

wires / terminals

929 960

303

wires

929 961 / 963

306

screw terminals

989 408

321

screw terminals

920 344 + 920 300

189

screw terminals

920 244 + 920 300

197

spring terminals

919 941

211

wires / terminals

929 941

298

907 401
+ 907 498 + 907 442

232

ET 200

Fieldbus Foundation

J
Joker
actiVsense

LSA

158

20

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal


Bus systems and measuring and control technology
LifeCheck
Interface / Signal

For mounting on

Fieldbus Foundation
Ex (i)

FIPIO / FIPWAY

FIP I / O

FSK
J

Ex

Protected
Connection system
lines

TYPE

SPD

Part No.

Page

screw terminals

920 381 + 920 301

314

screw terminals

920 538 + 920 301

316

spring terminals

919 960

323

wires / terminals

929 960

303

wires

929 961 / 963

306

wires

929 971

309

screw terminals

989 408

321

screw terminals

920 344 + 920 300

189

screw terminals

920 244 + 920 300

196

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

screw terminals

920 371 + 920 300

193

screw terminals

920 271 + 920 300

199

spring terminals

919 970

214

screw terminals

920 342 + 920 300

189

screw terminals

920 242 + 920 300

196

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

LSA

20

907 401
+ 907 498 + 907 470

232

RJ45

929 100 / 110

254

RJ45

929 121

255

RJ45, LSA / RJ45

8x8

929 035 / 036

249

RJ45

8x8

929 037

249

RJ45

909 321

337

screw terminals

920 345 + 920 300

189

screw terminals

920 325 + 920 300

188

J
Joker

SPD
class

actiVsense

Genius I/O Bus

IEC Bus (RS 485)


J

J
Joker
actiVsense

Industrial Ethernet

INTERBUS INLINE (I/O)


J

J
Joker
actiVsense

J
Joker
actiVsense

www.dehn.de

For further details please refer to page 174

159

Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS


Bus systems and measuring and control technology
LifeCheck
Interface / Signal

For mounting on

Ex

Protected
Connection system
lines

SPD
class

TYPE

SPD

Part No.

Page

919 988

215

INTERBUS Loop

spring terminals

Interbus INLINE
Long-distance bus

screw terminals

920 371 + 920 300

193

screw terminals

920 271 + 920 300

2199

screw terminals

918 401

221

screw terminals

920 344 + 920 300

189

screw terminals

920 244 + 920 300

196

spring terminals

919 941

211

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

screw terminals

920 310 + 920 300

187

screw terminals

920 211 + 920 300

200

wires

925 001

291

LSA

20

907 401

232

screw terminals

920 340 + 920 300

189

screw terminals

920 240 + 920 300

196

TP/FTT10
(up to 1 A)
and TP/LPT10
(up to 1 A)

screw terminals

920 345 + 920 300

189

screw terminals

920 245 + 920 300

196

(up to 1.7 A)

spring terminals

919 942

212

907 401
+ 907 498 + 907 443

232

J
Joker
actiVsense

K Bus

KBR Energy bus

KNX Bus

LON
TP/XF 78

(up to 0.4 A)
TP/FTT 10

LUXMATE Bus
J

LSA

20

screw terminals

920 371 + 920 300

193

screw terminals

920 271 + 920 300

199

screw terminals

920 344 + 920 300

189

screw terminals

920 244 + 920 300

196

screw terminals

920 345 + 920 300

189

screw terminals

920 245 + 920 300

196

spring terminals

919 942

212

907 401
+ 907 498 + 907 443

232

Joker
actiVsense

M Bus
J

J
Joker
actiVsense

LSA

160

20

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal


Bus systems and measuring and control technology
LifeCheck
Interface / Signal

For mounting on

Melsec Net 2

MODBUS
J

J
Joker
actiVsense

Ex

Protected
Connection system
lines

SPD
class

TYPE

SPD

Part No.

Page

BNC

929 010

268

BNC

909 710 / 711

271

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

907 401
+ 907 498 + 907 465

232

LSA

20

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

screw terminals

920 371 + 920 300

193

screw terminals

920 271 + 920 300

199

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

BNC

909 710 / 711

271

N2 Bus (Johnson Controls,


LON, FTT 10)

screw terminals

920 371 + 920 300

193

screw terminals

920 271 + 920 300

199

Optocoupler
Interface

screw terminals

920 364 + 920 300

191

screw terminals

918 400

219

Procontic CS31 (RS 232)

screw terminals

920 322 + 920 300

188

Procontic T200 (RS 422)

screw terminals

920 371 + 920 300

193

screw terminals

918 401

221

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

D-Sub, 9-pole

924 017

282

spring terminals

919 970

214

907 401
+ 907 498 + 907 465

232

MPI Bus
J

J
Joker
actiVsense

N1 LAN

J
Joker
actiVsense

PROFIBUS DP/FMS

J
Joker
actiVsense

LSA

20

J
Joker
actiVsense

www.dehn.de

For further details please refer to page 174

161

Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS


Bus systems and measuring and control technology
LifeCheck
Interface / Signal

For mounting on

PROFIBUS PA

Ex

Protected
Connection system
lines

TYPE

SPD

Part No.

Page

screw terminals

920 344 + 920 300

189

screw terminals

920 244 + 920 300

196

spring terminals

919 941

211

wires / terminals

929 941

294

907 401
+ 907 498 + 907 442

232

J
Joker

SPD
class

actiVsense

PROFIBUS PA Ex (i)

PROFIBUS SIMATIC NET


J

LSA

20

screw terminals

920 381 + 920 301

314

screw terminals

920 538 + 920 301

316

spring terminals

919 960

323

wires / terminals

929 960

303

wires

929 961 / 963

306

wires

929 971

309

screw terminals

989 408

321

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

screw terminals

920 371 + 920 300

193

screw terminals

918 401

221

screw terminals

920 371 + 920 300

193

screw terminals

920 271 + 920 300

199

screw terminals

918 401

221

screw terminals

920 371 + 920 300

193

screw terminals

920 271 + 920 300

199

screw terminals

918 401

221

screw terminals

920 340 + 920 300

189

screw terminals

920 240 + 920 300

196

spring terminals

919 970

214

J
Joker
actiVsense

PSM EG RS 422
J

J
Joker
actiVsense

PSM EG RS 485
J

J
Joker
actiVsense

Rackbus (RS 485)


J

J
Joker
actiVsense

R Bus
Joker
actiVsense

162

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal


Bus systems and measuring and control technology
LifeCheck
Interface / Signal

RS 485

For mounting on

Ex

Protected
Connection system
lines

SPD
class

TYPE

SPD

Part No.

Page

screw terminals

920 370 + 920 300

192

screw terminals

920 538 + 920 301

316

screw terminals

920 270 + 920 300

198

screw terminals

918 401

221

spring terminals

919 970

214
232

J
Joker
actiVsense

LSA

20

907 401
+ 907 498 + 907 442

wires

929 971

309

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

screw terminals

918 401

221

spring terminals

919 970

214

D-Sub, 15-pole

924 051

287

D-Sub, 15-pole

924 016

284

LSA

20

907 401
+ 907 498 + 907 465

232

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

SafetyBUS p

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

RJ45, screw terminals

918 410

257

907 401
+ 907 498 + 907 470

232

RS 422, V11

J
Joker
actiVsense

S Bus

J
Joker
actiVsense

SDLS

SDLC

LSA

20

J
Joker
actiVsense

www.dehn.de

For further details please refer to page 174

163

Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS


Bus systems and measuring and control technology
LifeCheck
Interface / Signal

For mounting on

Ex

Protected
Connection system
lines

SPD
class

TYPE

SPD

Part No.

Page

Securilan LON Bus


(LONWORKS Technology
Standard Bus based on
Echelon)

screw terminals

920 340 + 920 300

189

screw terminals

920 240 + 920 300

196

spring terminals

919 970

214

SIGMASYS
(Siemens fire
alarm system)

screw terminals

920 345 + 920 300

189

screw terminals

920 245 + 920 300

196

screw terminals

920 325 + 920 300

188

screw terminals

920 225 + 920 300

197

907 401
+ 907 498 + 907 423

232

SINEC L1

SINEC L2

SS97 SIN/X (RS 232)

SUCONET
J

LSA

20

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

screw terminals

920 370 + 920 300

192

screw terminals

920 270 + 920 300

198

spring terminals

919 970

214

D-Sub, 9-pole

924 017

282

screw terminals

920 322 + 920 300

188

screw terminals

920 222 + 920 300

197

screw terminals

920 340 + 920 300

189

screw terminals

920 240 + 920 300

196

screw terminals

920 350 + 920 300

190

screw terminals

920 354 + 920 300

190

screw terminals

920 320 + 920 300

188

screw terminals

920 220 + 920 300

197

spring terminals

919 970

214

screw terminals

920 384 + 920 301

315

Joker
actiVsense

Temperature
measuring
PT 100, PT 1000
Ni 1000, NTC, PTC

Temperature
measuring Ex (i)
PT 100, PT 1000,
Ni 1000, NTC, PTC

164

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal


Bus systems and measuring and control technology
LifeCheck
Interface / Signal

TTL

TTY

TTY 4 20 mA

For mounting on

Ex

Protected
Connection system
lines

SPD
class

TYPE

SPD

Part No.

Page

screw terminals

920 322 + 920 300

188

screw terminals

920 222 + 920 300

197

spring terminals

919 920

210

D-Sub, 25-pole

4, 9

924 046

288

D-Sub, 9-pole

924 019

283

screw terminals

920 364 + 920 300

191

screw terminals

920 362 + 920 300

191

screw terminals

918 400

219

screw terminals

920 324 + 920 300

188

screw terminals

920 224 + 920 300

197

spring terminals

919 921

210

spring terminals

919 988

215

wires / terminals

929 921

295

J
Joker
actiVsense

www.dehn.de

For further details please refer to page 174

165

Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS


Telecommunications, Telephony
LifeCheck
Interface / Signal

For mounting on

Ex

Protected
Connection system
lines

SPDclass

TYPE

SPD

Part No.

Page

20

907 401
+ 907 498 + 907 430

232

RJ45, LSA / RJ45

8x2

929 071 / 072

250

screw terminals

920 347 + 920 300

189

RJ45, screw terminals

918 411

258

TAE, RJ12

909 310

339

spring terminals / RJ45

929 230

252

BT jack

929 026

266

screw terminals

920 347 + 920 300

189

screw terminals

920 247 + 920 300

196

LSA

20

907 401
+ 907 498 + 907 430

232

wires

924 272

291

TAE, RJ12

909 310

339

8x2

929 071 / 072

250

RJ45, screw terminals

918 411

258

spring terminals / RJ45

929 230

252

BT jack

929 026

266

LSA

20

907 401
+ 907 498 + 907 430

232

screw terminals

920 347 + 920 300

189

Datex P

screw terminals

920 375 + 920 300

193

E1

RJ45

929 100 / 110

254

20

907 401
+ 907 498 + 907 470

232

8x4

929 075

251

920 375 + 920 300

193

a/b wires

LSA

J
Joker
actiVsense

ADSL

J
Joker
actiVsense

RJ45, LSA / RJ45

ADSL 2+
J

J
Joker
actiVsense

LSA
LSA / RJ45

8x2

screw terminals

G.703 koax

1.6/5.6 connector

929 040

273

G.703 / G.704

insulation displacement
terminal

907 214

240

LSA / RJ45

8x4

929 075

251

RJ45

8x2

929 100 / 110

254

LSA

20

907 401
+ 907 498 + 907 470

232

screw terminals

920 375 + 920 300

193

166

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal


Telecommunications, Telephony
LifeCheck
Interface / Signal

For mounting on

HDSL
up to 30 dBm for 600 W

ISDN S0

Ex

Protected
Connection system
lines

SPDclass

TYPE
1

Part No.

Page

920 375 + 920 300

193

screw terminals

LSA

20

907 401
+ 907 498 + 907 470

232

RJ45

8x2

929 100 / 110

254

LSA / RJ45

8x4

929 075

251

920 375 + 920 300

193

929 024

262
232

screw terminals

RJ45

LSA

20

907 401
+ 907 498 + 907 470

wires

924 270

290

RJ45

909 320

340

RJ45

8x2

929 100 / 110

254

RJ45, screw terminals

918 410

257

RJ45, screw terminals

924 274

260

screw terminals

920 375 + 920 300

193

LSA

20

907 401
+ 907 498 + 907 470

232

RJ45

8x2

929 100 / 110

254

LSA / RJ45

8x4

929 075

251

J
Joker
actiVsense

SPD

ISDN S2m / U2m


J

J
Joker
actiVsense

ISDN UK0 / UP0

J
Joker
actiVsense

screw terminals

920 347 + 920 300

189

screw terminals

920 247 + 920 300

196

spring terminals

919 943

213

LSA

20

907 401
+ 907 498 + 907 430

232

8x2

929 071 / 072

250

TAE, RJ12

909 310

339

RJ45, screw terminals

918 411

258

929 230

252

RJ45, LSA / RJ45

spring terminals / RJ45 10 x 2


Modem M1

SDSL
J

screw terminals

920 322 + 920 300

188

screw terminals

920 222 + 920 300

199

RJ45

8x2

929 100 / 110

254

LSA

20

907 401
+ 907 498 + 907 470

232

screw terminals

920 375 + 920 300

193

929 075

251

J
Joker
actiVsense

LSA / RJ45

8x4

J
Joker
actiVsense

www.dehn.de

For further details please refer to page 174

167

Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS


Telecommunications, Telephony
LifeCheck
Interface / Signal

For mounting on

SHDSL

J
Joker
actiVsense

Ex

Protected
Connection system
lines

SPDclass

TYPE

SPD

Part No.

Page

screw terminals

920 371 + 920 300

193

screw terminals

920 375 + 920 300

193

RJ45

8x2

929 100 / 110

254

LSA

20

907 401
+ 907 498 + 907 470

232

screw terminals

920 310 + 920 300

187

screw terminals

920 211 + 920 300

195

929 075

251

920 247 + 920 300

196

LSA / RJ45
Telephony
System Telephony
e. g. Siemens, HICOM,
Alcatel

8x4
1

screw terminals

spring terminals

919 943

213

RJ45, RJ11

929 028

263

RJ12

929 081

264

LSA

20

907 401
+ 907 498 + 907 430

232

LSA

20

907 401
+ 907 498 + 907 445

232

wires

924 272

291

8x2

929 071 / 072

250

TAE, RJ12

909 310

339

RJ45, screw terminals

918 411

258

929 230

252

J
Joker
actiVsense

RJ45, LSA / RJ45

spring terminals / RJ45 10 x 2


T-DSL

screw terminals

920 347 + 920 300

189

screw terminals

920 247 + 920 300

196
232

LSA

20

907 401
+ 907 498 + 907 430

wires

924 272

291

TAE, RJ12

909 310

339

8x2

929 071 / 072

250

918 411

258

spring terminals / RJ45 10 x 2

929 230

252

LSA

20

907 401
+ 907 498 + 907 430

232

RJ45, LSA / RJ45

8x2

929 071 / 072

250

screw terminals

920 347 + 920 300

189

RJ45, screw terminals

918 411

258

TAE, RJ12

909 310

339

spring terminals / RJ45 10 x 2

929 230

252

BT jack

929 026

266

J
Joker
actiVsense

RJ45, LSA / RJ45


RJ45, screw terminals

Telecommunication
systems

Joker
actiVsense

168

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal


Telecommunications, Telephony
LifeCheck
Interface / Signal

For mounting on

Universal lightning
equipotential bonding

VDSL
J

Ex

Protected
Connection system
lines

SPDclass

TYPE

SPD

Part No.

Page

screw terminals

920 310 + 920 300

187

screw terminals

920 211 + 920 300

200

LSA

20

907 400

231

LSA
insulation displacement
terminal
insulation displacement
terminal

20

907 401

232

20

907 214

240

20

907 216

240

LSA

20

907 401

232

screw terminals

920 310 + 920 300

187

screw terminals

920 211 + 920 300

200

Joker
actiVsense

J
Joker
actiVsense

www.dehn.de

For further details please refer to page 174

169

Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS


Data networks
LifeCheck
Interface / Signal

For mounting on

Arcnet

ATM

Ethernet 10/100/1000

10 Base T

FDDI, CDDI

Industrial Ethernet

Power over Ethernet


PoV

170

Protected
Connection system
lines

SPDclass

TYPE

SPD

Part No.

Page

BNC

929 010

268

BNC

909 710 / 711

271

RJ45

929 100 / 110

254

RJ45

929 121

255

RJ45, LSA / RJ45

8x8

929 035 / 036

249

RJ45

8x8

929 037

249

RJ45

909 321

337

RJ45

929 100 / 110

254

RJ45

929 121

255

RJ45, LSA / RJ45

8x8

929 035 / 036

249

RJ45

8x8

929 037

249

RJ45

909 321

337

RJ45, screw terminals

924 274

260

RJ45

909 320

336

LSA

20

907 401
+ 907 498 + 907 470

232

RJ45

929 100 / 110

254

RJ45

929 121

255

RJ45, LSA / RJ45

8x8

929 035 / 036

249

RJ45

8x8

929 037

249

RJ45

909 321

337

LSA

20

907 401
+ 907 498 + 907 470

232

RJ45

929 100 / 110

254

RJ45

929 121

255

RJ45, LSA / RJ45

8x8

929 035 / 036

249

RJ45

8x8

929 037

249

RJ45

909 321

337

RJ45

929 100 / 110

254

RJ45

929 121

255

RJ45

8x8

929 037

249

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal


Data networks
LifeCheck
Interface / Signal

Token Ring

V 24 (RS 232 C)

VG AnyLAN

Voice over IP

For mounting on

Protected
Connection system
lines

SPDclass

TYPE

SPD

Part No.

Page

LSA

20

907 401
+ 907 498 + 907 470

232

RJ45

929 100 / 110

254

RJ45

929 121

255

RJ45, LSA / RJ45

8x8

929 035 / 036

249

RJ45

8x8

929 037

249

RJ45

909 321

337

screw terminals

920 322 + 920 300

188

spring terminals

919 921

210
232

LSA

20

907 401
+ 907 498 + 907 421

D-Sub 9-, 25-pole

4, 9

924 046 / 061

288

D-Sub 9-, 25-pole

924 018 / 019

283

RJ45

929 100 / 110

254

RJ45

929 121

255

RJ45, LSA / RJ45

8x8

929 035 / 036

249

RJ45

8x8

929 037

249

RJ45

909 321

337

RJ45

929 100 / 110

254

RJ45

8x8

929 037

249

RJ45

909 321

337

J
Joker
actiVsense

www.dehn.de

For further details please refer to page 174

171

Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS


Antenna systems, Broadband systems, Transmitting and receiving systems, Video systems

Interface / Signal

For mounting on

AMPS, NADAC
(824 894 MHz)

BWA (Broadband
Wireless Access)

CATV

DCS 1800 B162


(1710 1880 MHz)

DCF 77

GPS (1565 1585 MHz)

GSM 900, GSMR


(876 960 MHz)

172

Protected
Connection system
lines

Frequency
range

BNC

d.c. 4 GHz

BNC

N Connector

SPDclass

TYPE

SPD

Part No.

Page

929 042

274

d.c. 1 GHz

929 043

275

d.c. 5.8 GHz

929 044

274

N Connector

d.c. 2.5 GHz

929 045

275

7/16 Connector

d.c., 806 2200 MHz

929 046

276

7/16 Connector

d.c., 806 2200 MHz

929 446

276

7/16 Connector

880 2200 MHz

929 048

277

BNC

d.c. 4 GHz

929 042

274

N Connector

d.c. 5.8 GHz

929 044

274

N Connector

2.0 6.0 GHz

929 059

278

F Connector

d.c., 5 2400 MHz

909 705

272

IEC / F Connector

d.c. 2400 MHz

909 300

334

BNC

d.c. 4 GHz

929 042

274

N Connector

d.c. 5.8 GHz

929 044

274

N Connector

d.c. 2.5 GHz

929 045

275

7/16 Connector

d.c., 806 2200 MHz

929 046

276

7/16 Connector

d.c., 806 2200 MHz

929 446

276

7/16 Connector

880 2200 MHz

929 048

277

BNC

d.c. 4 GHz

929 042

274

BNC

d.c. 1 GHz

929 043

275

BNC

d.c. 4 GHz

929 042

274

N Connector

d.c. 5.8 GHz

929 044

274

N Connector

d.c. 2.5 GHz

929 045

275

7/16 Connector

d.c., 806 2300 MHz

929 046

276

7/16 Connector

d.c., 806 2200 MHz

929 446

276

7/16 Connector

880 2200 MHz

929 048

277

BNC

d.c. 4 GHz

929 042

274

BNC

d.c. 1 GHz

929 043

275

N Connector

d.c. 5.8 GHz

929 044

274

N Connector

d.c. 2.5 GHz

929 045

275

7/16 Connector

d.c., 806 2200 MHz

929 046

276

7/16 Connector

d.c., 806 2200 MHz

929 446

276

7/16 Connector

880 2200 MHz

929 048

277

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS Easy Choice according to Interface / Signal


Antenna systems, Broadband systems, Transmitting and receiving systems, Video systems

Interface / Signal

Frequency
range

BNC

d.c. 4 GHz

N Connector

N Connector

SPDclass

TYPE

Part No.

Page

929 042

274

d.c. 5.8 GHz

929 044

274

d.c. 2.5 GHz

929 045

275

7/16 Connector

d.c., 806 2200 MHz

929 046

276

7/16 Connector

d.c., 806 2200 MHz

929 446

276

7/16 Connector

880 2200 MHz

929 048

277

BNC

d.c. 4 GHz

929 042

274

BNC

d.c. 1 GHz

929 043

275

N Connector

d.c. 5.8 GHz

929 044

274

N Connector

d.c. 2.5 GHz

929 045

275

7/16 Connector

d.c., 806 2200 MHz

929 046

276

7/16 Connector

d.c., 806 2200 MHz

929 446

276

U Connector

d.c. - 300 MHz

929 057

235

7/16 Connector

380 512 MHz

929 047

277

7/16 Connector

880 2200 MHz

929 048

277

N Connector

2,0 6,0 GHz

929 059

278

SAT

F Connector

d.c., 5 2400 MHz

909 705

272

Sky DSL

F Connector

d.c., 5 2400 MHz

909 705

272

TETRA, NMT 450


(380 512 MHz)

BNC

d.c. 4 GHz

929 042

274

BNC

d.c. 1 GHz

929 043

275

N Connector

d.c. 5.8 GHz

929 044

274

N Connector

d.c. 2.5 GHz

929 045

275

7/16 Connector

380 512 MHz

929 047

277

F Connector

d.c., 5 3000 MHz

909 703

272

F Connector

d.c. 2400 MHz

909 704

272

F Connector

d.c., 5 2400 MHz

909 705

272

IEC / F Connector

d.c. 2400 MHz

909 300

334

PCS 1900
(1850 1990 MHz)

Radio systems

TV

For mounting on

Protected
Connection system
lines

SPD

J
Joker
actiVsense

www.dehn.de

For further details please refer to page 174

173

Easy Choice according to Interface / Signal INFORMATION TECHNOLOGY SYSTEMS


Antenna systems, Broadband systems, Transmitting and receiving systems, Video systems

Interface / Signal

For mounting on

Protected
Connection system
lines

Frequency
range

BNC

d.c. 4 GHz

N Connector

N Connector

SPDclass

TYPE

Part No.

Page

929 042

274

d.c. 5.8 GHz

929 044

274

d.c. 2.5 GHz

929 045

275

7/16 Connector

d.c., 806 2200 MHz

929 046

276

7/16 Connector

d.c., 806 2200 MHz

929 446

276

7/16 Connector

880 2200 MHz

929 048

277

WiMax

N Connector

2.0 6.0 GHz

929 059

278

WLAN (2.4 GHz band)

BNC

d.c. 4 GHz

929 042

274

N Connector

d.c. 5.8 GHz

929 044

274

N Connector

d.c. 5.8 GHz

929 044

274

N Connector

2.0 6.0 GHz

929 059

278

screw terminals

d.c. 100 MHz

920 370 + 920 300

192

RJ45

d.c. 250 MHz

929 100 / 110

254

RJ45

d.c. 250 MHz

929 121

255

screw terminals

d.c. 100 MHz

920 270 + 920 300

198

RJ45

909 321

337

BNC

d.c. 300 MHz

929 010

268

BNC

0 300 MHz

909 710 / 711

271

UMTS

WLAN (5 GHz band)

Video (2-wire)

Video (coax)

SPD

BLITZDUCTOR XTU
Universal lightning current / surge arrester with actiVsense technology
Automatically detects the operating voltage
Optimally adjusts the voltage protection level to the voltage currently applied

Joker
actiVsense

Application:
Suitable fo the vast majority of applications in information technology systems
Ideally suited for telecommunications systems, bus systems and measuring and control equipment
 The nominal current of the SPD is limited to 100 mA, allowing the device to be used for the vast majority of applications

in information technology systems. In some applications where the signal line is also used for power supply the current
may exceed 100 mA.
 All signals are transmitted with signal frequencies up to 25 MHz.
 In bus systems the SPD can be used for applications based on RS 485 / RS 422 interfaces (not RS 232).

For more detailed information, please refer to page 179.

174

www.dehn.de

SPDs for Information Technology Systems

Cate- Type of
gory test

Impulse
voltage

C1

0.5 kV or
0.25 kA or
1 kV, 1.2/50 s 0.5 kA, 8/20 s

300

2 kV, 4 kV,
or 10 kV,
1.2/50 s

1 kA, 2 kA
or 5 kA,
8/20 s

10

v 1 kV,
1 kV/s

10 A, 25 A
or 100 A,
10/1000 s

300

v 1 kV

0.5 kA, 1 kA
or 2.5 kA,
10/350 s

C2

steep
rate of
rise

C3

D1

high
energy

Impulse
current

Minimum quantity of impulses

Test
for

Surge arrester

INFORMATION TECHNOLOGY SYSTEMS

*)

*) Lightning current arrester / Combined lightning current and surge arrester

Voltage and current impulses (preferred values) for determining the voltage limiting
characteristics (based on Table 3 of IEC 61643-21 / EN 61643-21)

General
The surge protection components of SPDs have no radioactive isotopes
and usually consist of at least one voltage-limiting or voltage-switching
device, and sometimes of overcurrent-limiting components as well. SPDs
consisting of several stages, must be designed without blind spot, i.e. it has
to be ensured that the different protective stages are fully coordinated
with each other. Otherwise, the protective stages will respond only partially and lead to faults within the surge protective device.

Selection of SPDs
When selecting SPDs, the following aspects must be especially taken into
consideration:
Protective effect [Yellow/Line SPD class (discharge capacity and protection level)]
System parameters (system voltage, nominal current and transmission
parameters)
Installation environment (design, connection conditions and certifications)
The selection guide according to interface/signal on pages 156 to 174 shall
facilitate the choice of the right SPD.

Relevant product standard for the SPDs:


IEC 61643-21 / EN 61643-21
Low voltage surge protective devices Part 21: Surge protective devices
connected to telecommunications and signalling networks Performance
requirements and testing methods.

Discharge capacity

Immunity of terminal devices to be protected


Within the scope of the test for electromagnetic compatibility (EMC), electrical and electronic equipment (devices) must have a predefined immunity against conducted pulse interferences (surges).
Requirements for the immunity and test set-up are specified in EN 610004-5.
Different electromagnetic environmental conditions make different demands on the immunity of the devices. The immunity of a device is linked
to the test level applied. For classifying the different immunities of terminal devices, the test levels are subdivided into four different stages. Test
level 1 includes the minimum requirements for the immunity of the terminal device. Generally, the test level can be taken from the documentation
on the device or requested from its manufacturer.
Test levels
according to EN 61000-4-5

Corresponds to charging voltage


of the test generator

1
2
3
4

0.5 kV
1 kV
2 kV
4 kV

Protective effect of SPDs


Yellow/Line SPDs for use in IT systems can limit conducted interferences to
safe values to ensure that the immunity of the terminal device is not
exceeded. For protecting a terminal device tested for test level 2, a surge
arrester with a let-through value below the EMC test values of the terminal device has to be chosen:
Impulse voltage < 1 kV in combination with a pulse current of some
amperes (depending on the coupling network).

According to IEC 61643-21 / EN 61643-21, SPDs must be tested with at


least one impulse voltage or impulse current as mentioned in the
following table, with the indicated number of impulses. Further tests can
be performed even with different pulse amplitudes or quantities. The
maximum protection level during this or these tests is indicated
as voltage protection level UP measured at the output of the device.
Category C represents especially disturbing pulses with a steep rate of rise
and less energy, compared to the disturbing pulses of category D, which is
supposed to simulate high energy loads due to induced partial lightning
currents. The category is also indicated in the technical data of the SPDs
both in the description of the discharge capacity (In, Iimp) and protection
level (UP).

www.dehn.de

175

Yellow/Line SPD Classes Symbols

INFORMATION TECHNOLOGY SYSTEMS

All SPD types of the Yellow/Line family for IT systems are assigned a Yellow/Line SPD class and marked correspondingly with a symbol in the technical
data sheet and on their rating plates. The symbol for the Yellow/Line SPD class graphically connects 3 important characteristics of the SPD and can be
one single symbol or a combination of individual symbols:
Characteristics

Single symbol

Discharge capacity of an SPD


(according to categories from
IEC 61643-21 / EN 61643-21)

Definition

Impulse D1 (10/350 s), lightning impulse current v 2.5 kA/line or v 5 kA/total


exceeds the discharge capacity of B D

Impulse C2 (8/20 s), increased impulse load v 2.5 kA/line or v 5 kA/total


exceeds the discharge capacity of C D

Impulse C1 (8/20 s), impulse load v 0.25 kA/line or v 0.5 kA/total


exceeds the discharge capacity of D

Load < C

Protective effect of an SPD


(limitation below the test levels
according to EN 61000-4-5)

Required test level of the terminal device: 1 or higher


Required test level of the terminal device: 2 or higher
Required test level of the terminal device: 3 or higher
Required test level of the terminal device: 4

Energy coordination
(with a further Yellow/Line SPD)

SPD with decoupling impedance, suitable


for coordination with an SPD marked

SPD is suitable for coordination with an SPD


with decoupling impedance k

Examples for energy coordination of SPDs according to Yellow/Line SPD classes:


Use of a combined lightning current and surge arrester
immunity severity
acc. to EN 61000-4-5

lightning current

M
terminal
device
1

Cascaded use of SPDs


lightning current

immunity severity
acc. to EN 61000-4-5

surge

terminal
device
1

Energy coordination of Yellow/Line


is independent from the conductor length

O
G
discharge capacity

G
SPD suitable for coordination
with another SPD (
)

176

O
decoupling for coordination
with a further SPD (
)

specific protection of
terminal equipment
EN 61000-4-5

www.dehn.de

LifeCheck SPD Test

INFORMATION TECHNOLOGY SYSTEMS

SPD
diagnostics with early
warning function!
Higher protection and availability of installations and systems due to integrated LifeCheck
monitoring system
Integrated three-stage monitoring of all circuit
components
Quick diagnostics of surge protective devices
Easy testing of SPD modules without downtime via
contactless RFID technology
Even detects previously damaged SPDs

Regular testing of SPDs installed


During operation, an SPD can be overloaded by discharge processes
exceeding the equipment specification. In order to ensure high system
availability, it is therefore essential to test SPDs on a regular basis.
DIN EN 62305-3, supplement 3 (see table excerpt) specifies the maximum
intervals between tests of external and internal lightning protection systems.
Protection
level

Visual
inspection

Complete
inspection

Complete inspection
of critical systems

I and II

1 year

2 years

1 year

III and IV

2 years

4 years

1 year

Easy testing with LifeCheck


Maintenance of BLITZDUCTOR XT with integrated LifeCheck is particularly easy. LifeCheck uses modern RFID (Radio Frequency Identification) technology for monitoring the protective circuit and for communication.
Irrespective of downtimes of the system, LifeCheck allows for quick and
easy testing of SPDs by means of the hand-held DRC LC M3+ reader or a
stationary DRC MCM XT condition monitoring unit.

Signal before arrester failure


The 3-stage LifeCheck monitoring circuit with early warning function
detects the extreme electrical or thermal load of all protection elements
of an SPD below their destruction limit. This can be read out within seconds and without contact by means a RFID reader. If the reader displays
OK, no extreme load was detected. If the contrary is the case, the module has to be replaced as soon as possible in order not to threaten the
availability of the protected circuit.

protected

www.dehn.de

If LifeCheck monitors a protective


circuit of an SPD, this is shown
graphically in the basic circuit diagram. For BXT, the complete protective circuit is monitored.

Functional principal of the LifeCheck diagnostics systems


Transponder (SPD)

Reader (test device)

energy
SPD

indication
of operating
state

identification IC

Testing an SPD module via RFID technology (LifeCheck)

reader IC

microcontroller

power

communication

data

Principle of communication of an SPD a test device

The diagnostics system consists of two functional units:


1. RFID reading and signalling device (reader)
Combined with a visual and electrical display, an electronic system
transmits energy without contact to the RFID transponder in the SPD
via antenna. If the operating state can be read out, an OK message
is displayed.
2. Monitoring unit within the SPD:
Diagnostics of the 3-stage LifeCheck monitoring circuit is combined
with communication of the RFID transponder:
Diagnostics of electrical overload (impulse current)
Lightning strikes or overvoltage exceeding the specified discharge
capacity of the SPD will damage or even destroy the protection elements. This electrical overload is detected by the LifeCheck monitoring device. When reading out the transponder, the Replace SPD!
message appears.
Diagnostics of thermal overload (overheating)
Active and passive protection elements which are operated in the
critical temperature range will be pre-damaged or even destroyed
depending on the type and duration. This overload is detected by the
LifeCheck monitoring device. When reading out the transponder, the
Replace SPD! message appears.

177

INFORMATION TECHNOLOGY SYSTEMS

178

www.dehn.de

BLITZDUCTOR XTU
Universal lightning current /
surge arrester

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

With actiVsense technology


Automatically detects the operating voltage of
the wanted signal from 0 to 180 V
Optimally adjusts the voltage protection level to
the operating voltage currently applied
Low voltage protection level, also suited for the
protection of terminal equipment

Eases your processes

Reduction of the variety of types


Only one type of SPD for different signal lines
Easy planning and storage
Can be easily retrofitted

Example of use of BLITZDUCTOR XTU.

BLITZDUCTOR XTU combined lightning current and surge arresters for the
protection of information and automation systems stand out due to their
new, revolutionary technology: The nominal voltage is not specified thus
the arrester can be used for any voltage in the range from 0 to 180 V d.c.
Its innovative technology allows the arrester to automatically detect the
signal voltage of the wanted signal and to adjust its protection performance to this voltage. Moreover, it continuously adjusts its voltage protection level to the operating voltage currently applied and is thus ideally
suited for all applications where changing voltages occur.

Completely mounted BLITZDUCTOR XTU.


Two-part design with base part and SPD
module. Particularly space-saving, for DIN
rail mounting.

In case of interference, BLITZDUCTOR XTU arresters always have an


adjusted, minimal residual voltage for every signal voltage thus providing
maximum protection for the devices and systems connected to them.
BLITZDUCTOR XTU arresters also considerably reduce planning efforts
and minimise storage requirements. Even if it is not known at the planning stage which voltages are used for signal transmission, BLITZDUCTOR
XTU arresters now allow to specify a concrete protective device even at
the planning stage thus facilitating procurement and storage at the execution stage of the project.
BLITZDUCTOR XTU arresters are also ideally suited to be retrofitted into
existing systems or to replace existing arresters as it is frequently not
entirely clear which types of nominal voltage are to be used. This does not
matter if BLITZDUCTOR XTU arresters are used.

clic

The function-optimised design of the arrester allows both to safely plug


the arrester module into the base part and to remove it without problems.
The module is secured in the base part by snapping it in (audible click).
When pressing the grey buttons, the module can be removed with little
effort. This is ensured by the laminated contacts in the base part and the
release spring of the module. A mechanical reverse voltage protection
ensures that the module is installed in the correct position.

www.dehn.de

179

BLITZDUCTOR XTU
Universal lightning current /
surge arrester

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

Combined lightning current and surge arrester


Capable of carrying lightning currents up to 10 kA
(10/350 s)
Low voltage protection level, also suited for the
protection of terminal equipment
For use in conformity with the lightning protection zones concept at the boundaries from 0A 2
and higher

LifeCheck
RFID Symbol

SPD consists of a protection module and base


part
Easy replacement of protection modules
Make-before-break switch contact in the base
part allows removal and insertion without interruption

With integrated LifeCheck monitoring function


SPDs can be tested without downtime
Even detects previously damaged arresters

BLITZDUCTOR XTU arresters are pluggable, multipole and universal DIN


rail mounted lightning current and surge arresters for the protection of
measuring and control circuits, bus systems and telecommunication systems in which high levels of availability are essential. For effective protection of terminal equipment against lightning effects and surges, BLITZDUCTOR XTU arresters combine the permanently high impulse current
discharge capacity of a lightning current arrester with the low voltage
protection level of a surge arrester which is optimally adjusted to the
operating voltage currently applied.
LifeCheck allows easy and fast testing of SPDs without removing the
module from the system circuit. Integrated into the SPD modules,
LifeCheck permanently monitors the proper condition of the SPD and acts
like an early warning system, detecting imminent electrical or thermal
overload of the protection components. The LifeCheck status can be read
out within a matter of seconds via contactless RFID technology by means
of the portable DEHNrecord LC reader and shows the date of the last test
of the SPD module.
Stationary installed, a condition monitoring system allows conditionbased maintenance of 10 BXT arresters (for more detailed information,
please refer to page 359).
The module locking mechanism ensures safe operation, thus the arrester
provides protection against vibration effects and shock loads up to a 30fold acceleration of gravity. The function-optimised design of the arrester
ensures both fast and easy replacement of the arrester module which
houses all relevant protection elements.
A wide range of accessories makes the BLITZDUCTOR XTU arrester particularly user-friendly. Elements for labelling, earthing of unused lines or
easy testing of lines complete the product range.

180

Testing of an SPD module via RFID technology (LifeCheck)

2'4

'

1'3

'

24
13

Up to four lines can be connected on two levels. For DIN rail mounting
purposes, lines of a pair belonging to each other are connected on top of
one another.

LifeCheck module
BXTU ML2 ... S ...
2
4

2
4
4 3 2 1

1 2 3 4

1
3

Base part
BXT BAS

1
3

If the line shield cannot be directly earthed on both sides for technical reasons, one-sided indirect shield earthing might be advisable. This can be
performed by using arrester modules of type BXTU ML2 ... S. The terminal
3, 3 is connected to a gas discharge tube which is capable of carrying
lightning currents and prevents compensating currents. Transient impulse
currents on the shield are discharged via indirect shield earthing.

www.dehn.de

920 349

BXTU ML4 BD 0-180

BLITZDUCTOR XTU
BXTU ML4 BD 0-180

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

NEW

BXTU ML4 BD 0-180


920 349

U>UN

protected

U>UN

Dimension drawing BXTU ML4 BD 0-180

Basic circuit diagram BXTU ML4 BD 0-180

Universal voltage type with


actiVsense technology

Space-saving combined SPD module with actiVsense and LifeCheck technology for protecting
2 pairs with the same operating voltage or with a different operating voltage of balanced interfaces which are galvanically isolated. Automatically detects the operating voltage of the wanted
signal and optimally adjusts the voltage protection level to it.

For installation in compliance with


the lightning protection zones concept at the boundaries from 0A 2
and higher
With integrated LifeCheck monitoring
function

BXTU ML4 BD 0-180


SPD class
SPD monitoring system
Operating voltage UN
Frequency of the operating voltage fUN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Permissible superimposed signal voltage USignal
Cut-off frequency line-line (Usignal, balanced 100 ohms) fG
Nominal current at 80 C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for C2/C3/D1
Series impedance per line R
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection (SPD plugged-in)
Pluggable into
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications

LifeCheck
0 - 180 V
) 400 Hz
180 V
127 V
) +/- 5 V
25 MHz
100 mA
10 kA
2.5 kA
20 kA
10 kA
see diagram on page 183, line C2
see diagram on page 183, line C3
) UN + 53 V
) 550 V
) 10 ohms; typically 7.5 ohms
) 200 pF
) 16 pF
-40C...+80C
IP 20
BXT BAS base part
BXT BAS base part
polyamide PA 6.6
yellow
EN 61643-21
GOST

Ordering information
Type
Part No.
Packing unit

BXTU ML4 BD 0-180


920 349
1 pc(s).

Accessory Part for BLITZDUCTOR XTU


LifeCheck Module

DRC LC M3+

910 653
M3+

Portable device with LifeCheck sensor for


flexible use. For fast and easy testing of
LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

DRC LC M3+
Ableiterprfgert LifeCheck

Accessory Part for BLITZDUCTOR XTU


LifeCheck Module
DRC LC

910 653

DRC MCM XT

910 695
MCM XT

DIN rail mountable device with integrated


LifeCheck sensor for condition monitoring of
max. 10 BXT devices with LifeCheck function.
Type
DRC MCM XT

DRC MCM XT
Monitoring System LifeCheck

Accessory Part for BLITZDUCTOR XTU


LifeCheck Module
DRC

Condition
910 695

PU
Part
pc(s).
No.
1
910 695

BXT BAS

920 300

Base part for use as very space-saving,


four-pole, universal feed-through terminal for
insertion of SPD modules without signal interruption.
Type
BXT BAS

BXT BAS
Basisteil

BXT BAS

BXT920 300

PU
Part
pc(s).
No.
1
920 300

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 183/360/362.
www.dehn.de

181

BLITZDUCTOR XTU
BXTU ML2 BD S 0-180

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

NEW

U>UN

protected

Basic circuit diagram BXTU ML2 BD S 0-180

Universal voltage type with


actiVsense technology
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

BXTU ML2 BD S 0-180


920 249

920 249

Dimension drawing BXTU ML2 BD S 0-180

Space-saving combined SPD module with actiVsense and LifeCheck technology for protecting
1 pair. Direct or indirect shield earthing. Automatically detects the operating voltage of the wanted signal and optimally adjusts the voltage protection level to it.

With integrated LifeCheck monitoring


function
BXTU ML2 BD S 0-180

SPD class
SPD monitoring system
Operating voltage UN
Frequency of the operating voltage fUN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Permissible superimposed signal voltage USignal
Cut-off frequency line-line (Usignal, balanced 100 ohms) fG
Nominal current at 80 C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for C2/C3/D1
Series impedance per line R
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection (SPD plugged-in)
Pluggable into
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications

LifeCheck
0 - 180 V
) 400 Hz
180 V
127 V
) +/- 5 V
25 MHz
100 mA
9 kA
2.5 kA
20 kA
10 kA
see diagram page on 183, line C2
see diagram page on 183, line C3
) UN + 53 V
) 550 V
) 10 ohm(s); typically 7.5 ohm(s)
) 200 pF
) 25 pF
-40C...+80C
IP 20
BXT BAS base part
BXT BAS base part
polyamide PA 6.6
yellow
EN 61643-21
GOST

Ordering information
Type
Part No.
Packing unit

BXTU ML2 BD S 0-180


920 249
1 pc(s).

Accessory Part for BLITZDUCTOR XTU


LifeCheck Module
920 300

BXT BAS
Basisteil

BXT BAS

BXT920 300

BXT BAS

910 695
MCM XT

Base part for use as very space-saving,


four-pole, universal feed-through terminal for
insertion of SPD modules without signal interruption.
Type
BXT BAS

Accessory Part for BLITZDUCTOR XTU


LifeCheck Module

PU
Part
pc(s).
No.
1
920 300

DRC MCM XT
Monitoring System LifeCheck

DRC

Condition
910 695

DRC MCM XT

910 653
M3+

DIN rail mountable device with integrated


LifeCheck sensor for condition monitoring of
max. 10 BXT devices with LifeCheck function.
Type
DRC MCM XT

Accessory Part for BLITZDUCTOR XTU


LifeCheck Module

PU
Part
pc(s).
No.
1
910 695

DRC LC M3+
Ableiterprfgert LifeCheck

DRC LC

910 653

DRC LC M3+
Portable device with LifeCheck sensor for
flexible use. For fast and easy testing of
LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 183/360/362.

182

www.dehn.de

BXTU ML2 BD S 0-180

BLITZDUCTOR XTU
Diagrams

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING
250 V

Up

Operating voltage UN
C2
C3
UN

200 V

USignal
150 V

UN

100 V

t [time]

Operating voltage UN and superimposed signal voltage


USignal

Up line-line for In (8/20 s) C2


Up line-line for 1 kV/s C3

50 V

UN
0V

20 V

40 V

60 V

80 V

100 V

120 V

140 V

160 V

180 V

Operating voltage UN

Voltage protection level Up as a function of the operating voltage UN

920 300

BLITZDUCTOR XT Base Part


BXT BAS

BXT BAS

BXT BAS
920 300

2
4

BXT BAS

2
4
1234

1
3

protected

4 3 21

1
3

BXT ML4...
2
4

2
4
BXT BAS

1 2 3 4

1
3

1
3

Dimension drawing BXT BAS

protected

4 3 2 1

Basic circuit diagram with and without plug-in


module

The BLITZDUCTOR XT base part is a very space-saving, four-pole, universal feed-through terminal
for the insertion of SPD modules without signal interruption. The snap-in mechanism at the supporting foot of the base part allows the device to be safely earthed via the DIN rail. As no components of the protective circuit are situated in the base part, maintenance operation is only required
for the protection modules.

Four-pole version for universal use


with all types of SPD modules
Allows to plug in and remove the
modules without signal interruption
Universal design without protection
elements

BXT BAS
Operating temperature range
Degree of protection
For mounting on
Connection type input / output
Cross-sectional area, solid
Cross-sectional area, flexible
Tightening torque (terminals)
Earthing via
Enclosure material
Colour
Ex certifications *)
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.08 - 4 mm2
0.08 - 2.5 mm2
0.4 Nm
35 mm DIN rail acc. to EN 60715
polyamide PA 6.6
yellow
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
CSA, VdS, UL, GOST

BXT BAS
920 300
1 pc(s).

*) In combination with certified module


www.dehn.de

183

BLITZDUCTOR XT
Lightning current / surge arrester

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

Combined lightning current and surge arrester


Maximum discharge capacity for two-, three- or
four-pole interfaces
Lightning current carrying capacity up to 10 kA
(10/350 s)
Low voltage protection level, also suited for the
protection of terminal equipment

SPD consists of a protection module and base


part
Easy replacement of protection modules with
little effort
Base part incorporates make-before-break switch
contact for insertion and removal without interruption
All protection components integrated in the protection module

Example of use of BLITZDUCTOR XT with an earthing module (grey). The


lines can be measured by means of the measuring module (grey strings)
without disconnecting the clamps.

Functional and appealing design


DIN rail mounting with integrated earthing
Minimum space requirements, 2 pairs over
a width of 2/3 modules
Vibration- and shock-proof for safe operation
BLITZDUCTOR XT combined arresters are pluggable, multipole, universal
DIN rail mounted lightning current and surge arresters for the protection
of measuring and control circuits, bus systems and telecommunication
systems. They are particularly suited for installations and systems in which
high levels of availability are essential. For effective protection of terminal equipment against the effects of lightning and overvoltages, BLITZDUCTOR XT arresters combine the permanently high impulse current discharge capacity of a lightning current arrester with the low protection
level of a surge arrester.
LifeCheck allows quick and easy SPD testing without removing the module. Integrated into the SPD modules, LifeCheck permanently monitors the

Completely installed BLITZDUCTOR XT.


Two-part design with universal base part
and application-specific SPD module.
Especially space-saving design, for DIN
rail mounting.

Dimension drawing of BLITZDUCTOR XT


base part with plugged-in SPD module.
Width: 2/3 modules (12 mm), for DIN rail
mounting in distribution boards.

184

proper condition of the SPD and acts like an early warning system, detecting imminent electrical or thermal overload of the protection components.
The status of the SPD can be read out within a matter of seconds via contactless RFID technology by means of the portable DEHNrecord LC reader. The LifeCheck feature also saves the date of the last test of the SPD
module and indicates it. Stationary installed, the condition monitoring
system permanently monitors the condition of up to 10 BXT devices (for
more detailed information, please refer to page 359).
The module locking system ensures safe operation; thus the SPD provides
protection against vibration effects and shock up to a 30-fold acceleration
of gravity. The function-optimised design of the device ensures both quick
and easy replacement of SPD modules which house all relevant protection
elements.
A wide range of accessories makes BLITZDUCTOR XT arresters especially
user-friendly. Elements for easy labelling, earthing of unused lines or easy
testing of lines complete the product range.

Universal base part accommodates all


types of SPD modules thereby minimising
storage requirements and easing prewiring
and maintenance operations. The modules
can be easily removed from the base part
without signal interruption due to makebefore-break switch contacts.

BXT ML4 B ...:


LifeCheck-equipped SPD modules for 4 single lines or 2 pairs for high partial lightning
currents.
BXT ML2 B:
LifeCheck-equipped SPD modules for 2 single lines or 1 pair for high partial lightning
currents. Type BXT ML2 ... S additionally
provides contacts for direct or indirect
shield earthing.

www.dehn.de

BLITZDUCTOR XT
Lightning current / surge arrester

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

General Technical Data for BLITZDUCTOR XT LifeCheck Modules


Degree of protection (plugged-in)
Pluggable into
Earthing by
Enclosure material
Colour

IP 20
BLITZDUCTOR XT base part
BLITZDUCTOR XT base part
polyamide PA 6.6
yellow

clic

k
Maximum nominal current at ambient temperature

2'4

'

2.0
1.9

Nominal current IL in A

The function-optimised design of the device allows both to safely plug the
SPD module into the base part and to remove it without problems. The
module is secured in the base part by snapping it in (audible click). When
pressing the grey buttons, the module can be removed with little effort.
This is ensured by the laminated spring contacts and the module release
spring. A mechanical reverse voltage protection ensures that the module
is installed in the correct position.

1'3

'

24
13

1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0.0
40

20

20

40

60

80

Ambient temperature in C
Colour-coded characteristic curves:
BXT ML4 / ML2 ...

Up to 4 lines can be connected on 2 levels. For DIN rail mounting purposes, lines of a pair belonging to each other are connected on top of one
another.

BE
BD
BC
BE HF
BD HF

5 12 24 36 48 60 180
5 12 24
48 60 180
5
24
5
5
24

LifeCheck module
BXTU ML2 ... S ...
2
4

2
4

4 3 2 1

1 2 3 4

1
3

1
3

Base part
BXT BAS

If the line shield cannot be earthed on both sides for technical reasons,
one-sided indirect shield earthing might be advisable. This can be performed by using SPD modules of type BXT ML2 ... S. The terminal 3, 3 is
connected to a gas discharge tube which is capable of carrying lightning
currents and prevents compensating currents. Transient impulse currents
on the shield are discharged via indirect shield earthing.

protected

The protected lines always


have to be assigned to terminals 1 to 4 (protected) of the
base part. In order not to
reduce the protective effect,
protected and unprotected
lines have to be installed separately.

ok

Earthing Module
BXT M4 E
2
4

2
4
4 3 2 1

1 2 3 4

1
3

Base Part
BXT BAS

1
3

In case of a stranded cable, unused lines should be laid and earthed. If the
unused lines are connected to base parts, earthing modules of type BXT
M4 E should be used. These reserve space for retrofitting the SPD modules and the lines can be integrated efficiently into the equipotential
bonding.

www.dehn.de

The terminals integrated into the base


part can be used with many two-pole
modules for shield earthing. Especially for
bus systems, the EMC spring terminal
should be used for large-area connection
of line shields.

For further types of BLITZDUCTOR XT for intrinsically safe circuits" please refer to pages 311-316.

185

BLITZDUCTOR XT Base Part


BXT BAS

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING
2
4

BXT BAS

BXT BAS
920 300

2
4
1234

1
3

920 300

protected

4 3 21

1
3

BXT ML4...
2
4

2
4
BXT BAS

1 2 3 4

1
3

1
3

Four-pole version for universal use


with all types of SPD modules
Allows to plug in and remove the
modules without signal interruption
Universal design without protection
elements

protected

4 3 2 1

Basic circuit diagram with and without plug-in


module

Dimension drawing BXT BAS

The BLITZDUCTOR XT base part is a very space-saving, four-pole, universal feed-through terminal
for the insertion of SPD modules without signal interruption. The snap-in mechanism at the supporting foot of the base part allows the device to be safely earthed via the DIN rail. As no components of the protective circuit are situated in the base part, maintenance operation is only required
for the protection modules.

BXT BAS
Operating temperature range
Degree of protection
For mounting on
Connection type input / output
Cross-sectional area, solid
Cross-sectional area, flexible
Tightening torque (terminals)
Earthing via
Enclosure material
Colour
Ex certifications *)
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.08 - 4 mm2
0.08 - 2.5 mm2
0.4 Nm
35 mm DIN rail acc. to EN 60715
polyamide PA 6.6
yellow
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
CSA, VdS, UL, GOST

BXT BAS
920 300
1 pc(s).

*) in combination with certified module

Clear identification of the


protected side for
faultless installation

Module release spring


for removing the protection
module without problems

The earthing foot ensures costeffective installation. No additional


earth connection is required since the
device is safely earthed via the DIN rail

Lightning current carrying


laminated contacts

Reverse polarity protection prevents


incorrect insertion of the protection
module

Designation space
for marking the circuits

186

Leading/retarded make-before-break
switch contacts for uninterrupted
removal and insertion without downtime

High-quality, four-pole screw terminals


for the following cross-sections:
stranded: 2.5 mm2
solid:
4 mm2

www.dehn.de

BXT BAS

920 310
B 180

BXT ML4

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML4 B 180

BXT ML4 B 180


920 310

protected

Dimension drawing BXT ML4 B

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Space-saving four-pole lightning current arrester module with LifeCheck monitoring function for
almost all types of applications. For use in connection with downstream surge arresters Q
or combined lightning current and surge arresters with a lower or equal voltage level.

LifeCheck SPD monitoring function


Four-pole lightning equipotential
bonding
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 1 and higher

BXT ML4 B 180


SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 45C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Test standards
SIL classification
Ex certifications
Approvals, Certifications

H
LifeCheck
180 V
180 V
127 V
1.2 A
10 kA
2.5 kA
20 kA
10 kA
) 600 V
) 550 V
) 650 V
) 550 V
0.4 ohm(s)
) 16 pF
) 16 pF
-40C...+80C
IEC 61643-21, UL 497B
SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
CSA, VdS, GOST

Ordering information
Type
Part No.
Packing unit

BXT ML4 B 180


920 310
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

DRC LC M3+

910 653
M3+

Portable device with LifeCheck sensor for


flexible use. For fast and easy testing of
LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

DRC LC M3+
Ableiterprfgert LifeCheck

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
DRC LC

910 653

DRC MCM XT

910 695
MCM XT

DIN rail mountable device with integrated


LifeCheck sensor for condition monitoring of
max. 10 BXT devices with LifeCheck function.
Type
DRC MCM XT

PU
Part
pc(s).
No.
1
910 695

DRC MCM XT
Monitoring System LifeCheck

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
DRC

Condition
910 695

BXT BAS

920 300

Base part for use as very space-saving,


four-pole, universal feed-through terminal for
insertion of SPD modules without signal interruption.
Type
BXT BAS

BXT BAS
Basisteil

BXT BAS

BXT920 300

PU
Part
pc(s).
No.
1
920 300

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.
www.dehn.de

187

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML4 BE 5 BE 180
1

920 320
BE 5
920 322
BE 12
920 324
BE 24
920 336
BE 36
920 325
BE 48
920 326
BE 60
920 327
BE 180

BXT ML4 BE 5
920 320
BXT ML4 BE 12
920 322
BXT ML4 BE 24
920 324
BXT ML4 BE 36
920 336
BXT ML4 BE 48
920 325
BXT ML4 BE 60
920 326
BXT ML4 BE 180
920 327

protected

LifeCheck SPD monitoring function


Optimal protection of 4 single lines
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

BXT ML4 ...

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring function for protecting 4 single lines with common reference potential as well as unbalanced interfaces.
BE 5

SPD class
M
SPD monitoring system
LifeCheck
Nominal voltage UN
5V
Max. continuous operating d.c. voltage UC
6.0 V
Max. continuous operating a.c. voltage UC
4.2 V
Nominal current at 45C IL
1.0 A
D1 Total lightning impulse current (10/350 s) Iimp
10 kA
D1 Lightning impulse current (10/350 s) per line Iimp 2.5 kA
C2 Total nominal discharge current (8/20 s) In
20 kA
C2 Nominal discharge current (8/20 s) per line In
10 kA
Voltage protection level line-line for Iimp D1 Up
) 29 V
Voltage protection level line-PG for Iimp D1 Up
) 27 V
Voltage protection level line-line at 1 kV/s C3 Up
) 18 V
Voltage protection level line-PG at 1 kV/s C3 Up
)9V
Series impedance per line
1.0 ohm(s)
Cut-off frequency line-PG fG
1.0 MHz
Capacitance line-line C
) 2.7 nF
Capacitance line-PG C
) 5.4 nF
Operating temperature range
-40C...+80C
Test standards
IEC 61643-21,
UL 497B
SIL classification

BE 12

BE 24

BE 36

BE 48

BE 60

BE 180

LifeCheck
12 V
15 V
10.6 V
0.75 A
10 kA
2.5 kA
20 kA
10 kA
) 50 V
) 37 V
) 38 V
) 19 V
1.8 ohm(s)
2.7 MHz
) 1.0 nF
) 2.0 nF
-40C...+80C
IEC 61643-21,
UL 497B

LifeCheck
24 V
33 V
23.3 V
0.75 A
10 kA
2.5 kA
20 kA
10 kA
) 102 V
) 66 V
) 90 V
) 45 V
1.8 ohm(s)
6.8 MHz
) 0.5 nF
) 1.0 nF
-40C...+80C
IEC 61643-21,
UL 497B

LifeCheck
LifeCheck
36 V
48 V
45 V
54 V
31 V
38.1 V
1.8 A
0.75 A
10 kA
10 kA
2.5 kA
2.5 kA
20 kA
20 kA
10 kA
10 kA

) 160 V
) 85 V
) 95 V
) 112 V
) 140 V
) 56 V
) 70 V
0.43 ohm(s)
1.8 ohm(s)
3.8 MHz
8.7 MHz
) 0.8 nF
) 0.35 nF
) 1.6 nF
) 0.7 nF
-40C...+80C
-40C...+80C
IEC 61643-21
IEC 61643-21,

UL 497B
SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
CSA, VdS,
VdS,
CSA, VdS,
UL, GOST
GOST
UL, GOST

Ex certifications
Approvals, Certifications

Ordering information
Type
Part No.
Packing unit

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
920 300

BXT BAS
Basisteil

BXT BAS

BXT920 300

BXT BAS

Type
BXT BAS

CSA, VdS,
UL, GOST

CSA, VdS,
UL, GOST

BXT ML4 BE 5
920 320
1 pc(s).

BXT ML4 BE 12
920 322
1 pc(s).

PU
Part
pc(s).
No.
1
920 300

BXT ML4 BE 24
920 324
1 pc(s).

BXT ML4 BE 36
920 336
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
910 695
MCM XT

Base part for use as very space-saving,


four-pole, universal feed-through terminal for
insertion of SPD modules without signal interruption.

Dimension drawing BXT ML4 BE

DRC MCM XT
Monitoring System LifeCheck

DRC

Condition
910 695

DRC MCM XT

LifeCheck
180 V
180 V
127 V
1.0 A
10 kA
2.5 kA
20 kA
10 kA
) 520 V
) 300 V
) 500 V
) 250 V
1.0 ohm(s)
25.0 MHz
) 120 pF
) 240 pF
-40C...+80C
IEC 61643-21,
UL 497B

CSA, VdS,
UL, GOST

CSA, VdS,
UL, GOST

BXT ML4 BE 60 BXT ML4 BE 180


920 326
920 327
1 pc(s).
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
910 653
M3+

DIN rail mountable device with integrated


LifeCheck sensor for condition monitoring of
max. 10 BXT devices with LifeCheck function.
Type
DRC MCM XT

BXT ML4 BE 48
920 325
1 pc(s).

LifeCheck
60 V
70 V
49.5 V
1.0 A
10 kA
2.5 kA
20 kA
10 kA
) 220 V
) 125 V
) 180 V
) 90 V
1.0 ohm(s)
9.0 MHz
) 250 pF
) 500 pF
-40C...+80C
IEC 61643-21,
UL 497B

DRC LC M3+
Ableiterprfgert LifeCheck

PU
Part
pc(s).
No.
1
910 695

DRC LC

910 653

DRC LC M3+
Portable device with LifeCheck sensor for
flexible use. For fast and easy testing of LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.

188

www.dehn.de

BXT ML4
BXT ML4
BXT ML4
BXT ML4
BXT ML4
BXT ML4
BXT ML4

920 340
BD 5
920 342
BD 12
920 344
BD 24
920 345
BD 48
920 346
BD 60
920 347
BD 180

BXT ML4
BXT ML4
BXT ML4
BXT ML4
BXT ML4

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML4 BD 5 BD 180

BXT ML4

BXT ML4 BD 5
920 340
BXT ML4 BD 12
920 342
BXT ML4 BD 24
920 344
BXT ML4 BD 48
920 345
BXT ML4 BD 60
920 346
BXT ML4 BD 180
920 347

protected

Dimension drawing BXT ML4 BD

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting 2 pairs of balanced interfaces which are galvanically isolated.
BXT ML4 ...

BD 5

SPD class
M
SPD monitoring system
LifeCheck
Nominal voltage UN
5V
Max. continuous operating d.c. voltage UC
6.0 V
Max. continuous operating a.c. voltage UC
4.2 V
Nominal current at 45C IL
1.0 A
D1 Total lightning impulse current (10/350 s) Iimp
10 kA
D1 Lightning impulse current (10/350 s) per line Iimp
2.5 kA
C2 Total nominal discharge current (8/20 s) In
20 kA
C2 Nominal discharge current (8/20 s) per line In
10 kA
Voltage protection level line-line for Iimp D1 Up
) 25 V
Voltage protection level line-PG for Iimp D1 Up
) 550 V
Voltage protection level line-line at 1 kV/s C3 Up
)9V
Voltage protection level line-PG at 1 kV/s C3 Up
) 550 V
Series impedance per line
1.0 ohm(s)
Cut-off frequency line-line fG
1.0 MHz
Capacitance line-line C
) 5.4 nF
Capacitance line-PG C
) 16 pF
Operating temperature range
-40C...+80C
Test standards
IEC 61643-21,
UL 497B
SIL classification

Ordering information
Type
Part No.
Packing unit

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

Marking system BA1-BA15


2 x 165 adhesive labels for labelling DRC MCM
XT monitoring devices with their bus addresses.
Type
BS BA1 BA15 BXT

PU
Part
pc(s).
No.
1
920 398

BS BA1 BA15 BXT


Bezeichnungssystem fr BXT

BS BA1

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0A 2 and higher

BD 24

BD 48

BD 60

BD 180

LifeCheck
12 V
15 V
10.6 V
1.0 A
10 kA
2.5 kA
20 kA
10 kA
) 26 V
) 550 V
) 19 V
) 550 V
1.0 ohm(s)
2.8 MHz
) 2.0 nF
) 16 pF
-40C...+80C
IEC 61643-21,
UL 497B

CSA, VdS,
UL, GOST

CSA, VdS,
UL, GOST

BXT ML4 BD 5
920 340
1 pc(s).

BXT ML4 BD 12
920 342
1 pc(s).

LifeCheck
LifeCheck
LifeCheck
24 V
48 V
60 V
33 V
54 V
70 V
23.3 V
38.1 V
49.5 V
1.0 A
1.0 A
1.0 A
10 kA
10 kA
10 kA
2.5 kA
2.5 kA
2.5 kA
20 kA
20 kA
20 kA
10 kA
10 kA
10 kA
) 52 V
) 80 V
) 110 V
) 550 V
) 550 V
) 550 V
) 45 V
) 70 V
) 90 V
) 550 V
) 550 V
) 550 V
1.0 ohm(s)
1.0 ohm(s)
1.0 ohm(s)
7.8 MHz
8.7 MHz
11.0 MHz
) 1.0 nF
) 0.7 nF
) 500 pF
) 16 pF
) 16 pF
) 16 pF
-40C...+80C
-40C...+80C
-40C...+80C
IEC 61643-21,
IEC 61643-21,
IEC 61643-21,
UL 497B
UL 497B
UL 497B
SIL2 / SIL3
for more details see: www.dehn.de/en/sil
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
CSA, VdS,
CSA, VdS,
CSA, VdS,
UL, GOST
UL, GOST
UL, GOST

BXT ML4 BD 24
920 344
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

920 398
BA15 BXT

Optimal protection of 2 single pairs

BD 12

Ex certifications
Approvals, Certifications

LifeCheck SPD monitoring function

Earthing module

920 308

For direct earthing of lines connected to the


BLITZDUCTOR XT base part.

BXT M4 E
Erdungsmodul

BXT ML4 BD 48
920 345
1 pc(s).

BXT ML4 BD 60
920 346
1 pc(s).

LifeCheck
180 V
180 V
127 V
0.75 A
10 kA
2.5 kA
20 kA
10 kA
) 270 V
) 550 V
) 250 V
) 550 V
1.8 ohm(s)
25.0 MHz
) 240 pF
) 16 pF
-40C...+80C
IEC 61643-21,
UL 497B

CSA, VdS,
UL, GOST

BXT ML4 BD 180


920 347
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
BXT M4 E

BXT920 308

Test / Disconnection Module


Module for testing lines, to be plugged into
the BLITZDUCTOR XT base part.

920 309

BXT M4 T
/Trennmodul

BXT M4 T

BXT-Prf920 309

920 398

Type
BXT M4 E

PU
Part
pc(s).
No.
1
920 308

Type
BXT M4 T

PU
Part
pc(s).
No.
1
920 309

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.
www.dehn.de

189

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML4 BC 5 / 24
1

920 350
BC 5
920 354
BC 24

BXT ML4 BC 5
920 350
BXT ML4 BC 24
920 354

protected

LifeCheck SPD monitoring function


Optimal protection of max. 4 lines
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting max. 4 earth-potential-free single lines with common reference potential.

SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 45C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Test standards
SIL classification
Ex certifications
Approvals, Certifications

920 300

BXT BAS
Basisteil

BXT BAS

BXT920 300

BXT BAS

Type
BXT BAS

PU
Part
pc(s).
No.
1
920 300

BXT ML4 BC 24

LifeCheck
24 V
33 V
23.3 V
0.75 A
10 kA
2.5 kA
20 kA
10 kA
) 55 V
) 550 V
) 45 V
) 550 V
1.8 ohm(s)
5.7 MHz
) 1.0 nF
) 16 pF
-40C...+80C
IEC 61643-21, UL 497B
SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
CSA, VdS, GOST

BXT ML4 BC 5
920 350
1 pc(s).

BXT ML4 BC 24
920 354
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
910 695
MCM XT

Base part for use as very space-saving,


four-pole, universal feed-through terminal for
insertion of SPD modules without signal interruption.

BXT ML4 BC 5
LifeCheck
5V
6.0 V
4.2 V
1.0 A
10 kA
2.5 kA
20 kA
10 kA
) 25 V
) 550 V
)9V
) 550 V
1.0 ohm(s)
1.0 MHz
) 5.4 nF
) 16 pF
-40C...+80C
IEC 61643-21, UL 497B
SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
CSA, VdS, GOST

Ordering information
Type
Part No.
Packing unit

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

Dimension drawing BXT ML4 BC

DRC MCM XT
Monitoring System LifeCheck

DRC

Condition
910 695

DRC MCM XT

910 653
M3+

DIN rail mountable device with integrated


LifeCheck sensor for condition monitoring of
max. 10 BXT devices with LifeCheck function.
Type
DRC MCM XT

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

DRC LC M3+
Ableiterprfgert LifeCheck

PU
Part
pc(s).
No.
1
910 695

DRC LC

910 653

DRC LC M3+
Portable device with LifeCheck sensor for
flexible use. For fast and easy testing of LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.

190

www.dehn.de

BXT ML4
BXT ML4

920 362
BE C 12
920 364
BE C 24

BXT ML4
BXT ML4

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML4 BE C 12 / 24

BXT ML4 BE C 12
920 362
BXT ML4 BE C 24
920 364

protected

Dimension drawing BXT ML4 BE C

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting 2 pairs of balanced interfaces with protective diode circuit at the input, current loops (TTY) and optocoupler inputs.

SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 80C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-PG fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Test standards
SIL classification
Ex certifications
Approvals, Certifications

2 x 165 adhesive labels for labelling DRC MCM


XT monitoring devices with their bus addresses.
Type
BS BA1 BA15 BXT

PU
Part
pc(s).
No.
1
920 398

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0A 2 and higher

BXT ML4 BE C 24

LifeCheck
24 V
33 V
23.3 V
0.1 A
10 kA
2.5 kA
20 kA
10 kA
) 52 V
) 66 V
) 45 V
) 45 V
28.8 ohm(s)
1.7 MHz
) 1.5 nF
) 1.5 nF
-40C...+80C
IEC 61643-21, UL 497B
SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
CSA, VdS, GOST

BXT ML4 BE C 12
NEW
920 362
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

Marking system BA1-BA15

Additional decoupling to the terminal


equipment

BXT ML4 BE C 12
LifeCheck
12 V
15 V
10.6 V
0.1 A
10 kA
2.5 kA
20 kA
10 kA
) 30 V
) 35 V
) 19 V
) 19 V
13.8 ohm(s)
1.57 MHz
) 3.2 nF
) 3.2 nF
-40C ... +80C
IEC 61643-21
SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
GOST

Ordering information
Type
Part No.
Packing unit

LifeCheck SPD monitoring function

BXT ML4 BE C 24
920 364
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

920 398
BA15 BXT

BS BA1 BA15 BXT


Bezeichnungssystem fr BXT

BS BA1

Earthing module

920 308

For direct earthing of lines connected to the


BLITZDUCTOR XT base part.

BXT M4 E
Erdungsmodul

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
BXT M4 E

BXT920 308

Test / Disconnection Module


Module for testing lines, to be plugged into
the BLITZDUCTOR XT base part.

920 309

BXT M4 T
/Trennmodul

BXT M4 T

BXT-Prf920 309

920 398

Type
BXT M4 E

PU
Part
pc(s).
No.
1
920 308

Type
BXT M4 T

PU
Part
pc(s).
No.
1
920 309

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.
www.dehn.de

191

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML4 BE HF 5
1

920 370
BE HF 5

BXT ML4 BE HF 5
920 370

protected

LifeCheck SPD monitoring function


Optimal protection of 4 single lines
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML4 BE HF

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting 4 single lines with common reference potential as well as high-frequency
transmissions without electrical isolation.

BXT ML4 BE HF 5

SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 45C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-PG fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Test standards
SIL classification

LifeCheck
5V
6.0 V
4.2 V
1.0 A
10 kA
2.5 kA
20 kA
10 kA
) 26 V
) 40 V
) 11 V
) 11 V
1.0 ohm(s)
100.0 MHz
) 20 pF
) 25 pF
-40C...+80C
IEC 61643-21, UL 497B
SIL2
for more details see: www.dehn.de/en/sil/
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
CSA, VdS, UL, GOST

Ex certifications
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

BXT ML4 BE HF 5
920 370
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
920 300

BXT BAS
Basisteil

BXT BAS

BXT920 300

BXT BAS

910 695
MCM XT

Base part for use as very space-saving,


four-pole, universal feed-through terminal for
insertion of SPD modules without signal interruption.
Type
BXT BAS

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

PU
Part
pc(s).
No.
1
920 300

DRC MCM XT
Monitoring System LifeCheck

DRC

Condition
910 695

DRC MCM XT

910 653
M3+

DIN rail mountable device with integrated


LifeCheck sensor for condition monitoring of
max. 10 BXT devices with LifeCheck function.
Type
DRC MCM XT

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

DRC LC M3+
Ableiterprfgert LifeCheck

PU
Part
pc(s).
No.
1
910 695

DRC LC

910 653

DRC LC M3+
Portable device with LifeCheck sensor for
flexible use. For fast and easy testing of LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.

192

www.dehn.de

BXT ML4

920 371
BD HF 5
920 375
BD HF 24

BXT ML4
BXT ML4

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML4 BD HF 5 / 24

BXT ML4 BD HF 5
920 371
BXT ML4 BD HF 24
920 375

protected

Dimension drawing BXT ML4 BD HF

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting 2 pairs in high-frequency bus systems or video transmission systems.

SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 45C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Test standards
SIL classification
Ex certifications
Approvals, Certifications

Marking system BA1-BA15


2 x 165 adhesive labels for labelling DRC MCM
XT monitoring devices with their bus addresses.
Type
BS BA1 BA15 BXT

PU
Part
pc(s).
No.
1
920 398

BS BA1 BA15 BXT


Bezeichnungssystem fr BXT

BS BA1

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0A 2 and higher

BXT ML4 BD HF 5

BXT ML4 BD HF 24

LifeCheck
24 V
33 V
23.3 V
1.0 A
10 kA
2.5 kA
20 kA
10 kA
) 65 V
) 550 V
) 47 V
) 550 V
1.0 ohm(s)
100.0 MHz
) 25 pF
) 16 pF
-40C...+80C
IEC 61643-21, UL 497B
SIL2
for more details see: www.dehn.de/en/sil/
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4
IECEx KEM 09.0053X: Ex nA II T4 Gc
CSA, VdS, UL, GOST

BXT ML4 BD HF 5
920 371
1 pc(s).

BXT ML4 BD HF 24
920 375
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

920 398
BA15 BXT

Minimum signal disturbance

LifeCheck
5V
6.0 V
4.2 V
1.0 A
10 kA
2.5 kA
20 kA
10 kA
) 25 V
) 550 V
) 11 V
) 550 V
1.0 ohm(s)
100.0 MHz
) 25 pF
) 16 pF
-40C...+80C
IEC 61643-21, UL 497B
SIL2
for more details see: www.dehn.de/en/sil/
ATEX: KEMA 09ATEX0114 X: II 3 G Ex nA II T4 c
IECEx KEM 09.0053X: Ex nA II T4 Gc
CSA, VdS, UL, GOST

Ordering information
Type
Part No.
Packing unit

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

LifeCheck SPD monitoring function

Earthing module

920 308

For direct earthing of lines connected to the


BLITZDUCTOR XT base part.

BXT M4 E
Erdungsmodul

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
BXT M4 E

BXT920 308

Test / Disconnection Module


Module for testing lines, to be plugged into
the BLITZDUCTOR XT base part.

920 309

BXT M4 T
/Trennmodul

BXT M4 T

BXT-Prf920 309

920 398

Type
BXT M4 E

PU
Part
pc(s).
No.
1
920 308

Type
BXT M4 T

PU
Part
pc(s).
No.
1
920 309

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.
www.dehn.de

193

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML4 MY 250
1

920 389

BXT ML4 MY 250


920 389

protected

LifeCheck SPD monitoring function


Distinctive Y circuit
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML4 MY

Space-saving surge arrester module with LifeCheck monitoring function for protecting 4 lines of
stranded signal interfaces up to 250 V a.c.

BXT ML4 MY 250

SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 45C IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Test standards
SIL classification

LifeCheck
250 V
line - PG 320 V
line - PG 250 V
3.0 A
10 kA
2.5 kA
) 1700 V
) 1300 V
) 1100 V
) 1200 V
20 MHz
) 300 pF
) 16 pF
-40C...+80C
IEC 61643-21
SIL2
for more details see: www.dehn.de/en/sil/
GOST

Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

BXT ML4 MY 250


920 389
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
920 300

BXT BAS
Basisteil

BXT BAS

BXT920 300

BXT BAS

910 695
MCM XT

Base part for use as very space-saving,


four-pole, universal feed-through terminal for
insertion of SPD modules without signal interruption.
Type
BXT BAS

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

PU
Part
pc(s).
No.
1
920 300

DRC MCM XT
Monitoring System LifeCheck

DRC

Condition
910 695

DRC MCM XT

910 653
M3+

DIN rail mountable device with integrated


LifeCheck sensor for condition monitoring of
max. 10 BXT devices with LifeCheck function.
Type
DRC MCM XT

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

DRC LC M3+
Ableiterprfgert LifeCheck

PU
Part
pc(s).
No.
1
910 695

DRC LC

910 653

DRC LC M3+
Portable device with LifeCheck sensor for
flexible use. For fast and easy testing of LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.

194

www.dehn.de

BXT ML4 MY 250

920 211

BXT ML2 B 180

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML2 B 180
NEW

BXT ML2 B 180


920 211

Dimension drawing BXT ML2 B

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Space-saving two-pole lightning current arrester module with LifeCheck monitoring function and
shield earthing for almost all applications. For use in connection with downstream surge arresters
Q or combined lightning current and surge arresters with a lower or equal voltage level.

LifeCheck SPD monitoring function


Two-pole lightning equipotential
bonding with 4 terminals for shield
and/or functional earthing
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 1 and higher

BXT ML2 B 180


SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 45C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Test standards
SIL classification
Approvals, Certifications

H
LifeCheck
180 V
180 V
127 V
1.2 A
10 kA
2.5 kA
20 kA
10 kA
) 600 V
) 550 V
) 650 V
) 550 V
0.4 ohm(s)
) 16 pF
) 16 pF
-40C...+80C
IEC 61643-21
SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
CSA, GOST

Ordering information
Type
Part No.
Packing unit

BXT ML2 B 180


920 211
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

Marking system BA1-BA15


2 x 165 adhesive labels for labelling DRC MCM
XT monitoring devices with their bus addresses.
Type
BS BA1 BA15 BXT

PU
Part
pc(s).
No.
1
920 398

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

920 398
BA15 BXT

BS BA1 BA15 BXT


Bezeichnungssystem fr BXT

BS BA1

Earthing module

920 308

For direct earthing of lines connected to the


BLITZDUCTOR XT base part.

BXT M4 E
Erdungsmodul

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
BXT M4 E

BXT920 308

Test / Disconnection Module


Module for testing lines, to be plugged into
the BLITZDUCTOR XT base part.

920 309

BXT M4 T
/Trennmodul

BXT M4 T

BXT-Prf920 309

920 398

Type
BXT M4 E

PU
Part
pc(s).
No.
1
920 308

Type
BXT M4 T

PU
Part
pc(s).
No.
1
920 309

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.
www.dehn.de

195

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML2 BD 180

920 247
BD 180

BXT ML2 BD 180


920 247

protected

LifeCheck SPD monitoring function


Optimal protection of 1 pair
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML2 BD

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting 1 pair of balanced interfaces which are galvanically isolated.

BXT ML2 BD 180

SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 45C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Test standards
SIL classification

LifeCheck
180 V
180 V
127 V
0.75 A
5 kA
2.5 kA
20 kA
10 kA
) 270 V
) 550 V
) 250 V
) 550 V
1.8 ohm(s)
25.0 MHz
) 240 pF
) 16 pF
-40C...+80C
IEC 61643-21
SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
CSA, GOST

Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

BXT ML2 BD 180


920 247
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
920 300

BXT BAS
Basisteil

BXT BAS

BXT920 300

BXT BAS

910 695
MCM XT

Base part for use as very space-saving,


four-pole, universal feed-through terminal for
insertion of SPD modules without signal interruption.
Type
BXT BAS

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

PU
Part
pc(s).
No.
1
920 300

DRC MCM XT
Monitoring System LifeCheck

DRC

Condition
910 695

DRC MCM XT

910 653
M3+

DIN rail mountable device with integrated


LifeCheck sensor for condition monitoring of
max. 10 BXT devices with LifeCheck function.
Type
DRC MCM XT

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

DRC LC M3+
Ableiterprfgert LifeCheck

PU
Part
pc(s).
No.
1
910 695

DRC LC

910 653

DRC LC M3+
Portable device with LifeCheck sensor for
flexible use. For fast and easy testing of LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.

196

www.dehn.de

BXT ML2

920 240
BD S 5
920 242
BD S 12
920 244
BD S 24
920 245
BD S 48

BXT ML2
BXT ML2
BXT ML2
BXT ML2

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML2 BD S 5 BD S 48

BXT ML2 BD S 5
920 240
BXT ML2 BD S 12
920 242
BXT ML2 BD S 24
920 244
BXT ML2 BD S 48
920 245

protected

Dimension drawing BXT ML2 BD

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting 1 pair of balanced interfaces which are galvanically isolated, available with
direct or indirect shield earthing.

BXT ML2 BD S 5
SPD class
M
SPD monitoring system
LifeCheck
Nominal voltage UN
5V
Max. continuous operating d.c. voltage UC
6.0 V
Max. continuous operating a.c. voltage UC
4.2 V
Nominal current at 45C IL
1.0 A
D1 Total lightning impulse current (10/350 s) Iimp
9 kA
D1 Lightning impulse current (10/350 s) per line Iimp
2.5 kA
C2 Total nominal discharge current (8/20 s) In
20 kA
C2 Nominal discharge current (8/20 s) per line In
10 kA
Voltage protection level line-line for Iimp D1 Up
) 25 V
Voltage protection level line-PG for Iimp D1 Up
) 550 V
Voltage protection level line-line at 1 kV/s C3 Up
)9V
Voltage protection level line-PG at 1 kV/s C3 Up
) 550 V
Series impedance per line
1.0 ohm(s)
Cut-off frequency line-line fG
1.0 MHz
Capacitance line-line C
) 5.4 nF
Capacitance line-PG C
) 25 pF
Operating temperature range
-40C...+80C
Test standards
IEC 61643-21
SIL classification
Approvals, Certifications

CSA, GOST

Ordering information
Type
Part No.
Packing unit

BXT ML2 BD S 5
920 240
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

Marking system BA1-BA15


2 x 165 adhesive labels for labelling DRC MCM
XT monitoring devices with their bus addresses.
Type
BS BA1 BA15 BXT

PU
Part
pc(s).
No.
1
920 398

BS BA1 BA15 BXT


Bezeichnungssystem fr BXT

BS BA1

Optimal protection of 1 pair and


shield
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

BXT ML2 BD S 12

BXT ML2 BD S 24

BXT ML2 BD S 48

LifeCheck
12 V
15 V
10.6 V
1.0 A
9 kA
2.5 kA
20 kA
10 kA
) 26 V
) 550 V
) 19 V
) 550 V
1.0 ohm(s)
2.8 MHz
) 2.0 nF
) 25 pF
-40C...+80C
IEC 61643-21

LifeCheck
24 V
33 V
23.3 V
1.0 A
9 kA
2.5 kA
20 kA
10 kA
) 52 V
) 550 V
) 45 V
) 550 V
1.0 ohm(s)
7.8 MHz
) 1.0 nF
) 25 pF
-40C...+80C
IEC 61643-21

LifeCheck
48 V
54 V
38.1 V
1.0 A
9 kA
2.5 kA
20 kA
10 kA
) 80 V
) 550 V
) 70 V
) 550 V
1.0 ohm(s)
8.7 MHz
) 0.7 nF
) 25 pF
-40C...+80C
IEC 61643-21

SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
CSA, GOST
CSA, GOST

BXT ML2 BD S 12
920 242
1 pc(s).

BXT ML2 BD S 24
920 244
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

920 398
BA15 BXT

LifeCheck SPD monitoring function

Earthing module

920 308

For direct earthing of lines connected to the


BLITZDUCTOR XT base part.

BXT M4 E
Erdungsmodul

CSA, GOST

BXT ML2 BD S 48
920 245
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
BXT M4 E

BXT920 308

Test / Disconnection Module


Module for testing lines, to be plugged into
the BLITZDUCTOR XT base part.

920 309

BXT M4 T
/Trennmodul

BXT M4 T

BXT-Prf920 309

920 398

Type
BXT M4 E

PU
Part
pc(s).
No.
1
920 308

Type
BXT M4 T

PU
Part
pc(s).
No.
1
920 309

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.
www.dehn.de

197

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML2 BD DL S 15
NEW

920 243

BXT ML2 BD DL S 15
920 243

protected

Suitable for Dupline buses


LifeCheck SPD monitoring function

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML2 BD

Effective protection for 1 pair and


shield
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

Space-saving LifeCheck-equipped combined SPD module for protecting 1 pair of balanced and galvanically isolated interfaces, which specifically fulfils the requirements of Dupline buses, direct or
indirect shield earthing.

BXT ML2 BD DL S 15

SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 70 C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Test standards
SIL classification

LifeCheck
15 V
17 V
12 V
0.4 A
9 kA
2.5 kA
20 kA
10 kA
) 30 V
) 550 V
) 35 V
) 600 V
) 24 V
) 550 V
2.2 ohm(s)
2.7 MHz
) 1.9 nF
) 25 pF
-40C...+80C
IEC 61643-21
SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
GOST

Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

BXT ML2 BD DL S 15
920 243
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
920 300

BXT BAS
Basisteil

BXT BAS

BXT920 300

BXT BAS

910 695
MCM XT

Base part for use as very space-saving,


four-pole, universal feed-through terminal for
insertion of SPD modules without signal interruption.
Type
BXT BAS

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

PU
Part
pc(s).
No.
1
920 300

DRC MCM XT
Monitoring System LifeCheck

DRC

Condition
910 695

DRC MCM XT

910 653
M3+

DIN rail mountable device with integrated


LifeCheck sensor for condition monitoring of
max. 10 BXT devices with LifeCheck function.
Type
DRC MCM XT

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

DRC LC M3+
Ableiterprfgert LifeCheck

PU
Part
pc(s).
No.
1
910 695

DRC LC

910 653

DRC LC M3+
Portable device with LifeCheck sensor for
flexible use. For fast and easy testing of LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.

198

www.dehn.de

BXT ML2 BD DL S 15

920 220
BE S 5
920 222
BE S 12
920 224
BE S 24
920 225
BE S 48

BXT ML2
BXT ML2
BXT ML2
BXT ML2

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML2 BE S 5 BE S 48

BXT ML2 BE S 5
920 220
BXT ML2 BE S 12
920 222
BXT ML2 BE S 24
920 224
BXT ML2 BE S 48
920 225

protected

Dimension drawing BXT ML2 BE

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting 2 single lines with common reference potential as well as unbalanced interfaces, available with direct or indirect shield earthing.

BXT ML2 BE S 5
SPD class
M
SPD monitoring system
LifeCheck
Nominal voltage UN
5V
Max. continuous operating d.c. voltage UC
6.0 V
Max. continuous operating a.c. voltage UC
4.2 V
Nominal current for 45C IL
1.0 A
D1 Total lightning impulse current (10/350 s) Iimp
9 kA
D1 Lightning impulse current (10/350 s) per line Iimp
2.5 kA
C2 Total nominal discharge current (8/20 s) In
20 kA
C2 Nominal discharge current (8/20 s) per line In
10 kA
Voltage protection level line-line for Iimp D1 Up
) 29 V
Voltage protection level line-PG for Iimp D1 Up
) 27 V
Voltage protection level line-line at 1 kV/s C3 Up
) 18 V
Voltage protection level line-PG at 1 kV/s C3 Up
)9V
Series impedance per line
1.0 ohm(s)
Cut-off frequency line-PG fG
1.0 MHz
Capacitance line-line C
) 2.7 nF
Capacitance line-PG C
) 5.4 nF
Operating temperature range
-40C...+80C
Test standards
IEC 61643-21
SIL classification
Approvals, Certifications

CSA, GOST

Ordering information
Type
Part No.
Packing unit

BXT ML2 BE S 5
920 220
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

Marking system BA1-BA15


2 x 165 adhesive labels for labelling DRC MCM
XT monitoring devices with their bus addresses.
Type
BS BA1 BA15 BXT

PU
Part
pc(s).
No.
1
920 398

BS BA1 BA15 BXT


Bezeichnungssystem fr BXT

BS BA1

Optimal protection of 2 single lines


and shield
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

BXT ML2 BE S 12

BXT ML2 BE S 24

BXT ML2 BE S 48

LifeCheck
12 V
15 V
10.6 V
0.75 A
9 kA
2.5 kA
20 kA
10 kA
) 50 V
) 37 V
) 38 V
) 19 V
1.8 ohm(s)
2.7 MHz
) 1.0 nF
) 2.0 nF
-40C...+80C
IEC 61643-21

LifeCheck
24 V
33 V
23.3 V
0.75 A
9 kA
2.5 kA
20 kA
10 kA
) 102 V
) 66 V
) 90 V
) 45 V
1.8 ohm(s)
6.8 MHz
) 0.5 nF
) 1.0 nF
-40C...+80C
IEC 61643-21

LifeCheck
48 V
54 V
38.1 V
0.75 A
9 kA
2.5 kA
20 kA
10 kA
) 160 V
) 95 V
) 140 V
) 70 V
1.8 ohm(s)
8.7 MHz
) 0.35 nF
) 0.7 nF
-40C...+80C
IEC 61643-21

SIL2 / SIL3
for more details see: www.dehn.de/en/sil/
CSA, GOST
CSA, GOST

BXT ML2 BE S 12
920 222
1 pc(s).

BXT ML2 BE S 24
920 224
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

920 398
BA15 BXT

LifeCheck SPD monitoring function

Earthing module

920 308

For direct earthing of lines connected to the


BLITZDUCTOR XT base part.

BXT M4 E
Erdungsmodul

CSA, UL, GOST

BXT ML2 BE S 48
920 225
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
BXT M4 E

BXT920 308

Test / Disconnection Module


Module for testing lines, to be plugged into
the BLITZDUCTOR XT base part.

920 309

BXT M4 T
/Trennmodul

BXT M4 T

BXT-Prf920 309

920 398

Type
BXT M4 E

PU
Part
pc(s).
No.
1
920 308

Type
BXT M4 T

PU
Part
pc(s).
No.
1
920 309

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.
www.dehn.de

199

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML2 BE HFS 5
1

920 270
BE HFS 5

BXT ML2 BE HFS 5


920 270

protected

LifeCheck SPD monitoring function


Optimal protection of 1 pair and
shield
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Dimension drawing BXT ML2 BE HFS

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting 1 pair in high-frequency transmissions without electrical isolation; available
with direct or indirect shield earthing.

BXT ML2 BE HFS 5

SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 45C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-PG fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Test standards
SIL classification

LifeCheck
5V
6.0 V
4.2 V
1.0 A
9 kA
2.5 kA
20 kA
10 kA
) 26 V
) 40 V
) 11 V
) 11 V
1.0 ohm(s)
100 MHz
) 20 pF
) 30 pF
-40C...+80C
IEC 61643-21
SIL2
for more details see: www.dehn.de/en/sil/
CSA, UL, GOST

Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

BXT ML2 BE HFS 5


920 270
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
920 300

BXT BAS
Basisteil

BXT BAS

BXT920 300

BXT BAS

910 695
MCM XT

Base part for use as very space-saving,


four-pole, universal feed-through terminal for
insertion of SPD modules without signal interruption.
Type
BXT BAS

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

PU
Part
pc(s).
No.
1
920 300

DRC MCM XT
Monitoring System LifeCheck

DRC

Condition
910 695

DRC MCM XT

910 653
M3+

DIN rail mountable device with integrated


LifeCheck sensor for condition monitoring of
max. 10 BXT devices with LifeCheck function.
Type
DRC MCM XT

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

DRC LC M3+
Ableiterprfgert LifeCheck

PU
Part
pc(s).
No.
1
910 695

DRC LC

910 653

DRC LC M3+
Portable device with LifeCheck sensor for
flexible use. For fast and easy testing of LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.

200

www.dehn.de

BXT ML2

920 271
BD HFS 5

BXT ML2

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR XT LifeCheck Modules
PLUGGABLE SPDs FOR DIN RAIL MOUNTING
BXT ML2 BD HFS 5

BXT ML2 BD HFS 5


920 271

protected

Dimension drawing BXT ML2 BD HFS

If LifeCheck detects thermal and electrical overload,


the SPD has to be replaced. This status is indicated
contactlessly by the DEHNrecord LC reader.

Space-saving combined lightning current and surge arrester module with LifeCheck monitoring
function for protecting 1 pair in high-frequency bus systems or video transmission systems, available with direct or indirect shield earthing.

LifeCheck SPD monitoring function


Minimum signal interference
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

BXT ML2 BD HFS 5


SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 45C IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Test standards
SIL classification
Approvals, Certifications

M
LifeCheck
5V
6.0 V
4.2 V
1.0 A
9 kA
2.5 kA
20 kA
10 kA
) 25 V
) 550 V
) 11 V
) 550 V
1.0 ohm(s)
100 MHz
) 25 pF
) 25 pF
-40C...+80C
IEC 61643-21
SIL2
for more details see: www.dehn.de/en/sil/
CSA, UL, GOST

Ordering information
Type
Part No.
Packing unit

BXT ML2 BD HFS 5


920 271
1 pc(s).

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

Marking system BA1-BA15


2 x 165 adhesive labels for labelling DRC MCM
XT monitoring devices with their bus addresses.
Type
BS BA1 BA15 BXT

PU
Part
pc(s).
No.
1
920 398

Accessory Part for BLITZDUCTOR XT


LifeCheck Module

920 398
BA15 BXT

BS BA1 BA15 BXT


Bezeichnungssystem fr BXT

BS BA1

Earthing module

920 308

For direct earthing of lines connected to the


BLITZDUCTOR XT base part.

BXT M4 E
Erdungsmodul

Accessory Part for BLITZDUCTOR XT


LifeCheck Module
BXT M4 E

BXT920 308

Test / Disconnection Module


Module for testing lines, to be plugged into
the BLITZDUCTOR XT base part.

920 309

BXT M4 T
/Trennmodul

BXT M4 T

BXT-Prf920 309

920 398

Type
BXT M4 E

PU
Part
pc(s).
No.
1
920 308

Type
BXT M4 T

PU
Part
pc(s).
No.
1
920 309

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 186/202/203/204/360/362.
www.dehn.de

201

Accessories for BLITZDUCTOR XT


Earthing module

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

920 308

BXT M4 E

BXT M4 E
920 308

protected

For plugging onto BLITZDUCTOR XT


base parts
Easy handling
Quick replacement when retrofitting
an SPD module

Basic circuit diagram BXT M4 E

Dimension drawing BXT M4 E

The plugged-in earthing module short-circuits all lines connected to the BLITZDUCTOR XT base part
to PG. It directly earths initially used cable cores, which are already connected to the base part.

BXT M4 E
D1 Total lightning impulse current (10/350 s) Iimp
Operating temperature range
Degree of protection (plugged-in)
For plugging into
Enclosure material
Colour
Ordering information
Type
Part No.
Packing unit

10 kA
-40C...+80C
IP 20
base part
polyamide PA 6.6
grey

BXT M4 E
920 308
1 pc(s).

920 395
LR

EMC spring terminals

SAK BXT LR
920 395

Lightning current carrying capability

Dimension drawing SAK BXT LR

Flat conductor with low impedance


Flexible spring terminal

Two spring terminals for permanent low-impedance shield contact with the protected and unprotected side of a BXT device. With integrated terminal coding for direct or indirect shield earthing,
cable ties and insulating strips included.
SAK BXT LR

D1 Lightning impulse current (10/350 s)


For plugging into

5 kA
clamp connection BXT BAS

Clamping range
Colour
Accessories

3 - 10 mm
bare
cable tie, insulating strips

Ordering information
Type
Part No.
Packing unit
202

SAK BXT LR
920 395
1 pc(s).

www.dehn.de

SAK BXT

920 309

BXT M4 T

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

Accessories for BLITZDUCTOR XT


Test / Disconnection Module

BXT M4 T
920 309

Dimension drawing BXT M4 T

Basic circuit diagram BXT M4 T

The plugged-in test/disconnection module interrupts the cable run of the lines connected to the BLITZDUCTOR XT base part and leads them to a test socket at the front side of the module. This allows to
carry out measurements in the installation without removing the lines from the base part.

For plugging into the BLITZDUCTOR XT


base parts
Easy maintenance and troubleshooting
Measuring lines included

BXT M4 T
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 80 C IL
Volume resistance
Operating temperature range
Degree of protection (plugged-in)
For plugging into
Test sockets
Enclosure material
Colour
Accessories
Ordering information
Type
Part No.
Packing unit

www.dehn.de

180 V
127 V
1.0 A
0.1 ohm
-40C ... +80C
IP 20
base part
gold-plated, 1 mm
polyamide PA 6.6
grey
2 measuring lines (1 m), protective bag

BXT M4 T
920 309
1 pc(s).

203

Accessories for BLITZDUCTOR XT


Marking system BA1-BA15

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

NEW

920 398

BS BA1 BA15 BXT

BS BA1 BA15 BXT


920 398

For DRC MCM XT condition monitoring system


Abrasion-proof
Pre-printed
Transparent

2 x 165 adhesive labels for labelling DRC MCM XT monitoring devices with their bus addresses (BA1
to BA15) and with consecutive numbers of the assigned BXT base parts or modules (1.1-1.10 to
15.1-15.10)

BS BA1 BA15 BXT


Dimension W x H

13 x 7 mm

Ordering information
Type
Part No.
Packing unit

BS BA1 BA15 BXT


920 398
1 pc(s).

Marking system 1-50

920 399

BS 1 50 BXT
920 399

Abrasion-proof
Pre-printed

Plate with 2 plate numbers from 1 to 50 for attaching to BXT base parts or modules.

BS 1 50 BXT
Dimension W x H

11 x 4 mm

Ordering information
Type
Part No.
Packing unit

BS 1 50 BXT
920 399
1 pc(s).

204

www.dehn.de

BS 1 50 BXT

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

www.dehn.de

BLITZDUCTOR XT
ATEX Certificate

205

BLITZDUCTOR XT
IECEx Certificate

206

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

www.dehn.de

BLITZDUCTOR XT
Information on SIL

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING
The term safety integration level (SIL) is defined in the international
IEC 61508 and IEC61511 standards and is used in the field of functional
safety. It is intended for assessing the reliability and safety of electrical,
electronic or programmable electronic systems. "Functional safety"
describes the safety level of a system or installation, which depends on
the correct operation of sub-systems and external installations to reduce

SD
Surge Protection Device

SU

the risk. The aim of functional safety is to minimise the risk of failure of
the individual sub-systems so that the risk for the entire system or installation is reduced to an acceptable level. The values in the table below can
be used for calculating the functional safety of systems with the surge
protective devices used.

DD

DU

Failure rates according to IEC 61508 in FIT


*1

*2

*1

*2

SFF *3

SIL AC *4

Safe Failure Fraction

SIL

Total
*1

*2

*1

*2

BXT ML2(4) B 180

21

24

86.8%

92.7%

SIL2

SIL3

BXT ML4(2) BD *, BXT ML2 BD S *

21

27

78.2%

92.8%

SIL2

SIL3

BXT ML4 BD HF *, BXT ML2 BD HFS *

29

14

10

43

67.7%

76.8%

SIL2

SIL2

BXT ML2 BD DL S 15

21

27

78.2%

92.8%

SIL2

SIL3

BXT ML4 BE *, BXT ML2 BE S *

21

30

71.4%

93.0%

SIL2

SIL3

BXT ML4 BE HF *, BXT ML2 BE HFS *

33

18

10

51

64.9%

80.4%

SIL2

SIL2

BXT ML4 BE C *

23

12

35

65.4%

91.3%

SIL2

SIL3

BXT ML4 BC EX 24

39

11

50

78.8%

93.7%

SIL2

SIL3

BXT ML4 BD EX 24

57

10

67

85.3%

94.1%

SIL2

SIL3

BXT ML2 BD HF EX 6

28

16

15

44

64.0%

67.2%

SIL2

SIL2

BXT ML4 BC *

21

30

71.4%

93.0%

SIL2

SIL3

BXT ML4 MY 250

20

0.5

10

9.5

30

66.6%

67.9%

SIL2

SIL2

All voltages available

*1 Analysis 1 represents a worst-case analysis


*2 Analysis 2 represents an analysis with the assumption that line short circuits and short circuits to GND are detectable or do not have an effect.
*3 The complete sensor or final element subsystem will need to be evaluated to determine the overall Safe Failure Fraction. The number listed is for reference only.
*4 SIL AC (architectural constraints) means that the calculated values are within the range for hardware architectural constraints for the corresponding SIL but does not
imply all related IEC 61508 requirements are fulfilled. See also previous footnote.

www.dehn.de

207

INFORMATION TECHNOLOGY SYSTEMS


PLUGGABLE SPDs FOR DIN RAIL MOUNTING

208

www.dehn.de

DEHNconnect RK
Terminal block with integrated
surge protection

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING

Minimum installation width of only 6 mm


Quick installation with jumper bar
(accessory part)
Spring-loaded connection system

6 mm two-pole terminal block with integrated surge protection and cage


clamp terminal. Earthing via DIN rail or clamp.
DEHNconnect RK is a 6 mm terminal block with integrated surge protection and has five spring-loaded cage clamp terminals allowing two lines
to be protected and equipotential bonding to the terminal equipment to
be established. The snap-in fixing at the supporting foot allows the device

to be safely earthed via the DIN rail. For reduced wiring, jumper bars can
be plugged into the protected side of the SPD to transmit signals. As the
enclosure of the SPDs is open on one side to minimise the width, a covering plate should be used at the end of every SPD block.

DEHNconnect RK is available in two performance classes:


DCO RK M:
Surge arrester with energy-coordinated
protection stages
DCO RK E (D):
Surge arrester with diodes only, for
improving the electromagnetic compatibility (EMC) of terminal equipment

A wide range of accessories such as


jumper bars, marking plates or covering
plates make DCO RK a system easy to
operate, which has been specifically
designed for use in industrial environments.

DCO RK

In order to minimise the width, the enclosure is open to one side. For protection
against electrical shock, the SPD can be
closed with a covering plate (accessories).
If several devices are arranged next to
each other, one covering plate could be
sufficient.

IP 20

DCO RK Accessories

OUT 3

KB 10 DCO RK

DCO RK with covering plate


2
3

ok

marking plates
Use of jumper bars

Operating state controls of switch contacts in industrial environments are


often fed by a common power source. If several DCO RK units are used,
wiring can be reduced by bridging the feeding signal on the protected side
(accessories).

www.dehn.de

209

DEHNconnect RK
DCO RK ME

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING

DCO RK ME 12
DEHNconnect RK 12 V
DCO RK ME 24
DEHNconnect RK 24 V
DCO RK ME 48
DEHNconnect RK 48 V
DCO RK ME 110
DEHNconnect RK 110 V

OUT

IN

Energy-coordinated gas discharge tubes and


diodes to earth

Standard protection with modular terminal blocks

919 920
ME 12
919 921
ME 24
919 922
ME 48
919 923
ME 110

Dimension drawing DCO RK ME

Low series impedance


For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

2-stage SPD for protecting 2 single lines with common reference potential as well as unbalanced
interfaces.

DCO RK ME 12

DCO RK ME 24

DCO RK ME 48

DCO RK ME 110

SPD class
Q
Q
Q
R
Nominal voltage UN
12 V
24 V
48 V
110 V
Max. continuous operating d.c. voltage Uc
14 V
33 V
55 V
170 V
Max. continuous operating a.c. voltage Uc
9.5 V
23 V
38.5 V
120 V
Nominal current IL
0.5 A
0.5 A
0.5 A
0.5 A
C2 Total nominal discharge current (8/20 s) In
10 kA
10 kA
10 kA
10 kA
C2 Nominal discharge current (8/20 s) per line In
5 kA
5 kA
5 kA
5 kA
Voltage protection level line-line for In C2 Up
) 55 V
) 110 V
) 175 V
) 500 V
Voltage protection level line-PG for In C2 Up
) 40 V
) 65 V
) 100 V
) 270 V
Voltage protection level line-line at 1 kV/s C3 Up
) 36 V
) 90 V
) 160 V
) 460 V
Voltage protection level line-PG at 1 kV/s C3 Up
) 19 V
) 45 V
) 80 V
) 230 V
Series impedance per line
1.8 ohms
1.8 ohms
1.8 ohms
1.8 ohms
Cut-off frequency line-PG fG
2.5 MHz
6 MHz
10 MHz
16 MHz
Capacitance line-line C
) 1.2 nF
) 0.5 nF
) 0.3 nF
) 0.2 nF
Capacitance line-PG C
) 2.4 nF
) 1 nF
) 0.6 nF
) 0.4 nF
Operating temperature range
-40C...+80C
-40C...+80C
-40C...+80C
-40C...+80C
Degree of protection
IP 00, with cover IP 20
IP 00, with cover IP 20
IP 00, with cover IP 20
IP 00, with cover IP 20
For mounting on
35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60175
Connection input/output
spring / spring
spring / spring
spring / spring
spring / spring
Cross-sectional area, solid
0.08 - 2.5 mm2
0.08 - 2.5 mm2
0.08 - 2.5 mm2
0.08 - 2.5 mm2
Cross-sectional area, flexible
0.08 - 2.5 mm2
0.08 - 2.5 mm2
0.08 - 2.5 mm2
0.08 - 2.5 mm2
Earthing via
DIN rail / terminal
DIN rail / terminal
DIN rail / terminal
DIN rail / terminal
Enclosure material
polyamide PA 6.6
polyamide PA 6.6
polyamide PA 6.6
polyamide PA 6.6
Colour
yellow
yellow
yellow
yellow
Test standards
IEC 61643-21
IEC 61643-21
IEC 61643-21
IEC 61643-21
Approvals, Certifications
GOST
GOST
GOST
GOST
Ordering information
Type
Part No.
Packing unit

DCO RK ME 12
919 920
1 pc(s).

DCO RK ME 24
919 921
1 pc(s).

Accessory Part for DEHNconnect RK

AD DCO RK GE
Plate for DCO, yellow

AD DCO

Covering
919 979

210

BS 1 50

Covering plate

Quick marking system, horizontal imprint

For DCO RK
Type
Enclosure material
AD DCO RK GE
polyamide PA 6.6

DCO RK ME 110
919 923
1 pc(s).

Accessory Part for DEHNconnect RK


919 977
DCO RK

919 979
RK GE

DCO RK ME 48
919 922
1 pc(s).

BS 1 50 DCO RK
Marking System for DCO RK

Colour
yellow

PU
pc(s).
1

Part
No.
919 979

Quick
919 977

Plate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint
Type
BS 1 50 DCO RK

Material
plastic

PU
pc(s).
1

Part
No.
919 977

www.dehn.de

DCO RK
DCO RK
DCO RK
DCO RK

919 920
919 921
919 922
919 923

919 940
MD 12
919 941
MD 24

DCO RK
DCO RK

DCO RK MD 12
DEHNconnect RK 12 V
DCO RK MD 24
DEHNconnect RK 24 V

DEHNconnect RK
DCO RK MD 12 / MD 24

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING

919 940
919 941

4
OUT

IN

Dimension drawing DCO RK MD 12 / MD 24

Protective circuit, no leakage currents to earth,


energy-coordinated

Standard protection with modular terminal blocks


Low series impedance

2-stage SPD for protecting a floating pair as well as balanced interfaces.

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications

DCO RK MD 12

DCO RK MD 24

12 V
14 V
9.5 V
0.5 A
10 kA
5 kA
) 25 V
) 750 V
) 19 V
) 650 V
1.8 ohms
2.5 MHz
) 2.4 nF
) 5 pF
-40C...+80C
IP 00, with cover IP 20
35 mm DIN rail acc. to EN 60715
spring / spring
0.08 - 2.5 mm2
0.08 - 2.5 mm2
DIN rail / terminal
polyamide PA 6.6
yellow
IEC 61643-21
GOST

24 V
33 V
23 V
0.5 A
10 kA
5 kA
) 50 V
) 750 V
) 45 V
) 650 V
1.8 ohms
6 MHz
) 1 nF
) 5 pF
-40C...+80C
IP 00, with cover IP 20
35 mm DIN rail acc. to EN 60715
spring / spring
0.08 - 2.5 mm2
0.08 - 2.5 mm2
DIN rail / terminal
polyamide PA 6.6
yellow
IEC 61643-21
GOST

DCO RK MD 12
919 940
1 pc(s).

DCO RK MD 24
919 941
1 pc(s).

Ordering information
Type
Part No.
Packing unit

Accessory Part for DEHNconnect RK

Accessory Part for DEHNconnect RK

Quick marking system, vertical imprint

919 976
DCO RK

Plate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint
Type
BS 1 50 S DCO RK

www.dehn.de

Material
plastic

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0B 2 and higher

PU
pc(s).
1

Part
No.
919 976

BS 1 50 S

NEW

Covering plate
For DCO RK

BS 1 50 S DCO RK
919 976

Type
Enclosure material
AD DCO RK GE
polyamide PA 6.6

Colour
yellow

PU
pc(s).
1

919 979
RK GE

AD DCO

AD DCO RK GE
Plate for DCO, yellow

Covering
919 979

Part
No.
919 979

211

DEHNconnect RK
DCO RK MD 48

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING
1

DCO RK

DCO RK MD 48
DEHNconnect RK 48 V

919 942

OUT

IN

Protective circuit, no leakage currents to earth,


energy-coordinated

Standard protection with modular terminal blocks

919 942
MD 48

Dimension DCO RK MD 48

Extremely low series impedance


For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

2-stage SPD for protecting a floating pair as well as balanced interfaces up to 1.7 A.

DCO RK MD 48

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications

48 V
55 V
38.5 V
1.7 A
10 kA
5 kA
) 100 V
) 750 V
) 70 V
) 650 V
0.4 ohms
10 MHz
) 0.6 nF
) 10 pF
-40C...+80C
IP 00, with cover IP 20
35 mm DIN rail acc. to EN 60715
spring / spring
0.08 - 2.5 mm2
0.08 - 2.5 mm2
DIN rail / terminal
polyamide PA 6.6
yellow
IEC 61643-21
GOST

Ordering information
Type
Part No.
Packing unit

DCO RK MD 48
919 942
1 pc(s).

Accessory Part for DEHNconnect RK

Accessory Part for DEHNconnect RK


919 977
DCO RK

919 979
RK GE

AD DCO RK GE
Plate for DCO, yellow

AD DCO

Covering
919 979

Quick marking system, horizontal imprint

For DCO RK

Plate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint

Type
Enclosure material
AD DCO RK GE
polyamide PA 6.6

212

BS 1 50

Covering plate
BS 1 50 DCO RK
Marking System for DCO RK

Colour
yellow

PU
pc(s).
1

Part
No.
919 979

Quick
919 977

Type
BS 1 50 DCO RK

Material
plastic

PU
pc(s).
1

Part
No.
919 977

www.dehn.de

919 943
MD 110

DCO RK

DCO RK MD 110
DEHNconnect RK 110 V

919 943

DEHNconnect RK
DCO RK MD 110

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING

4
OUT

IN

Dimension drawing DCO RK MD 110

Protection circuit, free of leakage currents to


earth, energy-coordinated

Standard protection with modular terminal blocks


Low series impedance

2-stage SPD for protecting a floating pair, telecommunications.

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0B 2 and higher

DCO RK MD 110

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications

110 V
170 V
120 V
0.5 A
10 kA
5 kA
) 260 V
) 750 V
) 230 V
) 650 V
1.8 ohms
16 MHz
) 0.4 nF
) 5 pF
-40C...+80C
IP 00, with cover IP 20
35 mm DIN rail acc. to EN 60715
spring / spring
0.08 - 2.5 mm2
0.08 - 2.5 mm2
DIN rail / terminal
polyamide PA 6.6
yellow
IEC 61643-21
GOST

Ordering information
Type
Part No.
Packing unit

DCO RK MD 110
919 943
1 pc(s).

Accessory Part for DEHNconnect RK

Accessory Part for DEHNconnect RK

Quick marking system, vertical imprint

919 976
DCO RK

Plate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint
Type
BS 1 50 S DCO RK

www.dehn.de

Material
plastic

PU
pc(s).
1

Part
No.
919 976

BS 1 50 S

NEW

Covering plate
For DCO RK

BS 1 50 S DCO RK
919 976

Type
Enclosure material
AD DCO RK GE
polyamide PA 6.6

Colour
yellow

PU
pc(s).
1

919 979
RK GE

AD DCO

AD DCO RK GE
Plate for DCO, yellow

Covering
919 979

Part
No.
919 979

213

DEHNconnect RK
DCO RK MD HF

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING

The capacitance of the protective circuit can be


minimised by combining several diodes to one
matrix.

Very good transmission performance


For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

DCO RK

DCO RK MD HF 5
DEHNconnect RK MD HF, 5 V

919 970

OUT

IN

Low self-capacitance

919 970
MD HF 5

Dimension drawing DCO RK MD HF

2-stage SPD for protecting balanced or unbalanced interfaces with extra-low voltages. Can also be
used for high transmission rates. For shielded bus lines, SAK shield connection systems should be used.

DCO RK MD HF 5

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Cut-off frequency line-PG fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications

5V
6.0 V
4.2 V
0.1 A
10 kA
5 kA
) 27 V
) 50 V
) 14 V
) 14 V
1.0 ohm
250 MHz
180 MHz
) 19 pF
) 16 pF
-40C...+80C
IP 00 with cover IP 20
35 mm DIN rail acc. to EN 60715
spring / spring
0.08 - 2.5 mm2
0.08 - 2.5 mm2
DIN rail / terminal
thermoplastic PA 6.6
yellow
IEC 61643-21
GOST

Ordering information
Type
Part No.
Packing unit

DCO RK MD HF 5
919 970
1 pc(s).

Accessory Part for DEHNconnect RK


919 979
RK GE

AD DCO

AD DCO RK GE
Plate for DCO, yellow

Covering
919 979

919 977
DCO RK

BS 1 50

BS 1 50 DCO RK
Marking System for DCO RK

Quick
919 977

Covering plate

Quick marking system, horizontal imprint

For DCO RK
Type
Enclosure material
AD DCO RK GE
polyamide PA 6.6

214

Accessory Part for DEHNconnect RK

Colour
yellow

PU
pc(s).
1

Part
No.
919 979

Plate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint
Type
BS 1 50 DCO RK

Material
plastic

PU
pc(s).
1

Part
No.
919 977

www.dehn.de

919 987
12
919 988
24
919 989
48
919 990
60

DCO RK E
DCO RK E
DCO RK E
DCO RK E

DCO RK E 12
DEHNconnect RK 12 V
DCO RK E 24
DEHNconnect RK 24 V
DCO RK E 48
DEHNconnect RK 48 V
DCO RK E 60
DEHNconnect RK 60 V

DEHNconnect RK
DCO RK E

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING

919 987
919 988
919 989
919 990

4
OUT

IN

Dimension drawing DCO RK E

Powerful diodes limit surges to earth.

Protection with modular terminal


blocks
High nominal current

Fine limiting surge protective device for 2 single lines with common reference potential as well as
unbalanced interfaces.

DCO RK E 12

DCO RK E 24

For installation in conformity with the


lightning protection zones concept at
the boundaries from 1 2 and higher

DCO RK E 48

DCO RK E 60

SPD class
W
W
[
[
Nominal voltage UN
12 V
24 V
48 V
60 V
Max. continuous operating d.c. voltage Uc
13 V
28 V
58 V
70 V
Max. continuous operating a.c. voltage Uc
9V
19.5 V
41 V
49.5 V
Nominal current IL
10 A
10 A
10 A
10 A
C1 Total nominal discharge current (8/20 s) In
0.8 kA
0.6 kA
0.3 kA
0.24 kA
C1 Nominal discharge current (8/20 s) per line In
0.4 kA
0.3 kA
0,15 kA
0.12 kA
Voltage protection level line-line for In C1 Up
) 50 V
) 96 V
) 180 V
) 220 V
Voltage protection level line-PG for In C1 Up
) 25 V
) 48 V
) 90 V
) 110 V
Voltage protection level line-line at 1 kV/s C3 Up
) 36 V
) 76 V
) 156 V
) 190 V
Voltage protection level line-PG at 1 kV/s C3 Up
) 18 V
) 38 V
) 78 V
) 95 V
Cut-off frequency line-PG fG
2.5 MHz
5.5 MHz
11 MHz
14 MHz
Capacitance line-line C
) 1.2 nF
) 0.6 nF
) 0.3 nF
) 0.25 nF
Capacitance line-PG C
) 2.5 nF
) 1.2 nF
) 0.6 nF
) 0.5 nF
Operating temperature range
-40C...+80C
-40C...+80C
-40C...+80C
-40C...+80C
Degree of protection
IP 00, with cover IP 20
IP 00, with cover IP 20
IP 00, with cover IP 20
IP 00, with cover IP 20
For mounting on
35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715 35 mm DIN rail acc. to EN 60715
Connection input/output
spring / spring
spring / spring
spring / spring
spring / spring
Cross-sectional area, solid
0.08 - 2.5 mm2
0.08 - 2.5 mm2
0.08 - 2.5 mm2
0.08 - 2.5 mm2
Cross-sectional area, flexible
0.08 - 2.5 mm2
0.08 - 2.5 mm2
0.08 - 2.5 mm2
0.08 - 2.5 mm2
Earthing via
DIN rail / terminal
DIN rail / terminal
DIN rail / terminal
DIN rail / terminal
Enclosure material
polyamide PA 6.6
polyamide PA 6.6
polyamide PA 6.6
polyamide PA 6.6
Colour
yellow
yellow
yellow
yellow
Test standards
IEC 61643-21
IEC 61643-21
IEC 61643-21
IEC 61643-21
Approvals, Certifications
GOST
GOST
GOST
GOST
Ordering information
Type
Part No.
Packing unit

DCO RK E 12
919 987
1 pc(s).

DCO RK E 24
919 988
1 pc(s).

Accessory Part for DEHNconnect RK


919 976
DCO RK

Plate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint

www.dehn.de

Material
plastic

DCO RK E 60
919 990
1 pc(s).

Accessory Part for DEHNconnect RK

Quick marking system, vertical imprint


Type
BS 1 50 S DCO RK

DCO RK E 48
919 989
1 pc(s).

PU
pc(s).
1

Part
No.
919 976

BS 1 50 S

NEW

Covering plate
For DCO RK

BS 1 50 S DCO RK
919 976

Type
Enclosure material
AD DCO RK GE
polyamide PA 6.6

Colour
yellow

PU
pc(s).
1

919 979
RK GE

AD DCO

AD DCO RK GE
Plate for DCO, yellow

Covering
919 979

Part
No.
919 979

215

DEHNconnect RK
DCO RK D

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING

DCO RK D

DCO RK D 5 24
DEHNconnect RK 5/24 V

919 986

OUT

IN

EMC protection with modular terminal blocks

919 986
5 24

Powerful diodes limit surges between the signal


lines.

Dimension drawing DCO RK D

High nominal current


For installation in conformity with the
lightning protection zones concept at
the boundaries from 1 2 and higher

Surge protective device for SIEMENS-SPS S7-300 output digital modules (laboratory tested). The
terminal allows for increased EMC protection. No connection to PG.

DCO RK D 5 24

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Nominal current IL
C1 Total nominal discharge current (8/20 s) In
C1 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Cut-off frequency line-line fG
Capacitance line-line C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Enclosure material
Colour
Test standards
Approvals, Certifications

+24 V / -5 V
+30 V / -6 V
10 A
0.3 kA
0.3 kA
) 70 V
) 45 V
3.5 MHz
) 2 nF
-40C...+80C
IP 00, with cover IP 20
35 mm DIN rail acc. to EN 60715
spring / spring
0.08 - 2.5 mm2
0.08 - 2.5 mm2
polyamide PA 6.6
yellow
IEC 61643-21
GOST

Ordering information
Type
Part No.
Packing unit

DCO RK D 5 24
919 986
1 pc(s).

Accessory Part for DEHNconnect RK


919 979
RK GE

AD DCO RK GE
Plate for DCO, yellow

AD DCO

Covering
919 979

Covering plate
For DCO RK
Type
Enclosure material
AD DCO RK GE
polyamide PA 6.6

216

Colour
yellow

PU
pc(s).
1

Part
No.
919 979

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING

Accessories for DEHNconnect RK


Covering plate

919 979
RK GE

AD DCO

AD DCO RK GE
Plate for DCO, yellow

Covering
919 979

AD DCO RK GE
Enclosure material
Colour
Ordering information
Type
Part No.
Packing unit

polyamide PA 6.6
yellow

AD DCO RK GE
919 979
1 pc(s).

Easy to open

Jumper bar
919 880
DCO RK

KB 10

Multipole unit for DCO RK

KB 10 DCO RK
Bar for DEHNconnect RK

Jumper
919 880

KB 10 DCO RK
Poles
Ordering information
Type
Part No.
Packing unit

10

Reduced wiring
KB 10 DCO RK
919 880
1 pc(s).

Use at protected outputs of DCO RK


only

Quick marking system, horizontal imprint


919 977
DCO RK

BS 1 50

Plate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint
BS 1 50 DCO RK
Marking System for DCO RK

Quick
919 977

BS 1 50 DCO RK
Material
Ordering information
Type
Part No.
Packing unit

plastic

BS 1 50 DCO RK
919 977
1 pc(s).

Pre-printed marking for DCO RK

Quick marking system, vertical imprint


919 976

BS 1 50 S DCO RK

Plate with 2 plate numbers from 1 to 50 for DCO RK, vertical imprint

BS 1 50 S DCO RK
919 976

NEW

BS 1 50 S DCO RK
Material
Ordering information
Type
Part No.
Packing unit

www.dehn.de

plastic

BS 1 50 S DCO RK
919 976
1 pc(s).

Pre-printed marking for DCO RK

217

BLITZDUCTOR VT
Lightning current / Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING

Cost-effective protection of multi-core signal


lines
Interface-specific types, e.g. TTY, RS 485
Types for d.c. power supply systems

Compact protection with screw terminals for multi-core lines for DIN rail
mounting.
BLITZDUCTOR VT is a family of compact DIN rail mounted SPDs and consists of different types of enclosures. Most of the SPDs protect 4-wire sig-

nal lines or special applications. The equipment is earthed via a screw terminal.

The enclosure concept of BLITZDUCTOR VT


is variable. Depending on the application,
SPDs are distinguished between
width: 1.5 modules,
4 protected signal lines

BVT enclosure family

width: 1.5 modules,


2 protected lines for d.c. power supply
systems
width: 3 modules,
6 protected lines for RS 485/422
Connection

Connection to the ground has to be performed


with a terminal instead of the snap-on DIN rail.
Direct equipotential bonding can be established
to the terminal device with the second terminal
compartment of this double terminal.

218

www.dehn.de

918 400
24

BVT TTY

BVT TTY 24
DUCTOR VT TTY

BLITZ918 400

BLITZDUCTOR VT
BVT TTY

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING
1

3
OUT

IN
4

Dimension drawing BVT TTY

The resistors at the circuit output protect the


optocoupler and protective diodes in the terminal
equipment against overloads.

Owing to the additional decoupling resistors at the output, only diodes in the terminal equipment,
which can withstand loads only to a certain extent, are integrated into the energy coordination of
the protective stages. This is especially important for optocoupler interfaces.

Simultaneous protection of two TTY


loops
Additional decoupling to the terminal
device
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

BVT TTY 24
SPD class
Nominal d.c. voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 UP
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Tightening torque (terminals)
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

Q
24 V
26.8 V
18.9 V
0.1 A
10 kA
10 kA
) 65 V
) 700 V
) 36 V
) 600 V
17.2 ohms per pair
8 MHz
) 1 nF
-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.08 - 2.5 mm2
0.08 - 2.5 mm2
0.5 Nm
screw terminal
thermoplastic, UL 94 V-0
yellow
IEC 61643-21, UL 497B
CSA, GOST

BVT TTY 24
918 400
1 pc(s).

219

BLITZDUCTOR VT
BVT MTTY

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING
4

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0B 2 and higher

BVT MTTY 24
918 407

OUT

IN

Cost-effective compact protection

918 407
24

Protection circuit with simple decoupling, no leakage currents to earth, energy-coordinated.

Dimension drawing BVT MTTY

Surge arrester for two floating pairs. Unbalanced use of the decoupling impedance.

BVT MTTY 24
SPD class
Nominal d.c. voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 UP
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Tightening torque (terminals)
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

220

Q
24 V
26.8 V
18.9 V
0.1 A
20 kA
10 kA
) 65 V
) 700 V
) 36 V
) 600 V
2.2 ohms per pair
10 MHz
) 1 nF
-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.08 - 2.5 mm2
0.08 - 2.5 mm2
0.5 Nm
screw terminal
thermoplastic, UL 94 V-0
yellow
IEC 61643-21
GOST

BVT MTTY 24
918 407
1 pc(s).

www.dehn.de

BVT MTTY

918 401
RS485 5

BVT

BVT RS485 5
DUCTOR VT RS485

BLITZ918 401

BLITZDUCTOR VT
BVT RS485

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING
8

4
3

4
3

1
2

1
2

IN

Dimension drawing BVT RS485

OUT

Circuiting diodes to a common reference point


allows for a low protection level between the
signal lines.

Surge arrester for a wide range of applications, e.g. for balanced 4-wire RS 485/422 interfaces or
temperature sensors. Allows for either direct or indirect shield earthing and connection of a signal
ground (SG).

Terminals for 4 bus lines and SG


Direct or indirect shield earthing
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

BVT RS485 5
SPD class
Nominal d.c. voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 UP
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Tightening torque (terminals)
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

Q
5V
6V
4.2 V
0.5 A
10 kA
10 kA
) 20 V
) 700 V
) 8.5 V
) 600 V
1.8 ohms
1.7 MHz
) 5 nF
-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.08 - 2.5 mm2
0.08 - 2.5 mm2
0.5 Nm
screw terminal
thermoplastic, UL 94 V-0
yellow
IEC 61643-21, UL 497B
CSA, GOST

BVT RS485 5
918 401
1 pc(s).

221

BLITZDUCTOR VT
BVT AD

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING

0V

BVT AD

BVT AD 24
DUCTOR VT 24 V

BLITZ918 402

0V

+24 V

+24 V

OUT

IN

EMC protection for PLC 24 V power


supply

918 402
24

As a unipolar diode is used, negative operating


voltages are not permissible.

Dimension drawing BVT AD

Especially low protection level


For installation in conformity with the
lightning protection zones concept at
the boundaries from 1 2 and higher

Quickly responding surge protective device, for e.g. Siemens SPS S7-300 with d.c. power supply.
Especially for use in electromagnetically harsh environments where common varistor-based surge
arresters do not limit sufficiently.

BVT AD 24
SPD class
Nominal d.c. voltage UN
Max. continuous operating d.c. voltage UC
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 UP
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Tightening torque (terminals)
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

222

W
24 V
35 V
10 A
2 kA
1 kA
) 70 V
) 700 V
) 50 V
) 700 V
) 7 nF
) 10 pF
-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.5 - 4.0 mm2
0.5 - 4.0 mm2
0.8 Nm
screw terminal
thermoplastic, UL 94 V-0
yellow
IEC 61643-21, UL 497B
CSA, GOST, UL

BVT AD 24
918 402
1 pc(s).

www.dehn.de

918 408

BVT ALD 36

BLITZDUCTOR VT
BVT ALD

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING

NEW

BVT ALD 36
918 408

1
protected
2

Dimension drawing BVT ALD

Basic circuit diagram BVT ALD

Energy-coordinated combined lightning current and surge arrester for protection of unearthed d.c.
supplies for DIN rail mounting

For d.c. supplies up to nominal currents of 4 A


Low voltage protection level
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A - 2 and higher

BVT ALD 36
SPD class
Nominal d.c. voltage UN
Max. continuous operating d.c. voltage UC
Nominal current at 80C IL
D1 Lightning impulse current (10/350 s) per line Iimp
D1 Total lightning impulse current (10/350 s) Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 UP
Series impedance per line
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Tightening torque (terminals)
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

M
36 V
45 V
4A
2.5 kA
5 kA
20 kA
10 kA
) 80 V
) 1000 V
) 60 V
) 650 V
22 H
) 1.5 pF
) 100 pF
-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.5 - 6.0 mm2
0.5 - 4.0 mm2
0.8 Nm
screw terminal
thermoplastic, UL 94 V-0
yellow
IEC 61643-21
GOST

BVT ALD 36
918 408
1 pc(s).

223

INFORMATION TECHNOLOGY SYSTEMS


BLITZDUCTOR VT KKS
COMPACT SPDs FOR DIN RAIL MOUNTING
Combined lightning current and
surge arrester for cathodic corrosion protection systems
Maximum efficiency due to high discharge
capacity
Easy maintenance due to remote signalling
contact
Resistant to permanent interference voltages
up to 65 V a.c.

SPD for protecting active cathodic corrosion protection systems.


Integrated floating remote signalling contact (break contact) for function
monitoring.
The protective circuit and voltage measuring circuit are protected against
surge impulses caused by atmospheric discharges (lightning) or switching
operations (in power supply lines).
The devices are designed for operation at permanent interference voltages up to 65 V a.c. between pipelines and earth. If this value is exceeded, the relevant regulations for protection against electrical shock have to

be considered and further measures have to be taken.


The devices can be overloaded by overcurrents caused by mains faults
(short circuits or earth faults). Therefore, they should be installed into a
separate metallic enclosure or a prewired terminal unit (ITAK) should be
used. The integrated remote signalling contact indicates thermal overload
of the discharge paths.

In cathodic corrosion protection systems,


SPDs for protective circuits and voltage
measuring circuits are often used at the
same time. For easy identification, the
SPDs have different colours, i.e. yellow for
voltage measuring circuits and red for
protective circuits.
DEHN has longstanding experience
in using SPDs for
pipeline networks
and would be
pleased to assist
you to find the
appropriate protection for your applications.

BVT KKS surge arrester family

Experience has shown that the installation of SPDs into a separate metal enclosure is reasonable as the enclosure provides additional protection from overloads caused by short circuits. With ITAK,
DEHN provides adequate prewired units
for cathodic corrosion protection systems.
The ITAK serial number serves as reference number for ordering.

ITAK, Serial No. 4305

Application example

224

www.dehn.de

918 420
ALD 75

BVT KKS

BVT KKS ALD 75


DUCTOR VT

BLITZ918 420

BLITZDUCTOR VT KKS
BVT KKS ALD

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING
K

Kp

K+

Kp+

FM

Dimension drawing BVT KKS ALD

Thermal fuses monitor the varistors. Capacitive


control for a low impulse sparkover voltage.

Energy-coordinated combined lightning current and surge arrester for protecting the inverter in the
protective circuit (red colour). Plug-in remote signalling contact (break contact) for indicating overloads. Installation into the steel plate enclosure recommended.

For protective circuits


High nominal current
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

BVT KKS ALD 75


SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Nominal current IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s PG Up
A2 Total a.c. current carrying capacity
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Tightening torque (terminal)
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Type of remote signalling contacts
Switching capacity d.c.
Switching capacity a.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

www.dehn.de

M
70 V
75 V
12 A
7 kA
3.5 kA
40 kA
20 kA
) 400 V
) 400 V
) 350 V
) 350 V
20 A
5 H
1 MHz
) 2 nF
) 2 nF
-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.5 - 6 mm2
0.5 - 4 mm2
0.8 Nm
screw terminal
thermoplastic, UL 94 V-0
red
IEC 61643-21
GOST
break contact
250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A
250 V/0.5 A
max 1.5 mm2

BVT KKS ALD 75


918 420
1 pc(s).

225

BLITZDUCTOR VT KKS
BVT KKS APD

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING
M

Mp

M+

Mp+

918 421
APD 36

BVT KKS APD 36


918 421

FM

For voltage measuring circuits


Plug-in remote signalling contact
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

Thermal fuses monitor the discharge circuits.


Capacitive control for a low impulse sparkover
voltage.

Dimension drawing BVT KKS APD

Energy-coordinated combined lightning current and surge arrester for protecting voltage measuring circuits (yellow colour). Plug-in remote signalling contact (break contact) for indicating overloads. Installation into a steel plate enclosure recommended.

BVT KKS APD 36

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Nominal current IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s PG Up
A2 Total a.c. current carrying capacity
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid

36 V
36.8 V
0.05 A
7 kA
3.5 kA
40 kA
20 kA
) 65 V
) 800 V
) 48 V
) 600 V
20 A
70 ohms
4.5 dB at 1 MHz (100 ohms)
) 1 nF
) 10 pF
-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.5 mm - 6 mm2

Cross-sectional area, flexible


Tightening torque (terminal)
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Type of remote signalling contacts
Switching capacity d.c.
Switching capacity a.c.
Cross-sectional area for remote signalling terminals

0.5 mm - 4 mm2
0.8 Nm
screw terminal
thermplastic, UL 94 V-0
yellow
IEC 61643-21
GOST
break contact
250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A
250 V/0.5 A
max. 1.5 mm2

Ordering information
Type
Part No.
Packing unit

226

BVT KKS APD 36


918 421
1 pc(s).

www.dehn.de

BVT KKS

918 404
ALD SN

BVT KKS

BVT KKS ALD SN


DUCTOR VT

BLITZ918 404

BLITZDUCTOR VT KKS
BVT KKS ALD SN

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING
M

Mp

Dp

FM

Dimension drawing BVT KKS ALD SN

Thermal fuses monitor the varistors. Capacitive


control for a low impulse sparkover voltage.

Energy-coordinated combined lightning current and surge arrester for protecting the inverter in the
protective circuit (red colour). Plug-in remote signalling contact (break contact) for indicating overloads. Installation into steel plate enclosure recommended. Device according to SNAM specification.

For protective circuits


Device acc. to SNAM specification
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

BVT KKS ALD SN


SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Nominal current IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s PG Up
A2 Total a.c. current carrying capacity
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Tightening torque (terminal)
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Type of remote signalling contacts
Switching capacity d.c.
Switching capacity a.c.
Cross-sectional area for remote signalling terminals
Ordering information
Type
Part No.
Packing unit

www.dehn.de

M
70 V
75 V
12 A
7 kA
3.5 kA
40 kA
20 kA
) 400 V
) 400 V
) 350 V
) 350 V
20 A
5 H
1 MHz
) 2 nF
) 2 nF
-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.5 - 6 mm2
0.5 - 4 mm2
0.8 Nm
screw terminal
thermoplastic, UL 94 V-0
red
IEC 61643-21
SNAM specification, GOST
break contact
250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A
250 V/0.5 A
max. 1.5 mm2

BVT KKS ALD SN


918 404
1 pc(s).

227

BLITZDUCTOR VT KKS
BVT KKS APD SN

INFORMATION TECHNOLOGY SYSTEMS


COMPACT SPDs FOR DIN RAIL MOUNTING
E

Ep

Mp

918 405
APD SN

BVT KKS

BVT KKS APD SN


DUCTOR VT

BLITZ918 405

FM

For voltage measuring circuits


Device acc. to SNAM specification
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

Thermal fuses monitor the discharge circuits.


Capacitive control for a low impulse sparkover
voltage.

Dimension drawing BVT KKS APD SN

Energy-coordinated combined lightning current and surge arrester for protecting the voltage measuring circuit (yellow colour). Plug-in remote signalling contact (break contact) for indicating overloads. Installation into steel plate enclosure recommended. Device according to SNAM specification.

BVT KKS APD SN

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Nominal current IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s PG Up
A2 Total a.c. current carrying capacity
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid

36 V
36.8 V
0.1 A
7 kA
3.5 kA
40 kA
20 kA
) 65 V
) 900 V
) 48 V
) 600 V
20 A
10 ohms
6 MHz
) 1 nF
) 10 pF
-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.5 - 6 mm2

Cross-sectional area, flexible


Tightening torque (terminal)
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Type of remote signalling contacts
Switching capacity d.c.
Switching capacity a.c.
Cross-sectional area for remote signalling terminals

0.5 - 4 mm2
0.8 Nm
screw terminal
thermoplastic, UL 94 V-0
yellow
IEC 61643-21
SNAM specification, GOST
break contact
250 V/0.1 A, 125 V/0.2 A, 75 V/0.5 A
250 V/0.5 A
max. 1.5 mm2

Ordering information
Type
Part No.
Packing unit

228

BVT KKS APD SN


918 405
1 pc(s).

www.dehn.de

Modular system of lightning current and surge


arresters, allows also for combination to one
combined SPD

DRL plug-in SPD block (10 pairs):


Lightning current arrester for 10 pairs.
DRL plug (1 pair):
Surge protective plug for 1 pair, energy-coordinated with
DRL plug-in SPD blocks.

Lightning current arrester, surge arrester or combined lightning current


and surge arrester, pluggable into type 2 LSA disconnection blocks. The
10-pair plug-in SPD block with lightning current carrying capacity incorporates gas discharge tubes (optional visual fault indication) and disconnection block contacts. This allows for testing, disconnecting or patching

surge arrester

DRL XX XXX ...

+
DRL 10 B 180
lightning
current
arrester

G
O

EF 10 DRL

= combined lightning
current and
surge arrester

of pairs with plugged-in protection or the additional attachment of singlepair surge arresters for optimal protection of terminal equipment. The
surge arresters snap into the earthing frame and can be removed as a
block, whenever required.

The DEHNrapid LSA lightning current arrester for LSA disconnection blocks
effectively protects sensitive hardware from surges and allows for simultaneous testing, disconnecting and patching of connected lines. The modular SPD system for LSA disconnection blocks can be extended to a combined lightning current and surge arrester and features fail-safe overload
protection with visual fault indication of the discharge elements.

72.2
82.9

52.5

91.4

TL 2 10DA LSA

MB 2 10DA LSA

DRL system design

www.dehn.de

DRL assembly with the relevant heights

229

9
8
3
2
1

LSA disconnection block function integrated in


the lightning current arrester provides protection for testing, disconnecting and patching

Variable protection for 1 10 pairs for LSA systems, type series 2/10

DEHNrapid LSA
Lightning current / surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

DEHNrapid LSA
Lightning current / surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

With the appropriate earthing frame, the fine limiting DEHNrapid LSA single-pair surge arresters can be plugged directly into the DRL plug-in SPD
block or optionally into LSA disconnection blocks. The decoupling impedances integrated in the protective plugs allow energy coordination with
the DRL plug-in SPD block irrespective of the cable length. The single-pair
plug also allows partial insertion of disconnection blocks including the
possibility to plug protective plugs with different circuits or nominal voltages into one block.
DRL protective plugs with earthing frame

ab

ab

a b

a b

a'

a
a

a'

DRL 10 B 180...

TL 2 10DA LSA

DRL combined lightning current and surge arrester

Disconnection block function

The integrated unit of plug-in SPD block, earthing frame and protective
plug (combined lightning current and surge arrester) can be completely
removed and plugged in. The combined lightning current and surge
arrester corresponds to SPD Class G
O.

The plug-in SPD block has disconnection contacts that are compatible
with the disconnection block. A measuring or disconnection adapter can
be plugged into the DRL in the same way as a disconnection block to
ensure protection during maintenance operation.

A fail-safe function short-circuits the lines to earth to protect the gas discharge tube from a possible burn-off due to overcurrents. In the event of
an overcurrent, the disconnecting solder between the spring and the SPD
melts, the lines are short-circuited and the temperature-sensitive colour
on the spring changes from light pink to dark purple, signalling the user
to replace the SPD.

DRL 10 B 180 FSD


fail-safe
light pink

fail-safe
dark purple

new

ok

replace
Replace the faulty gas discharge tube

230

www.dehn.de

907 400
180

DRL 10 B

DEHNrapid LSA
DRL 10 B

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

DRL 10 B 180
907 400

IN
2

10

Dimension drawing DRL 10 B

OUT

SPD block with 3-pole gas discharge tubes.


Integrated isolating contacts for plugging
additional elements.

DRL plug-in SPD block (10 pairs) with lightning current carrying capacity, for nearly all kinds of applications. Extendible with DRL protective plug to a combined lightning current and surge arrester. The
integrated disconnection block contacts allow for testing, measuring and patching in case of pluggedin protection.

Lightning current arrester for use as


plug-in SPD block with integrated LSA
disconnection block function
Extendible to a combined lightning
current and surge arrester
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 1 and higher

DRL 10 B 180

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
Pluggable into
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications

180 V
180 V
127 V
0.4 A
5 kA
2.5 kA
10 kA
5 kA
) 500 V
) 500 V
) 500 V
) 450 V
) 0.005 ohms
) 5 pF
) 5 pF
-40C...+80C
IP 10
LSA disconnection block 2/10
mounting frame
polyamide PA 6.6
grey
IEC 61643-21
VdS, GOST

Ordering information
Type
Part No.
Packing unit

DRL 10 B 180
907 400
10 pc(s).

Accessory Part for DEHNrapid LSA

Accessory Part for DEHNrapid LSA

Label holder

907 497

Universal label holder made of stainless steel, for clear marking of


LSA connections. Can be snapped onto DEHNrapid LSA plug-in
SPD blocks, earthing frames with protective plug or mounting
frames with LSA SPD blocks, 2/10 series.
Type
SR DRL

PU
pc(s).
1

Part
No.
907 497

SR DRL
907 497

SR DRL

Gas discharge tube


High-capacity spare gas discharge tubes for DRL 10 or BM 10 DRL. Threepole unit with common arc chamber for a constant voltage protection level
for line-line and line-ground.
Type
Integrated into Part No.
Visual fault indicator
Fail-safe spring

Type
GDT 230 B3
GDT 230 B3 FSD

www.dehn.de

GDT 230 B3

GDT 230 B3 FSD

907 400

907 401

907 218
B3
907 219
B3 FSD

GDT 230
GDT 230

GDT 230 B3
907 218
GDT 230 B3 FSD
907 219

3
3

PU
pc(s).
1
1

Part
No.
907 218
907 219

231

DEHNrapid LSA
DRL 10 B FSD

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY
a

IN
2

DRL 10 B 180 FSD


907 401

10

907 401
180 FSD

Lightning current arrester for use as


plug-in SPD block with integrated LSA
disconnection block function
Visual fault indicator of the gas
discharge tubes
Extendible with DRL protective plugs
to a combined lightning current and
surge arrester
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 1 and higher

OUT

SPD block with 3-pole gas discharge tubes with


fail-safe function. Integrated isolating contacts
for plugging additional elements.

Dimension drawing DRL 10 B FSD

DRL plug-in SPD block (10 pairs) with lightning current carrying capacity, for nearly all types of applications. Extendible with DRL protective plug to a combined lightning current and surge arrester. The
integrated disconnection block contacts allow for testing, measuring and patching in case of pluggedin protection.The gas discharge tubes have a fail-safe function with visual indicator for potential faults.
DRL 10 B 180 FSD

SPD class
Fault indication
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current IL
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Capacitance line-line C
Capacitance line-PG C
Fail-safe performance
Operating temperature range
Degree of protection
Pluggable into
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications

visually by colour change


180 V
180 V
127 V
0.4 A
5 kA
2.5 kA
10 kA
5 kA
) 500 V
) 500 V
) 500 V
) 450 V
) 0.005 ohms
) 5 pF
) 5 pF
gas discharge tube with spring contacts
-40C...+80C
IP 10
LSA disconnection block 2/10
mounting frame
polyamide PA 6.6
grey
IEC 61643-21
VdS, GOST

Ordering information
Type
Part No.
Packing unit

DRL 10 B 180 FSD


907 401
10 pc(s).

Gas discharge tube


907 218
B3
907 219
B3 FSD

GDT 230 B3
907 218
GDT 230 B3 FSD
907 219

GDT 230
GDT 230

High-capacity spare gas discharge tubes for DRL 10 or BM 10 DRL. Threepole unit with common arc chamber for a constant voltage protection level
for line-line and line-ground.
Type
Integrated into Part No.
Visual fault indicator
Fail-safe spring

Type
GDT 230 B3
GDT 230 B3 FSD

232

907 497

GDT 230 B3

GDT 230 B3 FSD

907 400

907 401

3
3

PU
pc(s).
1
1

SR DRL
907 497

SR DRL

Label holder
Universal label holder made of stainless steel, for clear marking of
LSA connections. Can be snapped onto DEHNrapid LSA plug-in
SPD blocks, earthing frames with protective plug or mounting
frames with LSA SPD blocks, 2/10 series.
Type
SR DRL

PU
pc(s).
1

Part
No.
907 497

Part
No.
907 218
907 219

www.dehn.de

DRL 10 B

DRL RE 5
DRL RE
DRL RE
DRL RE
DRL RE

DEHNrapid LSA
DRL RE

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

DRL RE

DRL RE 5
907 420
DRL RE 12
907 421
DRL RE 24
907 422
DRL RE 48
907 423
DRL RE 60
907 424
DRL RE 180
907 425

22

5
2

Dimension drawing DRL RE

Protective circuit energy-coordinated with DRL 10 B


for protecting terminal equipment, fine limitation
between line and PG

Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block, for use as single-stage
protection for terminal equipment with decoupling impedances. Ideally suited for signal circuits
with common potential. Earthing via EF 10 DRL. For disconnection blocks or DRL plug-in SPD blocks
only.
DRL RE 5
SPD class
O
Nominal voltage UN
5V
Max. continuous operating d.c. voltage UC
6V
Max. continuous operating a.c. voltage UC
4.2 V
Nominal current IL
0.4 A
D1 Total lightning impulse current (10/350 s)
in combination with DRL 10 B... Iimp
5 kA
D1 Lightning impulse current (10/350 s) per line
in combination with DRL 10 B... Iimp
2.5 kA
C2 Total nominal discharge current (8/20 s)
in combination with DRL 10 B... In
10 kA
C2 Nominal discharge current (8/20 s) per line
in combination with DRL 10 B... In
5 kA
Voltage protection level line-PG for Iimp D1
in combination with DRL 10 B... Up
) 40 V
Voltage protection level line-line at 1 kV/s C3 Up ) 17.0 V
Voltage protection level line-PG at 1 kV/s C3 Up
) 9.5 V
Series impedance per line
4.7 ohms
Cut-off frequency line-PG fG
0.95 MHz
Capacitance line-line C
) 3 nF
Capacitance line-PG C
) 6 nF
Operating temperature range
-40C...+80C
Degree of protection
IP 20 plugged in
Pluggable into
Earthing via
earthing frame
Enclosure material
polyamide PA 6.6
Colour
yellow
Test standards
IEC 61643-21
Approvals, Certifications
VdS, GOST
Ordering information
Type
Part No.
Packing unit

www.dehn.de

PU
pc(s).
1

Part
No.
907 497

Energy-coordinated with DRL plug-in


SPD block
For installation in conformity with the
lightning protection zones concept at
the boundaries from 1 2 and higher

DRL RE 24

DRL RE 48

DRL RE 60

DRL RE 180

5 kA

5 kA

5 kA

5 kA

5 kA

2.5 kA

2.5 kA

2.5 kA

2.5 kA

2.5 kA

10 kA

10 kA

10 kA

10 kA

10 kA

5 kA

5 kA

5 kA

5 kA

5 kA

24 V
28 V
19.5 V
0.4 A

48 V
54 V
38 V
0.4 A

60 V
70 V
49.5 V
0.4 A

) 45 V
) 65 V
) 95 V
) 115 V
) 36 V
) 72 V
) 135 V
) 185 V
) 19 V
) 38 V
) 70 V
) 95 V
4.7 ohms
4.7 ohms
6.8 ohms
6.8 ohms
2.7 MHz
4.5 MHz
7.35 MHz
10.5 MHz
) 1 nF
) 0.55 pF
) 350 pF
) 250 pF
) 2 nF
) 1.1 nF
) 700 pF
) 500 pF
-40C...+80C
-40C...+80C
-40C...+80C
-40C...+80C
IP 20 plugged in
IP 20 plugged in
IP 20 plugged in
IP 20 plugged in
LSA disconnection block 2/10 or DRL 10 B ... plug-in SPD block
earthing frame
earthing frame
earthing frame
earthing frame
polyamide PA 6.6
polyamide PA 6.6
polyamide PA 6.6
polyamide PA 6.6
yellow
yellow
yellow
yellow
IEC 61643-21
IEC 61643-21
IEC 61643-21
IEC 61643-21
VdS, GOST
VdS, GOST
VdS, GOST
VdS, GOST

DRL RE 12
907 421
10 pc(s).

907 497

Universal label holder made of stainless steel, for clear marking of LSA
connections. Can be snapped onto DEHNrapid LSA plug-in SPD blocks,
earthing frames with protective plug or mounting frames with LSA SPD
blocks, 2/10 series.

Low voltage protection level for the


protection of terminal equipment

DRL RE 12
12 V
14 V
9.5 V
0.4 A

DRL RE 5
907 420
10 pc(s).

Label holder

Type
SR DRL

OUT

IN

33.4

9.4
8.5

907 420
907 421
12
907 422
24
907 423
48
907 424
60
907 425
180

SR DRL

SR DRL
907 497

DRL RE 24
907 422
10 pc(s).

DRL RE 48
907 423
10 pc(s).

DRL RE 60
907 424
10 pc(s).

Earthing frame

) 280 V
) 500 V
) 270 V
4.7 ohms
42 MHz
) 50 pF
) 80 pF
-40C...+80C
IP 20 plugged in
earthing frame
polyamide PA 6.6
yellow
IEC 61643-21
VdS, GOST

DRL RE 180
907 425
10 pc(s).

907 498

Earthing frame with snap-on mechanism, required for earthing and


mounting max. 10 DRL protective plugs. Pluggable onto a 10-pair disconnection block or DRL plug-in SPD block.
Type
EF 10 DRL

180 V
180 V
127 V
0.1 A

PU
pc(s).
1

EF 10 DRL

EF 10 DRL
907 498

Part
No.
907 498

233

DEHNrapid LSA
DRL RD

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

DRL RD 5
907 440
DRL RD 12
907 441
DRL RD 24
907 442
DRL RD 48
907 443
DRL RD 60
907 444
DRL RD 110
907 445

9.4

2
1

Low voltage protection level line/line


for the protection of terminal equipment
Energy-coordinated with DRL plug-in
SPD block
For installation in conformity with the
lightning protection zones concept at
the boundaries from 1 2 and higher

Line-line protective circuit, energy-coordinated


with DRL 10 B for protecting terminal equipment.

DRL RD 5

907 498

EF 10 DRL
907 498

EF 10 DRL

234

DRL RD 5
907 440
10 pc(s).

DRL RD 12

DRL RD 24

DRL RD 48

DRL RD 60

DRL RD 110

12 V
14 V
9.5 V
0.4 A

24 V
28 V
19.5 V
0.4 A

48 V
54 V
38 V
0.4 A

60 V
70 V
49.5 V
0.4 A

110 V
180 V
127 V
0.4 A

5 kA

5 kA

5 kA

5 kA

5 kA

2.5 kA

2.5 kA

2.5 kA

2.5 kA

2.5 kA

10 kA

10 kA

10 kA

10 kA

10 kA

5 kA

5 kA

5 kA

5 kA

5 kA

) 500 V
) 500 V
) 500 V
) 500 V
) 18 V
) 36 V
) 70 V
) 95 V
2.2 ohms
2.2 ohms
4.7 ohms
4.7 ohms
2.7 MHz
5.4 MHz
7.8 MHz
11 MHz
) 2.0 nF
) 1.1 nF
) 700 pF
) 500 pF
-40C...+80C
-40C...+80C
-40C...+80C
-40C...+80C
IP 20 plugged in
IP 20 plugged in
IP 20 plugged in
IP 20 plugged in
LSA disconnection block 2/10 or DRL 10 B... plug-in SPD block
polyamide PA 6.6
polyamide PA 6.6
polyamide PA 6.6
polyamide PA 6.6
yellow
yellow
yellow
yellow
IEC 61643-21
IEC 61643-21
IEC 61643-21
IEC 61643-21
VdS, GOST
VdS, GOST
VdS, GOST
VdS, GOST

DRL RD 12
907 441
10 pc(s).

Earthing frame

DRL RD 24
907 442
10 pc(s).

907 497

Earthing frame with snap-on mechanism, required for earthing and


mounting of max. 10 DRL protective plugs. Pluggable onto a 10-pair
disconnection block or DRL plug-in SPD block.
Type
EF 10 DRL

Dimension drawing DRL RD

Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block for use as single-stage protection for terminal equipment. Low voltage protection levels line-line for electrically isolated interfaces. For mounting with EF 10 DRL. Installation recommended only in combination with DRL plugin SPD block.

SPD class
O
Nominal voltage UN
5V
Max. continuous operating d.c. voltage UC
6V
Max. continuous operating a.c. voltage UC
4.2 V
Nominal current IL
0.4 A
D1 Total lightning impulse current (10/350 s)
in combination with DRL 10 B... Iimp
5 kA
D1 Lightning impulse current (10/350 s) per line
in combination with DRL 10 B... Iimp
2.5 kA
C2 Total nominal discharge current (8/20 s)
in combination with DRL 10 B... In
10 kA
C2 Nominal discharge current (8/20 s) per line
in combination with DRL 10 B... In
5 kA
Voltage protection level line-PG for Iimp D1
in combination with DRL 10 B... Up
) 500 V
Voltage protection level line-line at 1 kV/s C3 Up
) 8.5 V
Series impedance per line
2.2 ohms
Cut-off frequency line-line fG
1 MHz
Capacitance line-line C
) 5.5 nF
Operating temperature range
-40C...+80C
Degree of protection
IP 20 plugged in
Pluggable into
Enclosure material
polyamide PA 6.6
Colour
yellow
Test standards
IEC 61643-21
Approvals, Certifications
VdS, GOST
Ordering information
Type
Part No.
Packing unit

8.5

OUT

IN

33.4

22

907 440
907 441
12
907 442
24
907 443
48
907 444
60
907 445
110

PU
pc(s).
1

Part
No.
907 498

SR DRL
907 497

SR DRL

DRL RD 48
907 443
10 pc(s).

DRL RD 60
907 444
10 pc(s).

) 500 V
) 250 V
4.7 ohms
20 MHz
) 200 pF
-40C...+80C
IP 20 plugged in
polyamide PA 6.6
yellow
IEC 61643-21
GOST

DRL RD 110
907 445
10 pc(s).

Label holder
Universal label holder made of stainless steel, for clear marking of LSA
connections. Can be snapped onto DEHNrapid LSA plug-in SPD blocks,
earthing frames with protective plug or mounting frames with LSA SPD
blocks, 2/10 series.
Type
SR DRL

PU
pc(s).
1

Part
No.
907 497

www.dehn.de

DRL RD 5
DRL RD
DRL RD
DRL RD
DRL RD
DRL RD

907 430
180

DRL PD

DEHNrapid LSA
DRL PD

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

DRL PD 180
907 430

22

5
4

OUT

IN

8.5

33.4

9.4

Dimension drawing DRL PD

Protective circuit, energy-coordinated with DRL 10 B


for protecting terminal equipment, fine limitation
between the lines and additional overcurrent
protection.

Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block for use as single-stage protection for terminal equipment. Low voltage protection level line-line and integrated overcurrent protection for ADSL, ISDN Uk0 or a/b lines. For mounting with EF 10 DRL. Installation recommended only
in combination with DRL plug-in SPD block.

For maximum transmission rates


combined with overcurrent protection
Energy-coordinated with DRL plug-in
SPD block
For installation in conformity with the
lightning protection zones concept at
the boundaries from 1 2 and higher

DRL PD 180

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current IL
D1 Total lightning impulse current (10/350 s)
in combination with DRL 10 B... Iimp
D1 Lightning impulse current (10/350 s) per line
in combination with DRL 10 B... Iimp
C2 Total nominal discharge current (8/20 s)
in combination with DRL 10 B... In
C2 Nominal discharge current (8/20 s) per line
in combination with DRL 10 B... In
Voltage protection level line-PG for Iimp D1
in combination with DRL 10 B... Up
Voltage protection level line-line at 1 kV/s C3 Up
Series impedance per line

180 V
180 V
127 V
0.1 A
5 kA
2.5 kA
10 kA
5 kA
) 500 V
) 270 V
10 ohms

Cut-off frequency line-line fG


Capacitance line-line C
Integrated overcurrent protection
Operating temperature range

61 MHz
) 80 pF
3
0C...+70C

Degree of protection
Pluggable into
Enclosure material
Colour
Test standards
Approvals, Certifications

IP 20 plugged in
LSA disconnection block 2/10 or DRL 10 B... plug-in SPD block
polyamide PA 6.6
yellow
IEC 61643-21
GOST

Ordering information
Type
Part No.
Packing unit

DRL PD 180
907 430
10 pc(s).

Label holder

907 497

Universal label holder made of stainless steel, for clear marking of


LSA connections. Can be snapped onto DEHNrapid LSA plug-in
SPD blocks, earthing frames with protective plug or mounting
frames with LSA SPD blocks, 2/10 series.
Type
SR DRL

www.dehn.de

PU
pc(s).
1

Part
No.
907 497

SR DRL
907 497

SR DRL

Earthing frame

907 498

Earthing frame with snap-on mechanism, required for earthing and


mounting of max. 10 DRL protective plugs. Pluggable onto a 10-pair
disconnection block or DRL plug-in SPD block.
Type
EF 10 DRL

PU
pc(s).
1

EF 10 DRL

EF 10 DRL
907 498

Part
No.
907 498

235

DEHNrapid LSA
DRL HD

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

907 465
907 470
24

DRL HD 5
907 465
DRL HD 24
907 470

9.4

2
1

For maximum transmission rates


Energy-coordinated with DRL plug-in
SPD block
For installation in conformity with the
lightning protection zones concept at
the boundaries from 1 2 and higher

Protective circuit, energy-coordinated with DRL 10 B,


with low capacitance for protection of terminal
equipment line-line.

EF 10 DRL
907 498

DRL HD 24

5V
6.5 V
4.6 V
0.4 A

24 V
28 V
19.5 V
0.4 A

5 kA

5 kA

2.5 kA

2.5 kA

10 kA

10 kA

5 kA

5 kA

DRL HD 5
907 465
10 pc(s).

Earthing frame

DRL HD 24
907 470
10 pc(s).

907 497

Earthing frame with snap-on mechanism, required for earthing and


mounting of max. 10 DRL protective plugs. Pluggable onto a 10-pair
disconnection block or DRL plug-in SPD block.
Type
EF 10 DRL

236

DRL HD 5

) 500 V
) 500 V
) 25 V
) 46 V
2.2 ohms
4.7 ohms
90 MHz
94 MHz
) 22 pF
) 22 pF
-40C...+80C
-40C...+80C
IP 20 plugged in
IP 20 plugged in
LSA disconnection block 2/10 or DRL 10 B... plug-in SPD block
polyamide PA 6.6
polyamide PA 6.6
yellow
yellow
IEC 61643-21
IEC 61643-21
GOST
VdS, GOST

Ordering information
Type
Part No.
Packing unit

EF 10 DRL

Dimension drawing DRL HD

Protective plug (1 pair), energy-coordinated with DRL plug-in SPD block, for use as single-stage
protection for terminal equipment for high-frequency transmissions such as G.703 or ISDN U2m, S2m
and S0. To be mounted with EF 10 DRL. Installation recommended only in combination with DRL
plug-in SPD block.

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current IL
D1 Total lightning impulse current (10/350 s)
in combination with DRL 10 B... Iimp
D1 Lightning impulse current (10/350 s) per line
in combination with DRL 10 B... Iimp
C2 Total nominal discharge current (8/20 s)
in combination with DRL 10 B... In
C2 Nominal discharge current (8/20 s) per line
in combination with DRL 10 B... In
Voltage protection level line-PG for Iimp D1
in combination with DRL 10 B... Up
Voltage protection level line-line at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Operating temperature range
Degree of protection
Pluggable into
Enclosure material
Colour
Test standards
Approvals, Certifications

907 498

8.5

OUT

IN

33.4

22

PU
pc(s).
1

Part
No.
907 498

SR DRL
907 497

SR DRL

Label holder
Universal label holder made of stainless steel, for clear marking of LSA
connections. Can be snapped onto DEHNrapid LSA plug-in SPD blocks,
earthing frames with protective plug or mounting frames with LSA SPD
blocks, 2/10 series.
Type
SR DRL

PU
pc(s).
1

Part
No.
907 497

www.dehn.de

DRL HD 5
DRL HD

907 498

EF 10 DRL

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

Accessories for DEHNrapid LSA


Earthing frame

EF 10 DRL
907 498

Dimension drawing EF 10 DRL

Earthing frame with snap-on mechanism, required for earthing and mounting of max. 10 DRL protective plugs. Pluggable onto a 10-pair disconnection block or DRL plug-in SPD block.

EF 10 DRL
Pluggable into
Earthing via
Enclosure material
Colour
Ordering information
Type
Part No.
Packing unit

www.dehn.de

LSA disconnection blocks or DRL plug-in block


mounting frame or DRL plug-in block
polyamide PA 6.6
yellow

EF 10 DRL
907 498
1 pc(s).

237

DEHNrapid LSA Plug-in SPD Block


(without SPDs)
1

IN

907 499
DRL

BM 10 DRL
907 499

10

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

OUT

SPD block for 3-pole gas discharge tubes.


Integrated disconnection contacts for plugging
additional elements.

Integrated disconnection contacts


For LSA disconnection blocks of type
2/10

Dimension drawing BM 10 DRL

Plug-in SPD block (without SPDs) for 1 to max. 10 gas discharge tubes of type GDT 230 B3 ... .
Can also be used for inserting DRL protective plugs with earthing frame.

Individual insertion of SPDs

BM 10 DRL
Pluggable into
Earthing via
Enclosure material
Colour

LSA disconnection blocks


mounting frame
polyamide PA 6.6
grey

Ordering information
Type
Part No.
Packing unit

BM 10 DRL
907 499
10 pc(s).

Accessory Part for DEHNrapid LSA Plug-in SPD Block


(without SPDs)

Accessory Part for DEHNrapid LSA Plug-in SPD Block


(without SPDs)

Gas discharge tube


907 218
B3
907 219
B3 FSD

GDT 230 B3
907 218
GDT 230 B3 FSD
907 219

GDT 230
GDT 230

Type
Integrated into Part No.
Visual fault indicator
Fail-safe spring

Type
GDT 230 B3
GDT 230 B3 FSD

238

Label holder

High-capacity spare gas discharge tubes for DRL 10 or BM 10 DRL. Threepole unit with common arc chamber for a constant voltage protection level
for line-line and line-ground.
GDT 230 B3

GDT 230 B3 FSD

907 400

907 401

SR DRL
907 497

SR DRL

Universal label holder made of stainless steel, for clear marking of


LSA connections. Can be snapped onto DEHNrapid LSA plug-in
SPD blocks, earthing frames with protective plug or mounting
frames with LSA SPD blocks, 2/10 series.
Type
SR DRL

3
3

PU
pc(s).
1
1

907 497

PU
pc(s).
1

Part
No.
907 497

Part
No.
907 218
907 219

www.dehn.de

BM 10

Individually replaceable protection elements


(gas discharge tubes)

Pluggable SPDs for use in LSA systems, type series 2/10.


Unit for use as protection block for 10 pairs with individually replaceable
protection elements.

Pluggable surge arresters for use as protection blocks in IT installations


and devices, which have to be connected via terminal or disconnection
blocks with LSA IDC terminal. Installation onto terminal blocks, however,
is the preferred method, as their contact forces provide better fixation
even in case of slight vibrations.

The protection blocks consist of similar basic SPD blocks, which are supplied and tested with different protection elements according to
requirements.
DPL 10 G3:
10 standard gas discharge tubes
DPL 10 G3 FSD:
10 gas discharge tubes with fail-safe
function and visual indicator

The surge arresters for 10 pairs can be easily installed and removed for
testing purposes. The contact to earth via the mounting frame is automatically established when plugging in the SPD. After being overloaded, the
protection elements can be individually replaced.

DPL 10 G3 ...

AL 2 10DA LSA or
TL 2 10DA LSA

MB 2 10DA LSA

DPL 10 G3 family

www.dehn.de

Installation of DPL

239

9
8
3
2
1

For 10 pairs with individually tested gas discharge tubes

Suitable for terminal and disconnection blocks


of LSA systems, type series 2/10

DPL 10 G3
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

DPL 10 G3
DPL 10 G3

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY
IN
2

10

DPL 10

DPL 10 G3 110
Technology, 10 TC
DPL 10 G3 110 FSD
907 216

LSA-Plus
907 214

907 214
G3 110
907 216
G3 110 FSD

OUT

Block with 3-pole gas discharge tubes. As soon as


the fail-safe function is activated, the relevant
lines are short-circuited to earth.

Powerful SPD block


Types with/without fail-safe function
or visual indicator

Dimension drawing DPL 10 G3

Protective plug for 10 pairs with tripod gas discharge tubes for nearly all types of applications. SPDs
of type FSD have a fail-safe function and provide additional visual indication after the fail-safe feature has been activated. This helps to recognise immediately if an SPD has to be replaced.

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0B 1 and higher

DPL 10 G3 110
SPD class
Fault indicator
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Capacitance line-line C
Capacitance line-PG C
Fail-safe performance
Operating temperature range
Pluggable into
Earthing via
Enclosure material
Colour
Test standards

DPL 10 G3 110 FSD

110 V
180 V
127 V
0.4 A
10 kA
5 kA
) 600 V
) 600 V
) 600 V
) 600 V
) 5 pF
) 5 pF

-40C...+80C
LSA disconnection and terminal blocks (type 2)
mounting frame
polyamide
grey
IEC 61643-21

visually by colour change


110 V
180 V
127 V
0.4 A
10 kA
5 kA
) 600 V
) 600 V
) 600 V
) 600 V
) 5 pF
) 5 pF
gas discharge tube with spring contacts
-40C...+80C
LSA disconnection and terminal blocks (type 2)
mounting frame
polyamide
grey
IEC 61643-21

DPL 10 G3 110
907 214
10 pc(s).

DPL 10 G3 110 FSD


907 216
10 pc(s).

Ordering information
Type
Part No.
Packing unit

Accessory Part for DPL 10 G3


907 208
G3
907 217
G3 FSD

GDT 230 G3
907 208
GDT 230 G3 FSD
907 217

GDT 230
GDT 230

Gas discharge tube


High-capacity spare gas discharge tube for DPL 10 G3. Three-pole type
with common arc chamber for a constant protection level for both
line/line and line/earth.
Type
Integrated into Part No.
Visual fault indicator
Fail-safe spring

Type
GDT 230 G3
GDT 230 G3 FSD

240

GDT 230 G3

GDT 230 G3 FSD

907 214

907 216

3
3

PU
pc(s).
1
1

Part
No.
907 208
907 217

www.dehn.de

DPL 10

Optimised for equipotential bonding (surge


arrester and shield connection)
Metal enclosure, lockable against unauthorised
access

DEHN enclosures for equipotential bonding (DPG) are lockable metal


enclosures and intended for installation of wiring and protection components. Available in four different sizes, the enclosures which are capable
of carrying lightning currents provide terminals to integrate surge
arresters and shields into the equipotential bonding.
Enclosure with lightning current carrying capacity, IP 40, for different
designs of distribution boards and for the insertion of surge arresters. The
cover can be removed from the wall plate without tools and is equipped
with a lock with cylinder quarter turn and a key. The C-shaped design of
the wall plate facilitates installation work by sidewise or front access. LSA
mounting frames or DIN rails can be attached to the wall plate by means
of cable entry plates and cable rails.

Despite of a high packing density, a structured cabling management is


ensured crossings between cabling and wiring are avoided and the
cabling of e.g. the LSA blocks becomes concise due to the 30 mm grid. For
this kind of cabling, an optional shield connection system is available
(constant force spring). The sophisticated earthing system permanently
connects all conductive components of the enclosure system by mechanical contacting or earth conductors by means of an earthing block.

DEHN enclosures for equipotential bonding (DPG) are available in 4 different sizes, allowing for the insertion of 3/6/12/22 LSA blocks. Even if
20/50/100/200 pairs are used, enough space is provided for the earth conductor block for supporting shielded sheath wires.

The shields of incoming conductors can be contacted with constant force springs of type SA KRF
in a space-saving way and with
lightning current capacity. All
equipotential bonding conductors
are led together in the central
earthing block.
Shield connection with SA KRF

DEHN enclosures for equipotential bonding (DPG) in 4 different sizes

www.dehn.de

241

9
8
7
3
2
1

Tested lightning impulse current carrying


capacity

Premounted enclosure system for wiring and


protection components

INFORMATION TECHNOLOGY SYSTEMS DEHN Enclosure for Equipotential Bonding


SPDs FOR LSA TECHNOLOGY Enclosure system for SPDs protecting IT equipment

DEHN Enclosure for Equipotential Bonding INFORMATION TECHNOLOGY SYSTEMS


DPG LSA
SPDs FOR LSA TECHNOLOGY

DPG LSA 30 P
906 100
DPG LSA 60 P
906 101
DPG LSA 120 P
906 102
DPG LSA 220 P
906 103

Earthing system with lightning current


carrying capacity for SPDs and shield
connection

906 100
30 P
906 101
60 P
906 102
120 P
906 103
220 P

Integrated mounting frame for LSA


blocks with a grid dimension of 30 mm

Reserved space for uninterfered


cabling and surge arresters

DPG LSA is a completely premounted enclosure system with LSA mounting frame and allows optimised use of SPDs and shield connection systems (constant force spring).

DPG LSA 30 P
Carrying capacity of connection components
D1 Total lightning impulse current (10/350 s) Iimp
15 kA
LSA mounting frame for
1 x 3 blocks 2/10
Grid dimension of mounting frame
30 mm
Wirings
1 pc(s).
Cable entries
top / bottom
Cable rail
top / bottom
Lock
yes
For mounting on
wall
Degree of protection
IP 40
Earthing via
earthing block
Dimension W x H x D
240 x 260 x 130 mm
Enclosure material
steel plate
Colour
RAL 9002
Ordering information
Type
Part No.
Packing unit

DPG LSA 30 P
906 100
1 pc(s).

Accessory Part for DEHN Enclosure for Equipotential Bonding


919 030
9M SW

SKB 19 9M SW
Selfbonding Rubber Tape

SKB 19

919 030

Self-bonding rubber tape


Reel with 9 m self-bonding rubber tape for wrapping around constant
force springs for permanent corrosion protection.
Type
SKB 19 9M SW

PU
pc(s).
1

Part
No.
919 030

DPG LSA 60 P

DPG LSA 120 P

DPG LSA 220 P

30 kA
1 x 6 blocks 2/10
30 mm
2 pc(s).
top / bottom
top / bottom
yes
wall
IP 40
earthing block
240 x 350 x 130 mm
steel plate
RAL 9002

50 kA
2 x 6 blocks 2/10
30 mm
2 pc(s).
top / bottom
top / bottom
yes
wall
IP 40
earthing block
330 x 350 x 130 mm
steel plate
RAL 9002

50 kA
2 x 11 blocks 2/10
30 mm
3 pc(s).
top / bottom
top / bottom
yes
wall
IP 40
earthing block
330 x 500 x 130 mm
steel plate
RAL 9002

DPG LSA 60 P
906 101
1 pc(s).

DPG LSA 120 P


906 102
1 pc(s).

DPG LSA 220 P


906 103
1 pc(s).

Accessory Part for DEHN Enclosure for Equipotential Bonding


919 031
10 V2A
919 032
15 V2A
919 033
22 V2A
919 034
29 V2A
919 035
37 V2A
SA KRF 10 V2A
Force Spring for shield connection
SA KRF 15 V2A
Force Spring for shield connection
SA KRF 22 V2A
Force Spring for shield connection
SA KRF 29 V2A
Force Spring for shield connection
SA KRF 37 V2A
Force Spring for shield connection

SA KRF
SA KRF

Constant force spring

SA KRF
SA KRF
SA KRF

Contact
919 031
Contact
919 032
Contact
919 033
Contact
919 034
Contact
919 035

Constant force springs allow solderless shield connections for equipotential bonding or lightning equipotential bonding. They can be installed subsequently without interrupting the conductor shield or requiring
tools for installation. Approved for nuclear installations according to
TV Certificate No. T12-04-ETL003 (TV = German Technical
Inspectorate).
Type
SA KRF 10 V2A
SA KRF 15 V2A
SA KRF 22 V2A
SA KRF 29 V2A
SA KRF 37 V2A

242

Clamping range
4 - 10 mm
9 - 15 mm
14 - 22 mm
18.5 - 29 mm
23.5 - 37 mm

Material
StSt
StSt
StSt
StSt
StSt

PU
pc(s).
20
20
20
10
10

Part
No.
919 031
919 032
919 033
919 034
919 035

www.dehn.de

DPG LSA
DPG LSA
DPG LSA
DPG LSA

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

Accessories for LSA Technology

7
6
5
4
3
2
1

45 angled blades in the contact for a lower


cross-sectional variation in the conductor

Proven quality

Enhanced stability of the conductor


Enhanced corrosion resistance

Further accessories available on request

The IDC method is used for installing many lines quickly and economically. This method is commonly used in telecommunications (e.g. Deutsche
Telekom AG).
The blocks are suitable for connecting plastic-insulated wires with copper
conductor material:
Conductor diameter: 0.4-0.8 mm
Outer diameter: 0.7-1.5 mm

After using wires with a diameter of 0.65 mm, rewiring to smaller diameters is no longer possible.

Monuting frame for 10 LSA blocks, type series 2/10. Total width: 104.5 mm

Mounting frame

MB2 10 LSA
907 995
LSA

MB2 10 LSA
Frame 10 DA LSA-PLUS

MB2 10

Mounting
907 995

Ordering information
Type
Part No.
Packing unit

MB2 10 LSA
907 995
1 pc(s).

Insertion tools with sensor for LSA technology for connecting the wires and simultaneously cutting
residual lengths. With extractor hook and unlatching blade.
907 994

Insertion tools

AW2 LSA

AW2 LSA

AW2 LSA
Tool LSA-PLUS

Insertion
907 994

www.dehn.de

Ordering information
Type
Part No.
Packing unit

AW2 LSA
907 994
1 pc(s).

243

Terminal block

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

Type series 2 for LSA technology for connecting 10 pairs, each to a non-open termination on the
cable and routing side. Allows to plug in DPL 10 G3 arresters. Parallel protective circuit only.

907 997
LSA

AL2 10DA

AL2 10DA LSA


Block 10TC LSA-PLUS

Terminal
907 997

907 996
LSA

TL2 10DA

TL2 10DA LSA


Disconnection Modules 10 TC LSA-PLUS

907 996

907 993
LSA

EL2 38EA

EL2 38EA LSA


Conductor Block, 38-pole LSA-PLUS

Earth
907 993

Accessories for LSA Technology

AL2 10DA LSA


Enclosure material
Test standards
IPC terminal for solid conductor diameters
Outer diameter via insulation of IPC terminal
Contacting frequency ) 0.65 conductor diameter
Contacting frequency 0.8 conductor diameter
Contact material
Contact surface
Flame protection
Insulation resistance
Volume resistance of IPC terminal
Electric strength
Ordering information
Type
Part No.
Packing unit

Disconnection block

PBT
DIN 47608-1, -2
0.40 - 0.80 mm
0.70 - 1.50 mm
> 50 x
) 50 x
special brass
silver
UL 94 V-0
5 x 10.000 mohms
< 10 mohms
2 kV / 50 Hz

AL2 10DA LSA


907 997
1 pc(s).

Type series 2 for LSA technology for connecting 10 pairs, each on the cable and routing side. By
plugging in DRL, the protection is serially provided between the disconnection contacts. Allows also
for plugging in DPL 10 G3 arresters.
TL2 10DA LSA
Enclosure material
Test standards
Standards, Certifications
IPC terminal for solid conductor diameters
Outer diameter via insulation of IPC terminal
Contacting frequency ) 0.65 conductor diameter
Contacting frequency 0.8 conductor diameter
Contact material
Contact surface
Flame protection
Insulation resistance
Volume resistance of IPC terminal
Electric strength
Ordering information
Type
Part No.
Packing unit

Earth conductor block

PBT
DIN 47608-1, -2
corresponds to DTAG TS 0272/96
0.40 - 0.80 mm
0.70 - 1.50 mm
> 50 x
) 50 x
special brass
silver
UL 94 V-0
5 x 10.000 mohms
< 10 mohms
2 kV / 50 Hz

TL2 10DA LSA


907 996
1 pc(s).

Type series 2 for LSA technology for connecting 38 earth wires or shields.
EL2 38EA LSA
Ordering information
Type
Part No.
Packing unit

244

EL2 38EA LSA


907 993
1 pc(s).

www.dehn.de

0
9
8
7

Routing module with LSA spring-loaded terminal


for disconnection blocks

TL2 10DA

907 991
CC

Accessories for LSA Technology

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

TL2 10DA CC
907 991

Optional connection to LSA or springloaded terminals

Dimension drawing

Routing of different wire diameters


DIN rail mounted routing module for disconnection blocks with LSA disconnection block of type
series 2/10 as well as spring-loaded terminals for variable wire connection. DPL and DEHNrapid
LSA surge arresters can be plugged into the routing module.

DRL adapted to DIN rail systems

TL2 10DA CC
Carrying capacity of connection components
D1 Total lightning impulse current (10/350 s) Iimp
Operating temperature range
Degree of protection
For mounting on
Connection input / output
Cross-sectional area of spring terminal, solid
Cross-sectional area of spring terminal, flexible
Earthing via
Enclosure material
IPC terminal for solid conductor diameters
Outer diameter via insulation of IPC terminal
Volume resistance of IPC terminal
Ordering information
Type
Part No.
Packing unit

www.dehn.de

5 kA
-40C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
spring or LSA / spring or LSA
0.08 mm2 - 2.5 mm2
0.08 mm2 - 2.5 mm2
DIN rail / flat connector 6.3 mm
PA / PBT
0.40 - 0.80 mm
0.70 - 1.60 mm
< 10 mohms

TL2 10DA CC
907 991
1 pc(s).

245

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR LSA TECHNOLOGY

246

www.dehn.de

NET Protector
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR 482.6 MM (19 INCH) DATA CABINETS

Protects switches, HUBs and telecommunication systems


Allows for class D according to EN 50173
(Gigabit Ethernet)
Patch panels allow for flexible equipment
Retrofit versions with plug-in inputs and outputs

The 482.6 mm (19 inch) enclosure can be supplied with surge protective
boards for protecting network components (class D) or telecommunication systems.
The 482.6 mm (19 inch) enclosure can be equipped with up to 3 surge
protection boards to protect active network components such as HUBs,
switches (class D) or telecommunication systems. Typical applications:
Ethernet, Token Ring, E1 and telephones.
b

The NET Protector surge arresters require the space of only one vertical
module and are generally installed in terminal boards. They are inserted
as a patch panel with surge protection or as a retrofit version for patching between the patch panel and the device to be protected.

7
a

4
7

33
8

c
1
2

Assembly drawing

NET PRO is modular in design. The empty enclosure can be optionally


equipped with 1, 2 or 3 surge protective panels.

GHMT Certificate

The fully shielded 482.6 mm (19 inch) enclosure and its 4TP
circuit board allow class D networks to be established. This
has been confirmed by the independent GHMT test institute.

www.dehn.de

247

NET Protector
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR 482.6 MM (19 INCH) DATA CABINETS

protected
patch cable

protected
patch cable
active component

NET PRO ... LSA

active component

EBB min.
2.5 mm2

EBB min.
2.5 mm2

NET PRO ... LSA


active component
19" distribution board
EBB

NET PRO

protected
min.
patch cable
2.5 mm2

patch panel

The protective boards do not only provide a


different protective circuit, but also a different
connection. While the protected output is
always an RJ45 unit, the input can be an IDC
terminal or RJ45 unit. The IDC terminal is
often used for the first equipment in a new
installation, which does not include any patch
panel. The RJ45 unit is a retrofit version for
existing systems and it is patched easily between the patch panel and the active component.

patch cable
NET PRO
active component
19" distribution board
EBB

min.
2.5 mm2

protected cable

LSA type as patch panel (left) / retrofit version (right)

248

www.dehn.de

929 035
4TP
929 036
LSA 4TP
929 037
4TP 30

NET PRO

NET PRO 4TP


Protector 4TP
NET PRO LSA 4TP
Protector/LSA-PLUS/4TP
NET PRO 4TP 30
Protector 4TP 30

NET929 035
NET929 036
NET929 037

NET PRO
NET PRO

NET Protector
NET PRO 4TP

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR 482.6 MM (19 INCH) DATA CABINETS

Dimension drawing NET PRO 4TP

2
3

2
3

6
4

6
4

5
7

5
7

Surge protection for all pairs due to low


capacitance diode matrix for each pair.

GHMT certificate for class D channel


link
Low protection level for all lines

Surge protective board fitted with 8-way shielded ports for universal cablings (class D). For universal use as all 4 pairs (4 TP) are protected. To be installed into EG NET PRO 19 and mounted into
distribution cabinets as a patch panel or retrofit version.

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Nominal discharge current (8/20 s) per port In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Cut-off frequency line-line at 100 ohms fG
Insertion loss at 100 MHz
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For installation into
Connection input/output
Pinning
Earthing via
Dimension W x L
Test standards
Approvals, Certifications

For installation in conformity with the


lightning protection zones concept at
the boundaries from 1 2 and higher

NET PRO 4TP

NET PRO LSA 4TP

NET PRO 4TP 30

5V
6V
4.2 V
100 mA
2.4 kA
0.3 kA
) 35 V
) 35 V
) 13 V
) 13 V
165 MHz
< 0.4 dB
) 35 pF
) 50 pF
-40C...+80C
IP 00
enclosure
RJ45 shielded / RJ45 shielded
1/2, 3/6, 4/5, 7/8
enclosure
135 x 77 mm
IEC 61643-21
Class D, GOST

5V
6V
4.2 V
100 mA
2.4 kA
0.3 kA
) 35 V
) 35 V
) 13 V
) 13 V
170 MHz
< 0.3 dB
) 35 pF
) 50 pF
-40C...+80C
IP 00
enclosure
LSA / RJ45 shielded
1/2, 3/6, 4/5, 7/8
enclosure
135 x 107 mm
IEC 61643-21
GOST

24 V
30 V
21.1 V
100 mA
0.8 kA
0.1 kA
) 60 V
) 60 V
) 40 V
) 40 V
300 MHz
< 0.4 dB
) 16 pF
) 20 pF
-40C...+80C
IP 00
enclosure
RJ45 shielded / RJ45 shielded
1/2, 3/6, 4/5, 7/8
enclosure
135 x 77 mm
IEC 61643-21
GOST

NET PRO 4TP


929 035
1 pc(s).

NET PRO LSA 4TP


929 036
1 pc(s).

NET PRO 4TP 30


929 037
1 pc(s).

Ordering information
Type
Part No.
Packing unit

Accessory Part for NET Protector


482.6 mm (19 Inch) Enclosure

929 034
PRO 19

Fully shielded empty enclosure for max. 3 NET Protector protective


boards.
Type
Capacity
Enclosure material

Type
EG NET PRO 19

www.dehn.de

EG NET

EG NET PRO 19
929 034

EG NET PRO 19
1 vertical module
stainless steel front / galvanised sheet metal

PU
pc(s).
1

Part
No.
929 034

249

NET Protector
NET PRO TC

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR 482.6 MM (19 INCH) DATA CABINETS
4

PTC thermistors decouple the protective stages and


thus provide additional protection against power
crossings for terminal equipment.

Patch panel or retrofit version


Protection against power crossing
integrated
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

929 071
TC 2
929 072
TC 2 LSA

NET PRO

NET PRO TC 2
Protector TC 2, 110 V
NET PRO TC 2 LSA
Protector TC 2 LSA,+B433 110 V

NET929 071
NET929 072

Dimension drawing NET PRO TC

Protective board fitted with 8-way unshielded ports for protection against surges and a.c. interferences, for protecting telecommunication systems with analogue or system transmission technology.
For installation into EG NET PRO 19 as retrofit or patch panel version (LSA).

NET PRO TC 2

NET PRO TC 2 LSA

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Nominal discharge current (8/20 s) per port In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For installation into
Connection input/output
Pinning
Earthing via
Dimension W x L
Test standards
Approvals, Certifications

130 V
170 V
120 V
150 mA
10 kA
2.5 kA
) 250 V
) 600 V
) 230 V
) 600 V
10 ohms
10 MHz
) 300 pF
) 15 pF
-40C...+80C
IP 00
enclosure
RJ45 / RJ45
4/5, 3/6
enclosure
135 x 77 mm
IEC 61643-21
GOST

130 V
170 V
120 V
150 mA
20 kA
5 kA
) 275 V
) 600 V
) 230 V
) 600 V
10 ohms
10 MHz
300 pF
15 pF
-40C...+80C
IP 00
enclosure
LSA / RJ45
4/5, 3/6
enclosure
135 x 107 mm
IEC 61643-21
GOST

Ordering information
Type
Part No.
Packing unit

NET PRO TC 2
929 071
1 pc(s).

NET PRO TC 2 LSA


929 072
1 pc(s).

Accessory Part for NET Protector


929 034
PRO 19

EG NET PRO 19
929 034

EG NET

482.6 mm (19 Inch) Enclosure


Fully shielded empty enclosure for max. 3 NET Protector protective
boards.
Type
Capacity
Enclosure material

Type
EG NET PRO 19

250

EG NET PRO 19
1 vertical module
stainless steel front / galvanised sheet metal

PU
pc(s).
1

Part
No.
929 034

www.dehn.de

NET PRO

929 075
E1 LSA G703

NET PRO

NET Protector
NET PRO E1 LSA

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR 482.6 MM (19 INCH) DATA CABINETS

NET PRO E1 LSA G703


929 075

Dimension drawing NET PRO E1 LSA

Energy-coordinated 2-pair protective circuit for E1


interfaces

Surge protective board, patch panel version, fitted with 8-way unshielded ports for E1 interfaces.
Installation into EG NET PRO 19 and mounting in distribution boards upstream of the telecommunication system. For 2 MBit/s transmissions according to G.703.

Patch panel version


Corresponds to G.703 specification
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

NET PRO E1 LSA G703

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Nominal discharge current (8/20 s) per port In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line at 100 ohms fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For installation into
Connection input/output
Pinning
Earthing via
Dimension W x L
Test standards
Approvals, Certifications

5V
6V
4.2 V
200 mA
20 kA
5 kA
) 40 V
) 500 V
) 15 V
) 450 V
1 ohm
210 MHz
) 20 pF
) 25 pF
-40C...+80C
IP 00
enclosure
LSA / RJ45 socket
1/2, 4/5
enclosure
135 x 108 mm
IEC 61643-21
GOST

Ordering information
Type
Part No.
Packing unit

NET PRO E1 LSA G703


929 075
1 pc(s).

Accessory Part for NET Protector


482.6 mm (19 Inch) Enclosure

929 034
PRO 19

Fully shielded empty enclosure for max. 3 NET Protector protective


boards.
Type
Capacity
Enclosure material

Type
EG NET PRO 19

www.dehn.de

EG NET

EG NET PRO 19
929 034

EG NET PRO 19
1 vertical module
stainless steel front / galvanised sheet metal

PU
pc(s).
1

Part
No.
929 034

251

NET Protector
NET PRO 10X TC1 RST

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR 482.6 MM (19 INCH) DATA CABINETS

929 230

available from May 2010


NEW

NET PRO 10X TC1 RST


929 230

5
RJ45

Basic circuit diagram per pair

Particularly compact design

Dimension drawing NET PRO 10X TC1 RST

Power crossing protection integrated


Installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

Protective board with 10 ports for protecting telecommunications systems with analogue or system transmission against overvoltage and a.c. interference.
Input equipped with cage spring terminals which can be removed from the PCB as a block. This
allows to test the lines. For installation into EG NET PRO 10X 19" or EG NET PRO 10X. Enclosure
for 3 vertical modules.
NET PRO 10X TC1 RST

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current at 20C / 50C / 70C IL
C2 Nominal discharge current (8/20 s) per port In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency at 100 ohms fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For installation into
Connection type input/output
Pinning
Earthing via
Dimension W x L
Test standards

180 V
180 V
120 V
120 mA / 100 mA / 60 mA
10 kA
5 kA
275 V
800 V
250 V
600 V
3 ohms to 12 ohms
55 MHz
50 pF
25 pF
-40C...+70C
IP 00
enclosure
plug-in spring terminal / RJ45
4/5
enclosure
75 x 73 mm
IEC 61643-21

Ordering information
Type
Part No.
Packing unit

NET PRO 10X TC1 RST


929 230
1 pc(s).

Accessory Part for NET Protector


929 234
PRO 10X 19

EG NET PRO 10X 19


929 234

EG NET

Unshielded 482.6 mm (19 Inch) Enclosure

Capacity
Enclosure material

Type
EG NET PRO 10X 19

252

929 235
PRO 10X 3HE

Unshielded 19 inch enclosure with a capacity of 5 NET PRO 10X vertical modules, two earth connections and cable anchoring rail.
Accessories: two nuts, two flat washers and two toothed lock washers
for installing the earth connection.
Type

NEW

Accessory Part for NET Protector

EG NET PRO 10X 19

EG NET PRO 10X 3HE


929 235

NEW

EG NET

Enclosure 482,6 mm (19 inches), 3 vertical modules


Unshielded 19 inch enclosure for vertical installation. 3 vertical modules for the insertion of a NET PRO 10X, with earth connection.
Accessories: nut, flat washer, toothed lock washer for installing the
earth connection.
Type

1 vertical module
StSt (V2A)

Capacity
Enclosure material

PU
pc(s).
1

Part
No.
929 234

Type
EG NET PRO 10X 3HE

EG NET PRO 10X 3HE


1 vertical module
StSt (V2A)

PU
pc(s).
1

Part
No.
929 235

www.dehn.de

NET PRO 10X TC1 RST

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION

DEHNpatch
Surge arrester
Patch cable with built-in surge protection
Cat. 6 according to ISO/IEC 11801
For universal use up to 48 V
Easy to retrofit

DEHNpatch is the first Cat. 6 certified patch cable with built-in surge protection that can be used universally according to EN 50173 for voltages
up to 48 V d.c.
Designed as a patch cable, DEHNpatch is easy to install. The unit is equally suited for use in new installations or retrofitting into existing installations at any time with little effort.
DEHNpatch is simply plugged in between the patch panel and the active
component (a switch for example) instead of the conventional patch
cable. The snap-in mechanism of the supporting foot allows the device to
be safely earthed via the DIN rail. For single applications, a section of DIN
rail and a fixing device are included as a standard while for multiple applications in 19 distribution boards an optional DEHNpatch mounting set
is available as an accessory. DEHNpatch fulfils the requirements of

GHMT Certificate DPA M CAT6 RJ45S 48

www.dehn.de

Category 6 and can be universally used for all data services up to nominal voltages of 48 V. It is equally applicable to existing services in offices
and industrial environments such as Gigabit Ethernet, ATM or ISDN as
well as future systems such as Voice over IP and Power over Ethernet.
Thanks to its fully shielded design, DEHNpatch can be used in shielded
and unshielded networks. Its width is similar to that of an RJ45 socket
thus allowing up to 24 devices to be installed in one series and integrated into a 19 rack.
DEHNpatch is supplied with a standard patch cable length of 3 m and 5 m
(other lengths available on request).

GHMT Certificate DPA M CAT6 RJ45H 48

253

DEHNpatch
DPA M CAT6

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION

1
2
3
4
5
6
7
8

DPA M

DPA M CAT6 RJ45S 48


cable with surge protection
DPA M CAT6 RJ45H 48
cable with surge protection

Patch
929 100
Patch
929 110

1
2
3
4
5
6
7
8

Protection of all pairs due to heavy-duty gas discharge tubes and an adapted filter matrix per pair.

Ideally suited for retrofitting, protection of all lines

929 100
CAT6 RJ45S 48
929 110
CAT6 RJ45H 48

Dimension drawing DPA M CAT6 RJ45S 48

Cat. 6 according to ISO/IEC 118001


Universal SPD ideal for use as a patch cable in Ethernet and similar applications in universally structured cabling systems. Certified according to Category 6 and class E. Fully shielded.

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0B 2 and higher

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Nominal discharge current (8/20 s) line-line In
C2 Total nominal discharge current (8/20 s) line-PG In
C2 Nominal discharge current (8/20 s) line-PG In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Insertion loss at 250 MHz
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Pinning
Connecting lead
Connector
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Accessories
Ordering information
Type
Part No.
Packing unit

DPA M CAT6 RJ45S 48

DPA M CAT6 RJ45H 48

48 V
48 V
34 V
1A
150 A
10 kA
2.5 kA
) 190 V
) 600 V
) 145 V
) 500 V
) 2 dB
) 165 pF
) 255 pF
-20C ...+60C
IP 20
35 mm DIN rail acc. to EN 60715
RJ45 connecting lead / RJ45 connecting lead
1/2, 3/6, 4/5, 7/8
Cat. 6, L1 = approx. 0.5 m, L2 = approx. 3 m
Stewart 39 series
35 mm DIN rail acc. to EN 60715
zinc die casting
bare
IEC 61643-21
Cat. 6 acc. to ISO/IEC 11801, GOST
fixing material

48 V
48 V
34 V
1A
150 A
10 kA
2.5 kA
) 190 V
) 600 V
) 145 V
) 500 V
) 3 dB
) 250 pF
) 400 pF
-20C ...+60C
IP 20
35 mm DIN rail acc. to EN 60715
RJ45 connecting lead / RJ45 connecting lead
1/2, 3/6, 4/5, 7/8
Cat. 6, L1 = approx. 1 m, L2 = approx. 5 m
Hirose TM 21P
35 mm DIN rail acc. to EN 60715
zinc die casting
bare
IEC 61643-21
Cat. 6 acc. to ISO/IEC 11801, GOST
fixing material

DPA M CAT6 RJ45S 48


929 100
1 pc(s).

DPA M CAT6 RJ45H 48


929 110
1 pc(s).

Mounting set for DEHNpatch


The set comprises a DIN rail for up to 24 DEHNpatch devices and different
distance bolts with sliding nuts for installation into data distributors. The
DIN rail can be mounted in a space-saving way at the panel of the distributor or even in front of the mounting stations according to a 19 grid.
Type
MS DPA

254

PU
pc(s).
1

929 199

MS DPA

MS DPA
Set for DEHNpatch

Mounting
929 199

Part
No.
929 199

www.dehn.de

DPA M

929 121
CLE RJ45B 48

DPA M

DEHNpatch
DEHNpatch Class E

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION

DPA M CLE RJ45B 48


929 121

1
2
3
4
5
6
7
8

1
2
3
4
5
6
7
8

(1 mod.)

Dimension drawing DPA CLE

Protection of all pairs due to heavy-duty gas


discharge tubes and an adapted filtering matrix
per pair.

Ideally suited for retrofitting, protection of all lines


Cat. 6 in channel (class E)

Universal SPD ideal for use in Industrial Ethernet and similar applications in structured cabling systems
according to class E up to 250 MHz. Fully shielded adapter with sockets for DIN rail mounting.

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0B 2 and higher

DPA M CLE RJ45B 48


SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Nominal discharge current (8/20 s) line-line In
C2 Total nominal discharge current (8/20 s) line-PG In
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Pinning
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Accessories
Ordering information
Type
Part No.
Packing unit

T
48 V
48 V
34 V
1A
150 A
10 kA
) 180 V
) 500 V
) 30 pF
) 25 pF
-40C ...+80C
IP 10
35 mm DIN rail acc. to EN 60715
RJ45 socket / RJ45 socket
1/2, 3/6, 4/5, 7/8
35 mm DIN rail acc. to EN 60715
zinc die casting
bare
IEC 61643-21
GOST
fixing material

DPA M CLE RJ45B 48


929 121
1 pc(s).

Mounting set for DEHNpatch


The set comprises a DIN rail for up to 24 DEHNpatch devices and different
distance bolts with sliding nuts for installation into data distributors. The
DIN rail can be mounted in a space-saving way at the panel of the distributor or even in front of the mounting stations according to a 19 grid.
Type
MS DPA

www.dehn.de

PU
pc(s).
1

929 199

MS DPA

MS DPA
Set for DEHNpatch

Mounting
929 199

Part
No.
929 199

255

BLITZDUCTOR VT
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION

Ideally suited for DIN rail mounted modems or


gateways
Ease of installation due to RJ sockets
Adaptable to the environment of the installation with additional screw terminals

DIN rail mounted surge arrester for telecommunications terminal devices


and telephone systems with RJ connector.
DIN rail mounted surge arrester for telecommunications terminal devices
and telephone systems with RJ connector. They are often used in installa-

tions upstream of residential gateways (TK/EiB interface) or for protecting


industrial DIN rail mounted modems.

RJ sockets and screw terminals at the


input and output of BVT TC 1 surge
arresters allow for universal use, e.g. for
installation upstream of NTBAs with
screw wiring or screw/plug-in connection
upstream of modems and telecommunication systems.

The DIN rail mounted SPD was developed


for installation-friendly protection of the
S0 input of residential gateways. The integrated distribution function at the protected output allows wiring of two protected outgoing ISDN bus circuits.

BLITZDUCTOR VT TC1

256

BLITZDUCTOR VT ISDN

www.dehn.de

918 410

BVT ISDN

BVT ISDN
DUCTOR VT

BLITZ918 410

BLITZDUCTOR VT
BVT ISDN

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION
3

5
a2
a1
b1
b2

IN

Dimension drawing BVT ISDN

OUT

Energy-coordinated ISDN 4-wire protective circuit


with additional protection for the remote power
supply.

For ISDN S0 buses with RJ45 connections. The additional screw terminal connection at the protected output allows for double wiring of the S0 bus (distribution function).

RJ45 sockets
Additional screw terminals for the
ISDN lines
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

BVT ISDN
SPD class
Nominal voltage UN
Nominal voltage pa-pa UN
Max. continuous operating d.c. voltage UC
Max. continuous operating d.c. voltage pa-pa UC
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level pa-pa for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Voltage protection level pa-pa at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Capacitance pa-pa C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Pinning
Cross-sectional area, solid
Cross-sectional area, flexible
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

Q
5V
40 V
7.5 V
60 V
200 mA
10 kA
2.5 kA
) 30 V
) 600 V
) 130 V
) 17 V
) 600 V
) 100 V
1.0 ohm
1.7 MHz
) 3.3 nF
) 15 pF
) 600 pF
-40C...+80C
IP 10
35 mm DIN rail acc. to EN 60715
RJ45 / RJ45 or terminals
3/6, 4/5
0.08 - 2.5 mm2
0.08 - 2.5 mm2
terminal
thermoplastic, UL 94 V-0
yellow
IEC 61643-21
GOST

BVT ISDN
918 410
1 pc(s).

257

BLITZDUCTOR VT
BVT TC

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION

IN

BLITZ918 411

a1
b1

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0B 2 and higher

BVT TC 1
DUCTOR VT

OUT

Additional screw terminals for a/b


lines

BVT TC 1

RJ sockets, compatible with RJ12 pins

918 411

a1
b1

Energy-coordinated protective circuit, no leakage


currents to earth.

Dimension drawing BVT TC

For a/b lines, ISDN Uk0 or ADSL with RJ45 connections and additional screw terminal connections.
Pinning of the RJ45 sockets is compatible with RJ11/12. The parallel screw terminals are more
robust than the RJ45 sockets and increase In to 10 kA.

BVT TC 1
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Pinning
Cross-sectional area, solid
Cross-sectional area, flexible
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

258

R
130 V
170 V
200 mA
5 kA
2.5 kA
) 275 V
) 600 V
) 240 V
) 600 V
4.7 ohms
17 MHz
) 300 pF
) 15 pF
-40C...+80C
IP 10
35 mm DIN rail acc. to EN 60715
RJ45 or terminals / RJ45 or terminals
4/5
0.08 - 2.5 mm2
0.08 - 2.5 mm2
screw terminal
thermoplastic, UL 94 V-0
yellow
IEC 61643-21
GOST

BVT TC 1
918 411
1 pc(s).

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION

DSM TM
Surge arrester
Surge arrester for ISDN or Ethernet applications
Minimum space required for flush mounting
Ideal for Touch Manager wave (Residential
Gateway)

Surge arrester for flush mounting used in LAN interfaces.

DSM TM is a surge arrester which is installed close to terminal devices


and designed for Touch Manager wave (Siemens). The SPD is ideally suited for installation into flush-mounted or small-sized distribution boards
and connected to the local equipotential bonding of the terminal device.

Because of the universal reservation of the pluggable RJ45 output, it can


be used for protecting both ISDN S0 and Ethernet 10 BT (class C cabling)
applications. As screw terminals are available at the input, they can be
connected to both rigid and flexible conductors or shields.

A self-adhesive fixing strip and a 4-pole


plug-in distribution terminal are included
in delivery.

Scope of delivery of DSM TM

www.dehn.de

259

DSM TM
DSM TM

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION

924 274

DSM TM
Data Sockets

1
2
3
4
5
6
7
8

a1
b1
a2
b2
SHL

Indirect shield earthing


Installation accessories included
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

Low-capacitance design with high discharge


capacity and low protection level between the
signal lines.

Dimension drawing DSM TM

For IT installations, class C, or services such as Ethernet 10 BT or ISDN S0 interfaces. Transition from
screw terminal to RJ45 plug. No leakage pickups are generated due to indirect shielding.

DSM TM
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current IL
C1 Nominal discharge current (8/20 s) line-line In
C2 Nominal discharge current (8/20 s) line-PG In
C2 Total nominal discharge current (8/20 s) line-PG In
Voltage protection level line-line for In C1 Up
Voltage protection level line-PG for In C2 UP
Voltage protection level shield-PG for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Voltage protection level shield-PG at 1 kV/s C3 UP
Cut-off frequency fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
Connection input/output
Pinning
Cross-sectional area, solid
Cross-sectional area, flexible
Tightening torque (terminal)
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Accessories
Ordering information
Type
Part No.
Packing unit

260

Q
5V
6V
4.2 V
200 mA
500 A
5 kA
10 kA
) 28 V
) 600 V
) 600 V
) 11 V
) 380 V
) 600 V
55 MHz
) 75 pF
) 20 pF
-40C...+80C
IP 20
screw terminal / RJ45 connecting lead
Ethernet 1/2, 3/6 or ISDN 4/5, 3/6
0 - 1.0 mm2
0 - 1.0 mm2
0.3 Nm
lead 1.0 mm2
polyamide PA 6.6
yellow
IEC 61643-21
GOST
adhesive pad, socket terminal

DSM TM
924 274
1 pc(s).

www.dehn.de

DSM TM

SPD for
924 274

DEHNlink
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION

Surface-mounted surge protective device for


telecommunication systems
Quick installation due to plug-in terminals
Different interface-specific types

Surge arrester for telecommunications terminal devices and telephone


systems with RJ plug-in connector for surface mounting.

Surge arrester for surface mounting with a modern design. It protects


especially modems and telephone systems with RJ plug-in connectors. The
plug-in connectors allow for easy installation.

Compared to conventional devices


( ... ECO), the different SPD units with ...I
type designation have an additional LED
indication of the supply voltage. This
helps to immediately recognise system
failures. Furthermore, they provide a wide
range of accessories such as connecting
cables or fixing material.
Devices with and without operating state indication

DLI ISDN I can protect two terminal devices at the same time due to the
integrated distribution function. The operating state indicator is only illuminated if the NTBA is also connected to the power supply and not in
case of emergency operation (remote supply of telecommunication network operators).

Wiring of DLI ISDN I

OK

LED on
State

NT

NT

LED off
State

ISDN SO Interface

The operating state indicator informs on the proper condition of the


device. In the event of a fault, the connections and cables have to be
checked. If no installation fault can be detected, the SPD has been overloaded and has to be replaced.

Service

Faulty

Operating state indication DLI ISDN I

www.dehn.de

261

DEHNlink
DLI ISDN I

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION
3

929 024

DLI ISDN I

DLI ISDN I
ISDN/I

DEHNlink
929 024

protected

3
6
4
5

2 protected outputs
Surge protection and LED indication
for the remote supply included
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

Energy-coordinated ISDN 4-wire protective circuit


with additional protection and indication of the
remote power supply.

Dimension drawing DLI ISDN I

SPD with two protected ISDN S0 outputs (distribution function) and operating state indication (LED)
of the remote supply voltage. No indication during emergency operation (supply from telephone
system only). Connecting cable and mounting material included.

DLI ISDN I
SPD class
Nominal voltage UN
Nominal voltage pa-pa UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Max. continuous d.c. voltage pa-pa UC
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level pa-pa for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Voltage protection level pa-pa at In C2 Up
Series impedance per line
Cut-off frequency line-line
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
Connection input/output
Pinning
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Accessories
Ordering information
Type
Part No.
Packing unit

262

Q
5V
40 V
7.5 V
5.2 V
45 V
200 mA
10 kA
2.5 kA
) 30 V
) 600 V
) 180 V
) 17 V
) 600 V
) 100 V
1 ohm
2 MHz
) 3 nF
) 15 pF
-40C...+80C
IP 20
RJ45 / 2 x RJ45
3/6, 4/5
flat connector 6.3 mm
polyamide PA 6.6
yellow
IEC 61643-21
GOST
connecting cable, mounting material

DLI ISDN I
929 024
1 pc(s).

www.dehn.de

929 028

DLI TC 2 I

DLI TC 2 I
TC 2

DEHNlink
929 028

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION

DEHNlink
DLI TC I

protected

Dimension drawing DLI TC I

2-stage protective circuit with overcurrent protection and system voltage indication of DLI TC 2 I.

Protective device for analogue or system telephones with operating state indication (LED). Protects
even against alternating current interference. Compatible with pins of RJ11/12 plugs. Connecting
cable and mounting material included.

LED indicates supply voltage


Protection against power crossing
integrated
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

DLI TC 2 I
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
Connection input/output
Pinning
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Accessories
Ordering information
Type
Part No.
Packing unit

www.dehn.de

R
110 V
170 V
120 V
150 mA
10 kA
2.5 kA
) 250 V
) 600 V
) 230 V
) 600 V
10 ohms
10 MHz
) 0.3 nF
) 15 pF
-40C...+80C
IP 20
RJ45 / RJ 45 (compatible with RJ12)
3/6, 4/5 (3/4, 2/5 for RJ12)
flat connector 6.3 mm
polyamide PA 6.6
yellow
IEC 61643-21
GOST
connecting cable, mounting material

DLI TC 2 I
929 028
1 pc(s).

263

DEHNlink
DLI TC

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR RJ CONNECTION

929 081
ECO RJ12

DLI TC ECO RJ12


Denmark

protected

Economical protection for 1 pair


Modern design
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

Using a high-capacity varistor makes decoupling


to the gas discharge tube unnecessary.

Dimension drawing DLI TC

Protective device for analogue or system telephones, RJ12 unit.

DLI TC ECO RJ12


SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Cut-off frequency line-line
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
Connection input/output
Pinning
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Accessories
Ordering information
Type
Part No.
Packing unit

264

R
130 V
170 V
120 V
200 mA
5 kA
2.5 kA
) 480 V
) 600 V
) 280 V
) 600 V
10 MHz
) 0.7 nF
) 15 pF
-40C...+80C
IP 20
RJ12 / RJ12
3/4
flat connector 6.3 mm
polyamide PA 6.6
yellow
IEC 61643-21
GOST
mounting material

DLI TC ECO RJ12


929 081
1 pc(s).

www.dehn.de

DLI TC

DEHNlink929 081

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR BT JACK CONNECTION

DEHNlink TC BT
Surge arrester
Surface-mountable protective device for telecommunication systems
Quick installation due to plug-in terminals
Device acc. to British Telecom requirements

Surge arrester for telecommunications terminal equipment and telephone


systems with BT plug-in connection for surface mounting.

Surge arrester for telecommunications terminal equipment and telephone


systems with BT plug-in connection for surface mounting. The device
meets the requirements of Oftel NS/G/23/L/100005 for connections

www.dehn.de

between a terminal point of a public telephone installation and any


telecommunications terminal equipment. Fulfils BS6651:1992, Appendix C,
Category C-High and CCITT K17.

265

DEHNlink TC BT
DLI TC BT

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR BT JACK CONNECTION
1

6
2

6
2

5
3

5
3

929 026

DLI TC BT

DLI TC BT
BT

DEHNlink
929 026

protected

Device acc. to British Telecom requirements

Energy-coordinated protective circuit for all pairs,


free of leakage currents to earth.

Dimension drawing DLI TC BT

Protection for all lines


For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

Protective device for analogue or system telephones in accordance with British Telecom requirements. Pluggable terminals for easy installation.

DLI TC BT
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Series impedance per line
Bandwidth fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
Connection input/output
Pinning
Earthing by
Enclosure
Colour
Test standards
Accessories
Ordering information
Type
Part No.
Packing unit

266

R
130 V
145 V
125 mA
10 kA
5 kA
) 210 V
) 550 V
) 185 V
) 450 V
4.7 ohms
13 MHz
) 400 pF
) 10 pF
-40C...+80C
IP 20
BT jack / BT jack
1/6, 2/5, 3/4
flat connector 6.3 mm
thermoplastic
black
IEC 61643-21
connecting cable, mounting material

DLI TC BT
929 026
1 pc(s).

www.dehn.de

UGKF
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

Plug-in surge protective adapter for easy retrofitting


Integrated indirect shield earthing avoids leakage pickups

Surge arrester for use as cable adapter to protect coaxial systems such as
video and camera systems from potential damage.

www.dehn.de

UGKF BNC surge arresters are shielded devices for plugging into coaxial
terminal devices or connections. Frequent fields of application are the protection of outdoor or central video surveillance systems. In order to avoid

being influenced by leakage pickups, the cable shield is earthed indirectly via a gas discharge tube. The SPD inputs are used as sockets and the
protected outputs as plugs.

UGKF BNC types

DGA BNC VC ...

Devices for protecting video surveillance systems with higher supply voltage or with a two-sided socket connection are also available on request.

DGA BNC VC ... surge arresters of the DEHNgate familiy can be easily
installed on supporting rails.

267

UGKF
UGKF BNC

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

929 010
BNC

UGKF

UGKF BNC
Comupter Systems

SPD for
929 010

protected

Easily adaptable
Avoids leakage pickups
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

Low-capacitance, 2-stage protective circuit with


indirect shield earthing to avoid leakage pickups.

Dimension drawing UGKF BNC

UGKF BNC surge arresters are suitable for protecting video cameras and Arcnet with BNC connection. Special versions for video cameras with higher nominal voltage available on request.

UGKF BNC
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
C2 Nominal discharge current (8/20 s) per line In
C2 Nominal discharge current (8/20 s) shield-PG In
Voltage protection level line-shield for In C2 UP
Voltage protection level line-shield at 1 kV/s C3 UP
Voltage protection level shield-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency fG
Return loss 20 dB up to
Capacitance line-shield C
Operating temperature range
Connection input/output
Earthing via
Shield earthing via
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

268

T
5V
8V
2.5 kA
10 kA
25 V
15 V
600 V
10 ohms
300 MHz
40 MHz
50 pF
-40C...+80C
BNC socket / BNC connector
outgoing earth conductor 0.75 mm2
indirectly by an integrated spark gap
IEC 61643-21
GOST

UGKF BNC
929 010
1 pc(s).

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

DEHNgate
Lightning current and surge arrester
Application-specific SPD designs
SPD for use in satellite and cable TV systems
with measuring output
Combined lightning current and surge arrester
with a high discharge capacity and low protection level
Contact materials
endurance

with

extremely

high

Lightning current and surge arrester for use as cable adapter to protect
coaxial systems such as CCTV, mobile radio stations and antenna systems
from potential damage.
DEHNgate is a family of lightning current and surge arresters with a cable
adapter design for protecting coaxial systems such as mobile radio sta-

tions and antenna systems from potential damage. Depending on the


application, different mechanical and electrical types are available.

The coaxial DGA arrester family comes in


different designs for different applications. Different types of plugs and arrester
technologies allow for optimised solutions. Further types are available on
request.

DGA FF TV can be mounted onto a DIN rail


in a space-saving way to protect satellite
systems with several outputs. For single
applications such as cable TV, the device
can be simply snapped into a wall-mounted adapter. 2 F cable connectors are also
included.

DGA arrester family

Principle of Lambda/4

The Lambda/4 surge arresters of type


DGA L4 feature an internal coaxial connection of the inner conductor as a bandpass. Only frequencies within this band
are transmitted. For low-frequency
impulses, such as lightning currents, they
cause a short circuit. This makes them
mechanically very robust and maintenance-free. Due to their low protection
level and high discharge capacity, they
can be used as combined lightning current and surge arresters.

Delivery of DGA FF TV

If high partial lightning currents can be


coupled into antenna lines or if very high
transmission performances are required,
the use of Lambda/4 surge arresters is
advisable. If additional remote supply is
needed for the antenna, a combination of
a gas discharge tube and Lambda/4 technology (DGA LG) should be used. The
surge arresters are made of top-quality
material and provide excellent endurance.

Spark-gap-based surge arresters have an internal gas-filled surge arrester and can be
defined as a low pass. This also allows for d.c. transmission (antenna supply). Peak voltages exceeding the threshold value of the gas discharge tube are discharged. These surge
arresters provide extensive contact surfaces from the inner conductor to the gas discharge tube. This minimises burn-off of the material during the discharge process and
ensures a constant transmission performance.

Application of Lambda/4
arresters

Principle of a spark-gap-based SPD

www.dehn.de

269

DEHNgate
Lightning current and surge arresters

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

signal test

DG A

DEHNga
te

SPD FF TV
No. 909
I N 703
U C 2A
24 V

HF test signal
5-2400 MHz

5-3000 MHz

TP

ok

-20 dB

meter

protected

DEHNgate

TP = test point

DGA FF TV

KLASSE

SPD
No. 909 703
IN 2A
UC 24 V

check
system

DG A

DEHNga
te

HF test signal

SPD FF TV
No. 909
I N 703
U C 2A
24 V

CLASS

5-2400 MHz

5-3000 MHz

TP

meter

-20 dB

protected

DEHNgate
DGA FF TV

KLASSE

input

SPD
No. 909 703
IN 2A
UC 24 V

protected output

CLASS

The DGA FF TV arrester is the first of its kind


to have an integrated measuring output for
antenna signals allowing the system to be
easily tested.

DGA

DEHNga
te

SPD FF TV
No. 909
I N 703
U C 2A
24 V

5-2400 MHz

5-3000 MHz

TP

-20 dB

protected

DEHNgate
DGA FF TV

KLASSE

SPD
No. 909 703
IN 2A
UC 24 V

CLASS

signal test for DGA FF TV

Earthing of the surge arresters is different


according to the various designs. For details,
please see the relevant technical data.

EB
cable length
max. 0.5 m
AWG 6/16 mm2
EB
Earthing of DGA AG N and DGA L ...

270

www.dehn.de

909 710
VCD
909 711
VCID

DGA BNC
DGA BNC

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

DEHNgate
DGA BNC VC

DGA BNC VCD


909 710
DGA BNC VCID
909 711

protected

(1 mod.)

DGA BNC VCD


Part No. 909 710

protected

DGA BNC VCID


Part No. 909 711

Dimension drawing DGA BNC VC ...

2-stage protective circuit with low capacitance.


DGA BNC VCD with direct shield earthing and
DGA BNC VCID with indirect shield earthing.

Space-saving surge arrester with BNC socket for mounting on supporting rails for protecting video
and camera systems. Available with direct (VCD) or indirect shield connection (VCID), according to
type, to avoid leakage pickups.

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Nominal current IL
C2 Nominal discharge current (8/20 s) shield-PG In
C2 Nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) line-shield In
Voltage protection level line-shield for In C2 Up
Voltage protection level shield-PG for In C2 Up
Voltage protection level line-shield at 1 kV/s C3 Up
Voltage protection level shield-PG at 1 kV/s C3 Up
Frequency range
Insertion loss
Return loss
Capacitance line-shield C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

Easily adaptable due to BNC sockets


Available with direct or indirect shield
earthing, according to type
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

DGA BNC VCD

DGA BNC VCID

5V
6.4 V
0.1 A
10 kA
5 kA
5 kA
) 35 V

) 13 V

0 - 300 MHz
at 160 MHz ) 0.4 dB
at 130 MHz * 20 dB
) 25 pF
-40C...+80C
IP 10
35 mm DIN rail according to EN 60715
BNC socket / BNC socket
35 mm DIN rail according to EN 60715
zinc die casting
bare
IEC 61643-21
GOST

5V
6.4 V
0.1 A
10 kA
5 kA
5 kA
) 35 V
) 650 V
) 13 V
) 600 V
0 - 300 MHz
at 160 MHz ) 0.4 dB
at 130 MHz * 20 dB
) 25 pF
-40C...+80C
IP 10
35 mm DIN rail according to EN 60715
BNC socket / BNC socket
35 mm DIN rail according to EN 60715
zinc die casting
bare
IEC 61643-21
GOST

DGA BNC VCD


909 710
1 pc(s).

DGA BNC VCID


909 711
1 pc(s).

271

DEHNgate
DGA TV

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION
DGA GFF TV

DGA GFF TV

DGA FF TV

DGA GF TV

909 703
TV
909 704
TV
909 705
TV

DGA FF TV
909 703
DGA GF TV
909 704
DGA GFF TV
909 705

TP
protected

Frequency range for analogue and digital


TV, also suitable for reverse LAN channels
SPDs of type FF and GFF with integrated
measuring output
3 types for adapted use for installation in
conformity with the lightning protection
zones concept at the boundaries from
0A 2 (combined lightning current
and surge arresters of type GFF),
0A 1 (lightning current arresters of
type GF)
1 2 (surge arresters of type FF)

SPD class
Max. continuous operating d.c. voltage UC
Nominal current IL
D1 Lightning impulse current (10/350 s) Iimp
C2 Nominal discharge current (8/20 s) In
Voltage protection level for Iimp D1 UP
Voltage protection level for In C2 UP
Voltage protection level at 1 kV/s C3 UP
Frequency range
Insertion loss
Insertion loss 5 - 862 MHz
Insertion loss 862 - 2400 MHz
Insertion loss 2400 - 3000 MHz
Return loss
Return loss (5 - 8 MHz)
Return loss (8 - 47 MHz)
Return loss (47 - 2400 MHz)
Return loss test socket (5 - 47 MHz)
Test socket connection loss
Shield attenuation 5 - 300 MHz
Shield attenuation 300 - 470 MHz
Shield attenuation 470 - 1000 MHz
Shield attenuation 1000 - 2400 MHz
Impedance Z
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Accessories
Ordering information
Type
Part No.
Packing unit

272

DGA GF TV

DGA FF TV

Schematic diagram of the protective circuit of


DGA GFF TV consisting of lightning current
arrester of type DGA GF TV and terminal
equipment protection DGA FF TV.

Dimension drawing DGA GFF TV Combination


of DGA GF TV and DGA FF TV

DGA ... TV are SPDs with F connector for remote supply for 75 ohm satellite and cable TV systems.
The SPDs fulfil the high shielding requirements of class A according to EN 50083-2. They allow for
space-saving installation into all common TV and satellite applications and are available as lightning current arresters, surge arresters as well as combined lightning current and surge arresters
with integrated measuring output for testing installations.
DGA FF TV

DGA GF TV

DGA GFF TV

H
_

24 V
2A
0.2 kA
1.5 kA
) 230 V
) 300 V
) 60 V
d.c., 5-3000 MHz

1.2 dB
1.4 dB
2 dB
* 14 dB

* 18 dB (-1.5 dB/octave)
* 18 dB
20 dB
* 85 dB
* 80 dB
* 75 dB
* 55 dB
75 ohms
-40C...+80C
IP 30
35 mm DIN rail acc. to EN 60715
or wall mounting
F socket / F socket
DIN rail or screw connection
metal
bare
IEC 61643-21
GOST
2 x F connector

60 V
2A
2.5 kA
10 kA
) 700 V
) 700 V
) 600 V
d.c. - 2400 MHz
0.5 dB

* 18 dB (-1.5 dB/octave) dB

* 85 dB
* 80 dB
* 75 dB
* 55 dB
75 ohms
-20C...+55C
IP 30
earthing bracket
F socket / F connector
earthing bracket with screw connection
metal
bare
IEC 61643-21
GOST
earthing bracket and 2 x F connector

24 V
2A
2.5 kA
10 kA
) 230 V
) 300 V
) 60 V
d.c., 5-2400 MHz

1.7 dB
1.9 dB

* 10 dB
* 14 dB
* 18 dB (-1.5 dB/octave)
* 18 dB
20 dB
* 85 dB
* 80 dB
* 75 dB
* 55 dB
75 ohms
-20C...+55C
IP 30
35 mm DIN rail acc. to EN 60715
or wall mounting
F socket / F socket
DIN rail or screw connection
metal
bare
IEC 61643-21
GOST
2 x F connector

DGA FF TV
909 703
1 pc(s).

DGA GF TV
909 704
1 pc(s).

DGA GFF TV
909 705
1 pc(s).

www.dehn.de

DGA FF
DGA GF
DGA GFF

DEHNgate

929 040
5.6

DGA F 1.6

DGA F 1.6 5.6


929 040

DEHNgate

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

Dimension drawing DGA F

Low-capacitance diode matrix for optimised


transmission performance.

Quickly responding surge arrester for G.703 interfaces. Earthing via enclosure. 1.6/5.6 connector.

DEHNgate
DGA F

For easy retrofitting


For high transmission rates
For installation in conformity with the
lightning protection zones concept at
the boundaries from 1 2 and higher

DGA F 1.6 5.6


SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Nominal current IL
C2 Nominal discharge current (8/20 s) In
Voltage protection level for In C2 UP
Voltage protection level at 1 kV/s C3 UP
Frequency range
Insertion loss
Impedance Z
Capacitance line-shield C
Operating temperature range
Degree of protection
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

W
5V
6V
0.25 A
0.3 kA
) 30 V
) 12 V
d.c. -80 MHz
) 0.2 dB
75 ohms
50 pF
-40C...+80C
IP 20
1.6/5.6 connector / 1.6/5.6 socket
externally via shield earthing
metal
bare
IEC 61643-21
GOST

DGA F 1.6 5.6


929 040
1 pc(s).

273

DEHNgate
DGA G

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

929 042
BNC
929 044

DGA G BNC
929 042
DGA G N
929 044

Minimal dimensions

Built-in coaxial gas discharge tube.

Extremely wide transmission range


For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 1 and higher

SPD class
Max. continuous operating d.c. voltage UC
Nominal current IL
Max. transmission capacity
D1 Lightning impulse current (10/350 s) Iimp
C2 Nominal discharge current (8/20 s) In
Voltage protection level for In C2 UP
Frequency range
Insertion loss
Return loss
Impedance Z
Operating temperature range
Degree of protection
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

274

Dimension drawing
DGA G BNC

Dimension drawing
DGA G N

Surge arrester for remote power supply with integrated gas discharge tube. Especially adapted to
wireless LAN and wireless local loop applications in BNC, N or 1.6/5.6 connectors for bushing
installation.

DGA G BNC

DGA G N

135 V
3.5 A
25 W
1 kA
5 kA
) 500 V
d.c. - 4 GHz
< 0.2 dB
* 20 dB
50 ohms
-40C...+85C
IP 20
BNC socket / BNC connector
bushing 12.9 mm
brass, refined surface with trimetal plating
gold
IEC 61643-21
GOST

135 V
6A
25 W
1 kA
5 kA
) 500 V
d.c. - 5.8 GHz
< 0.2 dB
* 20 dB
50 ohms
-40C...+85C
IP 65
N socket / N connector
bushing 16.2 mm
brass, refined surface with trimetal plating
gold
IEC 61643-21
GOST

DGA G BNC
929 042
1 pc(s).

DGA G N
929 044
1 pc(s).

www.dehn.de

DGA G
DGA G N

DEHNgate
DEHNgate

929 043
BNC
929 045
N
929 057
U

DGA AG BNC
929 043
DGA AG N
929 045
DGA AG U
929 057

DGA AG
DGA AG
DGA AG

DEHNgate
DGA AG

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

DEHNgate
DEHNgate

DGA AG BNC

DGA AG N

DGA AG U

Dimension drawings DGA AG

Replaceable gas discharge tube

Surge arrester suitable for remote supply with replaceable gas discharge tube. Excellent RF service
life due to minimum contact burn-off and large-area contact surface of the gas discharge tube in
a special cage.

SPD class
Max. continuous operating d.c. voltage UC
Nominal current IL
Max. transmission capacity
D1 Lightning impulse current (10/350 s) Iimp
C2 Nominal discharge current (8/20 s) In
Voltage protection level for In C2 UP
Frequency range
Insertion loss
Return loss
Impedance Z
Operating temperature range
Degree of protection
Connection input/output
Earthing via
Enclosure material
Colour
Replaceable gas discharge tube
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

Large surface for connecting gas discharge tubes


Longevity due to minimum contact
burn-off at the inner conductor
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 1 and higher

DGA AG BNC

DGA AG N

DGA AG U

180 V
3.5 A
150 W
5 kA
20 kA
) 750 V
d.c. - 1 GHz
< 0.1 dB
* 20 dB
50 ohms
-40C...+85C
IP 20
BNC socket / BNC connector
bushing 16.1 mm
brass, refined surface with trimetal plating
bare
yes
IEC 61643-21
GOST

180 V
6A
150 W
5 kA
20 kA
) 750 V
d.c. - 2.5 GHz
< 0.2 dB
* 20 dB
50 ohms
-40C...+85C
IP 65
N socket / N connector
bushing 16.1 mm or earthing screw
brass, refined surface with trimetal plating
bare
yes
IEC 61643-21
GOST

180 V
10 A
150 W
5 kA
20 kA
) 750 V
d.c. - 300 MHz
< 0.1 dB
* 20.8 dB
50 ohms
-40C...+85C
IP 20
UHF socket / UHF connector
bushing 19.3 mm
brass, refined surface with trimetal plating
bare
yes
IEC 61643-21
GOST

DGA AG BNC
929 043
1 pc(s).

DGA AG N
929 045
1 pc(s).

DGA AG U
929 057
1 pc(s).

Accessory Part for DEHNgate


Gas discharge tube

929 498
230
929 499
470

Spare gas discharge tube for DEHNgate with lightning current carrying
capability. High quality with especially low capacitance.
Type
Lightning impulse current
carrying capability (10/350 s)
Design

Type
GDT DGA 230

www.dehn.de

GDT DGA
GDT DGA

GDT DGA 230


929 498
GDT DGA 470
929 499

GDT DGA 230


5 kA
H 8 x 6 mm

PU
pc(s).
1

Part
No.
929 498

275

DEHNgate
DGA LG

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

929 046
16
929 446
16 X

DGA LG 7 16
929 046
DGA LG 7 16 X
929 446

NEW

/4

Quarterwave arrester combined with gas discharge tube

For multi-frequency applications with


d.c. power supply
Optionally available with self-extinguishing gas discharge capsule up to
a nominal current of 2.5 A
Maximum transmission and PIM performance
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 1 and higher

DGA LG 7 16 X with self-extinguishing gas discharge capsule with automatic reset function for a
high degree of safety and negligible system downtimes.
DGA LG 7 16

DGA LG 7 16 X

65 V
13 A
500 W
5 kA
20 kA
) 1000 V
d.c., 806 MHz - 2.2 GHz
) 0.15 dB
typically 0.1 dB
* 20 dB
typically 20.0 dB
50 ohms
typically -150 dBc @ 2*43 dBm
-40C...+85C
IP 65
7/16 socket / 7/16 connector
earthing screw
brass, refined surface with trimetal plating
bare
yes
IEC 61643-21
GOST

Ordering information
Type
Part No.
Packing unit

DGA LG 7 16 X
929 446
1 pc(s).

Spare gas discharge tube capable of carrying lightning currents with screw cap for
DEHNgate LG 7 16 X. Self-extinguishing gas capsule with automatic reset function in
case of d.c. feeding currents up to 2.5 A or higher HF performances.

Spare gas discharge tube for DEHNgate with lightning


current carrying capability. High quality with especially
low capacitance.

Also suited for retrofitting DEHNgate LG 7 16 with conventional gas capsule technology (replacement of the complete capsule unit!).

GDT DGA 90
929 497

276

NEW

Gas discharge tube with screw cap

Gas discharge tube

Type

GDT DGA 90

Lightning impulse current


carrying capability (10/350 s)
Design
Integrated into (Part No.)

5 kA
H 8 x 6 mm
929 046

Type
GDT DGA 90

65 V
2.5 A
500 W
5 kA
20 kA
) 1000 V
d.c., 806 MHz - 2.2 GHz
) 0.15 dB
typically 0.1 dB
* 20 dB
typically 20.0 dB
50 ohms
typically -150 dBc @ 2*43 dBm
-20C...+85C
IP 65
7/16 socket / 7/16 connector
earthing screw
brass, surface-coated with trimetal plating
bare
Part No. 929496
IEC 61643-21
GOST

DGA LG 7 16
929 046
1 pc(s).

Zubehr fr DEHNgate
GDT DGA

Dimension drawing
DGA LG 7 16 X

Quarterwave arrester combined with a spark gap suitable for remote supply for multi-frequency
applications (multi-carrier systems) due to minimum passive intermodulation. Broadband device
for all 4+3G services.

SPD class
Max. continuous operating d.c. voltage UC
Nominal current IL
Max. transmission capacity
D1 Lightning impulse current (10/350 s) Iimp
C2 Nominal discharge current (8/20 s) In
Voltage protection level for In C2 UP
Frequency range
Insertion loss
Insertion loss 2176 MHz
Return loss
Return loss 2176 MHz
Impedance Z
Intermodulation
Operating temperature range
Degree of protection
Connection input/output
Earthing via
Enclosure material
Colour
Replaceable gas discharge tube
Test standards
Approvals, Certifications

929 497
90

Dimension drawing
DGA LG 7 16

PU
pc(s).
1

Type
929 496
90 X

NEW
GDT DGA 90 X
929 496

Part
No.
929 497

GDT DGA

Lightning impulse current carrying capability (10/350 s)


Integrated into Part No.
Can be retrofitted into Part No.

Type
GDT DGA 90 X

GDT DGA 90 X
5 kA
929 446
929 046

PU
pc(s).
1

Part
No.
929 496

www.dehn.de

DGA LG 7
DGA LG 7

DEHNgate

929 047
16 S
929 048
16 B

DGA L4 7 16 S
929 047
DGA L4 7 16 B
929 048

DGA L4 7
DGA L4 7

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

DEHNgate
DGA L4

DEHNgate

/4

Dimension drawing
DGA L4 7 16 S

Dimension drawing
DGA L4 7 16 B

Maintenance-free quarterwave SPD without


discrete components.

Combined lightning current and surge arrester with maintenance-free quarterwave technology
with adapted frequency band. The SPDs can also discharge high partial lightning currents. No
remote supply possible as the SPD represents an electrical short circuit for low-frequency signals.

SPD class
Max. continuous operating d.c. voltage UC
Nominal current IL
Max. transmission capacity
D1 Lightning impulse current (10/350 s) Iimp
C2 Nominal discharge current (8/20 s) In
Voltage protection level for In C2 UP
Frequency range
Insertion loss
Return loss
Impedance Z
Intermodulation
Operating temperature range
Degree of protection
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

Maintenance-free combined lightning


current and surge arrester (high discharge capacity and low voltage protection level)
Maximum transmission and PIM performance
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

DGA L4 7 16 S

DGA L4 7 16 B

0V
0V
3000 W
25 kA
50 kA
) 130 V
380 MHz - 512 MHz
< 0.1 dB
* 20 dB
50 ohms

-40C...+85C
IP 65
7/16 socket / 7/16 connector
earthing screw
brass, refined surface with trimetal plating
bare
IEC 61643-21
GOST

0V
0V
1700 W
40 kA
80 kA
) 180 V
880 MHz - 2.2 GHz
< 0.15 dB
* 20 dB
50 ohms
typically -150 dBc @ 2*43 dBm
-40C...+85C
IP 65
7/16 socket / 7/16 connector
earthing screw
brass, refined surface with trimetal plating
bare
IEC 61643-21
GOST

DGA L4 7 16 S
929 047
1 pc(s).

DGA L4 7 16 B
929 048
1 pc(s).

277

DEHNgate
DGA L4 N EB

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

929 059
EB

DGA L4 N EB
929 059

/4

Maintenance-free combined lightning


current and surge arrester, optimised
bandwidth and dimensions
Maximum transmission performance
for WiMax and Wi-Fi applications
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0A 2 and higher

Maintenance-free quarterwave SPD without


discrete components.

Dimension drawing DGA L4 N EB

Especially broadband combined lightning current and surge arrester with maintenance-free quarterwave technology, adapted frequency band for Broadband Wireless Access applications and small
dimensions of the enclosure. No remote supply possible as the SPD represents an electrical short
circuit for low-frequency signals.

DGA L4 N EB
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Nominal current IL
Max. transmission capacity
D1 Lightning impulse current (10/350 s) Iimp
C2 Nominal discharge current (8/20 s) In
Voltage protection level for Iimp D1 UP
Voltage protection level for In C2 UP
Frequency range
Insertion loss
Return loss
Impedance Z
Operating temperature range
Degree of protection
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

278

M
0V
0V
0V
300 W
25 kA
50 kA
) 18 V
) 30 V
2.0 GHz - 6.0 GHz
) 0.2 dB
* 20 dB
50 ohms
-40C...+85C
IP 65
N socket / N socket
bushing 19.3 mm
aluminium
bare
IEC 61643-21
GOST

DGA L4 N EB
929 059
1 pc(s).

www.dehn.de

DGA L4 N

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION
Gas discharge tube
Spare gas discharge tube for DEHNgate with lightning current carrying
capability. High quality with especially low capacitance.
Type

GDT DGA 90

GDT DGA 230

GDT DGA 470

Lightning impulse current


carrying capability (10/350 s)
Design
Integrated into Part No.

5 kA
H 8 x 6 mm
929 046

5 kA
H 8 x 6 mm
929 043, 929 045

5 kA
H 8 x 6 mm

PU
pc(s).
1
1
1

Type
GDT DGA 90
GDT DGA 230
GDT DGA 470

929 497
90
929 498
230
929 499
470

GDT DGA 90
Gasentladungsableiter fr DEHNgate
GDT DGA 230
Gasentladungsableiter fr DEHNgate
GDT DGA 470
Gasentladungsableiter fr DEHNgate

GDT DGA
GDT DGA

Angled fixing plate

929 497

Made of stainless steel, suitable for installation of DEHNgate,


Part No. 929 045 929 048.

929 498

PU
pc(s).
20

929 499

GDT DGA

GDT DGA 90 X
Gasentladungsableiter fr DEHNgate mit Schraubverschluss

929 496

Made of stainless steel, suitable for direct screwing of 3 DEHNgate


devices, Part No. 929 045 929 049, 929 446.

GDT DGA 90 X
5 kA
929 046
929 046

PU
pc(s).
1

NEW
Part
No.
929 496

Type
PAS I 6AP M10 V2A

PU
pc(s).
1

Cable lug with earth conductor


Cable lug with highly flexible black copper earth conductor for earthing
of DEHNgate, Part No. 929 043, 929 044 or 929 045.
PU
pc(s).
1

Type
EL 16 B17

PAS I 6AP M10 V2A


Potentialausgleichsschiene

472 209

416 411

Part
No.
416 411

EL 16 B17
929 096

Part
No.
929 096

Earthing block 4xF

929 095

Four-pole earthing block with F sockets, for equipotential bonding of


satellite cable shields or DGA GF TV lightning current arresters.
Type

PU
pc(s).
1

PAS I 6AP

416 411

Cable lug, 1x open M8/M10 and 1x closed M8, suitable for combination with Part No. 106 310, 106 329 and 472 209.
EL 16 B17

472 209
M10 V2A

Part
No.
472 209

Earth conductor, open / closed cable lugs

929 096

106 329

Part
No.
106 329

Equipotential bonding bars for industrial


installations

Also suited for retrofitting DEHNgate LG 7 16 with conventional gas


capsule technology (replacement of the complete capsule unit!).

Type
GDT DGA 90 X

106 329

Made of stainless steel, with 3 mounting holes for 3 different sizes of


DEHNgate, e. g. 1x 929 042 + 1x 929 057 + 1x (929 043, 929 044,
929 045 or 929 058).

929 496
90 X

106 310

Part
No.
106 310

Angled fixing plate for HF arresters

PU
pc(s).
1

Spare gas discharge tube capable of carrying lightning currents with


screw cap for DEHNgate LG 7 16 X. Self-extinguishing gas capsule with
automatic reset function in case of d.c. feeding currents up to 2.5 A or
higher HF performances.

Lightning impulse current carrying capability (10/350 s)


Integrated into Part No.
Can be retrofitted into Part No.

106 310

GDT DGA

Part
No.
929 497
929 498
929 499

Gas discharge tube with screw cap

Type

Accessories for DEHNgate

EB 4 F

EB 4 F
929 095

EB 4 F

Max. continuous operating d.c. voltage


65 V
D1 Lightning impulse current (10/350 s)
10 kA
Frequency range
d.c. - 2400 MHz

Type
EB 4 F

www.dehn.de

PU
pc(s).
1

Part
No.
929 095

279

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR COAXIAL CONNECTION

280

www.dehn.de

FS / USD
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR D-SUB CONNECTION

Surge protective adapter for easy retrofitting


9-pole, 15-pole or 25-pole shielded types available
Adapter with single-stage (FS) and 2-stage
(USD) protective circuit

Surge protective adapter, D-Sub plug-in connection, socket-pin type.

Surge protective adapter available in a shielded enclosure with D-Sub


plug-in connection, socket-pin type. The UNC screws of the protection for
terminal equipment (FS) can be exchanged in any way. The thread is thus
situated either on the pin or socket side, depending on the application. For

use in switchgear cabinets, the powerful USD surge arrester can be


snapped onto DIN rails. Special types with other pinnings or circuits are
also available.

The surge arresters are available


in three different designs covering the most frequent applications. Due to their small size, they
can be easily integrated into the
cabling.

USD devices can be


snapped onto a DIN rail
which is supposed to discharge surges. Three plugin types are available.

9-pole, 15-pole and 25-pole


FS surge arrester

www.dehn.de

9-pole, 15-pole and 25-pole USD surge arrester

281

FS / USD
FS 9E PB

Adapted to Profibus-DP
Transmission up to 12 MBit/s
For installation in conformity with the
lightning protection zones concept at
the boundaries from 1 2 and higher

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR D-SUB CONNECTION
6

Diode protective circuit with very low capacity.


Pin 6 without protection for the
programming interface.

924 017
6

FS 9E PB

FS 9E PB 6
Surge Protection Adapter FS 6 V

Fine
924 017

Dimension drawing FS 9E PB

9-pole D-Sub, for Profibus-DP applications.

FS 9E PB 6
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
C2 Nominal discharge current (8/20 s) line-line In
C2 Nominal discharge current (8/20 s) line-SG In
C2 Nominal discharge current (8/20 s) SG-PG In
Voltage protection level line-line for In C2 UP
Voltage protection level line-SG for In C2 Up
Voltage protection level SG-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 UC
Voltage protection level line-SG at 1 kV/s C3 Up
Voltage protection level SG-PG at 1 kV/s C3 Up
Cut-off frequency fG
Capacitance line-line C
Capacitance line-SG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Pinning
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

282

[
6V
7V
0.2 kA
0.2 kA
0.4 kA
25 V
25 V
25 V
18 V
18 V
18 V
90 MHz
25 pF
35 pF
-40C...+80C
IP 40
D-Sub (2 threaded screws 4/40 UNC)
D-Sub 9 plug / D-Sub 9 socket
Line: 3/8, SG: 5, PG: 1, 6: unprotected
outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
plastic, metallised
silver
IEC 61643-21
GOST

FS 9E PB 6
924 017
1 pc(s).

www.dehn.de

924 019
12

FS 9E HS

FS 9E HS 12
Surge Protection Adapter FS 12 V

Fine
924 019

FS / USD
FS 9E HS

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR D-SUB CONNECTION
1
2
3
4
5
6
7
8
9

Dimension drawing FS 9E HS

1
2
3
4
5
6
7
8
9

8-pole fine protection to common SG.

All pins protected


Low voltage protection level
For installation in conformity with the
lightning protection zones concept at
the boundaries from 1 2 and higher

9-pole D-Sub. V-24 version with handshake function.

FS 9E HS 12
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
C2 Nominal discharge current (8/20 s) line-SG In
C2 Nominal discharge current (8/20 s) SG-PG In
Voltage protection level line-SG for In C2 Up
Voltage protection level SG-PG for In C2 Up
Voltage protection level line-SG at 1 kV/s C3 Up
Voltage protection level SG-PG at 1 kV/s C3 Up
Cut-off frequency fG
Capacitance line-SG C
Capacitance SG-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Pinning
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

[
12 V
15 V
0.1 kA
0.1 kA
) 24 V
) 200 V
) 21 V
) 90 V
10 MHz
700 pF
350 pF
-40C...+80C
IP 40
D-Sub (2 threaded screws 4/40 UNC)
D-Sub 9 plug / D-Sub 9 socket
line: 1/2/3/4/6/7/8/9, SG: 5
outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
plastic, metallised
silver
IEC 61643-21
GOST

FS 9E HS 12
924 019
1 pc(s).

283

FS / USD
FS 15E

For 4-wire interfaces

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR D-SUB CONNECTION
2

9
4

9
4

11

11

Fine protection for 2 pairs to common SG.

924 016

FS 15E 5

FS 15E 5
Surge Protection Adapter FS 5 V

Fine
924 016

Dimension drawing FS 15E

Low voltage protection level


For installation in conformity with the
lightning protection zones concept at
the boundaries from 1 2 and higher

15-pole D-Sub. RS-422, V.11 version.

FS 15E 5
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
C2 Nominal discharge current (8/20 s) line-SG In
C2 Nominal discharge current (8/20 s) SG-PG In
Voltage protection level line-line for In C2 UP
Voltage protection level line-SG for In C2 Up
Voltage protection level SG-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 UC
Voltage protection level line-SG at 1 kV/s C3 Up
Voltage protection level SG-PG at 1 kV/s C3 Up
Cut-off frequency fG
Capacitance line-line C
Capacitance line-SG C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Pinning
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

284

[
5V
8V
0.2 kA
0.6 kA
) 16 V
) 16 V
) 16 V
) 11 V
) 11 V
) 11 V
4 MHz
1500 pF
1600 pF
1200 pF
-40C...+80C
IP 40
D-Sub (2 threaded screws 4/40 UNC)
D-Sub 15 plug / D-Sub 15 socket
line: 2/9, 4/11, SG: 8, PG: 1
outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
plastic, metallised
silver
IEC 61643-21
GOST

FS 15E 5
924 016
1 pc(s).

www.dehn.de

924 018
12

FS 25E HS

FS 25E HS 12
Surge Protection Adapter FS 12 V

Fine
924 018

FS / USD
FS 25E HS

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR D-SUB CONNECTION

Dimension drawing FS 25E HS

2
3
4
5
6
8
20

2
3
4
5
6
8
20

8-pole fine protection to common SG.

All lines interconnected


Low voltage protection level
For installation in conformity with the
lightning protection zones concept at
the boundaries from 1 2 and higher

25-pole D-Sub. V.24 version with handshake function.

FS 25E HS 12
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
C2 Nominal discharge current (8/20 s) line-SG In
C2 Nominal discharge current (8/20 s) SG-PG In
Voltage protection level line-SG for In C2 Up
Voltage protection level SG-PG for In C2 Up
Voltage protection level line-SG at 1 kV/s C3 Up
Voltage protection level SG-PG at 1 kV/s C3 Up
Cut-off frequency fG
Capacitance line-SG C
Capacitance SG-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Pinning
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

[
12 V
15 V
0.1 kA
0.1 kA
) 24 V
) 200 V
) 21 V
) 90 V
10 MHz
700 pF
350 pF
-40C...+80C
IP 40
D-Sub (2 threaded screws 4/40 UNC)
D-Sub 25 plug / D-Sub 25 socket
line: 2/3/4/5/6/8/20, SG: 7, other lines are unprotected
outgoing earth conductor 0.75 mm2, 0.3 m long (PG)
plastic, metallised
silver
IEC 61643-21
GOST

FS 25E HS 12
924 018
1 pc(s).

285

FS / USD
USD 9 V24

Plug-in surge arrester with 2-stage


protective circuit
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR D-SUB CONNECTION
2

924 061
V24 S B

USD 9

USD 9 V24 S B
Adapter

Cable
924 061

protected

Combination of gas discharge tubes, decoupling


resistors and diodes to PG.

Dimension drawing USD 9 V24

9-pole D-Sub. V.24 version.

USD 9 V24 S B
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
C2 Nominal discharge current (8/20 s) line-PG In
C2 Nominal discharge current (8/20 s) SG-PG In
Voltage protection level line-SG for In C2 Up
Voltage protection level SG-PG for In C2 Up
Voltage protection level line-SG at 1 kV/s C3 Up
Voltage protection level SG-PG at 1 kV/s C3 Up
Series impedance per line
Operating temperature range
For mounting on
Connection input/output
Pinning
Earthing via
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

286

T
12 V
12.5 V
2.5 kA
7.5 kA
) 20 V
) 250 V
) 18 V
) 180 V
15 ohms
-40C...+80C
D-Sub or 35 mm DIN rail acc. to EN 60715
D-Sub 9 plug / D-Sub 9 socket
Line: 2/3, SG: 5
earthing screw or DIN rail
IEC 61643-21
GOST

USD 9 V24 S B
924 061
1 pc(s).

www.dehn.de

924 051
V11 S B

USD 15

USD 15 V11 S B
Adapter

Cable
924 051

FS / USD
USD 15 V11

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR D-SUB CONNECTION
11

11

protected

Dimension drawing USD 15 V11

The resistors at the output of the circuit protect


optocoupler and protective diodes in the terminal
equipment against overloads.

15-pole D-Sub. RS 422, V.11 version.

Plug-in surge arrester with 2-stage


protective circuit
Integrated decoupling of the protective circuit to the terminal equipment
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

USD 15 V11 S B
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
C2 Nominal discharge current (8/20 s) line-PG In
C2 Nominal discharge current (8/20 s) SG-PG In
Voltage protection level line-line/line-SG C2 Up
Voltage protection level SG-PG for In C2 Up
Voltage protection level line-line/line-SG at 1 kV/s C3 Up
Voltage protection level SG-PG at 1 kV/s C3 Up
Series impedance per line
Operating temperature range
For mounting on
Connection input/output
Pinning
Earthing via
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

T
8V
8.5 V
2.5 kA
7.5 kA
) 15 V
) 20 V
) 11 V
) 15 V
37 ohms
-40C...+80C
D-Sub or 35 mm DIN rail acc. to EN 60715
D-Sub 15 plug / D-Sub 15 socket
Line: 2/9/4/11, SG: 8, PG: 1
earthing screw or DIN rail
IEC 61643-21
GOST

USD 15 V11 S B
924 051
1 pc(s).

287

FS / USD
USD 25 V24

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR D-SUB CONNECTION
2
3
4
5
6
8
20

2
3
4
5
6
8
20

924 046
V24 HS S B

USD 25

USD 25 V24 HS S B
Adapter

Cable
924 046

protected

Plug-in surge arrester with 2-stage


protective circuit
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

Combination of gas discharge tubes, decoupling


resistors and diodes to signal ground (SG).

Dimension drawing USD 25 V24

25-pole D-Sub. V.24 version, HS type with handshake function.

USD 25 V24 HS S B
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
C2 Nominal discharge current (8/20 s) line-PG In
C2 Nominal discharge current (8/20 s) SG-PG In
Voltage protection level line-SG for In C2 Up
Voltage protection level SG-PG/line-PG for In C2 Up
Voltage protection level line-SG at 1 kV/s C3 Up
Voltage protection level SG-PG at 1 kV/s C3 Up
Series impedance per line
Operating temperature range
Connection input/output
Pinning
Earthing via
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

288

T
12 V
12.5 V
2.5 kA
7.5 kA
) 20 V
) 250 V
) 18 V
) 180 V
15 ohms
-40C...+80C
D-Sub 25 plug / D-Sub 25 socket
Line: 2/3/4/5/6/8/20, SG: 7, PG: 1
earthing screw or DIN rail
IEC 61643-21
GOST

USD 25 V24 HS S B
924 046
1 pc(s).

www.dehn.de

DSM
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR TERMINAL CONNECTION

SPD for telecommunications equipment


For space-saving flush mounting
Easy installation due to plug-in terminals

Surge arrester for protection of telecommunications equipment for installation into flush-type boxes or small-sized distribution boards. Plug-in terminals at the input.
In a typical installation, DSM surge arresters are integrated into the distribution socket downstream of the socket outlet of the terminal equipment or into the cable duct. This makes them independent from the switch
or box programme and protect, invisibly for the user, telecommunications

systems or devices. Of course, the SPDs can also be integrated into smallsized distribution boards. The use of the removable plug-in terminals
makes the installation of DSM easier. As each plug-in terminal is designed
for four lines, through-wiring of an S0 bus, for example, is possible.

3 4
1 2

5-

6m

l = 500 mm
min. 1.0 mm2

1
50.

DSM is compact enough to allow for


the types to be installed easily even
into small-sized distribution boards
situated in damp rooms.

Prewired cables
The plug-in connectors are prewired.
Through-wiring of the ISDN bus is possible.

www.dehn.de

A
k
5

,5
7

n
is

2
9

P
S

.
o
N

H
W
E
Y

D
R
K
B
d
cte
te
ro

p
->
S 0 PD
S
N
D

Installation Step 1

1
2
a1
3
1
b
4
a2
2
b

IS

Apart from plug-in terminals, delivery also


includes a prewired earth conductor.

UC

K
M S
S
D DN
IS D 270

DSM installed into a surfacemounted distribution board

Delivery (example)

Installation Step 2

Installation Step 3

Connecting DSM ... SK to the


telecommunications box
The lines fixed at DSM are connected to
the telecommunications box and DSM
is placed at the rear panel of the box.
Then, the prewired connectors can be
plugged in.

Final installation
The telecommunications box is inserted
into the mounting panel together with
the DSM surge arrester. Now, only an
adequate cover has to be mounted.

289

DSM
DSM ISDN

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR TERMINAL CONNECTION
1

RD

BK

WH

YE

924 270
SK

DSM ISDN

DSM ISDN SK
telecomm. terminal equipment

SPD for
924 270

protected

Optional through-wiring of the ISDN


bus via plug-in terminals

Energy-coordinated ISDN 4-wire protective circuit


with additional protection of the remote supply.

Dimension drawing DSM ISDN

Integrated protection for the remote


supply
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

For ISDN S0 interfaces. Through-wiring of the ISDN bus possible by means of four-pole terminal.

DSM ISDN SK
SPD class
Nominal voltage UN
Nominal voltage pa-pa UN
Max. continuous operating d.c. voltage UC
Max. continuous operating d.c. voltage pa-pa UC
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 UP
Voltage protection level pa-pa for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Voltage protection level pa-pa at 1 kV/s C3 UP
Series impedance per line
Cut-off frequency fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
Connection input/output
Pinning
Termination diameter, solid
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Accessories
Ordering information
Type
Part No.
Packing unit

290

Q
5V
40 V
7.5 V
45 V
200 mA
20 kA
5 kA
) 30 V
) 600 V
) 180 V
) 17 V
) 600 V
) 100 V
4.7 ohms
4 MHz
) 1.5 nF
) 15 pF
-40C...+80C
IP 20
quad pillar terminals / stranded conductors 0.25 mm2
2 pairs
0.5 - 1.0 mm
flat connector 2.8 mm
polyamide PA 6.6
yellow
IEC 61643-21
GOST
flat connector, earth conductor 500 mm

DSM ISDN SK
924 270
1 pc(s).

www.dehn.de

924 272
SK

DSM TC 2

DSM TC 2 SK
telecomm. terminal equipment

SPD for
924 272

DSM
DSM TC

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR TERMINAL CONNECTION
1

RD

BK

WH

YE

protected

Dimension drawing DSM TC

Energy-coordinated protective circuit, free of leakage currents to earth.

Excellent transmission performance


Also suitable for installation into distribution boards
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

For (system) telephones, Uk0, ADSL, for use with 2 pairs.

DSM TC 2 SK
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Series impedance per line
Cut-off frequency fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
Connection input/output
Pinning
Termination diameter, solid
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Accessories
Ordering information
Type
Part No.
Packing unit

www.dehn.de

R
110 V
170 V
200 mA
20 kA
5 kA
) 275 V
) 600 V
) 220 V
) 600 V
4.7 ohms
17 MHz
) 300 pF
) 10 pF
-40C...+80C
IP 20
quad pillar terminals / stranded conductors 0.25 mm2
2 pairs
0.5 - 1.0 mm
flat connector 2.8 mm
polyamide PA 6.6
yellow
IEC 61643-21
GOST
flat connector, earth conductor 500 mm

DSM TC 2 SK
924 272
1 pc(s).

291

BUStector
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR TERMINAL CONNECTION

Extremely space-saving due to EIB / KNX bus


terminal design
System-tested with EIBA certification
Also suitable for KNX buses

Surge arrester for EIB / KNX buses with connecting leads.


The discharge capacity, protective effect and mechanical design of
BUStector surge arresters is adapted to the installation environment of
EIB / KNX buses. Like a bus terminal it can be plugged onto the bus ter-

292

minal pins of a terminal device and can be wired with the existing connecting cables. It protects especially line and area couplers as well as
gateways and sensors installed at outer walls of buildings.

www.dehn.de

925 001

BT 24

BT 24
925 001

BUStector

BUStector
BT

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR TERMINAL CONNECTION
+

Dimension drawing BT

Heavy-duty gas discharge tube, adapted to the


withstand capability of the equipment of KNX
systems.

Suitable for EIB / KNX systems


Minimum space requirements
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 1 and higher

SPD with the design of a bus terminal. Approved by EIBA.

BT 24
SPD class
Nominal voltage Un
Max. continuous operating d.c. voltage UC
Nominal current IL
C2 Nominal discharge current per line In
Voltage protection level for In C2
Voltage protection level line-PG for In C2
Voltage protection level line-line at 1 kV/s C3
Voltage protection level line-PG at 1 kV/s C3
Cut-off frequency line-line
Capacitance line-line
Capacitance line-PG
Operating temperature range
Degree of protection
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

B
24 V
45 V
6A
5 kA
) 1200 V
) 650 V
) 750 V
) 500 V
70 MHz
) 10 pF
) 10 pF
-40C...+80C
IP 20
spring contacts 1 mm / connecting leads 0.8 mm
lead 0.75 mm2, length 200 mm
thermoplastic
blue
IEC 61643-21
EIBA Certification No. Z 32/1399/95

BT 24
925 001
1 pc(s).

293

AS IBAS
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR TERMINAL CONNECTION

Protects the data line of AS interfaces


No bus address required
Easy installation for use as coupling module

Surge arrester for devices with AS interface connection.

Surge arrester for devices with AS interface connection according to the


requirements of AS interface buses. The surge arresters are adapted to the
installation environment of the bus systems and require no bus address.

Due to the low self-impedance, the grey-coloured coupling module with


integrated surge protection can be inserted even into well-extended bus
segments. In addition, it provides a distribution function for data transmission.

294

www.dehn.de

925 013
YE

AS IBAS

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR TERMINAL CONNECTION

AS IBAS
AS IBAS

AS IBAS YE
925 013

2
3

Dimension drawing of coupling module

The especially low-capacitance protective circuit


hardly stresses the AS interface
(1/6 bus equivalent).

The coupling module protects the yellow data line of the AS interface. In addition, it provides a distribution function. Earthing via DIN rail or plug-in contact.

Also protects ESD and switching peak


voltages
Replaces coupling module with distribution function
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

AS IBAS YE
SPD class
Max. continuous operating d.c. voltage Uc
Nominal current IL
C2 Nominal discharge current (8/20 s) line-line In
C2 Nominal discharge current (8/20 s) line-PG In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Capacitance line-line C
Operating temperature range
Degree of protection for coupling module
For mounting on
Connection input/output
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

T
36 V
0.3 A
0.15 kA
5 kA
) 60 V
) 1100 V
* 50 V
) 900 V
< 13 pF
-40C...+80C
construction with AS interface module IP 67
DIN rail or plane surface
yellow AS interface line
IEC 61643-21
GOST

AS IBAS YE
925 013
1 pc(s).

295

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR TERMINAL CONNECTION

296

www.dehn.de

DEHNpipe
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SCREWABLE SPDs

Maximum protection due to installation into


the cable run
Surges are discharged via the enclosure of the
field device
For nearly all types of two-conductor field
devices with suitable cable gland

Surge arrester for outdoor use to be screwed onto two-conductor field


devices. Stainless steel, IP 67.
DEHNpipe is made of corrosion-resistant stainless steel and is screwed
onto the field device instead of a conventional cable gland. The permanently installed lines are then connected to the terminals of the field
device. Thus the protective components are directly situated in the cable
run. This provides an energy-coordinated surge protection. The SPD pro-

tects the inside of the field device against dangerous overvoltage with the
interfering impulses being discharged via the metal enclosure only and
not via the inside of the field device. Earthing accessories are also available for plastic field enclosures.

DEHNpipe is designed for two-conductor


measuring sensors with 4-20 mA interfaces. The surge arresters provide energycoordinated surge protection for spacelimited field devices in outdoor areas and
reduce installation work.

The universal surge


arrester is even suitable
for applications allowing
only for a single assignment of the terminals of
field devices, or providing
only one terminal for
cable glands.

DPI types

Advantages for installation

installation
1

BK cable (black)
tauten
the cable

transmitter
RD cable (red)

max. 10 Nm
+

receiver
removal
4

www.dehn.de

GNYE cable
(green/yellow)

GNYE

Installation of DPI MD 24 M 2S

Installation of DPI ME 24 N A2G

Due to the two-part design of the SPD, the field cable can be connected
as usual, just like being connected to a measuring sensor.
Thanks to the cable gland a degree of protection of IP 67 is achieved.
DEHNpipe supports common earthing concepts for cable shield treatment
of field cables. Depending on the cable gland used, the cable shield is
earthed directly or indirectly or is not earthed at all. Indirect earthing integrates the shield into the protective concept without leakage pickups.

The type for installation into pipes provides -14 NPT male threads and permanently installed lines. The device is installed as shown in the above figure.

297

DEHNpipe
DPI MD

INFORMATION TECHNOLOGY SYSTEMS


SCREWABLE SPDs

929 941
24 M 2S

DPI MD

DPI MD 24 M 2S
929 941

DEHNpipe

RD

SHL

protected

BK

Easy installation due to 2-part design


Suitable for 3 shielding concepts
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

Energy-coordinated protective circuit, no leakage


currents to earth, with gas discharge tube for
indirect shield earthing.

Dimension drawing DPI MD

For 4-20 mA interfaces with thread M20 x 1.5 (female/male). Direct, indirect or no shield earthing.
Cable gland available as accessory part.

DPI MD 24 M 2S
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current IL
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
C2 Nominal discharge current (8/20 s) shield-PG In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 UP
Voltage protection level shield-PG for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Voltage protection level shield-PG at 1 kV/s C3 UP
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Capacitance shield-PG C
Operating temperature range
Degree of protection
For mounting on the field/device side
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

298

Q
24 V
34.8 V
24.5 V
0.5 A
1 kA
10 kA
10 kA
20 kA
) 65 V
) 650 V
) 650 V
) 50 V
) 500 V
) 600 V
2.2 ohms
14 MHz
) 400 pF
) 20 pF
) 15 pF
-40C ...+80C
IP 67
M20 x 1.5 female thread / M20 x 1.5 male thread
screw/connecting leads 1.5 mm2, length of 200 mm
0.08 - 2.5 mm2
0.08 - 1.5 mm2
enclosure or earthing ring (accessories)
V2A
bare
IEC 61643-21
GOST

DPI MD 24 M 2S
929 941
1 pc(s).

www.dehn.de

929 921
24 N A2G

DPI ME

DPI ME 24 N A2G
929 921

DEHNpipe

DEHNpipe
DPI ME

INFORMATION TECHNOLOGY SYSTEMS


SCREWABLE SPDs

RD

BU

BK

BK
protected

GNYE

Dimension drawing DPI ME

GNYE

Gas discharge tube and diodes,


energy-coordinated to earth.

Robust design
Encapsulated protective circuit
Single-ended type available on
request

For unbalanced interfaces with thread -14 NPT (male/male). Earth conductor led through the
surge arrester.

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0B 2 and higher

DPI ME 24 N A2G
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current IL
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Series impedance per line
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on the field/device side
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

Q
24 V
34.8 V
24.5 V
0.5 A
1 kA
10 kA
10 kA
) 120 V
) 65 V
) 98 V
) 49 V
4.7 ohms
) 250 pF
) 450 pF
-40C...+80C
IP 67
-14 NPT male thread / -14 NPT male thread
connecting leads AWG 16, length of 500 mm
enclosure and connecting lead
V2A
bare
IEC 61643-21
GOST

DPI ME 24 N A2G
929 921
1 pc(s).

299

Accessories for DEHNpipe

INFORMATION TECHNOLOGY SYSTEMS


SCREWABLE SPDs

EMC cable gland


929 982
MS 9.5

KV S M20

KV S M20 MS 9.5
Cable Gland

EMC
929 982

929 984
MS 10.5

KV M20

KV M20 MS 10.5
Cable Gland

EMC
929 984

929 996
M20

ER DPI

ER DPI M20
Earthing Rings for DEHNpipe

Set of
929 996

Brass gland with shield connection.


KV S M20 MS 9.5

For direct shield earthing


Tested with DEHNpipe

Sealing range Rd
Shield diameter
For mounting on
Degree of protection
Material

6.5 - 9.5 mm
3.2 - 6.5 mm
M20 x 1.5
IP 68
nickel-plated brass

Ordering information
Type
Part No.
Packing unit

KV S M20 MS 9.5
929 982
1 pc(s).

Cable gland
Brass gland without shield connection.
KV M20 MS 10.5

No direct shield connection


Tested with DEHNpipe

Sealing range Rd
For mounting on
Degree of protection
Material

7.0 - 10.5 mm
M20 x 1.5
IP 68
nickel-plated brass

Ordering information
Type
Part No.
Packing unit

KV M20 MS 10.5
929 984
1 pc(s).

MS earthing ring
Earthing ring made of nickel-plated brass, for external earthing of DPI.
ER DPI M20
For mounting on
Material

Recommended for mounting


DEHNpipe in an insulating enclosure

300

Ordering information
Type
Part No.
Packing unit

DPI M20 x 1.5


nickel-plated brass

ER DPI M20
929 996
1 pc(s).

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe MD Ex (i)
Surge arrester

Maximum protection due to installation into


the cable run
For all field devices with suitable cable gland
Two-part design for easy installation
Tested according to ATEX and FISCO requirements

Surge arrester for outdoor use to be screwed onto two-conductor field


devices. Stainless steel, installation up to IP 67.
DEHNpipe is made of corrosion-resistant stainless steel and is screwed
onto the field device instead of the conventional cable gland. The permanently installed lines are then connected to the terminals of the field
device. Thus, the protective components are directly situated in the cable
run. This provides an energy-coordinated surge protection. The SPD pro-

tects the inside of the field device against dangerous surges with the
interfering impulses being discharged via the metal enclosure only and
not via the inside of the field device. DEHNpipe MD Ex (i) can be either
used in Ex zone 1 or 2.

DEHNpipe is designed for intrinsically safe


two-conductor measuring sensors with
4-20 mA or Profibus PA interfaces. The
surge arresters provide energy-coordinated surge protection for space-limited field
devices in outdoor areas and reduce
installation work.

The universal surge


arrester covers even applications allowing only single assignment of the terminals of field devices or
providing only one terminal for cable glands.

DPI MD EX

Advantages for installation

mounting
1

Due to the two-part design of the protective device, the field cable can be
connected as usual, like being connected to a measuring sensor.
Thanks to the cable gland a degree of protection of IP 67 is achieved.
DEHNpipe supports common earthing concepts for cable shield treatment
of field cables. Depending on the cable gland used, the cable shield is
earthed directly or is not earthed at all.

max. 10 Nm

removal
4

Installation of DPI MD EX

www.dehn.de

301

DEHNpipe MD Ex (i)
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

EC-Type Examination Certificate DPI MD EX

302

www.dehn.de

929 960
EX 24 M 2

DPI MD

DPI MD EX 24 M 2
929 960

DEHNpipe

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe MD Ex (i)
DPI MD EX

RD
protected
BK

Dimension drawing DPI MD EX

Low-capacitance, energy-coordinated protective circuit with an insulation resistance > 500 V to earth.

Easy installation due to two-part


design
Self-capacitance and self-inductance
negligibly small

Surge arrester for protecting intrinsically safe measuring circuits and bus systems, meets FISCO
requirements. Cable gland must be ordered separately.

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0B 2 and higher

DPI MD EX 24 M 2
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage UC
Max. input voltage acc. to EN 50020 Ui
Max. input current acc. to EN 50020 Ii
Nominal current IL
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on field/device side
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Earthing via
Enclosure material
Colour
Test standards
Ex certifications
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

T
24 V
34.8 V
24.5 V
30 V
0.5 A
0.5 A
1 kA
10 kA
5 kA
) 55 V
) 1100 V
) 49 V
) 1000 V
1.8 ohms
7 MHz
) 850 pF
) 15 pF
-40C...+80C
IP 67
M20 x 1.5 female thread / M20 x 1.5 male thread
screw / connecting leads 1.5 mm2, length of 200 mm
0.08 - 2.5 mm2
0.08 - 1.5 mm2
enclosure
V2A
bare
IEC 61643-21
ATEX: KEMA 09ATEX0122 X: II 2 (1) G Ex ia IIC T4 ... T6
GOST

DPI MD EX 24 M 2
929 960
1 pc(s).

303

Accessories for DEHNpipe MD Ex (i)

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

EMC cable gland

929 982
MS 9.5

KV S M20

KV S M20 MS 9.5
Cable Gland

EMC
929 982

Brass gland with shield connection.


KV S M20 MS 9.5

For direct shield earthing


Tested with DEHNpipe

Sealing range Rd
Shield diameter
For mounting on
Degree of protection
Material

6.5 - 9.5 mm
3.2 - 6.5 mm
M20 x 1.5
IP 68
nickel-plated brass

Ordering information
Type
Part No.
Packing unit

KV S M20 MS 9.5
929 982
1 pc(s).

Cable gland
929 984
MS 10.5

KV M20

KV M20 MS 10.5
Cable Gland

EMC
929 984

Brass gland without shield connection.


KV M20 MS 10.5

No direct shield connection


Tested with DEHNpipe

304

Sealing range Rd
For mounting on
Degree of protection
Material

7.0 - 10.5 mm
M20 x 1.5
IP 68
nickel-plated brass

Ordering information
Type
Part No.
Packing unit

KV M20 MS 10.5
929 984
1 pc(s).

www.dehn.de

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe CD Ex (i)
Surge arrester

Economical SPD for field devices with spare


cable gland
Easy to retrofit and extremely space-saving
Tested according to ATEX and FISCO requirements

Surge arrester for outdoor use to be screwed onto two-conductor field


devices. Stainless steel, installation up to a degree of protection of IP 67.

DEHNpipe C is made of corrosion-resistant stainless steel and is screwed


directly onto the field device. Like a field cable, the permanently installed
lines are connected to the terminals of the field device. Thus, the protective
components are situated in parallel to the cable run. The connection with
the metal or plastic enclosures can be carried out easily as the earth wire
of the protective device can be connected to the earth terminal of a field
device.

A degree of protection of IP 67 can be achieved due to the design of the


surge arrester.
Intrinsically safe surge arresters are typically used in 4-20 mA measuring
circuits or bus systems up to 30 V. According to the type used, DEHNpipe C
is designed for measuring sensors with M20 x 1.5 or -14 NPT cable gland
connections. DEHNpipe CD Ex (i) can be either installed in Ex zones 1 or 2.

EC-Type Examination Certificate DPI CD Ex(i)

www.dehn.de

305

DEHNpipe CD Ex (i)
DPI CD EXI

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

929 961
EXI 24 M
929 963
EXI 24 N

DPI CD EXI 24 M
929 961
DPI CD EXI 24 N
929 963

RD

BK
GNYE

Easy installation on field devices with


spare cable gland

Low-capacitance protective circuit with an


insulation strength > 500 V to earth.

Dimension drawing DPI CD EXI 24 M

Self-capacitance and self-inductance


negligibly small
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Max. input voltage acc. to EN 50020 Ui
Max. input current acc. to EN 50020 Ii
Nominal current IL
D1 lightning impulse current (10/350 s) line-PG Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) line-line In
C2 Nominal discharge current (8/20 s) line-PG In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on field/device side
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Ex certifications
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

306

Surge arrester for protecting intrinsically safe measuring circuits and bus systems, meets FISCO
requirements.

DPI CD EXI 24 M

DPI CD EXI 24 N

24 V
32 V
22.6 V
30 V
0.55 A
0.55 A
1 kA
10 kA
150 A
10 kA
) 58 V
) 1700 V
) 50 V
) 1200 V
67 MHz
) 25 pF

24 V
32 V
22.6 V
30 V
0.55 A
0.55 A
1 kA
10 kA
150 A
10 kA
) 58 V
) 1700 V
) 50 V
) 1200 V
67 MHz
) 25 pF

) 15 pF
-40C...+80C
design in IP 67
M20 x 1.5 male thread
connecting leads 1.3 mm2, length of 250 mm
connecting lead
V4A
bare

) 15 pF
-40C...+80C
design in IP 67
-14 NPT male thread
connecting leads 1.3 mm2, length of 250 mm
connecting lead
V4A
bare

IEC 61643-21
ATEX: KEMA 04ATEX1189 X: II 2 (1) G Ex ia IIC T5 ... T6
GOST

IEC 61643-21
ATEX: KEMA 04ATEX1189 X: II 2 (1) G Ex ia IIC T5 ... T6
GOST

DPI CD EXI 24 M
929 961
1 pc(s).

DPI CD EXI 24 N
929 963
1 pc(s).

www.dehn.de

DPI CD
DPI CD

DEHNpipe
DEHNpipe

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNpipe CD Ex (d)
Surge arrester

Economical SPD for field devices with spare


cable gland or field bus distributors in hazardous areas
Easy to retrofit and extremely space-saving
ATEX certification

Surge arrester for outdoor use to be screwed onto two-conductor field


devices. Stainless steel. Installation up to a degree of protection of IP 67.
The flameproof DEHNpipe C surge arrester is made of corrosion-resistant
stainless steel and is directly screwed onto the field device. Like a field
cable, the permanently installed lines are connected to the terminals of
the field device. Thus, the protection components are situated in parallel
to the cable run. The device can be easily installed into metal or plastic
field enclosures as the earth wire of the protective device can be connected to the earth terminal of a field device.

A degree of protection of IP 67 can be achieved due to the design of the


surge arrester. These flameproof SPDs are typically used in 4-20 mA measuring circuits or bus systems up to 30 V. According to the type used,
DEHNpipe C is designed for measuring sensors with M20 x 1.5 or -14
NPT cable gland connection. DEHNpipe CD Ex (d) can be either installed
in Ex zone 1 or 2.

EC-Type Examination Certificate DPI CD Ex (d)

www.dehn.de

307

DEHNpipe CD Ex (d)
DPI CD EXD

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

929 962
EXD 24 M
929 964
EXD 24 N

DPI CD

DPI CD EXD 24 M
929 962
DPI CD EXD 24 N
929 964

DEHNpipe

RD

BK
GNYE

Easy installation on the spare cable


gland of field devices

Low-capacitance protective circuit with an


insulation resistance > 500 V to earth.

Dimension drawing DPI CD EXD 24 M

Type Ex(d) for universal use


For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current IL
D1 Lightning impulse current (10/350 s) line-PG Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on field/device side
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Ex certifications
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

308

Flameproof surge arrester for use in potentially explosive atmospheres for protecting measuring
circuits and bus systems.

DPI CD EXD 24 M

DPI CD EXD 24 N

24 V
32 V
22.6 V
0.55 A
1 kA
10 kA
10 kA
) 58 V
) 1700 V
) 50 V
) 1200 V
67 MHz
) 25 pF
) 15 pF
-40C...+80C
design in IP 67

24 V
32 V
22.6 V
0.55 A
1 kA
10 kA
10 kA
) 58 V
) 1700 V
) 50 V
) 1200 V
67 MHz
) 25 pF
) 15 pF
-40C...+80C
design in IP 67

M20 x 1.5 male thread


connecting leads 1.3 mm2, length of 250 mm
connecting lead
V4A
bare
IEC 61643-21
ATEX: KEMA 04ATEX2190 X: II 2 G Ex d IIC T5 or T6
GOST

-14 npt male thread


connecting leads 1.3 mm2, length of 250 mm
connecting lead
V4A
bare
IEC 61643-21
ATEX: KEMA 04ATEX2190 X: II 2 G Ex d IIC T5 or T6
GOST

DPI CD EXD 24 M
929 962
1 pc(s).

DPI CD EXD 24 N
929 964
1 pc(s).

www.dehn.de

DPI CD

DEHNpipe

929 971

DPI CD HF EXD 5 M

DEHNpipe CD Ex (d)
DPI CD HF EXD

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

NEW

DPI CD HF EXD 5 M
929 971

approx.
300

M20 x 1.5

SW27

RD

75
BU
GNYE
BK

55

Dimension drawing DPI CD HF EXD 5 M

BN

Low-capacitance, energy-coordinated protective


circuit.

Easy installation on the spare cable


gland of field devices
Ex (d) version for a variety of applications

Flameproof surge arrester for use in potentially explosive atmospheres for protecting measuring
circuits and bus systems.

For installation in conformity with the


lightning protection zones concept at
the boundaries from 0B 2 and higher

DPI CD HF EXD 5 M
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current at 80 C IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on field/device side
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Ex certifications
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

www.dehn.de

T
5V
6V
4.2 V
0.1 A
20 kA
10 kA
) 55 V
) 1000 V
) 12 V
) 700 V
4.7 ohms
100 MHz
) 40 pF
) 30 pF
-40C...+80C
design in IP 67
M20 x 1.5 male thread
connecting cables 1.3 mm2, length of 300 mm
connecting cable
V4A
bare
IEC 61643-21
ATEX: KEMA 04ATEX2190 X: II 2 G Ex d IIC T5 or T6
GOST

DPI CD HF EXD 5 M
929 971
1 pc(s).

309

DEHNpipe CD Ex (d)
DPI CD EXD 230 24

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

929 969
929 970

Available by mid 2010


NEW

BK

DPI CD EXD 230 24 M


929 969
DPI CD EXD 230 24 N
929 970

GN/YE

M20 x 1.5

BL

SW27

120 V /
230 V

63

RD
24 V
BR

Dual surge protection for 120/230 V


power supplies and 0/4-20 mA interfaces
Easy installation on field devices with
a spare cable gland
Increased safety due to distinctive Y
circuit for 120/230 V power supplies
Protection for the data side
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Nominal current at 80 C IL
D1 Lightning impulse current (10/350 s) line-PG Iimp
C2 Total nominal discharge current (8/20 s) In
Voltage protection level line-line for In C2 UP
Voltage protection level line-PG for In C2 UP
Voltage protection level line-line at 1 kV/s C3 UP
Voltage protection level line-PG at 1 kV/s C3 UP
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on field/device side
Connection input/output
Earthing via
Enclosure material
Colour
Test standards
Approvals, Certifications
Protection for the power side

Basic circuit diagram DPI CD EXD 230 24 M/N

II 2 G Ex... version can be used for all


types of applications
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

approx.
250

Dimension drawing DPI CD EXD 230 24 M/N

Flameproof surge arrester for use in potentially explosive areas for protecting 120/230 V terminal equipment and 0/4-20 mA interfaces
ATEX certification (Ex d IIC T5 or T6) pending

DPI CD EXD 230 24 M

DPI CD EXD 230 24 N

24 V
32 V
22.6 V
0.55 A
1 kA
10 kA
58 V
900 V
50 V
850 V
25 pF
15 pF
-40C...+80C
design in IP 67
M20 x 1.5 male thread
connecting leads 1.3 mm2, length of 250 mm
connecting lead
V4A
bare
IEC 61643-21
GOST

24 V
32 V
22.6 V
0.55 A
1 kA
10 kA
58 V
900 V
50 V
850 V
25 pF
15 pF
-40C...+80C
design in IP 67
-14 NPT male thread
connecting leads 1.3 mm2, length of 250 mm
connecting lead
V4A
bare
IEC 61643-21
GOST

DPI CD EXD 230 24 M

DPI CD EXD 230 24 N

SPD according to EN 61643-11


SPD according to IEC 61643-1
Nominal a.c. voltage UN
Maximum continuous operating a.c. voltage Uc
Max. discharge current L-N Imax
Nominal discharge current (8/20 s) In
Total discharge current (8/20) L+N-PE Itotal
Voltage protection level L-N Up
Voltage protection level L/N-PE Up
Max. supply-side overcurrent protection
Short-circuit current withstand capability in case
of supply-side overcurrent protection with 16 A gL/gG
TOV L-N UT
TOV L/N-PE (1) UT
TOV L/N-PE (2) UT
Indication of the disconnection device

Type 2
Class II
120/230 V
255 V
3 kA
3 kA
5 kA
1.4 kV
1.5 kV
16 A gL/gG or B 16 A

Type 2
Class II
120/230 V
255 V
3 kA
3 kA
5 kA
1.4 kV
1.5 kV
16 A gL/gG or B 16 A

6 kArms
335 V/5 sec
400 V/5 sec
1200 V+U0 /200 ms
upstream fuse element

6 kArms
335 V/5 sec
400 V/5 sec
1200 V+U0 /200 ms
upstream fuse element

Ordering information
Type
Part No.
Packing unit

DPI CD EXD 230 24 M


929 969
1 pc(s).

DPI CD EXD 230 24 N


929 970
1 pc(s).

310

83

www.dehn.de

DPI CD EXD 230 24 M


DPI CD EXD 230 24 N

BLITZDUCTOR XT Ex (i)
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

Effective protection with minimum space


requirements
For use with 2-pole, 3-pole or 4-pole intrinsically safe interfaces
Function-optimised design for safe handling
and easy installation
Quick testing of LifeCheck-equipped SPD modules
ATEX approval, FISCO

Pluggable, multipole, universal surge arrester for use in intrinsically safe


systems with integrated LifeCheck monitoring device.

BLITZDUCTOR XT EX is a pluggable, four-pole, universal DIN rail mounted


surge arrester designed for the most stringent requirements on the availability of intrinsically safe measuring and control circuits and bus systems.
With regard to intrinsic safety, the SPD is considered earth-free and its
self-inductance and self-capacitance are negligibly small. The high
impulse current discharge capacity (min. 10x) and the low voltage protection level are supported by the low-impedance design of the device.
LifeCheck allows for quick and easy testing of SPDs. However, the SPD
modules may only be read out by means of the hand-held DRC LC reader
in non-explosive atmospheres.
Integrated into the SPD modules, LifeCheck permanently monitors the

proper condition of the SPD. Like an early warning system, LifeCheck reliably detects potential electrical and thermal overloads of the protection
components. The LifeCheck status can be read out within a matter of seconds by means of DEHNrecord LC via contactless RFID technology and
also shows the date of the last test of the SPD module. A stationary condition monitoring system allows status-oriented maintenance of 10 BXT.
To ensure safe operation, the SPD provides protection against vibration
effects and shock up to a 30-fold acceleration of gravity. The functionoptimised design of the devices allows both quick and easy replacement
of SPD modules which house all relevant protection elements. The SPD
module and the base part must be ordered separately.

Completely installed BLITZDUCTOR XT EX.


Two-part design with universal base part
and application-specific SPD module.
Particularly space-saving, for DIN rail
mounting.

Universal base part accommodates all


types of SPD modules. The SPD modules
can be easily removed from the base part
without signal interruption thereby minimising storage requirements as well as
prewiring and maintenance operations.

Base part

BLITZDUCTOR XT EX

Dimension drawing of a BLITZDUCTOR XT


EX base part with plugged-in SPD module.
Width: 2/3 mods. (12 mm), for use in distribution boards with DIN rails.

Dimension drawing

www.dehn.de

3 basic types

BXT ML4 BD EX 24:


Universal LifeCheck-equipped SPD module
for 2 intrinsically safe circuits such as 4-20
mA, HART, PROFIBUS-PA, FF, NAMUR.
BXT ML4 BC EX 24:
For protection of e.g. 3-wire or 4-wire temperature measuring systems.
BXT ML2 BD HF EX 6:
Protection of a pair for fast data transmission and a feeding currents up to 4.8 A.

311

BLITZDUCTOR XT Ex (i)
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

EC-Type Examination Certificate BXT EX

312

www.dehn.de

920 301
EX

BXT BAS

BLITZDUCTOR XT Ex (i) Base Part


BXT BAS EX

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS
2
4

BXT BAS EX
920 301

BXT BAS

2
4
1234

1
3

protected

4 3 21

1
3

BXT ML4...
2
4

2
4
BXT BAS

1 2 3 4

4 3 2 1

1
3

1
3

Dimension drawing BXT BAS EX

protected

Basic circuit diagram with and without


plugged-in module

BLITZDUCTOR XT base part for use as very space-saving, four-pole, universal feed-through terminal for intrinsically safe circuits for the insertion of SPD modules without signal interruption. The
snap-in mechanism at the supporting foot of the base part allows the device to be safely earthed
via the DIN rail. As no components of the protective circuit are situated in the base part, maintenance operation is only required for the protection modules.

Four-pole and universal device for all


types of intrinsically safe SPD modules
Insertion and removal without signal
interruption
Universal design without protection
components

BXT BAS EX
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Tightening torque (terminals)
Earthing via
Enclosure material
Colour
Ex certifications
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

BXT BAS EX
920 301
1 pc(s).

Clear identification of the


protected side for
faultless installation

Leading/retarded make-before-break
switch contacts for uninterrupted
removal and insertion without downtime

Module release spring


for removing the protection
module without problems

The earthing foot ensures costeffective installation. No additional


earth connection is required since the
device is safely earthed via the DIN rail

Lightning current carrying


laminated contacts

Reverse polarity protection prevents


incorrect insertion of the protection
module

Designation space
for marking the circuits

www.dehn.de

-50C...+80C
IP 20
35 mm DIN rail acc. to EN 60715
screw / screw
0.08 - 4 mm2
0.08 - 2.5 mm2
0.4 Nm
35 mm DIN rail acc. to EN 60715
polyamide PA 6.6
blue
ATEX: KEMA 06ATEX0274 X: II 2 (1) G Ex ia IIC T4 ... T6
CSA, GOST

High-quality, four-pole screw terminals


for the following cross-sections:
stranded: 2.5 mm2
solid:
4 mm2

313

BLITZDUCTOR XT Ex (i) LifeCheck Modules INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS
BXT ML4 BD EX 24

920 381
BD EX 24

BXT ML4 BD EX 24
920 381

protected

For universal use, with LifeCheck SPD


monitoring function
Self-capacitance and self-inductance
negligibly small
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

The RFID chip of the LifeCheck SPD monitoring


device can be read out without contact via
DEHNrecord LC. Insulation resistance > 500 V
line-earth.

Dimension drawing BXT ML4 BD EX

Space-saving LifeCheck-equipped surge arrester module for protecting 2 pairs in intrinsically safe
measuring circuits and bus systems, meets FISCO requirements.
BXT ML4 BD EX 24

SPD class
SPD monitoring
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Max. input voltage acc. to EN 60079-11 Ui
Max. input current acc. to EN 60079-11 Ii
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection (plugged-in)
For plugging into
Earthing via
Enclosure material
Colour
Test standards
SIL classification
Ex certifications
Approvals, Certifications

T
LifeCheck
24 V
33 V
23 V
30 V
0.5 A
4 kA
1 kA
20 kA
5 kA
50 V
1300 V
52 V
1400 V
45 V
1100 V
1.0 ohm
7.7 MHz
0.8 nF
16 pF
-40C...+80C
IP 20
base part
base part
polyamide PA 6.6
blue
IEC 61643-21, UL 497B
SIL2 / SIL3 for more details see: www.dehn.de/en/sil/
ATEX: KEMA 06ATEX0274 X: II 2 (1) G Ex ia IIC T4 ... T6
CSA, GOST

Ordering information
Type
Part No.
Packing unit
920 301
EX

BXT BAS EX
920 301

BXT BAS

BXT ML4 BD EX 24
920 381
1 pc(s).

BXT BAS EX

910 695
MCM XT

Base part for use as a feed-through terminal in


intrinsically safe circuits for the insertion of
SPD modules without signal interruption.
Type
BXT BAS EX

PU
Part
pc(s).
No.
1
920 301

DRC MCM XT
910 695

DRC

DRC MCM XT

910 653
M3

DIN rail mounted device with integrated


LifeCheck sensor for status-oriented monitoring of max. 10 BXT devices with LifeCheck
function.
Type
DRC MCM XT

DRC LC M3
Ableiterprfgert LifeCheck

PU
Part
pc(s).
No.
1
910 695

DRC LC

910 653

DRC LC M3+
Portable device with LifeCheck sensor for
flexible use. For fast and easy testing of
LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 313/317/318/319/360/362.

314

www.dehn.de

BXT ML4

920 384
BC EX 24

BXT ML4

INFORMATION TECHNOLOGY SYSTEMS BLITZDUCTOR XT Ex (i) LifeCheck Modules


SPDs FOR POTENTIALLY EXPLOSIVE AREAS
BXT ML4 BC EX 24

BXT ML4 BC EX 24
920 384

protected

Dimension drawing BXT ML4 BC EX

The RFID chip of the LifeCheck SPD monitoring


device can be read out without contact via
DEHNrecord LC. Insulation resistance > 500 V
line-earth.

Space-saving LifeCheck-equipped surge arrester module for protecting up to 4 earth-potential-free


single lines with common reference potential in intrinsically safe circuits, meets FISCO requirements.

For multi-wire measuring systems,


with LifeCheck SPD monitoring device
Self-capacitance and self-inductance
negligibly small
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

BXT ML4 BC EX 24
SPD class
SPD monitoring
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Max. input voltage acc. to EN 60079-11 Ui
Max. input current acc. to EN 60079-11 Ii
D1 Total lightning impulse current (10/350 s) Iimp
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection (plugged-in)
For plugging into
Earthing via
Enclosure material
Colour
Test standards
SIL classification
Ex certifications
Approvals, Certifications

T
LifeCheck
24 V
33 V
23.3 V
30 V
0.5 A
4 kA
1 kA
20 kA
5 kA
53 V
1300 V
55 V
1400 V
45 V
1100 V
1 ohm
6.4 MHz
0.8 nF
16 pF
-40C...+80C
IP 20
base part
base part
polyamide PA 6.6
blue
IEC 61643-21, UL 497B
SIL2 / SIL3 for more details see: www.dehn.de/en/sil/
ATEX: KEMA 06ATEX0274 X: II 2 (1) G Ex ia IIC T4 ... T6
CSA, GOST

Ordering information
Type
Part No.
Packing unit
Test / Disconnection Module

BXT ML4 BC EX 24
920 384
1 pc(s).

920 309

BXT M4 T

Module for testing lines, to be plugged into


the BLITZDUCTOR XT base part.
Type
BXT M4 T

PU
Part
pc(s).
No.
1
920 309

Earthing module
For direct earthing of lines connected to the
BLITZDUCTOR XT base part.

BXT M4 T
/Trennmodul

BXT-Prf920 309

Type
BXT M4 E

PU
Part
pc(s).
No.
1
920 308

920 308

BXT M4 E

BXT M4 E
Erdungsmodul

BXT920 308

Partition

910 697
MCM EX

TW DRC

TW DRC MCM EX
Trennwand f. DRC MCM

Ex i910 697

For DRC MCM XT


Type
TW DRC MCM EX

PU
Part
pc(s).
No.
1
910 697

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 313/317/318/319/360/362.
www.dehn.de

315

BLITZDUCTOR XT Ex (i) LifeCheck Modules INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS
BXT ML2 BD HF EX 6
NEW

920 538

BXT ML2 BD HF EX 6
920 538

protected

Universal use, with LifeCheck SPD


monitoring device
Self-capacitance and self-inductance
negligibly small
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

The RFID chip of the LifeCheck SPD monitoring


device can be read out without contact via
DEHNrecord LC. Insulation strength
> 500 V line-earth.

Dimension drawing BXT ML2 BD HF EX 6

Space-saving LifeCheck-equipped surge arrester module for protecting 1 pair in intrinsically safe
measuring circuits and RS485 bus systems.
BXT ML2 BD HF EX 6

SPD class
SPD monitoring
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Max. input voltage acc. to EN 60079-11 Ui
Max. input current acc. to EN 60079-11 Ii
Max. input current acc. to EN 60079-11
(without protection module only up to 60C) Ii
D1 Lightning impulse current (10/350 s) per line Iimp
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for Iimp D1 Up
Voltage protection level line-PG for Iimp D1 Up
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection (plugged-in)
For plugging into
Earthing via
Enclosure material
Colour
Test standards
SIL classification
Ex certifications

T
LifeCheck
6V
6V
4.2 V
4.2 V
4.8 A
4.8 A
1 kA
10 kA
5 kA
35 V
1600 V
35 V
1800 V
20 V
1400 V
100 MHz
25 nF
20 pF
-40C...+80C
IP 20
base part
base part
polyamide PA 6.6
blue
IEC 61643-21
SIL2 for more details see: www.dehn.de/en/sil/
ATEX: KEMA 06ATEX0274 X: II 2 G Ex ib IIC T4 ... T6

Ordering information
Type
Part No.
Packing unit

920 301
EX

BXT BAS EX
920 301

BXT BAS

BXT ML2 BD HF EX 6
920 538
1 pc(s).

BXT BAS EX

910 695
MCM XT

Base part for use as a feed-through terminal in


intrinsically safe circuits for the insertion of
SPD modules without signal interruption.
Type
BXT BAS EX

PU
Part
pc(s).
No.
1
920 301

DRC MCM XT
910 695

DRC

DRC MCM XT

910 653
M3

DIN rail mounted device with integrated


LifeCheck sensor for status-oriented monitoring of max. 10 BXT devices with LifeCheck
function.
Type
DRC MCM XT

DRC LC M3
Ableiterprfgert LifeCheck

PU
Part
pc(s).
No.
1
910 695

DRC LC

910 653

DRC LC M3+
Portable device with LifeCheck sensor for
flexible use. For fast and easy testing of
LifeCheck-equipped arresters.
Type
DRC LC M3+

PU
Part
pc(s).
No.
1
910 653

For further technical details about Accessories for BLITZDUCTOR XT LifeCheck modules please also refer to pages 313/317/318/319/360/362.

316

www.dehn.de

BXT ML2 BD HF EX 6

920 308

BXT M4 E

INFORMATION TECHNOLOGY SYSTEMS Accessories for BLITZDUCTOR XT Ex (i)


SPDs FOR POTENTIALLY EXPLOSIVE AREAS
Earthing module

BXT M4 E
920 308

protected

Dimension drawing BXT M4 E

Basic circuit diagram BXT M4 E

The plugged-in earthing module short-circuits all lines connected to the BLITZDUCTOR XT base part
to PG. It directly earths initially used cable cores, which are already connected to the base part.

For plugging onto BLITZDUCTOR XT


base parts
Easy handling
Quick replacement when retrofitting
an SPD module

BXT M4 E
D1 Total lightning impulse current (10/350 s) Iimp
Operating temperature range
Degree of protection (plugged-in)
For plugging into
Enclosure material
Colour
Ordering information
Type
Part No.
Packing unit

920 398

10 kA
-40C...+80C
IP 20
base part
polyamide PA 6.6
grey

BXT M4 E
920 308
1 pc(s).

Marking system BA1-BA15

BS BA1 BA15 BXT

NEW
BS BA1 BA15 BXT
920 398

For DRC MCM XT condition monitoring systems


2 x 165 adhesive labels for labelling DRC MCM XT monitoring devices with their bus address
(BA1 to BA15) and BXT base parts or modules with consecutive numbers (1.1-1.10 to 15.1-15.10)

Abrasion-proof
Pre-printed
Transparent

BS BA1 BA15 BXT


Dimension W x H
Ordering information
Type
Part No.
Packing unit

www.dehn.de

13 x 7 mm

BS BA1 BA15 BXT


920 398
1 pc(s).

317

Accessories for BLITZDUCTOR XT Ex (i) INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS
Test / Disconnection Module

920 309

BXT M4 T

BXT M4 T
920 309

For plugging into the BLITZDUCTOR XT


base part
Easy maintenance and troubleshooting
Measuring lines included

Basic circuit diagram BXT M4 T

Dimension drawing BXT M4 T

The plugged-in test/disconnection module interrupts the cable run of the lines connected to the
BLITZDUCTOR XT base part and leads them to a test socket at the front side of the module. This
allows to carry out measurements in the installation without removing the lines from the base part.

BXT M4 T
Max. continuous operating d.c. voltage UC
Max. continuous operating a.c. voltage UC
Nominal current at 80 C IL
Volume resistance
Operating temperature range
Degree of protection (plugged-in)
For plugging into
Test sockets
Enclosure material
Colour
Accessories
Ordering information
Type
Part No.
Packing unit

180 V
127 V
1.0 A
0.1 ohm
-40C ... +80C
IP 20
base part
gold-plated, 1 mm
polyamide PA 6.6
grey
2 measuring lines (1 m), protective bag

BXT M4 T
920 309
1 pc(s).

Marking system 1-50

920 399

BS 1 50 BXT
920 399

Abrasion-proof
Pre-printed

Plate with 2 plate numbers from 1 to 50 for attaching to BXT base parts or modules.

BS 1 50 BXT
Dimension W x H

11 x 4 mm

Ordering information
Type
Part No.
Packing unit

BS 1 50 BXT
920 399
1 pc(s).

318

www.dehn.de

BS 1 50 BXT

910 697

TW DRC MCM EX

INFORMATION TECHNOLOGY SYSTEMS Accessories for BLITZDUCTOR XT Ex (i)


SPDs FOR POTENTIALLY EXPLOSIVE AREAS
Partition
NEW

TW DRC MCM EX
910 697

2.5

76

90

137

Dimensional drawing of the partition

For DRC MCM XT


Certain installation instructions have to be observed when using Blitzductor XT Ex (i) surge protective
devices in intrinsically safe circuits.
In accordance with EN 60079-11;2007 a minimum distance (thread measure) of * 50 mm has to be
maintained between intrinsically and non-intrinsically safe circuits (connecting parts, e.g. terminals)!
When using the Ex i partition of type TW DRC MCM EX, this distance is also maintained if the surge
protective devices are arranged directly next to one other.

Allows non-intrinsically circuits to be


placed directly next to Ex i circuits
(space gain)
Increase of the thread measure to
* 50 mm in accordance with
EN 60079-11
Suitable for mounting rails with
a height of 7.5 mm and 15 mm
Easy installation by simply snapping
the partition onto a mounting rail

TW DRC MCM EX
Material
Colour
For mounting on
Ordering information
Type
Part No.
Packing unit

www.dehn.de

polyamide PA 6.6
blue
35 mm DIN rail according to EN 60715

TW DRC MCM EX
910 697
1 pc(s).

319

ITAK Ex (i)
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

Prewired unit
Built-in SPD, tested according to ATEX and FISCO
requirements
Further customised versions available on request

Example: ITAK for use in intrinsically safe circuits.

ITAK stands for the German designation InformationstechnikAnschaltkasten [English: switchbox for information technology systems].
Generally, ITAKs are a combination of enclosure, SPDs and terminals or
shield terminals. These switchboxes can be produced according to cus-

320

tomer specifications. Our standard product range includes e.g. ITAK EXI
BXT 24, a combination of ALGA 5 X enclosure and BXT BD EX 24 for protecting two intrinsically safe measuring circuits in outdoor systems.

www.dehn.de

989 408
BXT 24

ITAK EXI

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

ITAK EXI BXT 24


989 408

Dimension drawing ITAK EXI BXT

ITAK Ex (i)
ITAK EXI BXT

The RFID chip of the LifeCheck SPD monitoring


system can be read out without contact via
DEHNrecord LC. Insulation resistance
> 500 V line-earth.

BXT ML4 BD EX 24 and BXT BAS EX Completely mounted, meets FISCO requirements.

Prewired unit for 2 Ex(i) circuits


Self-capacitance and self-inductance
negligibly small
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B - 2 and higher

ITAK EXI BXT 24


SPD class
SPD monitoring system
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. input voltage acc. to EN 50020 Ui
Max. input current acc. EN 50020 Ii
Total nominal discharge current (8/20 s) In
Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 UP
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Cross-sectional area of equipotential bonding
Tightening torque (terminal)
Earthing via
Enclosure material
Test standards for installed BXT
Approvals, Certifications for installed BXT
Ordering information
Type
Part No.
Packing unit

T
LifeCheck
24 V
33 V
30 V
0.5 A
20 kA
5 kA
) 52 V
) 1400 V
) 45 V
) 1100 V
1.0 ohm
7.7 MHz
0.8 nF
-40C...+80C
IP 65
wall in Ex zones 1, 2
cable gland M20 x 1.5
0.08 - 4 mm2
0.08 - 2.5 mm2
4 mm2
0.4 Nm
screw terminal at enclosure panel
grey aluminium
IEC 61643-21, UL 497B
ATEX, CSA

ITAK EXI BXT 24


989 408
1 pc(s).

Accessory Part for ITAK Ex (i)


Mounting set

906 059
5X

MS ALGA

For ALGA 5 X enclosures for fixing at masts and pipes.


Type
MS ALGA 5 X

www.dehn.de

Enclosure
material
StSt

PU
pc(s).
1

Part
No.
906 059

MS ALGA 5 X
Set for Enclosures

Mounting
906 059

321

DEHNconnect RK Ex (i)
Terminal block with integrated
surge protection

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

Extremely space-saving (only 6 mm in width)


Spring pressure connection system
Tested by KEMA according to ATEX and FISCO
requirements

6 mm two-pole terminal block with integrated surge protection and cage


clamp terminal. Earthing via DIN rail or terminal.

DEHNconnect RK MD EX is a 6 mm terminal block with integrated surge


protection for intrinsically safe circuits. 2 lines can be protected with the
5 cage clamp spring measuring connections and additional equipotential
bonding to the terminal equipment can be established. The snap-in fixing

mechanism at the supporting foot of the base part allows the arrester to
be safely earthed via the DIN rail. As the enclosure of the arrester is open
to one side to minimise the width, it is advisable to use a cover plate at
the end of each terminal block.

application
Zones 1, 2

DEHNconnect RK EX 24

DCO RK MD EX with cover

cable length max. 1m


min. 4 mm2

min. 4 mm

Zone 0

EB
Application in an Ex(i) circuit

322

www.dehn.de

919 960
MD EX 24

DCO RK

DCO RK MD EX 24
DEHNconnect RK 24 V EX

919 960

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

DEHNconnect RK Ex (i)
DCO RK MD EX

4
OUT

IN

Dimension drawing DCO RK MD EX

Low-capacitance, energy-coordinated protective


circuit with an insulation resistance > 500 V to
earth.

Surge arrester for protecting intrinsically safe measuring circuits and bus systems, meets FISCO
requirements.

For universal use


Self-capacitance and self-inductance
negligibly small
For installation in conformity with the
lightning protection zones concept at
the boundaries from 0B 2 and higher

DCO RK MD EX 24
SPD class
Nominal voltage UN
Max. continuous operating d.c. voltage Uc
Max. continuous operating a.c. voltage Uc
Max. input voltage acc. to EN 50020 Ui
Max. input current acc. to EN 50020 Ii
Nominal current IL
C2 Total nominal discharge current (8/20 s) In
C2 Nominal discharge current (8/20 s) per line In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PG for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PG at 1 kV/s C3 Up
Series impedance per line
Cut-off frequency line-line fG
Capacitance line-line C
Capacitance line-PG C
Operating temperature range
Degree of protection
For mounting on
Connection input/output
Cross-sectional area, solid
Cross-sectional area, flexible
Earthing via
Enclosure material
Colour
Test standards
Ex certifications
Approvals, Certifications

T
24 V
33 V
23 V
30 V
0.5 A
0.5 A
10 kA
5 kA
) 50 V
) 1500 V
) 45 V
) 1400 V
1.8 ohms
6 MHz
) 1 nF
) 6 pF
-40C...+80C
IP 00, with cover IP 20
35 mm DIN rail acc. to EN 60715
spring / spring
0.08 - 2.5 mm2
0.08 - 2.5 mm2
DIN rail / terminal
polyamide PA 6.6
blue
IEC 61643-21
ATEX: KEMA 09ATEX0124 X: II 2 (1) G Ex ia IIC T4 ... T6
GOST

Ordering information
Type
Part No.
Packing unit

DCO RK MD EX 24
919 960
1 pc(s).

Accessory Part for DEHNconnect RK Ex (i)

Accessory Part for DEHNconnect RK Ex (i)

Quick marking system, horizontal imprint

919 977
DCO RK

BS 1 50

Plate with 2 plate numbers from 1 to 50 for DCO RK, horizontal imprint
Type
BS 1 50 DCO RK

www.dehn.de

Material
plastic

PU
pc(s).
1

Part
No.
919 977

Covering plate

919 978
RK BL

AD DCO

AD DCO RK BL
Plate for DCO, blue

Covering
919 978

For DCO RK
BS 1 50 DCO RK
Marking System for DCO RK

Quick
919 977

Type
Enclosure material
AD DCO RK BL polyamide PA 6.6

Colour
blue

PU
pc(s).
1

Part
No.
919 978

323

DEHNconnect RK Ex (i)
Terminal block with integrated
surge protection

INFORMATION TECHNOLOGY SYSTEMS


SPDs FOR POTENTIALLY EXPLOSIVE AREAS

EC-Type Examination Certificate for DCO RK MD EX

324

www.dehn.de

Shield Connection on Anchor Bars


INFORMATION TECHNOLOGY SYSTEMS
ACCESSORIES FOR TERMINAL BLOCK SYSTEMS
Tested with lightning impulse currents up to
10 kA (10/350 s)
Corrosion-resistant stainless steel material
Permanent shield connection due to spring element

Shield connection system for anchor bars which is capable of carrying


lightning currents. The yield of the cable materials used is compensated
by a slipping spring element.

Shield connection system, tested with lightning currents, for specific use
on anchor bars. As, in the course of time, the conductor materials are subject to a yield, this yield is compensated by a slipping spring element. The
shield connection of the rail types can also be installed using adequate
insulating elements after isolating it from local potential.

This very robust shield connection


system is particularly suited for
cables with medium-sized diameters. It has been tested with lightning currents and was approved
for nuclear installations.

Application on anchor bars

www.dehn.de

325

Shield Connection on Anchor Bars


INFORMATION TECHNOLOGY SYSTEMS
Shield terminals
ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Compensates the yield of cable


materials

Lightning impulse current capacity (10/350 s)


Clamping range Rd
Material
Spring pressure
For mounting on
Dimension W x L x H
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

SAK 10 AS V4A
SAK 14 AS V4A
SAK 18 AS V4A
SAK 21 AS V4A
SAK 26 AS V4A
SAK 33 AS V4A

SAK 10 AS V4A
stainless steel, Rd 5-10
SAK 14 AS V4A
stainless steel, Rd 8-14
SAK 18 AS V4A
stainless steel, Rd 13-18
SAK 21 AS V4A
stainless steel, Rd 17-21
SAK 26 AS V4A
stainless steel, Rd 19-26
SAK 33 AS V4A
stainless steel, Rd 25-33

Shielding Terminal,
308 403
Shielding Terminal,
308 404
Shielding Terminal,
308 405
Shielding Terminal,
308 406
Shielding Terminal,
308 407
Shielding Terminal,
308 408

Dimension drawing SAK

System for anchor bars which is capable of carrying lightning currents


Shield support with large surface

308 403
308 404
308 405
308 406
308 407
308 408

Shield terminals for earthing cable shields on anchor bars. Suitable for lightning equipotential
bonding purposes. Allows for subsequent use without interrupting the cable shield no tools
required for installation. Approved for use in nuclear facilities with TV test certificate ETL 10/PB
301/97 (TV = German Technical Inspectorate).
SAK 10 AS V4A

SAK 14 AS V4A

SAK 18 AS V4A

SAK 21 AS V4A

SAK 26 AS V4A

SAK 33 AS V4A

10 kA
5 - 10 mm
StSt
21 - 27 N
anchor bar
16 x 40 x 48 mm
ETL 10/PB 301/97

10 kA
8 - 14 mm
StSt
30 - 76 N
anchor bar
19.5 x 40 x 50 mm
ETL 10/PB 301/97

10 kA
13 - 18 mm
StSt
34 - 73 N
anchor bar
24 x 40 x 56 mm
ETL 10/PB 301/97

10 kA
17 - 21 mm
StSt
30 - 63 N
anchor bar
29 x 40 x 59 mm
ETL 10/PB 301/97

10 kA
19 - 26 mm
StSt
90 - 124 N
anchor bar
36.5 x 40 x 74 mm
ETL 10/PB 301/97

10 kA
25 - 33 mm
StSt
76 - 137 N
anchor bar
45 x 40 x 82 mm
ETL 10/PB 301/97

SAK 10 AS V4A
308 403
10 pc(s).

SAK 14 AS V4A
308 404
10 pc(s).

SAK 18 AS V4A
308 405
10 pc(s).

SAK 21 AS V4A
308 406
10 pc(s).

SAK 26 AS V4A
308 407
10 pc(s).

SAK 33 AS V4A
308 408
10 pc(s).

Anchor bar

Can be cut to length according to


requirements

308 421
1000 V2A

AS SAK

AS SAK 1000 V2A


Bar, stainless steel, 1 m long

Anchor
308 421

Dimension drawing AS SAK 1000 V2A

Mounting rail for earthing and fixing the shield terminals.

AS SAK 1000 V2A


Material
Dimension W x L x H
Approvals, Certifications

StSt
29 x 1000 x 15 mm
ETL 10/PB 301/97

Ordering information
Type
Part No.
Packing unit

AS SAK 1000 V2A


308 421
10 pc(s).

326

www.dehn.de

308 425
SAK K

ST AS

ST AS SAK K
Support, plastic

Bar
308 425

Shield Connection on Anchor Bars


INFORMATION TECHNOLOGY SYSTEMS
Insulated busbar support
ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Dimension drawing ST AS SAK K

Non-conductive connection of mounting plate and anchor bar

Busbar support for insulated fixing of the AS SAK 1000 V2A anchor bar, with M4 threaded socket.

Equipotential bonding via AK 16 AS


SAK MS terminal

ST AS SAK K
Material
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

308 411
SAK MS

plastic
ETL 10/PB 301/97

ST AS SAK K
308 425
10 pc(s).

AK 16 AS

Terminal
AK 16 AS SAK MS
Conductor Terminal, -16 mm3

Protective
308 411

Dimension drawing AK 16 AS SAK MS

Space-saving
2 fixing screws for conductor included

For connecting equipotential bonding conductors to AS SAK 1000 V2A anchor bars.

AK 16 AS SAK MS

www.dehn.de

Cross-sectional area, solid


For mounting on
Approvals, Certifications

16 mm2
anchor bar
ETL 10/PB 301/97

Ordering information
Type
Part No.
Packing unit

AK 16 AS SAK MS
308 411
5 pc(s).

327

Shield Connection on DIN Rails

INFORMATION TECHNOLOGY SYSTEMS


ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Tested with lightning impulse currents up to


5 kA (10/350 s)
Corrosion-resistant stainless steel material
Permanent shield connection with spring element

Shield connection system with lightning current carrying capability, particularly suited for smaller cables, for DIN rails with slipping spring element
for compensating the yield of the cable materials.

Shield connection system, tested with lightning currents, for versatile


applications in DIN rail installations. Suitable especially for smaller cable
diameters such as bus cables. As, in the course of time, the conductor

328

materials are subject to a yield, this is compensated by a slipping spring


element. The shield connection of the rail types can also be installed using
adequate insulating elements after isolating it from local potential.

www.dehn.de

919 010
SN MS
919 011
SN MS

SAK 6.5

SAK 6.5 SN MS
Terminal round wire 1,5-6,5
SAK 11 SN MS
Terminal 5-B42211

Shielding
919 010
Shielding
919 011

SAK 11

INFORMATION TECHNOLOGY SYSTEMS


ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Shield Connection on DIN Rails


Shield terminals

Dimension drawing SAK

Lightning current carrying system for


busbars

Shield terminals for earthing cable shields on busbars (18x3). Suitable for lightning equipotential
bonding purposes. Allows for subsequent use without interruption of the cable shield no tools
required for installation.

Lightning impulse current capacity (10/350 s)


Clamping range Rd
Material
Spring pressure
For mounting on
Dimension W x L x H
Ordering information
Type
Part No.
Packing unit

919 016
CU 1000

SN 18X3

SN 18X3 CU 1000
tinned

Busbar,
919 016

Shield support with large surface


Compensates the yield of cable materials

SAK 6.5 SN MS

SAK 11 SN MS

5 kA
1.5 - 6.5 mm
nickel-plated brass
8 - 13 N
SN 18x3 CU 1000
10 x 25 x 40 mm

5 kA
5 - 11 mm
nickel-plated brass
22 - 31 N
SN 18x3 CU 1000
17 x 25 x 47 mm

SAK 6.5 SN MS
919 010
10 pc(s).

SAK 11 SN MS
919 011
10 pc(s).

Busbar

Dimension drawing SN 18X3 CU 1000

Can be cut to length according to


requirements

Mounting rail for shield terminals. Can be mounted onto the busbar supports.

Can be mounted onto busbar supports

SN 18X3 CU 1000

www.dehn.de

Material
For mounting on
Dimension W x L x H

tin-plated copper
bar holder
18 x 1000 x 3 mm

Ordering information
Type
Part No.
Packing unit

SN 18X3 CU 1000
919 016
1 pc(s).

329

Shield Connection on DIN Rails


Rail support

Extremely space-saving

INFORMATION TECHNOLOGY SYSTEMS


ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Dimension drawing SH1 18X3 ST

919 012
ST
919 013
ST

SH1 18X3

SH1 18X3 ST
Holder, steel
SH2 18X3 ST
Holder ISO

Bar
919 012
Bar
919 013

SH2 18X3

Dimension drawing SH2 18X3 ST

With one or two shield terminals


For 35 mm DIN rails acc. to EN 60715

Version
Material
For mounting on
Ordering information
Type
Part No.
Packing unit

Rail support for earthed construction, suitable for DIN rail mounting. Low-impedance connection
of the shield terminals to the DIN rail via the busbar.

SH1 18X3 ST

SH2 18X3 ST

1 shield terminal
tin-plated steel
35 mm DIN rail acc. to EN 60715

2 shield terminals
tin-plated steel
35 mm DIN rail acc. to EN 60715

SH1 18X3 ST
919 012
1 pc(s).

SH2 18X3 ST
919 013
1 pc(s).

Insulated rail support

SH 18X3

SH 18X3 K
Holder, plastic

Bar
919 014

Dimension drawing SH 18X3 K

No conductive connection from busbar to DIN rail


Equipotential bonding via AK 35 SN
18X3 GG terminal

919 014
K

Rail support for insulated installation, for DIN rail mounting or screw connection.

SH 18X3 K
Material
Colour
For mounting on
Ordering information
Type
Part No.
Packing unit

330

plastic
black
DIN rail or mounting plate

SH 18X3 K
919 014
10 pc(s).

www.dehn.de

919 015
18X3 GG

AK 35 SN 18X3 GG
for Busbar

AK 35 SN

INFORMATION TECHNOLOGY SYSTEMS


ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Shield Connection on DIN Rails


Terminal

Terminal
919 015

Wide cross-sectional area

Dimension drawing AK 35 SN 18X3 GG

Particularly suited for insulated busbar constructions, e.g. for indirect shield earthing.

For insulated shield construction with


SH 18X3 K

AK 35 SN 18X3 GG
Cross-sectional area, solid
For mounting on
Ordering information
Type
Part No.
Packing unit

www.dehn.de

35 mm2
busbar

AK 35 SN 18X3 GG
919 015
1 pc(s).

331

Shield Connection for Cables

INFORMATION TECHNOLOGY SYSTEMS


ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Tested with lightning impulse currents up to


10 kA (10/350 s)
Extremely space-saving
Permanent shield connection with spring element

Extremely space-saving shield connection system for use as constant


force spring. A spring element compensates the yield of the cable materials used.

The shields of incoming IT and power supply lines can be contacted by


means of constant force springs of type SA KRF in a space-saving way and
with lightning current carrying capability. As, in the course of time, the

conductor materials are subject to a yield, this can be compensated by a


spring element. For permanent corrosion protection of the clamping point,
it is wrapped with a self-bonding SKB rubber tape.

Test certificate for constant force spring of type SA KRF ...

332

www.dehn.de

919 031
10 V2A
919 032
15 V2A
919 033
22 V2A
919 034
29 V2A
919 035
37 V2A
919 036
50 V2A
919 037
70 V2A
919 038
94 V2A

SA KRF
SA KRF
SA KRF
SA KRF
SA KRF

INFORMATION TECHNOLOGY SYSTEMS


ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

Shield Connection for Cables


Constant force spring

SA KRF
SA KRF
SA KRF

SA KRF 10 V2A
Force Spring for shield connection
SA KRF 15 V2A
Force Spring for shield connection
SA KRF 22 V2A
Force Spring for shield connection
SA KRF 29 V2A
Force Spring for shield connection
SA KRF 37 V2A
Force Spring for shield connection
SA KRF 50 V2A
Force Spring for shield connection
SA KRF 70 V2A
Force Spring for shield connection
SA KRF 94 V2A
Force Spring for shield connection

Contact
919 031
Contact
919 032
Contact
919 033
Contact
919 034
Contact
919 035
Contact
919 036
Contact
919 037
Contact
919 038

For solderless connection of a conductor to the shield


For use with all plastic and leadsheathed cables

Constant force springs allow solderless shield connections for equipotential bonding or lightning
equipotential bonding. They can be installed subsequently without interrupting the conductor
shield or requiring tools for installation. Approved for nuclear installations according to TV
Certificate No. T12-04-ETL003 (TV = German Technical Inspectorate).

SA KRF ...

919 030
9M SW

SKB 19

SKB 19 9M SW
Selfbonding Rubber Tape

919 030

Lightning impulse current


capacity (10/350 s)
Clamping range Rd
Material
Colour
For mounting on
Approvals, Certifications
Ordering information
Type
Part No.
Packing unit

Also suitable for steel-reinforced


lead-sheathed cables

10 V2A

15 V2A

22 V2A

29 V2A

37 V2A

50 V2A

70 V2A

94 V2A

10 kA

10 kA

10 kA

10 kA

10 kA

10 kA

10 kA

10 kA

4 - 10 mm
StSt
bare
cable shield
T12-04-ETL 003

9 - 15 mm
StSt
bare
cable shield
T12-04-ETL003

14 - 22 mm
StSt
bare
cable shield
T12-04-ETL003

18.5 - 29 mm
StSt
bare
cable shield
T12-04-ETL003

23.5 - 37 mm
StSt
bare
cable shield
T12-04-ETL003

31 - 50 mm
StSt
bare
cable shield
T12-04-ETL003

44 - 70 mm
StSt
bare
cable shield
T12-04-ETL003

58 - 94 mm
StSt
bare
cable shield
T12-04-ETL003

SA KRF 10 V2A
919 031
20 pc(s).

SA KRF 15 V2A
919 032
20 pc(s).

SA KRF 22 V2A
919 033
20 pc(s).

SA KRF 29 V2A
919 034
10 pc(s).

SA KRF 37 V2A
919 035
10 pc(s).

SA KRF 50 V2A
919 036
25 pc(s).

SA KRF 70 V2A
919 037
20 pc(s).

SA KRF 94 V2A
919 038
10 pc(s).

Self-bonding rubber tape

Roll with 9 m self-bonding rubber tape for


wrapping around constant force springs for
permanent corrosion protection.

Self-bonding
Flexible

SKB 19 9M SW

www.dehn.de

Colour
Dimension W x L x H

black
tape: 9 m x 19 mm

Ordering information
Type
Part No.
Packing unit

SKB 19 9M SW
919 030
1 pc(s).

333

Enclosure / Protective Conductor Terminal INFORMATION TECHNOLOGY SYSTEMS


Aluminium enclosure
ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

906 055

ALGA 5
Aluminium Enclosure IP65

DIN rail integrated


Different types available on request

ALGA 5

906 055

Dimension drawing of aluminium enclosure

For installing DIN rail mounted devices. With


2 brass glands PG 11.
ALGA 5

Degree of protection
For mounting on
Dimension W x H x D
Installation space

IP 65
wall
100 x 200 x 81 mm
6 mods.

Enclosure material

aluminium

Ordering information
Type
Part No.
Packing unit

ALGA 5
906 055
1 pc(s).

906 058

ALGA 5 X

ALGA 5 X
Aluminium Enclosure IP65 for BCT

906 058

Aluminium enclosure for Ex(i) surge arresters

DIN rail integrated


All cables entering from below

Dimension drawing of aluminium enclosure for


Ex(i) surge arresters

With 4 plastic glands M20 x 1.5, sealable,


pressure compensating membrane.
ALGA 5 X
Degree of protection
For mounting on
Dimension W x H x D
Installation space
Enclosure material

IP 65
wall
160 x 100 x 85 mm
6 mods., DIN 43880
aluminium

Ordering information
Type
Part No.
Packing unit

ALGA 5 X
906 058
1 pc(s).

334

www.dehn.de

906 059
5X

MS ALGA

MS ALGA 5 X
Set for Enclosures

Mounting
906 059

INFORMATION TECHNOLOGY SYSTEMS Enclosure / Protective Conductor Terminal


Mounting set
ACCESSORIES FOR TERMINAL BLOCK SYSTEMS

For ALGA 5 X enclosures for fixing at masts


and pipes.

Stainless steel
For rough environmental conditions

MS ALGA 5 X
For mounting on
Enclosure material
Ordering information
Type
Part No.
Packing unit

910 099

mast, pipe for diameters 25 - 140 mm


StSt

MS ALGA 5 X
906 059
1 pc(s).

SLK 16

Protective conductor terminal


SLK 16
Terminal

PE
910 099

Dimension drawing of protective conductor terminal

With lightning current carrying capability

For installing DIN rail mounted devices. For


earthing DIN rails, width: 12 mm.
SLK 16
Cross-sectional area, flexible
Cross-sectional area, solid
For mounting on
Enclosure material
Ordering information
Type
Part No.
Packing unit

www.dehn.de

6 - 16 mm2
6 - 25 mm2
DIN rail acc. to EN 60715
green-yellow polyamide 6.6

SLK 16
910 099
1 pc(s).

335

336

www.dehn.de

DEHNprotector
Surge arrester

INFORMATION TECHNOLOGY SYSTEMS


COMBINED ADAPTERS

Surge protective adapter with a modern design


for quick retrofitting
Easy integration of the power supply and data
side of a terminal device into equipotential
bonding

Combined surge protective adapter for plugging into earthed socket outlets, with visual operating state and fault indication.
The SPDs of the Protector family for plugging into earthed socket outlets
protect consumers with additional data interfaces. Surges will be discharged via the PE pin of the socket outlet. The plug-in installation makes

TAE/F

retrofitting of SPDs easier. The surge protection of the power supply side
provides a visual operating state and fault indicator to facilitate maintenance.

ISDN S0
RJ 45

socket outlet
earth contact

socket outlet with


earth contact

ISDN
fax / telephone

telephone
systems
or
router
PROTECTOR

PROTECTOR

TAE/F
NTBA
or
splitter

Application of DPRO 230 NT

LAN

socket outlet with


earth contact

Application of DPRO 230 ISDN

socket outlet with


earth contact

PC

TV

TV

PROTECTOR

PROTECTOR

Application of DPRO 230 LAN100

Application of DPRO 230 TV

Note
For further types of surge protective adapters for protecting the mains
supply of electronic devices please also refer to pages 138 140.

www.dehn.de

337

DEHNprotector
DPRO 230 TV

INFORMATION TECHNOLOGY SYSTEMS


COMBINED ADAPTERS
Protection for the data side

Protection for TV or radio applications with a modern design


Adapter for F sockets to IEC terminals
included
For installation in conformity with the
lightning protection zones concept at
the boundaries from 2 3 and higher
Combined surge protection for power and
antenna sides of TV, radio or video systems.
With visual operating state and fault indication.

L/N

red
PE

green

L'/N'
PE
N'/L'

N/L

Protection for the data side: A gas discharge tube


discharges potential surges to PE.

DPRO 230 TV

SPD class
Max. continuous operating d.c. voltage UC
C2 Nominal discharge current (8/20 s) line-shield (PE) In
Voltage protection level line-shield (PE) at 1 kV/s C3 Up
Insertion loss 0-2400 MHz
Operating temperature range
Degree of protection
Connection input / output
Earthing via
Enclosure material
Colour
Test standards
Protection for the power side

DPRO 230 SE TV

909 300
TV

DPRO 230 TV
909 300

B
60 V
5 kA
) 600 V
) 1.5 dB
-25C...+40C
IP 20
F socket / F socket
protective conductor connection
thermoplastic, UL 94 V-2
pure white
IEC 61643-21

DPRO 230 TV

DPRO 230 SE TV

SPD according to EN 61643-11


Type 3
SPD according to IEC 61643-1
Class III
Nominal a.c. voltage UN
230 V
Max. continuous operating a.c. voltage Uc
255 V
Nominal load current IL
16 A
Nominal discharge current (8/20 s) L-N In
3 kA
Nominal discharge current (8/20 s) L/N-PE In
5 kA [(L+N)-PE]
Combined impulse (1.2/50 s - 8/20 s) L-N Uoc
6 kV
Combined impulse (1.2/50 s - 8/20 s) L/N-PE Uoc
10 kV [(L+N)-PE]
Voltage protection level L-N Up
) 1.25 kV
Voltage protection level L/N-PE Up
) 1.5 kV
Response time L-N tA
) 25 ns
Response time L/N-PE tA
) 100 ns
Max. mains-side overcurrent protection
16 A gL/gG or B 16 A
Short-circuit withstand capability
for max. mains-side overcurrent protection
6 kArms a.c.
Temporary overvoltage (TOV) L-N UT
335 V/5 sec
Temporary overvoltage (TOV) L/N-PE (1) UT
400 V/5 sec
Temporary overvoltage (TOV) L/N-PE (2) UT
1200 V+U0 /200 ms
Fault indication
red light
Operating state indication
green light
For mounting on
plug-in system with
centre earthing contact system
earth contact
according to CEE 7,
DIN 49440/DIN 49441
standard sheet V
Test standards
IEC 61643-11
Ordering information
Type
Part No.
Packing unit

DPRO 230 TV
909 300
1 pc(s).

DPRO 230 SE TV
909 305
1 pc(s).

Dimension drawing DPRO TV

338

www.dehn.de

DPRO 230

909 310
NT

DPRO 230

INFORMATION TECHNOLOGY SYSTEMS


COMBINED ADAPTERS
Protection for the data side

DPRO 230 NT
909 310

DPRO 230 NT

SPD class
Max. continuous operating d.c. voltage UC
C2 Nominal discharge current (8/20 s) per line C2 In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PE for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PE at 1 kV/s C3 Up
Cut-off frequency line-line fG
Operating temperature range
Degree of protection
Connection input / output
Pinning
Earthing via
Enclosure material
Colour
Test standards
Protection for the power side

DEHNprotector
DPRO 230 NT
DPRO 230 SE NT

R
180 V
2.5 kA
) 300 V
) 500 V
) 300 V
) 500 V
50 MHz
-25C...+40C
IP 20
RJ12 socket / RJ12 socket
3/4
protective conductor connection
thermoplastic, UL 94 V-2
pure white
IEC 61643-21

DPRO 230 NT

DPRO 230 NT
909 310
1 pc(s).

Includes accessories, suitable for RJ


11/12 and TAE connections
For installation in conformity with the
lightning protection zones concept at
the boundaries from 2 3 and higher

DPRO 230 SE NT

SPD according to EN 61643-11


Type 3
SPD according to IEC 61643-1
Class III
Nominal a.c. voltage UN
230 V
Max. continuous operating a.c. voltage Uc
255 V
Nominal load current IL
16 A
Nominal discharge current (8/20 s) L-N In
3 kA
Nominal discharge current (8/20 s) L/N-PE In
5 kA [(L+N)-PE]
Combined impulse (1.2/50 s - 8/20 s) L-N Uoc
6 kV
Combined impulse (1.2/50 s - 8/20 s) L/N-PE Uoc
10 kV [(L+N)-PE]
Voltage protection level L-N Up
) 1.25 kV
Voltage protection level L/N-PE Up
) 1.5 kV
Response time L-N tA
) 25 ns
Response time L/N-PE tA
) 100 ns
Max. mains-side overcurrent protection
16 A gL/gG or B 16 A
Short-circuit withstand capability
for max. mains-side overcurrent protection
6 kArms a.c.
Temporary overvoltage (TOV) L-N UT
335 V/5 sec
Temporary overvoltage (TOV) L/N-PE (1) UT
400 V/5 sec
Temporary overvoltage (TOV) L/N-PE (2) UT
1200 V+U0 /200 ms
Fault indication
red light
Operating state indication
green light
For mounting on
plug-in system with
centre earthing contact system
earth contact
according to CEE 7,
DIN 49440/DIN 49441
standard sheet V
Test standards
IEC 61643-11
Ordering information
Type
Part No.
Packing unit

Protection for a telecommunication


terminal device with a modern design

Combined surge protection for power and


data sides of a digital network termination
(NT). Also suitable for telephones and fax
machines. With visual operating state and
fault indication.

L/N

red
green

PE

L'/N'
PE
N'/L'

N/L
3

4
2

4
2

Protection for the data side: Also suitable for


digital interfaces due to low-capacitance circuit
design

DPRO 230 SE NT
909 315
1 pc(s).

Dimension drawing DPRO NT

www.dehn.de

339

DEHNprotector
DPRO 230 ISDN

INFORMATION TECHNOLOGY SYSTEMS


COMBINED ADAPTERS
Protection for the data side

Protection of ISDN or Ethernet applications with a modern design


Shielded patch cable (1.5 m) included
For installation in conformity with the
lightning protection zones concept at
the boundaries from 2 3 and higher
Combined surge protection for the power
and ISDN S0 side of ISDN systems and devices. Shielded port allows for protection of
Ethernet 10 BT. With visual operating state
and fault indication.

L/N

red

L'/N'

green

PE

PE
N'/L'

N/L
1

Protection of the data side: Low-capacitance


4-wire protective circuit for ISDN and
Ethernet pin assignment.

DPRO 230 ISDN

SPD class
Max. continuous operating d.c. voltage UC
C2 Nominal discharge current (8/20 s) line-line In
C2 Nominal discharge current (8/20 s) line-PE In
C2 Total nominal discharge current (8/20 s) In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PE for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PE at 1 kV/s C3 Up
Cut-off frequency line-line fG
Operating temperature range
Degree of protection
Connection input / output
Pinning
Earthing via
Enclosure material
Colour
Test standards
Protection for the power side

DPRO 230 SE ISDN

909 320
ISDN

DPRO 230 ISDN


909 320

Q
48 V
120 A
2.5 kA
10 kA
) 100 V
) 500 V
) 80 V
) 500 V
50 MHz
-25C...+40C
IP 20
RJ45 shielded socket / RJ45 shielded socket
1(5)/2(4), 3/6
protective conductor connection
thermoplastic, UL 94 V-2
pure white
IEC 61643-21

DPRO 230 ISDN

DPRO 230 SE ISDN

SPD according to EN 61643-11


Type 3
SPD according to IEC 61643-1
Class III
Nominal a.c. voltage UN
230 V
Max. continuous operating a.c. voltage Uc
255 V
Nominal load current IL
16 A
Nominal discharge current (8/20 s) L-N In
3 kA
Nominal discharge current (8/20 s) L/N-PE In
5 kA [(L+N)-PE]
Combined impulse (1.2/50 s - 8/20 s) L-N Uoc
6 kV
Combined impulse (1.2/50 s - 8/20 s) L/N-PE Uoc
10 kV [(L+N)-PE]
Voltage protection level L-N Up
) 1.25 kV
Voltage protection level L/N-PE Up
) 1.5 kV
Response time L-N tA
) 25 ns
Response time L/N-PE tA
) 100 ns
Max. mains-side overcurrent protection
16 A gL/gG or B 16 A
Short-circuit withstand capability
for max. mains-side overcurrent protection
6 kArms a.c.
Temporary overvoltage (TOV) L-N UT
335 V/5 sec
Temporary overvoltage (TOV) L/N-PE (1) UT
400 V/5 sec
Temporary overvoltage (TOV) L/N-PE (2) UT
1200 V+U0 /200 ms
Fault indication
red light
Operating state indication
green light
For mounting on
plug-in system with
centre earthing contact system
earth contact
according to CEE 7,
DIN 49440/DIN 49441
standard sheet V
Test standards
IEC 61643-11
Ordering information
Type
Part No.
Packing unit

DPRO 230 ISDN


909 320
1 pc(s).

DPRO 230 SE ISDN


909 325
1 pc(s).

Dimension drawing DPRO ISDN

340

www.dehn.de

DPRO 230

909 321

DPRO 230 LAN100

Protection for the data side

DPRO 230 LAN100


909 321

DEHNprotector
DPRO 230 LAN100

INFORMATION TECHNOLOGY SYSTEMS


COMBINED ADAPTERS
DPRO 230 LAN100

SPD class
Max. continuous operating d.c. voltage UC
C2 Nominal discharge current (8/20 s) line-line In
C2 Nominal discharge current (8/20 s) line-PE In
C2 Total nominal discharge current (8/20 s) In
Voltage protection level line-line for In C2 Up
Voltage protection level line-PE for In C2 Up
Voltage protection level line-line at 1 kV/s C3 Up
Voltage protection level line-PE at 1 kV/s C3 Up
Operating temperature range
Degree of protection
Connection input / output
Pinning
Earthing via
Enclosure material
Colour
Test standards
Protection for the power side

Q
58 V
30 A
2.5 kA
10 kA
) 100 V
) 500 V
90 V
) 500 V
-20C...+40C
IP 20
RJ45 shielded socket / RJ45 shielded socket
1/2, 3/6, 4/5, 7/8
protective conductor connection
thermoplastic, UL 94 V-2
pure white
IEC 61643-21

DPRO 230 LAN100

DPRO 230 SE LAN100

SPD according to EN 61643-11


Type 3
SPD according to IEC 61643-1
Class III
Nominal a.c. voltage UN
230 V
Max. continuous operating a.c. voltage Uc
255 V
Nominal load current IL
16 A
Nominal discharge current (8/20 s) L-N In
3 kA
Nominal discharge current (8/20 s) L/N-PE In
5 kA [(L+N)-PE]
Combined impulse (1.2/50 s - 8/20 s) L-N Uoc
6 kV
Combined impulse (1.2/50 s - 8/20 s) L/N-PE Uoc
10 kV [(L+N)-PE]
Voltage protection level L-N Up
) 1.25 kV
Voltage protection level L/N-PE Up
) 1.5 kV
Response time L-N tA
) 25 ns
Response time L/N-PE tA
) 100 ns
Max. mains-side overcurrent protection
16 A gL/gG or B 16 A
Short-circuit withstand capability
for max. mains-side overcurrent protection
6 kArms a.c.
Temporary overvoltage (TOV) L-N UT
335 V/5 sec
Temporary overvoltage (TOV) L/N-PE (1) UT
400 V/5 sec
Temporary overvoltage (TOV) L/N-PE (2) UT
1200 V+U0 /200 ms
Fault indication
red light
Operating state indication
green light
For mounting on
plug-in system with
centre earthing contact system
earth contact
according to CEE 7,
DIN 49440/DIN 49441
standard sheet V
Test standards
IEC 61643-11
Ordering information
Type
Part No.
Packing unit

NEW

DPRO 230 SE LAN100

DPRO 230 LAN100


909 321
1 pc(s).

Protection of Ethernet applications


(1000 BASE-T) with an elegant design
Shielded Cat 5e patch cable (1.5 m)
included
For installation in conformity with the
lightning protection zones concept at
the boundaries from 2 3 and higher
Combined surge protection for the power
side and data input for the protection of LAN
components.
Meets the requirements for Channel Class D
in accordance with EN 50173 and is thus
suitable for 1000Base-T (Gigabit Ethernet).

L/N

red
PE

green

L'/N'
PE
N'/L'

N/L

1'

2
3

2'
3'

6
4

6'
4'

5
7

5'
7'

8'

Data side: Low-capacitance protective circuit of


all pairs for Ethernet pin assignment

DPRO 230 SE LAN100


909 326
1 pc(s).

Dimension drawing DPRO LAN100

www.dehn.de

341

342

www.dehn.de

Isolating Spark Gap


For lightning equipotential bonding

LIGHTNING EQUIPOTENTIAL BONDING


ISOLATING SPARK GAPS

For indirect connection/earthing of functionally


isolated installation components when being
affected by lightning
For lightning equipotential bonding application
according to IEC 62305
With corrosion-resistant stainless steel connections
For mounting inside of buildings, outdoors, in
damp rooms as well as for underground installation
Extremely heavy-duty devices

TFS: High-capacity isolating spark gap


KFSU: Isolating spark gap

For lightning equipotential bonding according to IEC 62305 as well as for


use in IT installations according to IEC 60364-5-54.

TFS / KFSU

923 023
923 021

TFS
Spark Gap
KFSU
Isolating Spark Gap

TFS
KFSU

Isolating
923 023
Ex923 021

Dimension drawing TFS / KFSU

Basic circuit diagram TFS / KFSU

TFS / KFSU: Isolating spark gaps with plastic coating and 2 connections (Rd 10 mm) made of stainless steel

Lightning impulse current (10/350 s) Iimp


Class of lightning current carrying capability acc. to EN 50164-3
Nominal discharge current (8/20 s) In
Rated power-frequency withstand voltage (50 Hz) UW/AC
100% Lightning impulse sparkover voltage Urimp
Power frequency sparkover voltage (50 Hz) Uaw
Operating temperature range TU
Degree of protection
Length
Diameter of enclosure
Enclosure material
Connection
Material (connection)
Ordering information
Type
Part No.
Packing unit

www.dehn.de

TFS

KFSU

100 kA
H
100 kA
300 V
) 4 kV
) 2.5 kV
-20C...+80C
IP 65
160 mm
43 mm
steel-plastic coating
Rd 10 mm
stainless steel

100 kA
300 V
) 4 kV
) 2.5 kV
-20C...+80C
IP 65
160 mm
43 mm
steel-plastic coating
Rd 10 mm
stainless steel

TFS
923 023
1 pc(s).

KFSU
923 021
1 pc(s).

343

EXFS 100 / EXFS 100 KU


For explosion-hazard areas

LIGHTNING EQUIPOTENTIAL BONDING


ISOLATING SPARK GAPS
For indirect connection/earthing of functionally
isolated installation components when being
affected by lightning
Device for lightning equipotential bonding
according to IEC 62305 in explosion-hazard
areas
For bridging insulating pieces, insulating
flanges etc. in cathodically corrosion-protected
pipe sections
For safe installation in explosion protected zone
1 (gas) or 21 (dust)
Especially low sparkover voltage
Especially high a.c. current withstand capability

ATEX-certified isolating spark gap for lightning equipotential bonding


according to IEC 62305 with low sparkover voltage

EXFS 100:
Isolating spark gap for use in explosion-hazard areas with plastic coating and M10 connecting thread nut
EXFS 100 KU: Isolating spark gap for use in explosion-hazard areas with 2 m connecting cable for underground installation
The Ex isolating spark gaps of the EXFS 100 / EXFS 100 KU product family are used when conductive installation components situated in explosion-hazard areas cannot be connected directly with each other.
The spark gaps with low sparkover voltage are especially efficient for isolated installation components with little insulation resistance.
No special regulations have to be observed for safe application in zone 1
with gases or zone 21 with dusts.
With a maximum lightning impulse current of 100 kA (10/350 s), EXFS
100 and EXFS 100 KU meet class H according to EN 50164-3 Lightning
Protection Components (LPC) Part 3: Requirements for isolating spark
gaps.
The ATEX-certified spark gaps EXFS 100 and EXFS 100 KU provide
approved safety according to harmonised European standards.
For connecting EXFS 100 spark gaps, prewired connecting cables with different lengths are available as accessories.
Flat and angled connection brackets (IF) make it easier to connect the
spark gaps to pipe flanges.
EXFS 100 KU types are enclosed by a damp-proof plastic coating and can
therefore be ideally used for underground installation at insulating couplings.

Type examination certificate

344

www.dehn.de

923 100

EXFS 100

LIGHTNING EQUIPOTENTIAL BONDING


ISOLATING SPARK GAPS

EXFS 100 / EXFS 100 KU


EXFS 100

EXFS 100
923 100

Dimension drawing EXFS 100

Installation of EXFS 100

EXFS 100: Ex isolating spark gap with plastic coating and M10 connecting thread nuts

EXFS 100
Lightning impulse current (10/350 s) Iimp
100 kA
Class of lightning current carrying capability acc. to EN 50164-3
H
Nominal discharge current (8/20 s) In
100 kA
Rated power-frequency withstand voltage (50 Hz) UW/AC
250 V
100% Lightning impulse sparkover voltage Urimp
) 1.25 kV
Power-frequency sparkover voltage (50 Hz) Uaw
) 0.5 kV
Rated discharge current (50 Hz) Imax
500 A / 0.5 sec. (TU: ) 45C)
(Ex) marking acc. to EN 60079 (gases)
II 2G Ex d IIC T6
(Ex) marking according to EN 61241 (dusts)
II 2D Ex tD A21 IP67 T 80C
Operating temperature range TU
-20C...+60C
Degree of protection
IP 67
Approvals, Certifications
BVS 06 ATEX E 099, IECEx KEM 09.0051...
Length of enclosure
100 mm
Diameter of enclosure
45,5 mm
Enclosure material
plastic coating
Connection of enclosure
thread nut M10, 2x M10x25 mm, 2x spring washer
Ordering information
Type
Part No.
Packing unit

EXFS 100
923 100
1 pc(s).

Accessory Part for EXFS 100 / EXFS 100 KU


EXFS 100: Connecting cable, Cu 25 mm2
Connecting cable for EXFS 100; 2 cable lugs 10.5 mm, hexagon screw and nut (M10), StSt and spring washer
Type
AL EXFS L100 KS
AL EXFS L200 KS
AL EXFS L300 KS

Cable lug
material
Cu/gal Sn
Cu/gal Sn
Cu/gal Sn

Cross
section
25 mm2
25 mm2
25 mm2

Cable
length
100 mm
200 mm
300 mm

PU
Part
pc(s).
No.
1
923 025
1
923 035
1
923 045

Accessory Part for EXFS 100 / EXFS 100 KU


923 025
L100 KS
923 035
L200 KS
923 045
L300 KS

AL EXFS L100 KS
923 025
AL EXFS L200 KS
923 035
AL EXFS L300 KS
923 045

AL EXFS
AL EXFS

Pair of angled connection brackets IF 1

923 011

AL EXFS

Pair of angled connection brackets for EXFS ...; diameter corresponds to bolt diameter of the bolted flange joint (d1 up to max.
60 mm, please indicate the diameter required when placing
your order)
Type
IF1

Material
St/tZn

PU
pc(s).
1

923 016

Pair of flat connection brackets for EXFS ...; diameter corresponds to bolt diameter of the bolted flange joint (d1 up to max.
60 mm, please indicated the diameter required when placing
your order)

www.dehn.de

Material
St/tZn

PU
pc(s).
1

923 011

Part
No.
923 011

Pair of flat connection brackets IF 3

Type
IF3

Connection Bracket Type IF -SET-

Connection Bracket Type IF -SET-

923 016

Part
No.
923 016

345

EXFS 100 / EXFS 100 KU


EXFS 100 KU

LIGHTNING EQUIPOTENTIAL BONDING


ISOLATING SPARK GAPS

923 101
KU

EXFS 100 KU
923 101

isolating spark gap/


Funkenstrecke

insulating piece/
Isolierstck

insulation / Isolierung

Installation of EXFS 100 KU

Dimension drawing EXFS 100 KU

EXFS 100 KU: Ex isolating spark gap with connecting cable for aboveground and underground
installation

EXFS 100 KU
Lightning impulse current (10/350 s) Iimp
100 kA
Class of lightning current carrying capability acc. to EN 50164-3
H
Nominal discharge current (8/20 s) In
100 kA
Rated power-frequency withstand voltage (50 Hz) UW/AC
250 V
100% Lightning impulse sparkover voltage Urimp
) 1.25 kV
Power-frequency sparkover voltage (50 Hz) Uaw
) 0.5 kV
Rated discharge current (50 Hz) Imax
500 A / 0.5 sec. (TU: ) 45C)
(Ex) marking acc. to EN 60079 (gases)
II 2G Ex d IIC T6
(Ex) marking according to EN 61241 (dusts)
II 2D Ex tD A21 IP67 T 80C
Operating temperature range TU
-20C...+60C
Degree of protection
IP 67
Approvals, Certifications
BVS 06 ATEX E 099, IECEx KEM 09.0051...
Length of enclosure
123 mm
Diameter of enclosure
34 mm
Enclosure material
plastic coating; water-proof coating
Connection of enclosure
NYY-J-1x25 mm2, approx. 2 m long
Ordering information
Type
Part No.
Packing unit

346

EXFS 100 KU
923 101
1 pc(s).

www.dehn.de

EXFS 100

LIGHTNING EQUIPOTENTIAL BONDING


ISOLATING SPARK GAPS

EXFS L / EXFS KU
For use in explosion-hazard areas
For indirect connection/earthing of functionally
isolated installation components when being
affected by lightning
Device for lightning equipotential bonding acc.
to IEC 62305 in explosion-hazard areas (Zone 2)
According to ATEX Directive 94/9/EC
Corrosion-resistant zinc diecasting enclosure
with plastic cover and flexible conductor connection
For bridging insulating pieces, insulating
flanges etc. in cathodically corrosion protected
pipe sections
Extremely heavy-duty device

ATEX-certified isolating spark gap for lightning equipotential bonding


according to IEC 62305, approved device with flexible conductor connection

EXFS L ...: Isolating spark gap for use in explosion-hazard areas with flexible connecting cable
EXFS KU: Isolating spark gap for use in explosion-hazard areas with 1.5 m connecting cable for underground installation

Ex isolating spark gaps of the EXFS L / EXFS KU product family are used
when the direct interconnection of electrically conductive installation
components in Ex areas is not applicable. As, for example, in case of
cathodically corrosion protected pipeline sections.
ATEX-certified EXFS L and EXFS KU spark gaps provide approved and tested safety in accordance with harmonised European standards.
The arc-resistant tungsten-copper electrodes ensure a long service life of
the Ex spark gaps.
The approved type EXFS L with flexible conductor connection quickly
adapts to any application environment. The prewired spark gaps provide
connecting cables with different lengths with cable lugs, screws and M10
nut. The flat or angled connection brackets (IF), which are available as
accessories, allow for easy connection of the spark gap to pipeline
flanges.
The EXFS KU type is enclosed in a damp-proof PVC enclosure and is ideal
for underground installation at insulating couplings.

www.dehn.de

347

EXFS L / EXFS KU
EXFS L

LIGHTNING EQUIPOTENTIAL BONDING


ISOLATING SPARK GAPS

923 060
L100
923 061
L200
923 062
L300

EXFS

EXFS L100
Isolating Spark Gap
EXFS L200
Isolating Spark Gap
EXFS L300
Isolating Spark Gap

Ex923 060
Ex923 061
Ex923 062

lmax = 300 mm
(avoid loops
where possible)

Installation of EXFS

Dimension drawing EXFS

EXFS L ...: Ex isolating spark gap for aboveground installation

EXFS L100
Lightning impulse current (10/350 s) Iimp
50 kA
Class of lightning current carrying capability acc. to EN 50164-3
N
Nominal discharge current (8/20 s) In
100 kA
Rated power-frequency withstand voltage (50 Hz) UW/AC
300 V
100% Lightning impulse sparkover voltage Urimp
) 2.5 kV
Power frequency sparkover voltage (50 Hz) Uaw
) 1.2 kV
Type of protection acc. to EN 50014, EN 50021
II 3 G EEx nC II T4
Operating temperature range TU
-20C...+80C
Degree of protection
IP 54
Approvals, Certifications
ZELM 03 ATEX 3192X
Length of enclosure
90 mm
Diameter of enclosure
63 mm
Enclosure material
zinc diecasting, plastic
Connecting cable
Cable length
100 mm
Suitable for flange size
20-130 mm
Ordering information
Type
Part No.
Packing unit

Connection Bracket Type IF -SET-

348

EXFS L200
923 061
1 pc(s).

EXFS L300
923 062
1 pc(s).

Material
St/tZn

300 mm
220-320 mm

PU
pc(s).
1

Pair of flat connection brackets IF 3

923 016

Pair of angled connection brackets for EXFS ...; diameter corresponds to bolt diameter of the bolted flange joint (d1 up to max.
60 mm, please indicate the diameter required when placing
your order)
Type
IF1

50 kA
N
100 kA
300 V
) 2.5 kV
) 1.2 kV
II 3 G EEx nC II T4
-20C...+80C
IP 54
ZELM 03 ATEX 3192X
90 mm
63 mm
zinc diecasting, plastic

Accessory Part for EXFS L / EXFS KU

Pair of angled connection brackets IF 1


923 011

EXFS L300

50 kA
N
100 kA
300 V
) 2.5 kV
) 1.2 kV
II 3 G EEx nC II T4
-20C...+80C
IP 54
ZELM 03 ATEX 3192X
90 mm
63 mm
zinc diecasting, plastic
H01N2-D 25 mm2 with cable lug and screw/nut (M10)
200 mm
120-230 mm

EXFS L100
923 060
1 pc(s).

Accessory Part for EXFS L / EXFS KU


923 011

EXFS L200

Part
No.
923 011

Connection Bracket Type IF -SET-

923 016

Pair of flat connection brackets for EXFS ...; diameter corresponds to bolt diameter of the bolted flange joint (d1 up to max.
60 mm, please indicated the diameter required when placing
your order)
Type
IF3

Material
St/tZn

PU
pc(s).
1

Part
No.
923 016

www.dehn.de

EXFS
EXFS

923 019

EXFS KU

EXFS KU
Isolating Spark Gap

Ex923 019

LIGHTNING EQUIPOTENTIAL BONDING


ISOLATING SPARK GAPS

EXFS L / EXFS KU
EXFS KU

Dimension drawing EXFS KU

EXFS KU: Ex isolating spark gap with connecting cables for aboveground
and underground installation

EXFS KU
Lightning impulse current (10/350 s) Iimp
Class of lightning current carrying capability acc. to EN 50164-3
Nominal discharge current (8/20 s) In
Rated power-frequency withstand voltage (50 Hz) UW/AC
100% Lightning impulse sparkover voltage Urimp
Power frequency sparkover voltage (50 Hz) Uaw
Type of protection acc. to EN 50014, EN 50021
Operating temperature range TU
Degree of protection
Approvals, Certifications
Length of enclosure
Diameter of enclosure
Enclosure material
Connecting cable
Cable length
Ordering information
Type
Part No.
Packing unit

www.dehn.de

50 kA
N
100 kA
300 V
) 2.5 kV
) 1.2 kV
II 3 G EEx nC II T4
-20C...+80C
IP 67
ZELM 03 ATEX 3192X
90 mm
63 mm
zinc diecasting, plastic
NYY-J-1x25 mm2
2 x approx. 1500 mm

EXFS KU
923 019
1 pc(s).

349

Pipe Clamp for Explosion Hazard Areas


LIGHTNING EQUIPOTENTIAL BONDING
For fixing at pipes in explosion hazard areas
For use in explosion hazard areas Ex zones 1
and 2 (gases, vapours, fogs) as well as Ex zones
21 and 22 (dusts)
Tested for explosion group IIB
Time-saving installation deactivation of the
system/areas for welding or drilling work not
necessary

Pipe clamp for explosion hazard areas from 26.9 mm


() to 88.9 mm (3); 88.9 mm (3) to 300 mm and
from 300 to 500 mm.
Separate clamping body for endless tightening strap (Part
No. 540 901) from 26.9 mm () to 500 mm.

So far, the method of choice for implementing equipotential bonding and


lightning equipotential bonding terminals in explosion hazard areas has
been welding or threaded bushings. Using pipe clamps was only permitted if there was proof of ignition spark immunity in case of lightning current loading. DEHN + SHNE has now provided evidence of ignition spark
absence for a pipe clamp at lightning current loading. By realising the test
according to EN 50164-1 (VDE 0185-201): Requirements for connection
components (clamps and connectors) in a potentially explosive atmosphere, absence of ignition sparks was proved for the test sample with a
lightning current carrying capability up to 50 kA (10/350 s). The design
of this novel pipe clamp for explosion risk areas not only provides a safe
electrical contact by means of two contact clips, but also the mechanical
fixing by an electrically insulated clamping body.

Pipe clamp for electrical contacting of pipes in explosion hazard areas, for
implementing of lightning equipotential bonding according to EN 62305-3
(VDE 0185-305-3)

The Ex pipe clamp can be connected by


round conductor, Cu, St/tZn, Al, StSt with 8/10 mm or flexible / stranded copper conductors, cross section 16-35 mm2, with E-Cu crimped
cable lug (DIN 46235)
flat copper conductor with minimum dimension 20x2.5 mm and a
10.5 mm bore hole

DECLARATION OF MANUFACTURER
Product:

Pipe clamp for explosive zones

Product description:

Part No. 540 821


Part No. 540 801
Part No. 540 803
Part No. 540 805
Part No. 540 810

Manufacturer:

DEHN + SHNE GmbH + Co.KG.


Hans-Dehn-Str. 1
92318 Neumarkt i.d.OPf., Germany

Application:
The pipe clamp for explosive zones is used for connecting pipes of different materials and
diameters to the lightning equipotential bonding structure in explosive atmospheres.
Lightning currents are discharged without formation of sparks as specified in the technical
data sheet.
We herewith confirm that the pipe clamp for explosive zones is suitable for the use in explosive zones 1 and 2 (gas, vapour, mist) and explosive zones 21 and 22 (combustible dust) in
connection with the installation instructions, P

ble and not necessary with respect to explosion protection.

not legally admissi-

Attached to a StSt pipe


Neumarkt i.d.OPf., 12 Okt. 2009

Dr.-Ing. Ralph Brocke


Director R&D

c:\dokume~1\drb\lokale~1\temp\xpgrpwise\herstellererklrung bandrohrschelle ex-bereiche upd ate ausfhrung klein und gro engl. .doc
Page 1

350

www.dehn.de

LIGHTNING EQUIPOTENTIAL BONDING


540 821
27

Pipe Clamp for Explosion Hazard Areas


Ex Pipe Clamp for 6 mm to 26.9 mm

EX BRS

EX BRS 27
540 821

Type EX BRS 27 clamping range from 6 mm


to 26.9 mm ()
EX BRS 27
Lightning impulse current (10/350 s) for Cu Iimp
Lightning impulse current (10/350 s) for St/tZn Iimp
Lightning impulse current (10/350 s) for StSt Iimp
Clamping range
Dimension tensioning strap (l1 x w x d)
Clamping body material
Grip head/strap material
Contact angle material

10 kA-> 6-12 mm I 20 kA-> 12-26.9 mm () I 25 kA-> 26.9 mm ()


25 kA-> 17.2-26.9 mm ()
10 kA-> 6-12 mm I 12 kA-> 12-26.9 mm () I 25 kA-> 26.9 mm ()
6 - 26.9 mm ()
190x10x0.25 mm
polyamide
StSt
Ms/gal Sn

Ordering information
Type

EX BRS 27

Part No.
Packing unit

540 821
1 pc(s).

540 801
540 803
540 805

Ex Pipe Clamp for 26.9 mm to 500 mm

540 801
540 803
540 805

Type EX BRS 90, Part No. 540 801, clamping


range from 26.9 mm () to 88.9 mm (3)
Type EX BRS 300, Part No. 540 803, clamping
range from 88.9 mm (3) to 300 mm and
Type EX BRS 500, Part No. 540 805, clamping
range from 300 to 500 mm
EX BRS 90
Lightning impulse current (10/350 s) for Cu Iimp
50 kA
Lightning impulse current (10/350 s) for St/tZn Iimp
50 kA
Lightning impulse current (10/350 s) for StSt Iimp
25 kA
Class of lightning current carrying capability acc. to DIN EN 50164-1
N
Clamping range
26.9 () - 88.9 mm (3)
Dimension tensioning strap (l1 x w x d)
410x25x0.3 mm
Clamping body material
polyamide
Grip head/strap material
StSt
Contact angle material
Cu/gal Sn
Ordering information
Type
Part No.
Packing unit

www.dehn.de

EX BRS 90
540 801
1 pc(s).

EX BRS 300

EX BRS 500

50 kA
50 kA
50 kA
N
88.9 (3) - 300 mm
1100x25x0.3 mm
polyamide
StSt
Cu/gal Sn

50 kA
50 kA
50 kA
N
300 - 500 mm
1850x25x0.3 mm
polyamide
StSt
Cu/gal Sn

EX BRS 300
540 803
1 pc(s).

EX BRS 500
540 805
1 pc(s).

NEW

351

Pipe Clamp for Explosion Hazard Areas


Separate clamping body for endless tightening strap

LIGHTNING PROTECTION
TECHNOLOGY SYSTEMS

540 810

540 810

Separate clamping body with endless strap (Part


No. 540 901)
Clamping ranges from 26.9 mm () to 500 mm

Lightning impulse current (10/350 s) for Cu Iimp


Lightning impulse current (10/350 s) for St/tZn Iimp
Lightning impulse current (10/350 s) for StSt Iimp
Class of lightning current carrying capability acc. to DIN EN 50164-1
Clamping range
Clamping body material
Grip head/strap material
Contact angle material

50 kA
50 kA
25 kA
N
26.9 mm () - 500 mm
polyamide
StSt
Cu/gal Sn

Ordering information
Part No.

540 810

Packing unit

1 pc(s).

Accessory Part for Pipe Clamp for Explosion Hazard Areas


540 901

Tensioning strap
Endless tensioning strap (100 m long)

540 901

Material
StSt (V2A)

352

Strap dimension
(l x w x d)
... x 25 x 0.3 mm

PU
pc(s).
1

Part
No.
540 901

www.dehn.de

LIGHTNING EQUIPOTENTIAL BONDING


ISOLATING SPARK GAPS

SDS
Voltage Limiting Device
Electrical isolation of insulated track sections
and earthed parts of installations
Safe equipotential bonding in case of a short
circuit or earth fault at the overhead contact
line due to high-current-resistant welding of
the electrodes
Discharge of surges without formation of short
circuits due to lightning-resistant SDS ... voltage limiting device
Short-circuit withstand capability 25 kArms /
100 ms; 36 kArms / 75 ms

SDS ...: Cylindrical SDS spark gap unit for insertion into rail adapter Siemens No. 8WL6503-xx

DIN EN 50122-1 describes the use of voltage limiting devices for d.c. and
a.c. railways for so-called open earthing of railways for live components of overhead contact lines and current collectors.
In order to prevent the occurrence of hazardous surges between the insulated tracks or track sections of electrical railways and earthed parts of
the installation, voltage limiting devices (SDS ...) are used.
Their function is to connect parts of the installation in overhead contact
lines and current collectors permanently to the return circuit, as soon as
the threshold voltage is exceeded.

mostly unnecessary

SDS spark gap unit for use with rail adapter, Siemens No. 8WL6503-xx

In case of atmospheric overvoltages, the lightning-resistant SDS ... voltage


limiting device is capable of returning to its initial state after discharging
the impulse current. Only if the specified lightning current loads are
exceeded, a permanent short circuit is initiated by heavy-current-resistant
welding of the electrodes and the fuse link has to be replaced.
The SDS voltage limiting device consists of a spark gap unit and the
respective connecting kit for direct connection to the rail or overhead contact line tower.
The spark gap unit type SDS 1, Part No. 923 110, developed by DEHN +
SHNE, has also been approved by the German Federal Railway Authority
(EBA).

www.dehn.de

353

SDS
SDS ...

LIGHTNING EQUIPOTENTIAL BONDING


ISOLATING SPARK GAPS

923 110

SDS 1
Sicherungseinsatz SDS 1

Basic circuit diagram SDS ...

SDS 1

SDS 2

Dimension drawing SDS ...

SDS 3

SDS 4

SDS 5

Power frequency sparkover voltage Uaw


) 940 V

d.c. sparkover voltage Uag


600 V +/- 20 %
350 V +/- 20 %
550 V
230 V +/- 20 %
120 V +/- 20 %
Impulse sparkover voltage
) 1400 V (1 kV/s)
) 900 V (1 kV/s)
) 1000 V (1 kV/s)
) 650 V (1 kV/s)
) 600 V (1 kV/s)
Self-extinguishing capability
300 A / 65 V

Lightning current discharge capacity


(10/350 s) 0.1x / 0.5x / 1x
5 kA
2 kA
2.5 kA
2.5 kA
2 kA
Lightning current withstand capability (10/350 s)
25 kA
25 kA
25 kA
25 kA
25 kA
Impulse current discharge capacity
(8/20 s) 0.1x / 0.5x / 1x

20 kA
20 kA
Safe short circuit due to welding of the
electrodes for alternating currents @ 100 ms * 1.5 kA / 1000 V / 100 ms

Safe short circuit due to welding of the


electrodes for alternating currents @ 30 ms
* 2.5 kA / 1000 V / 30 ms

Safe short circuit due to welding of the


electrodes for direct currents
* 750 A / 250 ms
* 600 A / 250 ms

* 600 A / 250 ms
* 600 A / 250 ms
Short circuit withstand capability
25 kArms / 100 ms;
25 kArms / 100 ms;
25 kArms / 100 ms;
25 kArms / 100 ms;
25 kArms / 100 ms;
36 kArms / 75 ms
36 kArms / 75 ms

36 kArms / 75 ms
36 kArms / 75 ms
Long-term current
1 kArms for t ) 120 s
1 kArms for t ) 120 s

1 kArms for t ) 120 s


1 kArms for t ) 120 s
Leakage current Ilc
< 1 A for 100 V d.c.
< 1 A for 100 V d.c.

< 1 A for 100 V d.c.


< 1 A for 100 V d.c.
Operating temperature range TU
-40C...+80C
-40C...+80C
-40C...+80C
-40C...+80C
-40C...+80C
For mounting on
allows for installation into voltage breakdown protector/SIEMENS rail adapter No. 8WL6503-xx
Tightening torque of the fuse link
in the busbar adapter
15 Nm
15 Nm
15 Nm
15 Nm
15 Nm
Approvals, Certifications
DB Drawing No.
Ordering information
Type
Part No.
Packing unit

354

EBA
4 Ebs 15.13.20 Sheet 2

SDS 1
923 110
10 pc(s).

SDS 2
923 117
10 pc(s).

SDS 3
923 116
10 pc(s).

SDS 4
923 118
10 pc(s).

SDS 5
923 119
10 pc(s).

www.dehn.de

SDS 1

923 110

LIGHTNING EQUIPOTENTIAL BONDING

Equipotential Bonding

Equipotential Bonding Bars

563 200

PAS 11AK
Busbar

PAS 11AK

Earthing
563 200

Equipotential busbar K12,

Contact
bar
Cu/gal Sn

Type
PAS 11AK
563 201
UV

PAS 11AK

PAS 11AK UV
563 201

563 222
PAS

AK FL40

AK FL40 PAS
for Fl 40

Terminal
563 222

Cross
section
30 mm2

Contact
bar
Cu/gal Sn

Cross
section
30 mm2

PAS 9AK

PAS 9AK
Busbar

Earthing
563 050

PU
Part
pc(s).
No.
1
563 201

Type
PAS 10RK

563 020

Type
PAS 9RK
PU
Part
pc(s).
No.
50 563 222

Contact
bar
Ms

Type
PAS 9AK

Cross
section
50 mm2

563 030

Type
PAS 14RK

563 105
OH

PAS 6RK

PAS 6RK OH
Busbar

Earthing
563 105

PU
Part
pc(s).
No.
1
563 050

Accessories / Construction Kit

RK 16

RK 16 PAS
Terminal, -16 mm3 for EB

mm2

Modular
563 011

Type
RK 16 PAS

Material
St/gal Zn

Connection Modules
2.5-25 mm2
1

PU
Part
pc(s).
No.
200 563 011

Up to 95 mm2 or Rd 8-10 mm
563 013

Type
RK 95 PAS

PU
Part
pc(s).
No.
1
563 020

563 019
PAS

RK FL40

RK FL40 PAS
Terminal, flat strip -40 mm for EB

Modular
563 019

Clamping
bar
Ms/gal Sn

Cross
section
100 mm2

PU
Part
pc(s).
No.
1
563 030

Miniature unit: For surface mounting without cover


Type
PAS 6RK OH

563 016
PAS
563 017
PAS
563 018
PAS

KS 198

KS 198 PAS
Bar, brass, 198 mm long
KS 398 PAS
bar, brass, 398 mm long
KS 798 PAS
bar, brass, 798 mm long

Terminal
563 016
Terminal
563 017
Terminal
563 018

563 014
RK

SB PAS

SB PAS RK
der, plastic, grey

Bar hol563 014

563 015
RK

AH PAS

AH PAS RK
cover, grey

Plastic
563 015

KS 398

Clamping
Cross
bar
Connection section
Ms/gal Sn 6 x 2.5-25 mm2 100 mm2

PU
Part
pc(s).
No.
10 563 105

Terminal Block

Material
St/gal Zn

Connection Modules
-40x5 mm
5

PU
Part
pc(s).
No.
25 563 019

Clamping Bar

KS 798

RK FL30

Material
St/gal Zn

Connection Modules
16-95 mm2
2

PU
Part
pc(s).
No.
100 563 013

Terminal Block
Flat conductor 30 mm

RK FL30 PAS
Terminal, flat strip -30 mm for EB

Cross
section
100 mm2

Type
KS 198 PAS
KS 398 PAS
KS 798 PAS

Material
Ms/gal Sn
Ms/gal Sn
Ms/gal Sn

Length
198 mm
398 mm
798 mm

Material
Plastic

Fixing
holes
6x4 mm

Modules
15
30
60

PU
Part
pc(s).
No.
10 563 016
10 563 017
10 563 018

Terminal Block

563 013

563 012
PAS

Clamping
bar
Ms/gal Sn

Flat conductor 40 mm

Terminal Block
2.5 to 25

PU
Part
pc(s).
No.
1
563 010

Equipotential Bonding Busbar,


with miniature terminal block system

Type
RK FL40 PAS
563 011
PAS

Cross
section
100 mm2

Type C:
13 terminal blocks 2.5 25 mm2
1 terminal block 16 95 mm2 or Rd 8 10 mm

563 030

Equipotential Bonding Bar MS


For equipotential bonding
Connections for:
7 Rd conductors Rd 2.5 16 mm2
1 Rd conductor 7 10 mm
1 Fl conductor 30x3.5 mm or Rd conductor 8 10 mm

Clamping
bar
Ms/gal Sn

Type B:
5 terminal blocks 2.5 25 mm2
3 terminal blocks 16 95 mm2 or Rd 8 10 mm
1 terminal block Fl 30x4 mm

563 020

Accessories
Snap-on Terminal for Fl 40 Conductors
Type
AK FL40 PAS

563 050

with Terminal Block System


For main equipotential bonding according to DIN VDE 0100 Part
410/540 and lightning equipotential bonding according to EN
62305-3 (DIN VDE 0185-305-3)
Type A:
7 terminal blocks 2.5 25 mm2
2 terminal blocks 16 95 mm2 or Rd 8 10 mm
1 terminal block Fl -30x4 mm

563 010

PU
Part
pc(s).
No.
1
563 200

Type K12 with 12 contact studs, UV-stabilised:


10 terminals for Rd 2.5 95 mm2 or Rd 10 mm conductors
and 1 terminal for Fl 30x4 mm
Type
PAS 11AK UV

Equipotential Bonding Bars R15,

563 010

with snap-on terminals


For equipotential bonding according to DIN VDE 0100 Part
410/540 and the lightning equipotential bonding according to
EN 62305-3 (VDE 0185-305-3)
Type K12 with 12 contact studs:
10 terminals for Rd 2.5 95 mm2 or Rd 10 mm conductors
and 1 terminal for Fl -30x4 mm conductors

Material
St/gal Zn

Type
SB PAS RK

PU
Part
pc(s).
No.
50 563 014

Cover
to snap on / to be labelled

Modular
563 012

Type
RK FL30 PAS

Bar Frame

Connection Modules
-30x4 mm
4

PU
Part
pc(s).
No.
25 563 012

Type
AH PAS RK

Material
Plastic

Modules
15

PU
Part
pc(s).
No.
10 563 015

Note: For our complete product range for earthing and equipotential bonding please refer to our current Lightning Protection catalogue, which
can be requested from Export Department.
www.dehn.de

355

Equipotential Bonding

LIGHTNING EQUIPOTENTIAL BONDING

Equipotential Bonding Bars

Earthing Busbars

for industial use


472 207
M10 CU
472 209
M10 V2A

PAS I 6AP M10 CU


Busbar
PAS I 6AP M10 V2A
Busbar

PAS I 6AP
PAS I 6AP

Earthing
472 207
Earthing
472 209

Equipotential Bonding Busbar for industrial use


For main equipotential bonding according to DIN VDE 0100 Part
410/540 and lightning equipotential bonding according to EN
62305-3 (DIN VDE 0185-305-3)
Also for use in hazardous zones (screws protected against selfloosening)
6 connections with insulators
Dimension
Type
Material (l x w x d)
PAS I 6AP M10 CU
Cu
295x40x5 mm
PAS I 6AP M10 V2A StSt
295x40x6 mm

472 227
M10 CU
472 229
M10 V2A

PAS I 8AP

PAS I 8AP M10 CU


Busbar
PAS I 8AP M10 V2A
Busbar

Earthing
472 227
Earthing
472 229

PAS I 8AP

472 217
10AP M10 CU
472 219
10AP M10 V2A

PAS I

PAS I 10AP M10 CU


Busbar
PAS I 10AP M10 V2A
Busbar

Earthing
472 217
Earthing
472 219

472 237
12AP M10 CU
472 239
12AP M10 V2A

PAS I

PAS I
PAS I

472 279
6AP V2A
472 269
8AP V2A
472 289
10AP V2A
472 299
12AP V2A

AD PAS

AD PAS 6AP V2A


NIRO, for 6-pole EB
AD PAS 8AP V2A
NIRO, for 8-pole EB
AD PAS 10AP V2A
NIRO, for 10-pole EB
AD PAS 12AP V2A
NIRO, for 12-pole EB

Cover
472 279
Cover
472 269
Cover
472 289
Cover
472 299

472 201
PAS

BS M10

BS M10 PAS
for EB

Fixing Set
472 201

472 210
M10

IS PAS

IS PAS M10
fr PAS Industrie

Isolator
472 210

AD PAS

ES 2X2AP
ES 2X2AP

8 connections with insulators


Dimension
Type
Material (l x w x d)
PAS I 8AP M10 CU
Cu
365x40x5 mm
PAS I 8AP M10 V2A StSt
365x40x6 mm

Cross
PU
Part
section pc(s).
No.
200 mm2 1
472 227
240 mm2 1
472 229

Type
Material
ES 2X2AP 10 ST St/tZn
ES 2X2AP 10 V2A StSt
472 022
10 ST
472 119
10 V2A

ES 2X3AP
ES 2X3AP

472 024
ST
472 129
10 V2A

ES 2X4AP
ES 2X4AP

Dimension
Type
Material (l x w x d)
PAS I 10AP M10 CU Cu
435x40x5 mm
PAS I 10AP M10 V2A StSt
435x40x6 mm

Cross
PU
Part
section pc(s).
No.
200 mm2 1
472 217
240 mm2 1
472 219

472 021
10 ST
472 139
10 V2A

ES 2X6AP 10 Stk.
472 021
ES 2X6AP 10 V2A
472 139

12 connections with insulators


Cross
PU
Part
section pc(s).
No.
2
200 mm
1
472 237
240 mm2 1
472 239

ES 2X6AP

PU
Part
pc(s).
No.
1
472 023
1
472 109

Dimension
Cross
(l x w x d) section
242x60x4 mm 240 mm2
242x60x5 mm 300 mm2

PU
Part
pc(s).
No.
1
472 022
1
472 119

Dimension
Cross
(l x w x d) section
293x60x4 mm 240 mm2
293x60x5 mm 300 mm2

PU
Part
pc(s).
No.
1
472 024
1
472 129

Dimension
Cross
(l x w x d) section
393x60x4 mm 240 mm2
393x60x5 mm 300 mm2

PU
Part
pc(s).
No.
1
472 021
1
472 139

2x4 connections
Type
Material
ES 2X4AP ST
St/tZn
ES 2X4AP 10 V2A StSt

ES 2X6AP

Dimension
Cross
(l x w x d) section
196x60x4 mm 240 mm2
196x60x5 mm 300 mm2

2x3 connections
Type
Material
ES 2X3AP 10 ST St/tZn
ES 2X3AP 10 V2A StSt

ES 2X4AP Stk.
472 024
ES 2X4AP 10 V2A
472 129

10 connections with insulators

Earthing Busbars
To be screwed or welded to steel structures
Borehole distance 50 mm
2x2 connections

ES 2X2AP 10 Stk.
472 023
ES 2X2AP 10 V2A
472 109

ES 2X3AP 10 Stk.
472 022
ES 2X3AP 10 V2A
472 119

Dimension
Type
Material (l x w x d)
PAS I 12AP M10 CU Cu
505x40x5 mm
PAS I 12AP M10 V2A StSt
505x40x6 mm

PAS I 12AP M10 CU


472 237
PAS I 12AP M10 V2A
472 239

Cross
PU
Part
section pc(s).
No.
200 mm2 1
472 207
240 mm2 1
472 209

472 023
10 ST
472 109
10 V2A

2x6 connections
Type
Material
ES 2X6AP 10 ST St/tZn
ES 2X6AP 10 V2A StSt

Accessories Cover for EBB (Industry)

AD PAS
AD PAS

Covers for EBB with insulators


Material
EBB
Type
screw/nut type
AD PAS 6AP V2A StSt 6 connections
AD PAS 8AP V2A StSt 8 connections
AD PAS 10AP V2A StSt 10 connections
AD PAS 12AP V2A StSt 12 connections

Dimension PU
(l x w x d) pc(s).
301x60x0.8 mm 1
371x60x0.8 mm 1
441x60x0.8 mm 1
511x60x0.8 mm 1

Part
No.
472 279
472 269
472 289
472 299

Accessories Fixing Set for EBB (Industry)


Screw
Screw
Plastic
PU
Part
Type
material
type
dowel pc(s).
No.
BS M10 PAS St/tZn 45 mm c M10x20 mm 12x60 mm 1
472 201

Accessories Insulator for EBB (Industry)


Type
IS PAS M10

Material
Isolator
UP (thermoset)

Terminal
thread
M10

PU
Part
pc(s).
No.
1
472 210

Note: For our complete product range for earthing and equipotential bonding please refer to our current Lightning Protection catalogue, which
can be requested from Export Department.
356

www.dehn.de

LIGHTNING EQUIPOTENTIAL BONDING


Connecting Clamps

Equipotential Bonding
Components
for ring equipotential bonding

308 025
ST

VK A UNI Stk.
Connection Clamp St/tZn

VK A UNI

308 025

Connecting Clamp, for reinforcements

277 230
277 237
277 239

For connecting reinforced concrete mats or reinforcements to


round and flat conductors
For T, cross and parallel connections

277 230

Strip Holder, with thrust pad


For wall mounting
Thrust pad with M8 screw for strip conductor up to 11 mm and
round conductor 6-10 mm.
11 mm distance from the wall

277 237
277 239

Clamping range
PU
Part
Type
Material Rd / Rd
Rd / Fl
Fl / Fl pc(s).
No.
VK A UNI ST St/tZn (+) 6-10 / (+) 6-10 / (II) 30 / 50 308 025
6-10 mm
30 mm
30 mm
308 026
V2 ST

VK A UNI

VK A UNI V2 Stk.
Connection Clamp St/tZn

308 026

308 030
F40 STBL

VK A R22

VK A R22 F40 STBL


Connection Clamp St/bare

308 030

308 041
R16 R25 ST
308 040
R16 R25 STBL

MMVK

MMVK R16 R25 Stk.


terminal, St/bare
MMVK R16 R25 STBL
terminal, St/tZn

MAXI MV
308 041
MAXI MV
308 040

MMVK

Type
FBH 6 ST
FBH 6 CU
FBH 6 V2A

For T, cross and parallel connections


Type
Material
VK A UNI V2 ST
St/tZn

Clamping range
Rd / Fl
Fl / Fl
(+) 6-10 / (+ / II) 30 /
30 mm
30 mm

PU
Part
pc(s).
No.
25 308 026

Material
CH
St/tZn
Cu
StSt

Material
screw
StSt
StSt
StSt

PU
Part
pc(s).
No.
25 277 230
25 277 237
25 277 239

Material
screw
StSt

PU
Part
pc(s).
No.
25 277 240

15 mm distance from the wall

277 240

Conductors with Pressure Plate

Tape
277 240

563 169
V2A

AK RPA

Type
FBH 11 ST

Material
CH
St/tZn

For T and cross connections


Type
Material
VK A R22 F40 STBL St/bare

Clamping range
Rd / Fl
(+) 6-22 / 40 mm

PU
Part
pc(s).
No.
25 308 030

MAXI MV Clamp for T, cross and parallel connections

For universal connection to the ring equipotential bonding for


St/tZn, copper or stainless steel (StSt)

AK RPA V2A
563 169

Part No. 308 040 with UL certification


Clamping range
Type
Material
Rd/Rd
MMVK R16 R25 ST
St/tZn
(+/II) 8-16 / 15-25 mm
MMVK R16 R25 STBL St/bare (+/II) 8-16 / 15-25 mm

Terminal Clamp

CH
Cross-sectional PU
Part
Type
Material
Rd / Fl
area
pc(s).
No.
AK RPA V2A StSt 8-10 / 3-11x30 mm 2.5-95 mm2
50 563 169

PU
Part
pc(s).
No.
20 308 041
20 308 040

Components
for foundation earthing electrodes
308 120
R10 F30 ST
308 129
R10 F30 V2A

VK EH R10 F30 Stk.


Connection Clamp St/tZn
VK EH R10 F30 V2A
Connection Clamp StSt (V2A)

VK EH
VK EH

308 120
308 129

Connecting Clamp, for Foundation Earth


Electrodes
For connecting round and flat conductors in the concrete foundation
For T, cross and parallel connections, no threading of the conductors required
Clamping range mm
PU
Part
Type
Material Rd / Fl
Fl / Fl
pc(s).
No.
VK EH R10 F30 ST St/tZn
(+) 10 / 30 (+/II) 30 / 30 25 308 120
VK EH R10 F30 V2A StSt
(+) 10 / 30 (+/II) 30 / 30 25 308 129

308 150

308 150

290 001
VG

AH FE RF

AH FE RF V G
Holder St/tZn, reinf. version 300 mm

Distance
290 001

Spacer
Reinforced angled type
Type
AH FE RF V G

290 002

AH FE RF

AH FE RF
Holder St/tZn, DIN 48833 A, 280 mm

Distance
290 002

Material
St/tZn

Support
Fl
40 mm

Support
Rd
8-10 mm

PU
Part
pc(s).
No.
25 290 001

Material
St/tZn

Support
Fl
40 mm

Support
Rd
8-10 mm

PU
Part
pc(s).
No.
50 290 002

Spacer
Straight type
Type
AH FE RF

Expansion Strap for Foundation Earth Electrodes


For leading the foundation earth electrode in extended foundations (several sections) through the expansion or isolating
joints. Thus no need to lead the earth electrode out of the base
plate.
Strap
material
StSt (V2A)

Dimension
(l x w x d)
approx. 700x30x(4x1) mm

Block
material
styrene

PU
Part
pc(s).
No.
1
308 150

Note: For our complete product range for earthing and equipotential bonding please refer to our current Lightning Protection catalogue, which
can be requested from Export Department.
www.dehn.de

357

358

www.dehn.de

MEASURING AND TEST DEVICES

Condition Monitoring System LifeCheck

Maximum protection and availability of systems by means of permanent condition monitoring of LifeCheck-equipped SPDs
The early detection system already detects
arrester overload and warns of imminent failure of the arrester
Visual indication of faulty or previously damaged SPDs
Compact dimensions and minimum wiring
Monitoring of up to 10 SPDs (40 signal lines)
Remote signalling contact
Remote signalling also via RS 485 interface
and PC software
Example of use of the DEHNrecord condition monitoring system.

Condition Monitoring:

The Status Display and Service Console PC software

The DRC MCM XT condition monitoring system is a compact DIN rail


mounted device for monitoring the condition of up to 10 pre-programmed
BXT arresters with integrated LifeCheck monitoring circuit.

is an optional user software for the DRC MCM XT condition monitoring


system which indicates the status of the SPDs and addresses LifeCheckequipped BLITZDUCTOR modules.
The software can be installed on a standard PC using an RS485/USB interface converter of type USB-NANO 485 which is available as accessory.

ntegrated into the SPD modules, LifeCheck permanently monitors the


proper condition of the SPD and acts like an early warning system, detecting imminent electrical or thermal overload of the protection components.
The LifeCheck status can be read out within a matter of seconds via contactless RFID technology by means of the portable DEHNrecord LC device
and also shows the date of the last test of the SPD module. Stationary
installed, the condition monitoring system supports condition-based
maintenance of 10 BXT.

The software can be downloaded free of charge from


www.dehn.de/download/ or is available as CD for a nominal fee.

The unit acts like an early warning system, generating a fault message
even in case of imminent arrester overload, indicates it by means of the
integrated three-colour LED and transmits it to one of the two integrated
remote signalling contacts. Failure of the monitoring unit, e.g. due to a
voltage breakdown, is also indicated via the remote signalling contact.
The Show function integrated into the DRC MCM system allows to detect
previously damaged SPDs in the monitoring group.
If several condition monitoring systems are used in one switchgear cabinet, these systems are connected via the integrated RS 485 interfaces to
synchronise the monitoring cycles. Up to 15 DRC MCM systems can be
connected to the RS 485 bus. Thus, up to 150 BLITZDUCTORs or 300 pairs
can be monitored simultaneously with minimum wiring effort.
Graphical status indication of DRC MCM XT monitoring devices
and of all programmed protection modules assigned to them.
The Service functions allow to switch to the Service Console
function complex. The protection modules can be easily addressed,
tested and reset due to the user-friendly user interface.

www.dehn.de

359

Condition Monitoring System LifeCheck


DRC MCM XT

MEASURING AND TEST DEVICES


910 695
MCM XT

DRC MCM XT
910 695

Monitoring the condition of LifeCheck-equipped SPDs


Permanent monitoring of up to
10 SPDs (40 signal lines)
Minimum wiring effort
Optional remote signalling via RS 485
or remote signalling contacts

The DRC MCM XT Status Display software allows


PC-aided remote indication of the status of all
SPDs monitored.

The Service Console offers various service functions, e.g. SPDs can be parameterised or reset
by means of the address data.

DIN rail mounted device with integrated LifeCheck sensor for monitoring the condition of max. 10
LifeCheck-equipped BLITZDUCTOR XT devices. Visual three-coloured SPD operating state indication combined with remote signalling function (break or make contact). The free Status Display
and Service Console software can be optionally used via an RS 485 interface converter.
DRC MCM XT

For testing

up to 10 BLITZDUCTOR XT ML devices
up to 10 BLITZDUCTOR XT ML EX devices; for use in non-hazardous atmospheres only! Observe thread measure!
Operating elements
multiway button, DIP switch
Indicator element
3-coloured LED (green, orange, red)
Input d.c. voltage range UIN
18...48 V
Max. nominal current input IIN
100 mA
RFID transmission frequency
125 kHz
Message: Replacing of SPD recommended
LED, remote signalling contact (break and make contact)
Test cycle
continuous
Operating temperature range for monitoring 10 BXT devices
-20C...+60C
Operating temperature range for monitoring 8 BXT devices
-40C...+80C
Degree of protection
IP 20
For mounting on
35 mm DIN rail acc. to EN 60715
Connection type
screw
Cross-sectional area, solid
0.08 - 4 mm2
Cross-sectional area, flexible
0.08 - 2.5 mm2
Tightening torque (terminal)
0.4 Nm
Enclosure material
polyamide PA 6.6
Colour
grey
Test standards
EN 61010-1, 61000-6-2/4
Type of remote signalling contact
make (no) and break contact (nc)
Switching capacity d.c.
350 V/0.12 A
Switching capacity a.c.
250 V/0.07 A
Delivery includes
base part, monitoring module, quick guide and marking system
Ordering information
Type
Part No.
Packing unit

DRC MCM XT
910 695
1 pc(s).

Accessory Part for Condition Monitoring System LifeCheck


910 486
NANO 485

USB NANO 485


910 486

USB

Accessory Part for Condition Monitoring System LifeCheck

USB interface converter of type USB NANO 485


USB NANO 485 converts signals between USB and RS-485. The interface converter is specifically designed for 2-wire RS-485 buses. LEDs indicate operation (yellow), Rx (green) and Tx (red).
USB NANO 485 is ideally suited for use with notebooks due to its small size.
Stationary use is also possible.
Type
USB NANO 485

360

PU
Part
pc(s).
No.
1 910 486

920 398
BA15 BXT

BS BA1 BA15 BXT


920 398

BS BA1

Marking system BA1-BA15


2 x 165 adhesive labels for labelling DRC MCM XT monitoring devices with their bus address (BA1 to BA15) and BXT
base parts or modules with consecutive numbers (1.1-1.10
to 15.1-15.10)
Type
BS BA1 BA15 BXT

PU
Part
pc(s).
No.
1 920 398

www.dehn.de

DRC

LifeCheck SPD Test Device

MEASURING AND TEST DEVICES

A higher degree of protection and availability is


achieved by preventive maintenance.
The LifeCheck monitoring device detects
thermal or electrical overload of all components.
To avoid imminent failure and thus system
downtime, the SPD module should be
replaced as soon as possible.
This type of SPD testing has the following benefits:
Very easy and within a matter of seconds
Module does not have to be removed during
system operation
Detection of thermal or electrical overload of
all components

Protection
level

Visual
inspection

Complete
inspection

Transponder (SPD)
energy

Complete inspection
of critical systems

I and II

1 year

2 years

1 year

III and IV

2 years

4 years

1 year

It makes no sense to inspect SPDs for information technology systems


visually since the status of the devices is generally not visible. For this purpose, another method has to be selected as is the case for complete
inspections. In the past, measurement equipment was used to test SPDs.
These measurements were very time consuming, required expertise and
the measurements did not provide sufficient information.

Preventive maintenance:
When using this maintenance strategy, SPDs are tested and measured at
regular intervals. The SPDs are assessed according to certain criteria and,
if required, replaced.

Reader (test device)

SPD

indication
of operating
state

identification IC

DIN EN 62305-3, supplement 3 (see table excerpt) specifies maintenance


tests and intervals of a lightning protection systems. However, these specifications are only normative minimum requirements.

reader IC

microcontroller

power

communication

data

Principle of operation of the LifeCheck diagnostic system

This type of monitoring reliably detects thermal and electrical overload of


all components, generally before the SPD fails and the availability of the
system to be protected is limited. In addition, no expertise is required for
testing. The reader also facilitates documentation of the test results,
which is mandatory in compliance with the EN 62305-3 standard.
The test data (date, time, results) of all SPDs are saved and can be transmitted to a PC for printing or storage via USB interface. Thus a higher
degree of protection and availability is achieved by means of preventive
maintenance with LifeCheck as it already detects overload of components
before the protection of the system circuit fails.

In the past, this was very time consuming, expensive and required downtime of the system.
For some years, SPDs with LifeCheck feature have been available which
allow to determine the status of the SPD via RFID technology. A monitoring circuit with a transponder in the SPD permanently monitors the protective circuit for impermissible overload due to thermal overheating or
electrical impulse currents.
Information is read out via a hand-held tester. This tester incorporates the
reader, an RFID reader unit.
It contactlessly transmits electromagnetic energy to the transponder in
the SPD, reads out the status and displays it. Information is simple: "SPD
OK" or "Replace SPD!". This test is carried out easily within a matter of
seconds and without removing the SPD. The test can be carried out at any
time without interruption as it does not interrupt signal transmission.

www.dehn.de

361

LifeCheck SPD Test Device


DRC LC M3+

MEASURING AND TEST DEVICES


910 653

NEW

DRC LC M3+
910 653

The database function allows easy documentation


of the test results on the PC

Fast testing of LifeCheck-equipped


SPDs
Hand-held device, easy transport and
operation

NEW

Snap-on LifeCheck sensor

Portable device with LifeCheck sensor for flexible use. For fast and easy testing of LifeCheckequipped arresters. Visual and acoustic indication. With additional USB connection and database
software for PC-aided management of test objects and documentation of the test results. DRC LC
M3+ features a new snap-on LifeCheck sensor, allowing to test the SPD without holding the sensor. The handheld device allows parameterisation of SPDs for condition monitoring.

With database function for documentation


Easy and fast parameterisation of
SPDs for condition monitoring with
LifeCheck

DRC LC M3+
For testing
Voltage supply (included in delivery)
RFID transmission frequency
Measured value indication
Testing period
Operating temperature range
Battery test
Cable length to LifeCheck sensor
Dimensions of LifeCheck sensor
Dimensions of handheld device
Delivery includes
Dimensions of storage case

BLITZDUCTOR XT ML
BLITZDUCTOR XT ML EX; for use in non-hazardous atmospheres only!
Li-ion battery
125 kHz
beep and LCD
typically 3 to 10 sec.
-10C...+65C
automatic switch-off in case of flat battery
approx. 1000 mm
90 x 51 x 12 mm
166 x 95 x 30 mm
handheld device, LifeCheck sensor BXT, charging device, USB cable,
test module for reference, software CD, storage case
340 x 275 x 83 mm

Ordering information
Type
Part No.
Packing unit

DRC LC M3+
910 653
1 pc(s).

Accessory Part for LifeCheck SPD Test Device


910 652
BXT
910 654
BCT

LCS DRC BXT


Sensor fr DRC BXT
LCS DRC BCT
Sensor fr DRC BCT

LCS DRC
LCS DRC

LifeCheck910 652
LifeCheck910 654

LifeCheck Sensor for DRC BXT / BCT


LifeCheck sensor and test module for use as spare part / extension for
portable LifeCheck test devices.
Type
LCS DRC BXT
LCS DRC BCT

362

Testing of
BLITZDUCTOR XT ML
BLITZDUCTOR CT MLC

PU
pc(s).
1
1

Part
No.
910 652
910 654

www.dehn.de

DRC LC M3+

MEASURING AND TEST DEVICES

SPD Test Device

For routine tests of surge protective devices


Compact dimensions
Suitable for mains and battery operation
Low-battery indicator
Test cables included in delivery
Test adapter included as accessory part,
protected against accidental contact

For testing the sparkover voltage of surge arresters. The sample to be tested is connected via the included test cables or special test adapters.

The PM 20 SPD test device with integrated sparkover detection allows to


test Yellow/Line or Red/Line surge arresters with integrated varistor, Zener
diode or gas discharge tube. Both the response performance between the
connections of the SPDs as well as the continuity can be tested. The
results can be compared to reference values. In case of deviations, the SPD
or SPD module has to be replaced. Test adapters with a corresponding
support make testing of the SPD modules easier.

Scope of the delivery of PM20 SPD test device

www.dehn.de

363

SPD Test Device


PM 20

MEASURING AND TEST DEVICES


910 511

PM 20
910 511

Combined testing of protective circuits with gas discharge tubes, varistors and zener diodes

Combined device for testing the sparkover voltage of surge arresters (with gas discharge
tubes/varistors/zener diodes). Storage bag and measuring accessories included.

Easy handling and flexible use


For use with PA BXT and PA DRL test
adapters

PM 20
Nominal d.c. voltage UN
8-12 V d.c.
Test parameter: Test voltage
max. 1250 V d.c.
Test parameter: Test current (reference voltage)
1 mA d.c., constant
Measured value indication
alphanumeric, 8-digit LCD display
Test output sockets
safety pole terminals (4 mm), positive pole: red colour, negative pole: black colour
Testing period
1.5 sec.
Number of individual tests during battery operation
typically 2000
Accessories included in delivery
2 test cables, each 1 m long, 2 safety tapping test clips, 1 plug-in power supply unit (230 V a.c.), 1 storage bag
Dimension of storage bag
300x 110 x 110 mm
Ordering information
Type
Part No.
Packing unit

PM 20
910 511
1 pc(s).

Accessory Part for SPD Test Device


910 507

PA DRL
910 507

PA DRL

PA DRL test adapter

910 508

For connecting to PM 10 / PM 20 and for plugging in and testing SPD


modules
Type
PA DRL

364

Accessory Part for SPD Test Device

Plug-in SPD modules


DEHNrapid LSA and DPL

PU
pc(s).
1

Part
No.
910 507

PA BXT
910 508

PA BXT

PA BXT test adapter


For connecting to PM 10 / PM 20 and for plugging in and testing SPD
modules
Type
PA BXT

Plug-in SPD modules


BLITZDUCTOR XT and BLITZDUCTOR CT

PU
pc(s).
1

Part
No.
910 508

www.dehn.de

PM 20

MEASURING AND TEST DEVICES

DEHNisola
SPD monitoring device
SPD monitoring device for potential-free measuring of leakage currents of surge arresters
Measuring and evaluation device with a compact DIN rail mounted enclosure (1.5 modules)
3 hard-wired winding-type transformers
Self-test and reset function
Battery supply
2 limit values for the leakage currents to be
monitored
LED indication on site and remote signalling
contact

Continuous function test of installed lightning current and surge arresters


by DEHNisola monitoring device.

910 600

DISO 3

DISO 3
DEHNisola

910 600

Dimension drawing DISO 3

DEHNisola: Measuring and evaluation device with 3 hardwired winding-type transformers and fixing
material

DISO 3: Measuring and evaluation unit with 3 winding-type transformers


DISO 3

Indication of limit value 1 IL


0.5 mArms (indication only on site, will be reset when the value falls below the limit value)
Indication of limit value 2 IL
5 mArms (indication on site and remote signalling, will be reset only by pushing the reset button at the device)
Measuring cycle
every hour or acyclically after every discharge process of the protective device to be monitored
Self-test
generation of fault currents in each sensor for testing the measuring unit, reset > 2 sec.
Battery supply
battery life: approx. 10 years, LowBatt indication and remote signalling
Remote signalling contact: Max. a.c. switching voltage
125 V
Remote signalling contact: Max. d.c. switching voltage
110 V
Remote signalling contact: Max. switching capacity
30 W
Remote signalling contact: Max. switching current
1A
Remote signalling contact: Cross-sectional area
0.5 to 4 mm2
Operating temperature range
-25C...+60C
For mounting on
35 mm DIN rail acc. to EN 60715
Enclosure material of measuring and evaluation device
thermoplastic, red, UL 94 V-0
Degree of protection of measuring and evaluation device
IP 20
Dimension of measuring and evaluation device
1.5 mods., DIN 43880
Dimension of sensors
inner 11 mm, outer 33 mm
Length of the sensor lines
300 mm each
Weight
0.23 kg
Ordering information
Type
Part No.
Packing unit

www.dehn.de

DISO 3
910 600
1 pc(s).

365

Impulse Meter
Registration of discharges

MEASURING AND TEST DEVICES

Potential-free registration of discharge currents of surge protective devices


Easy installation by enclosing the earth conductor of the arrester with an open toroidal core
Counter in a DIN rail mounted enclosure
(2 modules)
Twisted sensor cable, 1 m long

P2 Impulse Meter: Counter, sensor cable and toroidal core


with fixing material
Counter with integrated battery supply (9 V) and battery
charge control. Indication by 2-digit LCD display with setting
and resetting buttons.
L1

Imp
uls
zh

ler

P2

910 502

P2

P2
Meter P2

Impulse
910 502

Dimension drawing P2
P2
Response wave for impulse currents (rise time 8 s)
> 1 kA
Sequence of impulses
>1s
LCD display
electronic counter 0...99
Power supply
9 V battery, IEC 6LR61 included in delivery, replaceable, battery life > 1 year
Battery charge control
button and LED situated at device
Setting device
button at device for setting the counter (e.g. after replacing a battery)
Resetting device
button at device for resetting the counter to 0
Operating temperature range
-10C...+50C
For mounting on
35 mm DIN rail acc. to EN 60715
Enclosure material (counter)
thermoplastic, red, UL 94 V-0
Enclosure material (sensor)
PA 6, grey colour
Degree of protection
IP 20
Dimension (counter)
2 mods., DIN 43880
Dimension (sensor)
inner 15 mm, outer 36 mm
Length of the connecting cable (between sensor and counter)
max. 1 m, twisted
Weight (counter, sensor and connecting cable)
0.2 kg
Accessories included in delivery
9 V battery, IEC 6LR61; cable tie (fixing of sensors)
Ordering information
Type
Part No.
Packing unit

366

P2
910 502
1 pc(s).

www.dehn.de

More Information and Documentation


Publications

DEHN CD

Seminars

DS103

DEHN protects Wind Turbines.

We also give seminars about

DS104

DEHN protects Cell Sites.

DS707 DEHNtour
DEHN + SHNE Company
Presentation

DS107

Surge Protection: Safety for Sewage


Plants.

DS109

DEHN protects Photovoltaic Systems.

DS113

DEHN tests and analyses.

DS122

DEHN protects the Oil and Gas


Industry.

DS137

DEHN protects Antenna Feeders.

DS143

BLITZDUCTOR XT with LifeCheck.

DS144

DEHN protects Biogas Plants.

DS708 3D Animated films


DEHN protects photovoltaic systems
DEHNguard T H...LI
with Pro-Active-Thermo-Control
New Red/Line-DEHNventil modular
DEHN protects Cell Sites
Protection of Ex (i) circuits
Maintenance strategy with
BLITZDUCTOR XT

61E Surge Protection Practice-Oriented and


Standard-Conform; from etz, 10/2006

DS164E BLITZDUCTOR XTU

63E Lightning and Surge Protection for


Telecommunications and Signalling
Networks; from etz, 02/2007

Easy choice surge protection.

DS509

DEHN protects.

Surge Protection
Safety Equipment
as well as protection for special applications
like cell sites, photovoltaics, wind turbines, etc.
For more information regarding topics, dates,
locations, etc., please contact the responsible
representative of DEHN + SHNE in your
country. They shall be pleased to give you the
requested information.

Reprints

DS145E LSA with Lightning Current Carrying


Capacity.

DS150

Lightning Protection

Note
Like our catalogues and publications, our
installation and mounting instructions
can also be downloaded from our website
www.dehn.de.

DS614E DEHN stops Surges.

Contact

DS641E Coordinated Surge Protection.

The printed publications can be ordered free of


charge from our Export Department
Fax +49 9181 906-444
export@dehn.de

DS649E Surge Protection Easy choice.


DS702E Lightning Protection Guide

Further main catalogues


DS396E Safety Equipment
DS427E Lightning Protection

www.dehn.de

367

Literature
DIN VDE Standards, VDE-Verlag, Berlin

DIN EN 62305-1

DIN VDE 0800-1:1989-05

DIN VDE 0100-100:2009-06

VDE 0185-305-1:2006-10
Protection against lightning Part 1:
General principles (IEC 62305-1:2006);
German version EN 62305-1:2006

Telecommunications;
General concepts; requirements and tests for
the safety of facilities and apparatus

Low-voltage electrical istallations - Part 1:


Fundamental principles, assessment of general
characteristics, definitions (IEC 60364-1:2005,
modified);
German implementation HD 60364-1:2008
DIN VDE 0100-410:2007-06
Low-voltage electrical installations Part 4-41:
Protection for safety Protection against
electric shock
(IEC 60364-4-41:2005, modified);
German implementation HD 60364-4-41:2007
DIN VDE 0100-540:2007-06
Low-voltage electrical installations Part 5-54:
Selection and erection of electrical equipment
Earthing arrangements, protective conductors and protective bonding conductors
(IEC 60364-5-54:2002, modified);
German implementation HD 60364- 5-54:2007
DIN VDE 0100-443:2007-06
Low-voltage electrical installations Part 4-44:
Protection for safety Protection against
voltage disturbances and electromagnetic
disturbances Clause 443: Protection against
overvoltages of atmospheric origin or due to
switching
(IEC 60364-4-44:2001 + A1:2003, modified);
German implementation HD 60364-4-443:2006
DIN VDE 0100-534:2009-02
Low-voltage electrical installations - Part 5-53:
Selection and erection of electrical equipment Isolation, switching and control - Clause 534:
Devices for protection against overvoltages
(IEC 60364-5-53:2001/A1:2002 (Clause 534),
modified);
German implementation HD 60364-5-534:2008
DIN EN 60664-1
DIN VDE 0110-1:2008-01
Insulation coordination for equipment within
low-voltage systems Part 1: Principles,
requirements and tests
(IEC 60664-1:2007) German version
EN 60664-1:2007
DIN VDE 0141:2000-01
Earthing system for special power installations
with nominal voltages above 1 kV
DIN EN 50178
DIN VDE 0160:1998-04
Electronic equipment for use in power installations
German version EN 50178:1997

368

DIN EN 62305-2
VDE 0185-305-2:2006-10
Protection against lightning Part 2:
Risk management (IEC 62305-2:2006);
German version EN 62305-2:2006
DIN EN 62305-3
VDE 0185-305-3:2006-10
Protection against lightning Part 3:
Physical damage to structures and live hazard
(IEC 62305-3:2006, modified);
German version EN 62305-3:2006
DIN EN 62305-4
VDE 0185-305-4:2006-10
Protection against lightning Part 4: Electrical
and electronic systems within structures
(IEC 62305-4:2006);
German version EN 62305-4:2006

DIN VDE 0800-2:1985-07


Telecommunications;
Earthing and equipotential bonding
DIN VDE 0800-10:1991-03
Telecommunications;
Transitional requirements on erection and
operation of installations
DIN EN 50114
DIN VDE 0805-514:2009-04
Audio, video and information technology
equipment - Routine electrical safety testing
in production;
German version EN 50514:2008
DIN EN 41003
DIN VDE 0804-100:2009-04
Particular safety requirements for equipment to
be connected to telecommunication networks;
German version EN 41003:2008

DIN EN 50164-1
DIN VDE 0185-201:2009-03
Lightning protection components (LPC)
Part 1: Requirements for connection components
German version EN 50164-1:2008

DIN VDE 0845-1:1987-10

DIN IEC 60060-1

E DIN VDE 0845-2:1993-10

DIN VDE 0432-1:1994-06


High voltage test techniques Part 1: General
specifications and test requirements
(IEC 60060-1:1989 + corrigendum March
1990); German version HD 588.1 S1:1991

Protection of information technology and


telecommunication against lightning, electrostatic discharges and overvoltages from electric
power installations; requirements and tests of
overvoltage protection devices

DIN VDE 0618-1:1989-08

DIN EN 60728-11

Equipment for equipotential bonding; equipotential bonding busher for main equipotential
bonding

VDE 0855-1:2005-10
Cable networks for television signals, sound
signals and interactive services
Part 11: Safety (IEC 60728-11:2005);
German version EN 60728-11:2005
remain valid alongside this standard until
2008-04-01.

DIN EN 60099-1
DIN VDE 0675-1:2000-08
Surge arresters Part 1: Non-linear resistor
type gapped surge arresters for a.c. systems
(IEC 60099-1:1991)
German version EN 60099-1:1994 + A1:1999

Protection of telecommunication systems


against lightning, electrostatic discharges and
overvoltages from electric power installations;
provisions against overvoltages

DIN 18014:2007-09
Foundation earth electrode General planning
criteria

DIN EN 61643-11
VDE 0675-6-11:2007-08
Low-voltage surge protective devices
Part 11: Surge protective devices connected to
low-voltage power systems; Requirements and
tests
(IEC 61643-1:1998 + corrigendum 1998, modified); German version EN 61643-11:2002 +
A11:2007

IEC 60664-1:2007-04
Insulation coordination for equipment within
low-voltage systems; part 1: principles,
requirements and tests
IEC 61643-1:2005-03
Low-voltage surge protective devices Part 1:
Surge protective devices connected to lowvoltage power distribution systems
Requirements and tests

www.dehn.de

IEC 61643-21:2000-09

Books

Low voltage surge protective devices


Part 21: Surge protective devices connected to
telecommunications and signalling networks
Performance requirements and testing methods

Hasse P., Wiesinger J., Zischank W.:


"Handbuch fr Blitzschutz und Erdung"
[Lightning Protection and Earthing Guide]
Pflaum Verlag GmbH & Co.KG, Munich,
5th edition of 2006, ISBN 3-7905-0931-0

IEC 62305-1:2006-01
Protection against lightning Part 1:
General principles
IEC 62305-3:2006-01
Protection against lightning Part 2:
Risk
management
IEC 62305-3:2006-01
Protection against lightning Part 3:
Physical damage to structures and life hazard
IEC 62305-4:2006-01
Protection against lightning Part 4: Electrical
and electronic systems within structures

Hasse P., Landers U., Wiesinger J.,


Zahlmann P.:
"EMV-Blitzschutz von elektrischen und
elektronischen Systemen in baulichen
Anlagen Risiko-Management, Planen und
Ausfhren nach den neuen Normen der
Reihe VDE 0185-305
2. vollstndig berarbeitete und erweiterte
Auflage 2007, [EMC-based lightning protection for electrical and electronic systems
installed into structures Risk management, design and performance according
to new standard series DIN VDE 0185-305,
2nd completely revised and amended
edition of 2007], series volume No. 185,
Berlin-Offenbach: VDE Verlag GmbH,
ISBN 9-783800-730018

Raab V.:
"berspannungsschutz in Verbraucheranlagen Auswahl, Errichtung, Prfung"
[Surge protection for consumers installations Selection, Installation and Testing],
Huss-Medien GmbH Verlag Technik, Berlin
2nd updated and amended edition of 2003
ISBN 3-341-01347-4
Raab P., Zahlmann P.:
"Loseblattsammlung VDE-Kompass"
[VDE Guide Loose leaf collection]
InfoPLUS-Paket 6 (12th supplemental set)
"Neue Blitzschutz-Normen in der Praxis",
[New lightning protection standards in
practice], VDE Verlag, Berlin Offenbach

VG Standards, Beuth-Verlag GmbH


VG 95 372:2009-04
Electromagnetic Compatibility (EMC) including
Electromagnetic Pulse (EMP) and Lightning
Protection Survey
VG 95 371-10:2003-08
Electromagnetic compatibility (EMC) including
electromagnetic pulse (EMP) and lightning protection Fundamentals Part 10: Threat levels
for NEMP and lightning
VG 96 907-1:2006-10
Nuclear Electromagnetic Pulse (NEMP) and
lightning protection Design guidelines and
protective devices Part 1: Fundamentals

Legal Notes
Since we do not carry out the design of systems
or system components, the suggested application of our products should be regarded as product information and for advisory purposes only.
Our oral and written advice on application is
based on experience and given to the best of our
knowledge. However, it must be also considered
as not binding. This particularly applies to the

different conditions of use which are beyond our


control. We recommend to check whether the
respective DEHN product is suitable for the
intended application.
Application, use and processing of our products
take place beyond our control. Therefore, the
product is completely subject to the users responsibility.

Further Standards
DVGW GW 309: Elektrische berbrckung bei
Rohrtrennungen [Electrical bridging of separate
pipe sections]. ZfGW-Verlag GmbH, Frankfurt.

Trademarks
actiVsense

Arbeitsgemeinschaft DVGW/VDE fr Korrosionsfragen (AfK): AfK-Empfehlung Nr. 5/02.86,


Kathodischer Korrosionsschutz in Verbindung
mit explosionsgefhrdeten Bereichen [German
Corrosion Protection Committee (AfK): AfK recommendation No. 5/02.86, Cathodic corrosion
protection in connection with potentially explosive areas] ZfGW-Verlag GmbH, Frankfurt

BLITZDUCTOR
DEHNbloc
DEHNguard
DEHNport
DEHNrapid
DEHNventil

KTA 2206/2000-06: Auslegung von Kernkraftwerken gegen Blitzeinwirkung [Protection for


nuclear power plants against lightning effects]

www.dehn.de

and our brand

LifeCheck

are registered trademarks of


DEHN + SHNE GMBH + CO. KG.
in Germany

...MIT SICHERHEIT DEHN.

369

General Terms of Sale


1. General, Scope
1.1 All deliveries and services in business dealings with
entrepreneurs take place exclusively under our general
terms of sale (hereinafter terms of sale). We oppose
deviating regulations, especially conflicting terms of purchase of the customer, unless we expressly agreed to the
validity in writing. Our terms of sale apply even if we
complete unconditional delivery to the customer while
knowing that the terms of sale of the customer are in
conflict with our own.
1.2 Our terms of sale only apply to entrepreneurs within the
meaning of section 310, paragraph 1 of the German Civil
Code (BGB), to current business relationships and to all
future transactions with the customer.
2.
2.1

2.2

2.3

2.4

2.5

2.6

Offer and Order, Reservation of Right of Modification and Copyright


Insofar as not expressly indicated by us as binding, documents such as diagrams, drawings, and measurements
are only roughly binding.
Should our order confirmation contain reasonable expansions, limitations, or other modifications with respect to
the order, then the customers agreement is implied, if it
does not immediately, at the latest however within 3
business days from receipt of the order confirmation,
oppose it.
Any order placed in our web shop shall be regarded as an
offer to conclude a sales contract. A sales contract only
comes into existence if the customer receives a written
order confirmation or the goods are delivered / services
are rendered.
Our goods are only delivered in the packaging units indicated in the catalogues. If a different number of items is
ordered, the amount and price of the next larger packaging unit is considered agreed upon.
We reserve the right to make technical modifications to
our services, insofar as such modifications promote technical progress or are unavoidable based on other circumstances and are reasonable for the customer.
We reserve ownership and copyright rights to diagrams,
drawings, calculations, and other documents; these may
not be made available to third parties without our
express written consent.

3. Prices, Value-Added Tax, Packaging Costs


3.1 Our prices are subject to change without notice.
3.2 Prices include, insofar as nothing else is arranged, customary packaging from our plant without value-added
tax. On the day of invoicing, the legally identified VAT
amount is to be reimbursed to us.
3.3 The cost of non-customary packaging, e.g., collective or
seaworthy packaging, is invoiced separately. The customer bears the cost of the disposal or return of packaging.
4.

5.
5.1

5.2

5.3

5.4

370

Passing of Risk, Optional Insurance


The risk of accidental loss, destruction, or deterioration
passes to the customer upon dispatch to the customer
from our plant, even if carriage-paid delivery is agreed
upon. At the request and expense of the customer, we
will insure the delivery against breakage, damage to
goods in transit and fire damage.
Payment Due Dates, Discounts, Right of Refusal,
Default, Small Order Quantity Surcharge
Unless otherwise agreed, invoices are payable net 10
days. Purchaser shall pay the costs of payment. Discount
amounts are deductible only if they have been agreed on
with us and all accounts payable due have been paid.
If purchaser is in default with his payments, interest on
the outstanding amount shall be payable at the rate of
8 % above the base interest rate. We reserve the right to
prove and allege higher default damages. We reserve the
right to cause default by demanding early payment. If we
are required to advance performance and, if after the
execution of the contract, it becomes apparent that our
claim, in particular for payment, may be jeopardised by
purchasers inability to perform we may refuse performance.
The customer cannot charge counter-claims against our
due payment claims or exercise a right of retention,
unless the customer is entitled to a claim recognised by
declaratory judgement that is not contested by us and if,
while exercising the right of retention, the counter-claim
from the customer is based on the same contractual relationship.
Orders, with the exception of cash sales, for which the
net amount (invoiced amount without shipping costs and
value-added tax) is less than 75.00, a small order surcharge of 25.00 will be charged.

6. Retention of Title, Assignment, Release of Securities


6.1 Delivered goods remain our property until the payment
of all open business claims up to the point of invoicing.
The claims of the customer including value-added tax
from the resale of reserved goods, i.e., from a work performance using our goods, should already be transferred
to us in the amount of the open invoice. In the case that
the reserved goods from the customer are sold together
with other goods that do not belong to us, whether it be
without or after processing, or are delivered within the
framework of a working contract, the assignment of the
resulting claim of the reserve buyer is calculated in the
amount of the value of the reserved goods.
6.2 Should the value of the granted securities exceed the
claims by more than 10 %, we are obliged to retransfer
or release the securities upon request. We shall select the
securities to be released.
6.3 Our goods may only be transferred within the framework
of proper business activity. The customer is not allowed
to pawn or transfer the ownership of goods that are still
in our possession.
6.4 At our request, the customer is obliged to inform us of
the purchaser and the arranged price and to show the
assignment to its debtor.

10. Return of Goods without Legal Liability


10.1 If no legal claim to return exists, delivered goods will
be accepted only with previous agreement from us.
Returns without previous agreement will be send back
postage-due to the sender without inspection. The
customer bears the shipping costs for the return delivery
in No. 10.1.
10.2 The goods must still be in their original packaging.
Special orders or deliveries, which date back more than
three months or the net value of which is less than
75.00, cannot be returned. A processing fee of 15 % of
the net value of the goods will be charged to cover the
cost of the return. If the goods can no longer be resold at
the list price at the time of the return, an additional
deduction (old goods deduction) will be made in addition
to the processing fee. If we make an exception and agree
to accept the return of parts that are unpackaged or that
are no longer in their original packaging, an expense
remuneration of at least 15 % will be charged for
reworking and repackaging in addition to the processing
fee and, if applicable, the old goods deduction.
10.3 Returned goods will only be credited to a new invoice.
Credits cannot be used to clear invoices due at the time
of the return.

7. Delivery Period and Appointment


7.1 The start of the delivery period presupposes the involvement of the customer for the clarification of all technical
questions.
7.2 Delivery periods as well as delivery schedules will be
appropriately extended if they cannot be adhered to as a
result of military mobilisation, war, uprising, strike or
lockout, delayed delivery of raw and auxiliary materials,
late delivery by our suppliers, or similar circumstances
beyond our control. A lasting obstruction under these circumstances gives us the right to withdraw from the contract without liability for damages.

11. Product Information, No Advisory Obligation


Our deliveries are intended only for speciality stores or
skilled users. Our user information and instructions are
limited to the details of each written product information
(e.g., installation instructions, catalogues, data sheets).
Further advisory obligations do not exist. Application,
use, and processing of the products lie solely in the customers realm of responsibility.

8. Liability for Material and Title Defects


8.1 Insofar as there exists a defect of the contract subject
that was beyond our control, we can choose to fix the
defect or provide a defect-free contract subject (replacement).
8.2 Should the replacement (No. 8.1) not function properly,
or should it be unreasonable to the customer, or should
we seriously and conclusively refuse it or unreasonably
delay it, or if other circumstances exist that, upon weighing mutual interests, justify immediate resignation or
compensation, then the customer is entitled to choose to
lower the contract price or to withdraw from the contract
and/or demand compensation (No. 8.3). The customer is
not entitled to withdraw from the contract if only
insignificant contract inconformities exist, especially
insignificant defects.
8.3 Should the customer exclusively choose compensation
after proper replacement (No. 8.2), the contract subject
remains with the customer, if it considers this reasonable.
Compensation is limited to the difference between the
purchase price (without value-added tax) and the value
of the defective subject of the contract that remains with
the customer.
8.4 Material and title defect claims, including claims for compensation due to material and title defects, with the
exception of claims under the Product Liability Act, lapse
12 months after delivery of the goods.
8.5 Numbers 8.1 through 8.4 do not impair the customers
rights if we maliciously concealed a defect or if we
offered a quality guarantee.

12. Use and Protection of Customer Data


We use customer data, which concern the business dealings with the customer, in terms of the Federal Data
Protection Act.
13. Applicable Law, Jurisdiction
13.1 German law applies to the mutual contractual obligations, their materialisation, interpretation, and implementation as well as all resulting contractual and business relationships. The application of the UN Agreement
on Contracts on the International Purchase of Goods and
the thereafter enacted laws of the Federal Republic of
Germany is excluded.
13.2 Place of performance and jurisdiction for delivery, payment, and for all obligations, including those from exchange and cheque payments, is exclusively Nuremberg.
We reserve the right to file a complaint against the customer at its official location.
14. VAT Identification Number
VAT ID No. DE 133251475

DEHN + SHNE GmbH + Co. KG.


Nrnberg Neumarkt
Update July 2009

9. Liability for Other Reasons


9.1 Our liability is excluded for slightly negligent infringement of immaterial contractual obligations. Our liability
is limited to the contractual, foreseeable damage for
negligent infringement of other obligations.
9.2 The above regulation does not apply to claims under the
Product Liability Act. Insofar as the limitation on liability
pursuant to No. 9.1 for claims from the producers liability pursuant to 823 of the German Civil Code does not
interfere, our liability is limited to the replacement of the
insurance. Insofar as this does not occur or does not
occur in full, we are liable up to the insured amount.
9.3 Insofar as our liability is excluded or limited, this also
applies for the personal liability of all of our employees,
representatives, and vicarious agents.
9.4 Our liability is unrestricted if the customer loses his/her
life or suffers a bodily or health injury due to an action or
failure attributable to us.

www.dehn.de

Key to Symbols used in Basic Circuit Diagrams


Symbol

Description

Standard

Description

Standard

Creepage discharge spark gap,


energy-controlled, encapsulated
(DEHNventil TNC/TNS/TT/2P/2P TT)

Gas discharge tube


(single)
tA 100 ns

EN 60617
Part 7
07-22-04

Creepage discharge spark gap,


non-exhausting, encapsulated
(DEHNbloc, DEHNbloc NH)

Gas discharge tube


(balanced)
tA 100 ns

EN 60617
Part 7
07-22-05

Creepage discharge spark gap

Resistor,
Decoupling element,
general

EN 60617
Part 4
04-01-01

EN 60617
Part 4
04-01-04

Capacitor

EN 60617
Part 4
04-02-01

EN 60617
Part 7
07-09-03

Inductor

EN 60617
Parts 7 + 11
07-09-03
111-07-02

Resistor,
temperature-controlled

Spark gap, general

EN 60617
Part 7
07-22-01

Socket and plug connector

EN 60617
Part 3
03-03-05

Fuse

EN 60617
Part 7
07-21-01

Break contact

EN 60617
Part 7
07-02-03

Changeover contact

EN 60617
Part 7
07-02-04

Close contact

EN 60617
Part 7
07-02-01

Enclosure with
terminals

EN 60617
Parts 2 + 3
02-01-07
03-02-02

Acoustic signal

EN 60617
Part 8
08-10-05

Varistor
tA 25 ns

Thermal disconnector

Thermo Dynamic Control

Temperature fuse

www.dehn.de

Filter, general

EN 60617
Part 10
10-16-03

LED, general

EN 60617
Part 8
08-10-01

Suppressor diode, bipolar


tA 1 ns

EN 60617
Part 5
05-03-07

Z diode, unipolar
tA 1 ns

EN 60617
Part 5
05-03-06

Symbol

371

Part No. Index


Part No. Type

Page

106 310
106 329

279
279

277 230
277 237
277 239
277 240

FBH 6 ST
FBH 6 CU
FBH 6 V2A
FBH 11 ST

357
357
357
357

290 001
290 002

AH FE RF V G
AH FE RF

357
357

308 001
308 025
308 026
308 030
308 040
308 041
308 120
308 129
308 150
308 403
308 404
308 405
308 406
308 407
308 408
308 411
308 421
308 425

KV FE UNI
VK A UNI ST
VK A UNI V2 ST
VK A R22 F40 STBL
MMVK R16 R25 STBL
MMVK R16 R25 ST
VK EH R10 F30 ST
VK EH R10 F30 V2A

SAK 10 AS V4A
SAK 14 AS V4A
SAK 18 AS V4A
SAK 21 AS V4A
SAK 26 AS V4A
SAK 33 AS V4A
AK 16 AS SAK MS
AS SAK 1000 V2A
ST AS SAK K

357
357
357
357
357
357
357
357
357
326
326
326
326
326
326
327
326
327

416 411

279

472 021
472 022
472 023
472 024
472 109
472 119
472 129
472 139
472 201
472 207
472 209
472 210
472 217
472 219
472 227
472 229
472 237
472 239
472 269
472 279
472 289
472 299

ES 2X6AP 10 ST
ES 2X3AP 10 ST
ES 2X2AP 10 ST
ES 2X4AP ST
ES 2X2AP 10 V2A
ES 2X3AP 10 V2A
ES 2X4AP 10 V2A
ES 2X6AP 10 V2A
BS M10 PAS
PAS I 6AP M10 CU
PAS I 6AP M10 V2A
IS PAS M10
PAS I 10AP M10 CU
PAS I 10AP M10 V2A
PAS I 8AP M10 CU
PAS I 8AP M10 V2A
PAS I 12AP M10 CU
PAS I 12AP M10 V2A
AD PAS 8AP V2A
AD PAS 6AP V2A
AD PAS 10AP V2A
AD PAS 12AP V2A

356
356
356
356
356
356
356
356
356
356
356
356
356
356
356
356
356
356
356
356
356
356

540 801
540 803
540 805
540 810
540 821
540 901

EX BRS 90
EX BRS 300
EX BRS 500

EX BRS 27

351
351
351
352
351
352

372

Part No. Type

Page

563 010
563 011
563 012
563 013
563 014
563 015
563 016
563 017
563 018
563 019
563 020
563 030
563 050
563 105
563 169
563 200
563 201
563 222

PAS 10RK
RK 16 PAS
RK FL30 PAS
RK 95 PAS
SB PAS RK
AH PAS RK
KS 198 PAS
KS 398 PAS
KS 798 PAS
RK FL40 PAS
PAS 9RK
PAS 14RK
PAS 9AK
PAS 6RK OH
AK RPA V2A
PAS 11AK
PAS 11AK UV
AK FL40 PAS

355
355
355
355
355
355
355
355
355
355
355
355
355
355
357
355
355
355

900 050
900 120
900 132
900 159
900 216
900 220
900 222
900 255
900 261
900 262
900 263
900 264
900 269
900 270
900 271
900 273
900 330
900 390
900 391
900 411
900 417
900 471
900 589
900 595
900 610
900 611
900 612
900 614
900 615
900 617
900 813
900 814
900 815
900 848

DGPM 1 255 S
DB 3 255 H
DGP BN 255
DB 1 440
T C H 255
DBM 1 255 S
DB 1 255 H
DBM NH00 255
V NH00 280
VA NH00 280
V NH00 280 FM
VA NH00 280 FM
DGP B NH00 N 255
V NH1 280
VA NH1 280
DB NH00 255 H
DLM PV 1000
DV ZP TNC 255
DV ZP TT 255
EB DG 1000 1 3
EB 1 4 9
VC 280 2
STAK 2X16
MVS 3 6
MVS 1 4
MVS 1 8
MVS 1 57
MVS 4 56
MVS 1 3
MVS 1 2
MVS 3 6 8
MVS 4 8 11
MVS 1 6
MVS 1 7

65
59
66
61
102
55
59
50
116
117
116
117
67
116
117
60
43
40
41
151
151
144
145
150
149
150
150
151
149
149
150
151
149
150

902 315
902 471
902 472
902 485

IGA 10 V2 IP54
IGA 12 IP54
IGA 24 IP54
IGA 6 IP54

146
147
147
148

906 055

ALGA 5

334

Part No. Type

Page

906 058
906 059
906 100
906 101
906 102
906 103

ALGA 5 X
MS ALGA 5 X
DPG LSA 30 P
DPG LSA 60 P
DPG LSA 120 P
DPG LSA 220 P

334
335
242
242
242
242

907 208
907 214
907 216
907 217
907 218
907 219
907 400
907 401
907 420
907 421
907 422
907 423
907 424
907 425
907 430
907 440
907 441
907 442
907 443
907 444
907 445
907 465
907 470
907 497
907 498
907 499
907 991
907 993
907 994
907 995
907 996
907 997

GDT 230 G3
DPL 10 G3 110
DPL 10 G3 110 FSD
GDT 230 G3 FSD
GDT 230 B3
GDT 230 B3 FSD
DRL 10 B 180
DRL 10 B 180 FSD
DRL RE 5
DRL RE 12
DRL RE 24
DRL RE 48
DRL RE 60
DRL RE 180
DRL PD 180
DRL RD 5
DRL RD 12
DRL RD 24
DRL RD 48
DRL RD 60
DRL RD 110
DRL HD 5
DRL HD 24
SR DRL
EF 10 DRL
BM 10 DRL
TL2 10DA CC
EL2 38EA LSA
AW2 LSA
MB2 10 LSA
TL2 10DA LSA
AL2 10DA LSA

240
240
240
240
238
238
231
232
233
233
233
233
233
233
235
234
234
234
234
234
234
236
236
238
237
238
245
244
243
243
244
244

909 230
909 235
909 240
909 245
909 300
909 305
909 310
909 315
909 320
909 325
909 321
909 326
909 703
909 704
909 705
909 710
909 711

DPRO 230
DPRO 230 SE
DPRO 230 F
DPRO 230 SE F
DPRO 230 TV
DPRO 230 SE TV
DPRO 230 NT
DPRO 230 SE NT
DPRO 230 ISDN
DPRO 230 SE ISDN
DPRO 230 LAN100
DPRO 230 SE LAN100
DGA FF TV
DGA GF TV
DGA GFF TV
DGA BNC VCD
DGA BNC VCID

139
139
140
140
338
338
339
339
340
340
341
341
272
272
272
271
271

910 099
910 486

SLK 16
USB NANO 485

335
360

Part No. Type

Page

910 502
910 507
910 508
910 511
910 600
910 631
910 641
910 642
910 652
910 653
910 654
910 695
910 697

P2
PA DRL
PA BXT
PM 20
DISO 3
DSI E 3
LWL ST DSI
LWL DSI 18M
LCS DRC BXT
DRC LC M3+
LCS DRC BCT
DRC MCM XT
TW DRC MCM EX

366
364
364
364
365
57
57
57
362
362
362
360
319

912 253
912 254
912 260
912 261

SPS PRO
NF 10
SFL PRO
SFL PRO SE

127
125
142
142

918 400
918 401
918 402
918 404
918 405
918 407
918 408
918 410
918 411
918 420
918 421

BVT TTY 24
BVT RS485 5
BVT AD 24
BVT KKS ALD SN
BVT KKS APD SN
BVT MTTY 24
BVT ALD 36
BVT ISDN
BVT TC 1
BVT KKS ALD 75
BVT KKS APD 36

219
221
222
227
228
220
223
257
258
225
226

919 010
919 011
919 012
919 013
919 014
919 015
919 016
919 030
919 031
919 032
919 033
919 034
919 035
919 036
919 037
919 038
919 880
919 920
919 921
919 922
919 923
919 940
919 941
919 942
919 943
919 960
919 970
919 976
919 977

SAK 6.5 SN MS
SAK 11 SN MS
SH1 18X3 ST
SH2 18X3 ST
SH 18X3 K
AK 35 SN 18X3 GG
SN 18X3 CU 1000
SKB 19 9M SW
SA KRF 10 V2A
SA KRF 15 V2A
SA KRF 22 V2A
SA KRF 29 V2A
SA KRF 37 V2A
SA KRF 50 V2A
SA KRF 70 V2A
SA KRF 94 V2A
KB 10 DCO RK
DCO RK ME 12
DCO RK ME 24
DCO RK ME 48
DCO RK ME 110
DCO RK MD 12
DCO RK MD 24
DCO RK MD 48
DCO RK MD 110
DCO RK MD EX 24
DCO RK MD HF 5
BS 1 50 S DCO RK
BS 1 50 DCO RK

329
329
330
330
330
331
329
333
333
333
333
333
333
333
333
333
217
210
210
210
210
211
211
212
213
323
214
217
217

www.dehn.de

Part No. Index


Part No. Type

www.dehn.de

Page

919 978
919 979
919 986
919 987
919 988
919 989
919 990

AD DCO RK BL
AD DCO RK GE
DCO RK D 5 24
DCO RK E 12
DCO RK E 24
DCO RK E 48
DCO RK E 60

323
217
216
215
215
215
215

920 211
920 220
920 222
920 224
920 225
920 240
920 242
920 243
920 244
920 245
920 247
920 249
920 270
920 271
920 300
920 301
920 308
920 309
920 310
920 320
920 322
920 324
920 325
920 326
920 327
920 336
920 340
920 342
920 344
920 345
920 346
920 347
920 349
920 350
920 354
920 362
920 364
920 370
920 371
920 375
920 381
920 384
920 389
920 395
920 398
920 399
920 538

BXT ML2 B 180


BXT ML2 BE S 5
BXT ML2 BE S 12
BXT ML2 BE S 24
BXT ML2 BE S 48
BXT ML2 BD S 5
BXT ML2 BD S 12
BXT ML2 BD DL S 15
BXT ML2 BD S 24
BXT ML2 BD S 48
BXT ML2 BD 180
BXTU ML2 BD S 0-180
BXT ML2 BE HFS 5
BXT ML2 BD HFS 5
BXT BAS
BXT BAS EX
BXT M4 E
BXT M4 T
BXT ML4 B 180
BXT ML4 BE 5
BXT ML4 BE 12
BXT ML4 BE 24
BXT ML4 BE 48
BXT ML4 BE 60
BXT ML4 BE 180
BXT ML4 BE 36
BXT ML4 BD 5
BXT ML4 BD 12
BXT ML4 BD 24
BXT ML4 BD 48
BXT ML4 BD 60
BXT ML4 BD 180
BXTU ML4 BD 0-180
BXT ML4 BC 5
BXT ML4 BC 24
BXT ML4 BE C 12
BXT ML4 BE C 24
BXT ML4 BE HF 5
BXT ML4 BD HF 5
BXT ML4 BD HF 24
BXT ML4 BD EX 24
BXT ML4 BC EX 24
BXT ML4 MY 250
SAK BXT LR
BS BA1 BA15 BXT
BS 1 50 BXT
BXT ML2 BD HF EX 6

195
199
199
199
199
197
197
198
197
197
196
182
200
201
183
313
202
203
187
188
188
188
188
188
188
188
189
189
189
189
189
189
181
190
190
191
191
192
193
193
314
315
194
202
204
204
316

923 011
923 016
923 019

IF1
IF3
EXFS KU

345
345
349

Part No. Type

Page

923 021
923 023
923 025
923 035
923 045
923 060
923 061
923 062
923 100
923 101
923 110
923 116
923 117
923 118
923 119

KFSU
TFS
AL EXFS L100 KS
AL EXFS L200 KS
AL EXFS L300 KS
EXFS L100
EXFS L200
EXFS L300
EXFS 100
EXFS 100 KU
SDS 1
SDS 3
SDS 2
SDS 4
SDS 5

343
343
345
345
345
348
348
348
345
346
354
354
354
354
354

924 016
924 017
924 018
924 019
924 046
924 051
924 061
924 270
924 272
924 274
924 328
924 329
924 335
924 336
924 337
924 338
924 339
924 340
924 342
924 343
924 350
924 370
924 389
924 395
924 396

FS 15E 5
FS 9E PB 6
FS 25E HS 12
FS 9E HS 12
USD 25 V24 HS S B
USD 15 V11 S B
USD 9 V24 S B
DSM ISDN SK
DSM TC 2 SK
DSM TM
AR1 STW
ZAP STW
NSM PRO TW
AR1 TW
NSM PRO SI
AR1 SI
NSM PRO AZ
AR1 AZ
NSM PRO EW
AR1 EW
STC 230
DSA 230 LA
DFL A 255
DFL D 255
DFL M 255

284
282
285
283
288
287
286
290
291
260
129
129
137
137
137
137
137
137
137
137
131
129
134
135
133

925 001
925 013

BT 24
AS IBAS YE

293
295

929 010
929 024
929 026
929 028
929 034
929 035
929 036
929 037
929 040
929 042
929 043
929 044
929 045
929 046

UGKF BNC
DLI ISDN I
DLI TC BT
DLI TC 2 I
EG NET PRO 19
NET PRO 4TP
NET PRO LSA 4TP
NET PRO 4TP 30
DGA F 1.6 5.6
DGA G BNC
DGA AG BNC
DGA G N
DGA AG N
DGA LG 7 16

268
262
266
263
249
249
249
249
273
274
275
274
275
276

Part No. Type

Page

929 047
929 048
929 057
929 059
929 071
929 072
929 075
929 081
929 095
929 096
929 100
929 110
929 121
929 199
929 230
929 234
929 235
929 446
929 496
929 497
929 498
929 499
929 921
929 941
929 960
929 961
929 962
929 963
929 964
929 969
929 970
929 971
929 982
929 984
929 996

DGA L4 7 16 S
DGA L4 7 16 B
DGA AG U
DGA L4 N EB
NET PRO TC 2
NET PRO TC 2 LSA
NET PRO E1 LSA G703
DLI TC ECO RJ12
EB 4 F
EL 16 B17
DPA M CAT6 RJ45S 48
DPA M CAT6 RJ45H 48
DPA M CLE RJ45B 48
MS DPA
NET PRO 10X TC1 RST
EG NET PRO 10X 19
EG NET PRO 10X 3HE
DGA LG 7 16 X
GDT DGA 90 X
GDT DGA 90
GDT DGA 230
GDT DGA 470
DPI ME 24 N A2G
DPI MD 24 M 2S
DPI MD EX 24 M 2
DPI CD EXI 24 M
DPI CD EXD 24 M
DPI CD EXI 24 N
DPI CD EXD 24 N
DPI CD EXD 230 24 M
DPI CD EXD 230 24 N
DPI CD HF EXD 5 M
KV S M20 MS 9.5
KV M20 MS 10.5
ER DPI M20

277
277
275
278
250
250
251
264
279
279
254
254
255
254
252
252
252
276
279
279
279
279
299
298
303
306
308
306
308
310
310
309
300
300
300

950 102
950 112
950 120
950 121
950 130
950 131
950 150
950 151
950 160
950 170
950 500
950 501
950 502
950 505
950 506
950 507

DG 1000
DG 1000 FM
DG T H 275 LI
DG T H 385 LI
T H 275 LI
T H 385 LI
DG TT H230 400 LI
DG TT H230 400 LI385
DG TNC H230 400 LI
DG TNS H230 400 LI
DG PV 500 SCP
DG PV 700 SCP
DG PV 1200 SCP
DG PV 500 SCP FM
DG PV 700 SCP FM
DG PV 1200 SCP FM

111
111
103
103
103
103
102
102
100
101
108
108
108
109
109
109

951 001
951 050
951 100
951 110
951 115
951 200

DV MOD 255
DV MOD NPE 50
DV MOD NPE 100
DV M TT 2P 255
DV M TT 2P 255 FM
DV M TN 255

38
38
38
36
36
35

Part No. Type


951 205
951 300
951 305
951 310
951 315
951 400
951 405

DV M TN 255 FM
DV M TNC 255
DV M TNC 255 FM
DV M TT 255
DV M TT 255 FM
DV M TNS 255
DV M TNS 255 FM

952 010
952 011
952 012
952 013
952 014
952 015
952 016
952 017
952 018
952 020
952 025
952 027
952 029
952 030
952 035
952 050
952 051
952 053
952 054
952 060
952 070
952 071
952 072
952 073
952 074
952 075
952 076
952 077
952 078
952 079
952 080
952 082
952 084
952 085
952 087
952 089
952 090
952 091
952 092
952 093
952 094
952 095
952 096
952 097
952 098
952 099
952 110
952 111
952 115
952 116
952 130

DG MOD 275
DG MOD 75
DG MOD 150
DG MOD 320
DG MOD 385
DG MOD 440
DG MOD 600
DG MOD 750
DG MOD 48
DG MOD CI 275
DG MOD 75 VA
DG MOD 275 VA
DG MOD 385 VA
DGP C S
DGP C S FM
DG MOD NPE
DG MOD PV SCI 500
DG MOD PV SCI 300
DG MOD PV SCI 600
DGP C MOD
DG S 275
DG S 75
DG S 150
DG S 320
DG S 385
DG S 440
DG S 600
DG S WE 600
DG S 48
DG S CI 275
DG S 75 VA
DG S 275 VA
DG S 385 VA
DG S 75 VA FM
DG S 275 VA FM
DG S 385 VA FM
DG S 275 FM
DG S 75 FM
DG S 150 FM
DG S 320 FM
DG S 385 FM
DG S 440 FM
DG S 600 FM
DG S WE 600 FM
DG S 48 FM
DG S CI 275 FM
DG M TT 2P 275
DG M TT 2P 385
DG M TT 2P 275 FM
DG M TT 2P 385 FM
DG M TT 2P 320

Page
35
32
32
34
34
33
33
95
95
95
95
95
95
95
95
95
98
97
97
97
93
93
96
97
97
97
96
89
89
89
89
89
89
89
91
89
75
113
113
113
114
114
114
90
90
90
90
90
90
90
91
90
75
85
85
86
86
85

373

Part No. Index


Part No. Type
952 135
952 171
952 173
952 176
952 178
952 200
952 201
952 205
952 206
952 300
952 302
952 303
952 304
952 305
952 307
952 308
952 309
952 310
952 311
952 313
952 314

374

DG M TT 2P 320 FM
DG M TT 2P CI 275
DG M TN CI 275
DG M TT 2P CI 275 FM
DG M TN CI 275 FM
DG M TN 275
DG M TN 150
DG M TN 275 FM
DG M TN 150 FM
DG M TNC 275
DG M WE 600
DG M TNC 440
DG M TNC CI 275
DG M TNC 275 FM
DG M WE 600 FM
DG M TNC 440 FM
DG M TNC CI 275 FM
DG M TT 275
DG M TT 385
DG M TNC 150
DG M TNC 385

Page
86
74
73
74
73
83
83
84
84
77
87
77
70
78
87
78
70
81
81
77
77

Part No. Type


952 315
952 316
952 318
952 319
952 320
952 322
952 325
952 327
952 400
952 401
952 403
952 404
952 405
952 406
952 408
952 409
952 510
952 511
952 512
952 515
952 516

DG M TT 275 FM
DG M TT 385 FM
DG M TNC 150 FM
DG M TNC 385 FM
DG M TT 320
DG M TT CI 275
DG M TT 320 FM
DG M TT CI 275 FM
DG M TNS 275
DG M TNS CI 275
DG M TNS 150
DG M TNS 385
DG M TNS 275 FM
DG M TNS CI 275 FM
DG M TNS 150 FM
DG M TNS 385 FM
DG M YPV SCI 1000
DG M YPV SCI 600
DG M YPV SCI 1200
DG M YPV SCI 1000 FM
DG M YPV SCI 600 FM

Page
82
82
78
78
81
72
82
72
79
71
79
79
80
71
80
80
105
105
105
106
106

Part No. Type

Page

952 517
952 699

DG M YPV SCI 1200 FM 106


DK 25
145

953 010
953 011
953 012
953 013
953 014
953 020
953 200
953 201
953 202
953 203
953 204
953 205
953 206
953 207
953 208
953 209
953 400
953 405

DR MOD 255
DR MOD 30
DR MOD 60
DR MOD 75
DR MOD 150
DR MOD 4P 255
DR M 2P 255
DR M 2P 30
DR M 2P 60
DR M 2P 75
DR M 2P 150
DR M 2P 255 FM
DR M 2P 30 FM
DR M 2P 60 FM
DR M 2P 75 FM
DR M 2P 150 FM
DR M 4P 255
DR M 4P 255 FM

124
124
124
124
124
124
120
120
120
120
120
121
121
121
121
121
123
123

Part No. Type

Page

961 001
961 002
961 003
961 010
961 101
961 105
961 110
961 115
961 120
961 125
961 130
961 135
961 140
961 145
961 160
961 165
961 175

DB M MOD 150
DB M MOD 255
DB M MOD 320
DGP M MOD 255
DGP M 255
DGP M 255 FM
DB M 1 150
DB M 1 150 FM
DB M 1 255
DB M 1 255 FM
DB M 1 320
DB M 1 320 FM
DBM 1 440
DBM 1 440 FM
DGPM 440
DGPM 440 FM
DBM 1 760 FM

48
48
48
64
64
64
46
47
46
47
46
47
52
52
68
68
53

989 408

ITAK EXI BXT 24

321

www.dehn.de

Type / Product Index

www.dehn.de

Type

Product

Part No. Page

Type

Product

Part No. Page

Angled fixing plate for DEHNgate


Angled fixing plate for DEHNgate
Expansion strap f. foundation earthing electrodes
Earth conductor, open/closed cable lugs
Separate clamping element
Tensioning strap

106 310
106 329
308 150
416 411
540 810
540 901

279
279
357
279
352
352

AD DCO RK BL
AD DCO RK GE
AD PAS 6AP V2A
AD PAS 8AP V2A
AD PAS 10AP V2A
AD PAS 12AP V2A
AH FE RF
AH FE RF V G
AH PAS RK
AK 16 AS SAK MS
AK 35 SN 18X3 GG
AK FL40 PAS
AK RPA V2A
AL EXFS L100 KS
AL EXFS L200 KS
AL EXFS L300 KS
AL2 10DA LSA
ALGA 5
ALGA 5 X
AR1 AZ
AR1 EW
AR1 SI
AR1 STW
AR1 TW
AS IBAS YE
AS SAK 1000 V2A
AW2 LSA

Covering Plate for DCO, blue


Covering Plate for DCO, yellow
Cover NIRO, for 6-pole EB
Cover NIRO, for 8-pole EB
Cover NIRO, for 10-pole EB
Cover NIRO, for 12-pole EB
Distance Holder St/tZn, DIN 48833 A, 280 mm
Distance Holder St/tZn, reinf. version 300 mm
Plastic cover, grey
Protective Conductor Terminal, -16 mm
Terminal for Busbar
Terminal for Fl 40
Terminal St/tZn
Connecting cable for EXFS 100, length: 100 mm
Connecting cable for EXFS 100, length: 200 mm
Connecting cable for EXFS 100, length: 300 mm
Terminal Block 10TC LSA-PLUS
Aluminium Enclosure IP65
Aluminium Enclosure IP65 for BCT
Protector Cover, single piece, anthracite
Protector Cover, single piece, studio white
Protector Cover, single piece, silver
Covering Frame for DEHNsafe, studio white
Protector Cover, single-piece, titan white
Coupling Module
Anchor Bar, stainless steel, 1 m long
Insertion Tool LSA-PLUS

919 978
919 979
472 279
472 269
472 289
472 299
290 002
290 001
563 015
308 411
919 015
563 222
563 169
923 025
923 035
923 045
907 997
906 055
906 058
924 340
924 343
924 338
924 328
924 336
925 013
308 421
907 994

323
217
356
356
356
356
357
357
355
327
331
355
357
345
345
345
244
334
334
137
137
137
129
137
295
326
243

BM 10 DRL
BS 1 50 BXT
BS 1 50 DCO RK
BS 1 50 S DCO RK
BS BA1 BA15 BXT
BS M10 PAS
BT 24
BVT AD 24
BVT ALD 36
BVT ISDN
BVT KKS ALD 75
BVT KKS ALD SN
BVT KKS APD 36
BVT KKS APD SN
BVT MTTY 24
BVT RS485 5
BVT TC 1
BVT TTY 24
BXT BAS
BXT BAS EX
BXT M4 E
BXT M4 T
BXT ML2 B 180
BXT ML2 BD 180

Plug-in SPD Block (without SPDs)


Labelling System, printed with numbers 1-50
Quick Marking System for DCO RK
Quick Marking System for DCO RK
Marking System for BXT
Fixing Set for EB
BUStector
BLITZDUCTOR VT
BLITZDUCTOR VT
BLITZDUCTOR VT
BLITZDUCTOR VT
BLITZDUCTOR VT
BLITZDUCTOR VT
BLITZDUCTOR VT
BLITZDUCTOR VT
BLITZDUCTOR VT
BLITZDUCTOR VT
BLITZDUCTOR VT
BXT Base Part
BXT Base Part Ex(i)
BXT Earthing Module
BXT Testing / Disconnecting Module
BXT Protection Module LifeCheck B, 180 V
BXT Protection Module LifeCheck BD, 180 V

907 499
920 399
919 977
919 976
920 398
472 201
925 001
918 402
918 408
918 410
918 420
918 404
918 421
918 405
918 407
918 401
918 411
918 400
920 300
920 301
920 308
920 309
920 211
920 247

238
204
217
217
204
356
293
222
223
257
225
227
226
228
220
221
258
219
183
313
202
203
195
196

BXT ML2 BD DL S 15
BXT ML2 BD HF EX 6
BXT ML2 BD HFS 5
BXT ML2 BD S 5
BXT ML2 BD S 12
BXT ML2 BD S 24
BXT ML2 BD S 48
BXT ML2 BE HFS 5
BXT ML2 BE S 5
BXT ML2 BE S 12
BXT ML2 BE S 24
BXT ML2 BE S 48
BXT ML4 B 180
BXT ML4 BC 5
BXT ML4 BC 24
BXT ML4 BC EX 24
BXT ML4 BD 5
BXT ML4 BD 12
BXT ML4 BD 24
BXT ML4 BD 48
BXT ML4 BD 60
BXT ML4 BD 180
BXT ML4 BD EX 24
BXT ML4 BD HF 5
BXT ML4 BD HF 24
BXT ML4 BE 5
BXT ML4 BE 12
BXT ML4 BE 24
BXT ML4 BE 36
BXT ML4 BE 48
BXT ML4 BE 60
BXT ML4 BE 180
BXT ML4 BE C 12
BXT ML4 BE C 24
BXT ML4 BE HF 5
BXT ML4 MY 250
BXTU ML4 BD 0-180
BXTU ML2 BD S 0-180

BXT Protection Module LifeCheck BD DL, 17 V


BXT Protection Module LifeCheck BD HF EX, 6 V
BXT Protection Module LifeCheck BD, 6 V
BXT Protection Module LifeCheck BD, 6 V
BXT Protection Module LifeCheck BD, 15 V
BXT Protection Module LifeCheck BD, 33 V
BXT Protection Module LifeCheck BD, 54 V
BXT Protection Module LifeCheck BE, 6 V
BXT Protection Module LifeCheck BE, 6 V
BXT Protection Module LifeCheck BE, 15 V
BXT Protection Module LifeCheck BE, 33 V
BXT Protection Module LifeCheck BE, 54 V
BXT Protection Module LifeCheck B, 180 V
BXT Protection Module LifeCheck BC, 6 V
BXT Protection Module LifeCheck BC, 33 V
BXT Protection Module LifeCheck BC EX, 24 V
BXT Protection Module LifeCheck BD, 6 V
BXT Protection Module LifeCheck BD, 15 V
BXT Protection Module LifeCheck BD, 33 V
BXT Protection Module LifeCheck BD, 54 V
BXT Protection Module LifeCheck BD, 70 V
BXT Protection Module LifeCheck BD, 180 V
BXT Protection Module LifeCheck BD EX, 24 V
BXT Protection Module LifeCheck BD HF, 6 V
BXT Protection Module LifeCheck BD HF, 24 V
BXT Protection Module LifeCheck BE, 6 V
BXT Protection Module LifeCheck BE, 15 V
BXT Protection Module LifeCheck BE, 33 V
BXT Protection Module LifeCheck BE, 45 V
BXT Protection Module LifeCheck BE, 54 V
BXT Protection Module LifeCheck BE, 70 V
BXT Protection Module LifeCheck BE, 180 V
BXT Protection Module LifeCheck BE C, 12 V
BXT Protection Module LifeCheck BE C, 33 V
BXT Protection Module LifeCheck BE HF, 6 V
BXT Protection Module LifeCheck MY, 320 V
BXT Protection Module LifeCheck BD, 0-180 V
BXT Protection Module LifeCheck BD S, 0-180 V

920 243
920 538
920 271
920 240
920 242
920 244
920 245
920 270
920 220
920 222
920 224
920 225
920 310
920 350
920 354
920 384
920 340
920 342
920 344
920 345
920 346
920 347
920 381
920 371
920 375
920 320
920 322
920 324
920 336
920 325
920 326
920 327
920 362
920 364
920 370
920 389
920 349
920 249

DB 1 255 H
DB 1 440
DB 3 255 H
DB M 1 150
DB M 1 150 FM
DB M 1 255
DB M 1 255 FM
DB M 1 320
DB M 1 320 FM
DB M MOD 150
DB M MOD 255
DB M MOD 320
DB NH00 255 H
DBM 1 255 S
DBM 1 440
DBM 1 440 FM
DBM 1 760 FM
DBM NH00 255
DCO RK D 5 24
DCO RK E 12

DEHNbloc 1 255 H
DEHNbloc 1 440
DEHNbloc 3 255 H
DEHNbloc Maxi modular 1 150
DEHNbloc Maxi modular 1 150 FM
DEHNbloc Maxi modular 1 255
DEHNbloc Maxi modular 1 255 FM
DEHNbloc Maxi modular 1 320
DEHNbloc Maxi modular 1 320 FM
Protection module for DB M, 150 V
Protection module for DB M, 255 V
Protection module for DB M, 320 V
DEHNbloc NH00 255 H
DEHNbloc Maxi S
DEHNbloc Maxi 1 440
DEHNbloc Maxi 1 440 FM
DEHNbloc Maxi 1 760 FM
DEHNbloc Maxi NH00
DEHNconnect RK D, +24/-5 V
DEHNconnect RK E, 12 V

900 222 59
900 159 61
900 120 59
961 110 46
961 115 47
961 120 46
961 125 47
961 130 46
961 135 47
961 001 48
961 002 48
961 003 48
900 273 60
900 220 55
961 140 52
961 145 52
961 175 53
900 255 50
919 986 216
919 987 215

198
316
201
197
197
197
197
200
199
199
199
199
187
190
190
315
189
189
189
189
189
189
314
193
193
188
188
188
188
188
188
188
191
191
192
194
181
182

375

Type / Product Index


Type

Product

Part No. Page

Type

Product

Part No. Page

DCO RK E 24
DCO RK E 48
DCO RK E 60
DCO RK MD 12
DCO RK MD 24
DCO RK MD 48
DCO RK MD 110
DCO RK MD EX 24
DCO RK MD HF 5
DCO RK ME 12
DCO RK ME 24
DCO RK ME 48
DCO RK ME 110
DFL A 255
DFL D 255
DFL M 255
DG 1000
DG 1000 FM
DG M TN 150
DG M TN 150 FM
DG M TN 275
DG M TN 275 FM
DG M TN CI 275
DG M TN CI 275 FM
DG M TNC 150
DG M TNC 150 FM
DG M TNC 275
DG M TNC 275 FM
DG M TNC 385
DG M TNC 385 FM
DG M TNC 440
DG M TNC 440 FM
DG M TNC CI 275
DG M TNC CI 275 FM
DG M TNS 150
DG M TNS 150 FM
DG M TNS 275
DG M TNS 275 FM
DG M TNS 385
DG M TNS 385 FM
DG M TNS CI 275
DG M TNS CI 275 FM
DG M TT 2P 275
DG M TT 2P 275 FM
DG M TT 2P 320
DG M TT 2P 320 FM
DG M TT 2P 385
DG M TT 2P 385 FM
DG M TT 2P CI 275
DG M TT 2P CI 275 FM
DG M TT 275
DG M TT 275 FM
DG M TT 320
DG M TT 320 FM
DG M TT 385
DG M TT 385 FM
DG M TT CI 275
DG M TT CI 275 FM
DG M WE 600

DEHNconnect RK E, 24 V
DEHNconnect RK E, 48 V
DEHNconnect RK E, 60 V
DEHNconnect RK MD, 12 V
DEHNconnect RK MD, 24 V
DEHNconnect RK MD, 48 V
DEHNconnect RK MD, 110 V
DEHNconnect RK MD EX, 24 V
DEHNconnect RK MD HF, 5 V
DEHNconnect RK ME, 12 V
DEHNconnect RK ME, 24 V
DEHNconnect RK ME, 48 V
DEHNconnect RK ME, 110 V
DEHNflex A
DEHNflex D
DEHNflex M
DEHNguard 1000
DEHNguard 1000 FM
DEHNguard modular TN, 2-pole
DEHNguard modular TN FM, 2-pole
DEHNguard modular TN, 2-pole
DEHNguard modular TN FM, 2-pole
DEHNguard modular TN CI, 2-pole
DEHNguard modular TN CI FM, 2-pole
DEHNguard modular TNC, 3-pole
DEHNguard modular TNC FM, 3-pole
DEHNguard modular TNC, 3-pole
DEHNguard modular TNC FM, 3-pole
DEHNguard modular TNC, 3-pole
DEHNguard modular TNC FM, 3-pole
DEHNguard modular TNC, 3-pole
DEHNguard modular TNC FM, 3-pole
DEHNguard modular TNC CI, 3-pole
DEHNguard modular TNC CI FM, 3-pole
DEHNguard modular TNS, 4-pole
DEHNguard modular TNS FM, 4-pole
DEHNguard modular TNS, 4-pole
DEHNguard modular TNS FM, 4-pole
DEHNguard modular TNS, 4-pole
DEHNguard modular TNS FM, 4-pole
DEHNguard modular TNS CI, 4-pole
DEHNguard modular TNS CI FM, 4-pole
DEHNguard modular TT, 2-pole
DEHNguard modular TT FM, 2-pole
DEHNguard modular TT, 2-pole
DEHNguard modular TT FM, 2-pole
DEHNguard modular TT, 2-pole
DEHNguard modular TT FM, 2-pole
DEHNguard modular TT CI, 2-pole
DEHNguard modular TT CI FM, 2-pole
DEHNguard modular TT, 4-pole
DEHNguard modular TT FM, 4-pole
DEHNguard modular TT, 4-pole
DEHNguard modular TT FM, 4-pole
DEHNguard modular TT, 4-pole
DEHNguard modular TT FM, 4-pole
DEHNguard modular TT CI, 4-pole
DEHNguard modular TT CI FM, 4-pole
DEHNguard modular M WE, 3-pole

919 988
919 989
919 990
919 940
919 941
919 942
919 943
919 960
919 970
919 920
919 921
919 922
919 923
924 389
924 395
924 396
950 102
950 112
952 201
952 206
952 200
952 205
952 173
952 178
952 313
952 318
952 300
952 305
952 314
952 319
952 303
952 308
952 304
952 309
952 403
952 408
952 400
952 405
952 404
952 409
952 401
952 406
952 110
952 115
952 130
952 135
952 111
952 116
952 171
952 176
952 310
952 315
952 320
952 325
952 311
952 316
952 322
952 327
952 302

DG M WE 600 FM
DG M YPV SCI 600
DG M YPV SCI 600 FM
DG M YPV SCI 1000
DG M YPV SCI 1000 FM
DG M YPV SCI 1200
DG M YPV SCI 1200 FM
DG MOD 48
DG MOD 75
DG MOD 75 VA
DG MOD 150
DG MOD 275
DG MOD 275 VA
DG MOD 320
DG MOD 385
DG MOD 385 VA
DG MOD 440
DG MOD 600
DG MOD 750
DG MOD CI 275
DG MOD NPE
DG MOD PV SCI 300
DG MOD PV SCI 500
DG MOD PV SCI 600
DG PV 500 SCP
DG PV 500 SCP FM
DG PV 700 SCP
DG PV 700 SCP FM
DG PV 1200 SCP
DG PV 1200 SCP FM
DG S 48
DG S 48 FM
DG S 75
DG S 75 FM
DG S 75 VA
DG S 75 VA FM
DG S 150
DG S 150 FM
DG S 275
DG S 275 FM
DG S 275 VA
DG S 275 VA FM
DG S CI 275
DG S CI 275 FM
DG S 320
DG S 320 FM
DG S 385
DG S 385 FM
DG S 385 VA
DG S 385 VA FM
DG S 440
DG S 440 FM
DG S 600
DG S 600 FM
DG S WE 600
DG S WE 600 FM
DG T H 275 LI
DG T H 385 LI
DG TNC H230 400 LI

DEHNguard modular M WE FM, 3-pole


DEHNguard M YPV SCI 600
DEHNguard M YPV SCI 600 FM
DEHNguard M YPV SCI 1000
DEHNguard M YPV SCI 1000 FM
DEHNguard M YPV SCI 1200
DEHNguard M YPV SCI 1200 FM
Protection Module for DG M and DG S, 48 V
Protection Module for DG M and DG S, 75 V
Protection Module for DG S VA, 75 V
Protection Module for DG M and DG S, 150 V
Protection Module for DG M and DG S, 275 V
Protection Module for DG S VA, 275 V
Protection Module for DG M and DG S, 320 V
Protection Module for DG M and DG S, 385 V
Protection Module for DG S VA, 385 V
Protection Module for DG M and DG S, 440 V
Protection Module for DG M and DG S, 600 V
Protection Module for DG M and DG S, 750 V
Protection Module for DG M CI, 275 V
N-PE Spark-gap-based prot. module, 255 V
Protection Module for DG M YPV SCI, 300 V
Protection Module for DG M YPV SCI, 500 V
Protection Module for DG M YPV SCI, 600 V
DEHNguard PV 500 SCP
DEHNguard PV 500 SCP FM
DEHNguard PV 700 SCP
DEHNguard PV 700 SCP FM
DEHNguard PV 1200 SCP
DEHNguard PV 1200 SCP FM
DEHNguard S, 48 V
DEHNguard S FM, 48 V
DEHNguard S, 75 V
DEHNguard S FM, 75 V
DEHNguard S VA, 75 V
DEHNguard S VA FM, 75 V
DEHNguard S, 150 V
DEHNguard S FM, 150 V
DEHNguard S, 275 V
DEHNguard S FM, 275 V
DEHNguard S VA, 275 V
DEHNguard S VA FM, 275 V
DEHNguard S CI, 275 V
DEHNguard S CI FM, 275 V
DEHNguard S, 320 V
DEHNguard S FM, 320 V
DEHNguard S, 385 V
DEHNguard S FM, 385 V
DEHNguard S VA, 385 V
DEHNguard S VA FM, 385 V
DEHNguard S, 440 V
DEHNguard S FM, 440 V
DEHNguard S, 600 V
DEHNguard S FM, 600 V
DEHNguard S WE, 600 V
DEHNguard S WE FM, 600 V
DEHNguard T H LI, single-pole, 275 V
DEHNguard T H LI, single-pole, 385 V
DEHNguard TNC H LI, 3-pole

952 307
952 511
952 516
952 510
952 515
952 512
952 517
952 018
952 011
952 025
952 012
952 010
952 027
952 013
952 014
952 029
952 015
952 016
952 017
952 020
952 050
952 053
952 051
952 054
950 500
950 505
950 501
950 506
950 502
950 507
952 078
952 098
952 071
952 091
952 080
952 085
952 072
952 092
952 070
952 090
952 082
952 087
952 079
952 099
952 073
952 093
952 074
952 094
952 084
952 089
952 075
952 095
952 076
952 096
952 077
952 097
950 120
950 121
950 160

376

215
215
215
211
211
212
213
323
214
210
210
210
210
134
135
133
111
111
83
84
83
84
73
73
77
78
77
78
77
78
77
78
70
70
79
80
79
80
79
80
71
71
85
86
85
86
85
86
74
74
81
82
81
82
81
82
72
72
87

87
105
106
105
106
105
106
95
95
97
95
95
97
95
95
97
95
95
95
98
96
97
97
97
108
109
108
109
108
109
89
90
89
90
113
114
89
90
89
90
113
114
75
75
89
90
89
90
113
114
89
90
89
90
91
91
103
103
100

www.dehn.de

Type / Product Index

www.dehn.de

Type

Product

Part No. Page

Type

Product

Part No. Page

DG TNS H230 400 LI


DG TT H230 400 LI
DG TT H230 400 LI385
DGA AG BNC
DGA AG N
DGA AG U
DGA BNC VCD
DGA BNC VCID
DGA F 1.6 5.6
DGA FF TV
DGA G BNC
DGA G N
DGA GF TV
DGA GFF TV
DGA L4 7 16 B
DGA L4 7 16 S
DGA L4 N EB
DGA LG 7 16
DGA LG 7 16 X
DGP B NH00 N 255
DGP BN 255
DGP C MOD
DGP C S
DGP C S FM
DGP M 255
DGP M 255 FM
DGP M MOD 255
DGPM 1 255 S
DGPM 440
DGPM 440 FM
DISO 3
DK 25
DLI ISDN I
DLI TC 2 I
DLI TC BT
DLI TC ECO RJ12
DLM PV 1000
DPA M CAT6 RJ45H 48
DPA M CAT6 RJ45S 48
DPA M CLE RJ45B 48
DPG LSA 30 P
DPG LSA 60 P
DPG LSA 120 P
DPG LSA 220 P
DPI CD EXD 230 24 M
DPI CD EXD 230 24 N
DPI CD EXD 24 M
DPI CD EXD 24 N
DPI CD EXI 24 M
DPI CD EXI 24 N
DPI CD HF EXD 5 M
DPI MD 24 M 2S
DPI MD EX 24 M 2
DPI ME 24 N A2G
DPL 10 G3 110
DPL 10 G3 110 FSD
DPRO 230
DPRO 230 SE
DPRO 230 F

DEHNguard TNS H LI, 4-pole


DEHNguard TT H LI, 4-pole
DEHNguard TT H LI, 4-pole, 385 V
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgate
DEHNgap B/NH00/n
DEHNgap B/n
N-PE Spark-gap-based prot. module f. DGP C S
DEHNgap C S
DEHNgap C S FM
DEHNgap M 255
DEHNgap M 255 FM
N-PE Spark-gap-based prot. module for DGP M
DEHNgap Maxi 1 255 S
DEHNgap Maxi 440
DEHNgap Maxi 440 FM
DEHNisola, SPD monitoring device
Feed-through Terminal, 25 mm2
DEHNlink ISDN/I
DEHNlink TC 2
DEHNlink BT
DEHNlink-Denmark
DEHNlimit
Patch cable with surge protection
Patch cable with surge protection
Patch cable with surge protection
DEHN enclosure for equipotential bonding, 15 kA
DEHN enclosure for equipotential bonding, 30 kA
DEHN enclosure for equipotential bonding, 50 kA
DEHN enclosure for equipotential bonding, 50 kA
DEHNpipe
DEHNpipe
DEHNpipe
DEHNpipe
DEHNpipe
DEHNpipe
DEHNpipe
DEHNpipe
DEHNpipe
DEHNpipe
LSA-Plus Technology, 10 DA
LSA-Plus Technology, 10 DA
DEHNpro
DEHNpro
DEHNpro integrated mains filter

950 170
950 150
950 151
929 043
929 045
929 057
909 710
909 711
929 040
909 703
929 042
929 044
909 704
909 705
929 048
929 047
929 059
929 046
929 446
900 269
900 132
952 060
952 030
952 035
961 101
961 105
961 010
900 050
961 160
961 165
910 600
952 699
929 024
929 028
929 026
929 081
900 330
929 110
929 100
929 121
906 100
906 101
906 102
906 103
929 969
929 970
929 962
929 964
929 961
929 963
929 971
929 941
929 960
929 921
907 214
907 216
909 230
909 235
909 240

DPRO 230 SE F
DPRO 230 ISDN
DPRO 230 SE ISDN
DPRO 230 LAN100
DPRO 230 SE LAN100
DPRO 230 NT
DPRO 230 SE NT
DPRO 230 TV
DPRO 230 SE TV
DR M 2P 30
DR M 2P 30 FM
DR M 2P 60
DR M 2P 60 FM
DR M 2P 75
DR M 2P 75 FM
DR M 2P 150
DR M 2P 150 FM
DR M 2P 255
DR M 2P 255 FM
DR M 4P 255
DR M 4P 255 FM
DR MOD 30
DR MOD 60
DR MOD 75
DR MOD 150
DR MOD 255
DR MOD 4P 255
DRC LC M3+
DRC MCM XT
DRL 10 B 180
DRL 10 B 180 FSD
DRL HD 5
DRL HD 24
DRL PD 180
DRL RD 5
DRL RD 12
DRL RD 24
DRL RD 48
DRL RD 60
DRL RD 110
DRL RE 5
DRL RE 12
DRL RE 24
DRL RE 48
DRL RE 60
DRL RE 180
DSA 230 LA
DSI E 3
DSM ISDN SK
DSM TC 2 SK
DSM TM
DV M TN 255
DV M TN 255 FM
DV M TNC 255
DV M TNC 255 FM
DV M TNS 255
DV M TNS 255 FM
DV M TT 255
DV M TT 255 FM

DEHNpro integrated mains filter


Protection adapter for ISDN/Ethernet applications
Protection adapter for ISDN/Ethernet applications
Protection adapter for LAN applications
Protection adapter for LAN applications
Prot. adapter for NTBA/DSL splitter applications
Prot. adapter for NTBA/DSL splitter applications
Protection adapter for TV/radio applications
Protection adapter for TV/radio applications
DEHNrail modular, 2-pole, 24 V
DEHNrail modular FM, 2-pole, 24 V
DEHNrail modular, 2-pole, 48 V
DEHNrail modular FM, 2-pole, 48 V
DEHNrail modular, 2-pole, 60 V
DEHNrail modular FM, 2-pole, 60 V
DEHNrail modular, 2-pole, 120 V
DEHNrail modular FM, 2-pole, 120 V
DEHNrail modular, 2-pole, 230 V
DEHNrail modular FM, 2-pole, 230 V
DEHNrail modular, 4-pole
DEHNrail modular FM, 4-pole
Protection module for DR M 2P, 2-pole, 30 V
Protection module for DR M 2P, 2-pole, 60 V
Protection module for DR M 2P, 2-pole, 75 V
Protection module for DR M 2P, 2-pole, 150 V
Protection module for DR M 2P, 2-pole, 255 V
Protection module for DR M 4P, 4-pole, 255 V
LifeCheck SPD test device
Condition Monitoring System LifeCheck
DRL plug-in SPD block (10 pairs), 180 V
DRL plug-in SPD block (10 pairs), fault indication
DEHNrapid LSA HD, 6 V
DEHNrapid LSA HD, 28 V
DEHNrapid LSA PD, 180 V
DEHNrapid LSA RD, 6 V
DEHNrapid LSA RD, 14 V
DEHNrapid LSA RD, 28 V
DEHNrapid LSA RD, 54 V
DEHNrapid LSA RD, 70 V
DEHNrapid LSA RD, 110 V
DEHNrapid LSA RE, 6 V
DEHNrapid LSA RE, 14 V
DEHNrapid LSA RE, 28 V
DEHNrapid LSA RE, 54 V
DEHNrapid LSA RE, 70 V
DEHNrapid LSA RE, 180 V
DEHNsafe
Optical-Fibre-Based Receiver Module
SPD for telecomm. terminal equipment
SPD for telecomm. terminal equipment
SPD for Data Sockets
DEHNventil modular TN, 2-pole
DEHNventil modular TN FM, 2-pole
DEHNventil modular TNC, 3-pole
DEHNventil modular TNC FM, 3-pole
DEHNventil modular TNS, 4-pole
DEHNventil modular TNS FM, 4-pole
DEHNventil modular TT, 4-pole
DEHNventil modular TT FM, 4-pole

909 245
909 320
909 325
909 321
909 326
909 310
909 315
909 300
909 305
953 201
953 206
953 202
953 207
953 203
953 208
953 204
953 209
953 200
953 205
953 400
953 405
953 011
953 012
953 013
953 014
953 010
953 020
910 653
910 695
907 400
907 401
907 465
907 470
907 430
907 440
907 441
907 442
907 443
907 444
907 445
907 420
907 421
907 422
907 423
907 424
907 425
924 370
910 631
924 270
924 272
924 274
951 200
951 205
951 300
951 305
951 400
951 405
951 310
951 315

101
102
102
275
275
275
271
271
273
272
274
274
272
272
277
277
278
276
276
67
66
96
93
93
64
64
64
65
68
68
365
145
262
263
266
264
43
254
254
255
242
242
242
242
310
310
308
308
306
306
309
298
303
299
240
240
139
139
140

140
340
340
341
341
339
339
338
338
120
121
120
121
120
121
120
121
120
121
123
123
124
124
124
124
124
124
362
360
231
232
236
236
235
234
234
234
234
234
234
233
233
233
233
233
233
129
57
290
291
260
35
35
32
32
33
33
34
34

377

Type / Product Index


Type

Product

Part No. Page

Type

Product

Part No. Page

DV M TT 2P 255
DV M TT 2P 255 FM
DV MOD 255
DV MOD NPE 50
DV MOD NPE 100
DV ZP TNC 255
DV ZP TT 255

DEHNventil modular TT 2P, 2-pole


DEHNventil modular TT 2P FM, 2-pole
Spark-gap-based protection module
N PE Spark-gap-based protection module, 50 kA
N PE Spark-gap-based protection module, 190 kA
DEHNventil ZP TNC 255
DEHNventil ZP TT 255

951 110
951 115
951 001
951 050
951 100
900 390
900 391

36
36
38
38
38
40
41

GDT DGA 90
GDT DGA 90 X

929 497 279

GDT DGA 230


GDT DGA 470

Gas Discharge Tube for DEHNgate


Gas Discharge Tube for DEHNgate
with screw cap
Gas Discharge Tube for DEHNgate
Gas Discharge Tube for DEHNgate

929 496 279


929 498 279
929 499 279

EB 1 4 9
EB 4 F
EB DG 1000 1 3
EF 10 DRL
EG NET PRO 10X 19
EG NET PRO 10X 3HE
EG NET PRO 19
EL 16 B17
EL2 38EA LSA
ER DPI M20
ES 2X2AP 10 ST
ES 2X2AP 10 V2A
ES 2X3AP 10 ST
ES 2X3AP 10 V2A
ES 2X4AP 10 V2A
ES 2X4AP ST
ES 2X6AP 10 ST
ES 2X6AP 10 V2A
EX BRS 27
EX BRS 90
EX BRS 300
EX BRS 500
EXFS 100
EXFS 100 KU
EXFS KU
EXFS L100
EXFS L200
EXFS L300

Earthing clip, 4-pole, single-phase


Earthing blocks 4xF
DB Earthing clip, 3-pole, single-phase
Earthing frame
Enclosure for NET Protector
Enclosure for NET Protector
Enclosure for NET Protector
Cable Lug with Earth Conductor
Earth Conductor Block, 38-pole LSA-PLUS
Set of Earthing Rings for DEHNpipe
Earthing busbars St/tZn, 2x2 connections
Earthing busbars St/St, 2x2 connections
Earthing busbars St/tZn, 2x3 connections
Earthing busbars St/St, 2x3 connections
Earthing busbars St/tZn, 2x4 connections
Earthing busbars St/tZn, 2x4 connections
Earthing busbars St/tZn, 2x6 connections
Earthing busbars St/tZn, 2x6 connections
Pipe clamp for use in hazardous areas
Pipe clamp for use in hazardous areas
Pipe clamp for use in hazardous areas
Pipe clamp for use in hazardous areas
Ex Isolating Spark Gap, 100 kA
Ex Isolating Spark Gap, 100 kA
Ex Isolating Spark Gap, 50 kA
Ex Isolating Spark Gap, 50 kA
Ex Isolating Spark Gap, 50 kA
Ex Isolating Spark Gap, 50 kA

900 417
929 095
900 411
907 498
929 234
929 235
929 034
929 096
907 993
929 996
472 023
472 109
472 022
472 119
472 129
472 024
472 021
472 139
540 821
540 801
540 803
540 805
923 100
923 101
923 019
923 060
923 061
923 062

151
279
151
237
252
252
249
279
244
300
356
356
356
356
356
356
356
356
351
351
351
351
345
346
349
348
348
348

IF1
IF3
IGA 6 IP54
IGA 10 V2 IP54
IGA 12 IP54
IGA 24 IP54
IS PAS M10
ITAK EXI BXT 24

Connection Bracket Type IF -SETConnection Bracket Type IF -SETInsulating Enclosure 6 mods.


Insulating Enclosure 10 mods.
Insulating Enclosure 12 mods.
Insulating Enclosure 24 mods.
Isolator for PAS Industry
IT Connection Box

923 011
923 016
902 485
902 315
902 471
902 472
472 210
989 408

345
345
148
146
147
147
356
321

KB 10 DCO RK
KFSU
KS 198 PAS
KS 398 PAS
KS 798 PAS
KV FE UNI
KV M20 MS 10.5
KV S M20 MS 9.5

Jumper Bar for DEHNconnect RK


Ex-Isolating Spark Gap
Terminal Bar, brass, length 198 mm
Terminal bar, brass, length 398 mm
Terminal bar, brass, length 798 mm
Wedge Connector St/tZn, with grid position
EMC Cable Gland
EMC Cable Gland

919 880
923 021
563 016
563 017
563 018
308 001
929 984
929 982

217
343
355
355
355
357
300
300

LCS DRC BCT


LCS DRC BXT
LWL DSI 18M
LWL ST DSI

LifeCheck-Sensor fr DRC BCT


LifeCheck-Sensor fr DRC BXT
Optical fibre, length 18 m
Plug for Optical Fibre

910 654 362


910 652 362
910 642 57
910 641 57

FBH 6 CU
FBH 6 ST
FBH 6 V2A
FBH 11 ST
FS 9E HS 12
FS 9E PB 6
FS 15E 5
FS 25E HS 12

Tape conductors with pressure plate 12 mm, Cu


Tape conductors with pressure plate 12 mm, St/tZn
Tape conductors with pressure plate 12 mm, St/St
Tape conductors with pressure plate 11 mm, St/tZn
Fine Surge Protection Adapter FS 12 V
Fine Surge Protection Adapter FS 6 V
Fine Surge Protection Adapter FS 5 V
Fine Surge Protection Adapter FS 12 V

277 237
277 230
277 239
277 240
924 019
924 017
924 016
924 018

357
357
357
357
283
282
284
285

MB2 10 LSA
MMVK R16 R25 STBL
MMVK R16 R25 ST
MS ALGA 5 X
MS DPA
MVS 1 2
MVS 1 3
MVS 1 4
MVS 1 6
MVS 1 7
MVS 1 8
MVS 1 57
MVS 3 6
MVS 3 6 8
MVS 4 8 11
MVS 4 56

Mounting Frame 10 DA LSA-PLUS


MAXI MV clamp, St/tZn
MAXI MV clamp, St/bare
Mounting Set for Enclosures
Mounting Set for DEHNpatch
Busbar single-phase, 2-pole
Busbar single-phase, 3-pole
Busbar single-phase, 4-pole
Busbar single-phase, 6-pole
Busbar single-phase, 7-pole
Busbar single-phase, 8-pole
Busbar single-phase, 57-pole
Busbar 3-phase, 6-pole
Busbar 3-phase, 8-pole
Busbar 4-phase, 11-pole
Busbar 4-phase, 56-pole

907 995
308 040
308 041
906 059
929 199
900 617
900 615
900 610
900 815
900 848
900 611
900 612
900 595
900 813
900 814
900 614

243
357
357
335
254
149
149
149
149
150
150
150
150
150
151
151

GDT 230 B3
GDT 230 B3 FSD
GDT 230 G3
GDT 230 G3 FSD

Gas Discharge Tube for DRL 10


Gas Discharge Tube for DRL 10
Gas Discharge Tube for DPL 10 G3
Gas Discharge Tube for DPL 10 G3

907 218
907 219
907 208
907 217

238
238
240
240

NET PRO 10X TC1 RST


NET PRO 4TP
NET PRO 4TP 30
NET PRO E1 LSA G703
NET PRO LSA 4TP

NET Protector 10X TC1 RST


NET Protector 4TP
NET Protector 4TP 30
NET Protector E1 LSA G703
NET Protector/LSA-PLUS/4TP

929 230
929 035
929 037
929 075
929 036

252
249
249
251
249

378

www.dehn.de

Type / Product Index

www.dehn.de

Type

Product

Part No. Page

Type

Product

Part No. Page

NET PRO TC 2
NET PRO TC 2 LSA
NF 10
NSM PRO AZ
NSM PRO EW
NSM PRO SI
NSM PRO TW

NET Protector TC 2, 110 V


NET Protector TC 2 LSA,+B433 110 V
Mains Filter 10 A
NSM Protector DELTA profile, anthracite
NSM Protector DELTA profile, studio white
NSM Protector DELTA profile, silver
NSM Protector DELTA profile, titanium white

929 071
929 072
912 254
924 339
924 342
924 337
924 335

250
250
125
137
137
137
137

P2
PA BXT
PA DRL
PAS 9AK
PAS 11AK
PAS 11AK UV
PAS 6RK OH
PAS 9RK
PAS 10RK
PAS 14RK
PAS I 10AP M10 CU
PAS I 10AP M10 V2A
PAS I 12AP M10 CU
PAS I 12AP M10 V2A
PAS I 6AP M10 CU
PAS I 6AP M10 V2A
PAS I 8AP M10 CU
PAS I 8AP M10 V2A
PM 20

Impulse Meter P2
Test adapter for BXT
Test adapter for BCT
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
Earthing Busbar
SPD Test Device

910 502
910 508
910 507
563 050
563 200
563 201
563 105
563 020
563 010
563 030
472 217
472 219
472 237
472 239
472 207
472 209
472 227
472 229
910 511

366
364
364
355
355
355
355
355
355
355
356
356
356
356
356
356
356
356
364

SAK BXT LR
SB PAS RK
SDS 1
SDS 2
SDS 3
SDS 4
SDS 5
SFL PRO
SFL PRO SE
SH 18X3 K
SH1 18X3 ST
SH2 18X3 ST
SKB 19 9M SW
SLK 16
SN 18X3 CU 1000
SPS PRO
SR DRL
ST AS SAK K
STAK 2X16
STC 230

EMC spring terminals


Bar Holder, plastic, grey
Voltage limiting device, SDS 1
Voltage limiting device, SDS 2
Voltage limiting device, SDS 3
Voltage limiting device, SDS 4
Voltage limiting device, SDS 5
SFL Protector
SFL Protector
Bar Holder, plastic
Bar Holder, steel
Bar Holder ISO
Selfbonding Rubber Tape
PE Terminal
Busbar, tinned
SPS Protector
Label Holder
Bar Support, plastic
Pin-shape terminal
STC Surge Protection Module

920 395
563 014
923 110
923 117
923 116
923 118
923 119
912 260
912 261
919 014
919 012
919 013
919 030
910 099
919 016
912 253
907 497
308 425
900 589
924 350

202
355
354
354
354
354
354
142
142
330
330
330
333
335
329
127
238
327
145
131

T C H 255
T H 275 LI
T H 385 LI
TFS
TL2 10DA CC
TL2 10DA LSA
TW DRC MCM EX

N-PE Spark-gap-based-Protection Module


Protection Module with Pro-Aktive Thermo Control
Protection Module with Pro-Aktive Thermo Control
Isolating Spark Gap
Routing module with LSA tension spring
Disconnection Modules 10 TC LSA-PLUS
Partition

900 216
950 130
950 131
923 023
907 991
907 996
910 697

102
103
103
343
245
244
319

RK 16 PAS
RK 95 PAS
RK FL30 PAS
RK FL40 PAS

Modular Terminal, -16 mm2 for EB


Modular Terminal, 16-95 mm2 for EB
Modular Terminal, flat strip -30 mm for EB
Modular Terminal, flat strip -40 mm for EB

563 011
563 013
563 012
563 019

355
355
355
355

SA KRF 10 V2A
SA KRF 15 V2A
SA KRF 22 V2A
SA KRF 29 V2A
SA KRF 37 V2A
SA KRF 50 V2A
SA KRF 70 V2A
SA KRF 94 V2A
SAK 10 AS V4A
SAK 14 AS V4A
SAK 18 AS V4A
SAK 21 AS V4A
SAK 26 AS V4A
SAK 33 AS V4A
SAK 6.5 SN MS
SAK 11 SN MS

Contact Force Spring f. shield connection 4-10 mm 919 031


Contact Force Spring f. shield connection 9-15 mm 919 032
Contact Force Spring f. shield connection 14-22 mm 919 033
Contact Force Spring f. shield connection 18,5-29mm 919 034
Contact Force Spring f. shield connection 23,5-37mm 919 035
Contact Force Spring f. shield connection 31-50 mm 919 036
Contact Force Spring f. shield connection 44-70 mm 919 037
Contact Force Spring f. shield connection 58-94 mm 919 038
Shielding Terminal, stainless steel, Rd 5-10 mm 308 403
Shielding Terminal, stainless steel, Rd 8-14 mm 308 404
Shielding Terminal, stainless steel, Rd 13-18 mm 308 405
Shielding Terminal, stainless steel, Rd 17-21 mm 308 406
Shielding Terminal, stainless steel, Rd 19-26 mm 308 407
Shielding Terminal, stainless steel, Rd 25-33 mm 308 408
Shielding Terminal, stainless steel, Rd 1,5-6,5 mm 919 010
Shielding Terminal, stainless steel, Rd 5-11 mm 919 011

333
333
333
333
333
333
333
333
326
326
326
326
326
326
329
329

UGKF BNC
USB NANO 485
USD 9 V24 S B
USD 15 V11 S B
USD 25 V24 HS S B

SPD for Comupter Systems


USB interface converter of type USB NANO 485
Cable Adapter
Cable Adapter
Cable Adapter

929 010
910 486
924 061
924 051
924 046

268
360
286
287
288

V NH00 280
V NH00 280 FM
V NH1 280
VA NH00 280
VA NH00 280 FM
VA NH1 280
VC 280 2
VK A R22 F40 STBL
VK A UNI ST
VK A UNI V2 ST
VK EH R10 F30 ST
VK EH R10 F30 V2A

VNH Surge Arrester, Size 00


VNH FM Surge Arrester, Size 00
VNH Surge Arrester, Size 1
VANH Surge Arrester, Size 00
VANH FM Surge Arrester, Size 00
VANH 280, Size 1
Mains Surge Protection Module, 2-pole
Connection Clamp St/bare
Connection Clamp St/tZn
Connection Clamp St/tZn
Connection Clamp St/tZn
Connection Clamp StSt (V2A)

900 261
900 263
900 270
900 262
900 264
900 271
900 471
308 030
308 025
308 026
308 120
308 129

116
116
116
117
117
117
144
357
357
357
357
357

ZAP STW

Central Covering Plate for DEHNsafe

924 329 129

379

Key Words
Accessories / Construction Kit
Accessories for BLITZDUCTOR XT
Accessories for BLITZDUCTOR XT
Ex (i)
Accessories for DEHNconnect
Accessories for DEHNgate
Accessories for DEHNpipe
Accessories for DEHNpipe MD Ex (i)
Accessories for LSA Technology
Accessories for terminal block
systems
Accessories Red/Line
Aluminium enclosure
Aluminium enclosure for Ex(i)surge arresters
Anchor bar
AS IBAS

355
202
317
217
279
300
304
243
325
145
334
334
326
294

218/256
BLITZDUCTOR VT
224
BLITZDUCTOR VT KKS
184
BLITZDUCTOR XT
311
BLITZDUCTOR XT Ex (i)
179
BLITZDUCTOR XTU
Busbar
329
Busbars / Modular wiring system 149
BUStector
292
Combined adapters
337
Combined lightning current and surge
arrester for cathodic corrosion
protection systems
224
Combined SPDs Type 1
31
Compact protection for terminal
equipment
143
Compact SPDs for DIN rail
Mounting
209
Components for foundation
earthing electrodes
357
Components for ring equipotential
bonding
357
Condition monitoring system
359
LifeCheck
Connecting clamps
357
Constant force spring
333
Coordinated lightning current arrester 49
Coordinated lightning current
arrester for busbars
54
Cross-reference Red/Line
29
Cross-reference Yellow/Line
154
DEHNbloc
DEHNbloc M
DEHNbloc Maxi
DEHNbloc Maxi S
DEHNbloc Maxi 440/760
DEHNconnect RK
DEHNconnect RK Ex (i)
DEHNflex
DEHNgap
DEHNgap C S

380

58
45
49
54
51
209
322
132
63
92

DEHNgate
269
99
DEHNguard ... H LI
76
DEHNguard modular
DEHNguard modular CI,
with integrated backup fuse
69
88
DEHNguard S
112
DEHNguard S ... VA
107
DEHNguard PV ... SCP
104
DEHNguard M YPV SCI
110
DEHNguard 1000 FM
DEHNisola
365
DEHNlimit
42
DEHNlink
261
DEHNlink TC BT
265
DEHNpatch
253
DEHNpipe
297
DEHNpipe CD Ex (d)
307
DEHNpipe CD Ex (i)
305
DEHNpipe MD Ex (i)
301
DEHN enclosure for equipotential bonding
241
DEHNprotector
138/337
DEHNrail modular
119
DEHNrail modular, multipole
122
229
DEHNrapid LSA
DEHNrapid LSA plug-in SPD block
(without SPDs)
238
DEHNsafe
128
DEHNsignal
56
31
DEHNventil modular
39
DEHNventil ZP
Disconnection block
244
Discontinued products RL/YL 29/154
DPL 10 G3
239
DSM
289
DSM TM
259
Earthing busbars
356
Earth conductor block
244
Earthing module
202
Easy choice Red/Line
18
Easy choice according to
Interface / Signal
156
EMC spring terminals
202
Enclosure / Protective conductor
terminal
334
Enclosure system for SPDs
protecting IT equipment
241
Equipotential bonding
355
Equipotential bonding bars 355/356
EXFS 100 / EXFS 100 KU
344
EXFS L / EXFS KU
347
Flexible protection of terminal
equipment
FS / USD

132
281

Gas discharge tube


General terms of sale

279
370

Impulse meter
Information technology systems
Insertion tools
Insulating enclosure
Insulated rail support
Insulated busbar support
Isolating spark gaps
ITAK Ex (i)

366
153
243
146
330
327
343
320

Protective adapter for LAN


Protective adapter for
NTBA/DSL splitter applications
Protective adapter for
TV/radio applications
Protective conductor terminal

338
335

Rail support
Registration of discharges

330
366

Key to symbols used in


basic circuit diagrams

371

Screwable SPDs
297
SDS
353
Self-bonding rubber tape
333
SFL Protector
141
Shield connection on anchor bars 325
Shield connection on DIN rails
328
Shield connection on cables
332
Shield terminals
326/329
SPDs for D-Sub connection
281
SPDs for BT Jack connection
265
SPDs for coaxial connection
267
SPDs for LSA technology
229
SPDs for RJ connection
253
SPDs for use in potentially
explosive areas
301
SPDs for 482.6 mm (19 inch)
data cabinets
247
SPD monitoring device
365
SPD test device
363
SPS Protector
126
STC Module
130
Surge arresters Type 2
69
Surge arresters Type 3
119
Surge arresters for earthed socket
outlets
130
Surge arresters for use in cable ducts128
Surge protective adapter
138
Surge protective multiple socket
outlet with filter
141
Surge protective socket outlet
136

177
LifeCheck SPD test
361
LifeCheck SPD test device
Lightning current arresters Type 1 45
Lightning equipotential bonding 343
Literature
368
Mains filter
125
Marking system
204
Measuring and test devices
359
Modular surge arrester with
integrated backup fuse
69
More information and
documentation
367
Mounting frame
243
Mounting set
335
Multipole combined lightning current
and surge arrester for primary
power systems
39
Multipole modular combined lightning
current and surge arrester
31
Multipole, modular surge arrester 76
Multipole surge arrester with
Pro-Active Thermo Control
99
N-PE Lightning current arresters
63
N-PE spark-gap-based protection
module
38/96
N-PE surge arrester
92
NET Protector
247
NH Surge arresters
115
NSM Protector
136
Part No. Index
372
Photovoltaic systems
42/104
Pipe clamp for explosion hazard
areas
350
Pluggable SPDs for DIN rail
mounting
179
Power supply systems
15
Power supply systems worldwide 28
Protection module for DEHNbloc M 48
Protection module for DEHNguard M,
... S and DEHNgap C/ S
94
Protection module for DEHNrail
modular
124
Protection module for DEHNventil
modular
37
Protective adapter for
ISDN / Ethernet applications
340

341
339

Terminal
327/331
Terminal block
244
Terminal block with integrated
surge protection
209
Test / Disconnection module
203
TFS / KFSU
343
Type / Product index
375
UGKF

267

V NH / VA NH
115
Varistor-based protection module 95
VC 280 2
143
Wiring accessories

145

Yellow/Line SPD classes Symbols 176

www.dehn.de

Lightning Protection
Surge Protection
Safety Equipment

DS570/E/0410

Tel. +49 9181 906-0


Fax +49 9181 906-444
www.dehn.de
export@dehn.de

Copyright 2010 DEHN + SHNE

DEHN + SHNE
GmbH + Co.KG.
Hans-Dehn-Str. 1
Postfach 1640
92306 Neumarkt
Germany

You might also like