FC4A-N08B1
FC4A-N16B1
FC4A-N16B3
FC4A-N32B3
8 points in 1
16 points in 1 com16 points in 1
32 points in 2
common line
mon line
common line
common lines
See Input Module Terminal Arrangement on pages 2-38 through 2-40.
24V DC sink/source input signal
20.4 to 28.8V DC
7 mA/point (24V DC)
5 mA/point (24V DC)
3.4 k:
4.4 k:
4 ms
4 ms
Between input terminals:
Not isolated
Internal circuit:
Photocoupler isolated
Not needed
Static
Both sinking and sourcing input signals can be connected. If any input exceeding
the rated value is applied, permanent damage may be caused.
3m (9.84 ft.) in compliance with electromagnetic immunity
MC1.5/10-G-3.81BK (Phoenix Contact)
FL20A2MA (Oki Electric Cable)
100 times minimum
25 mA (5V DC)
40 mA (5V DC)
35 mA (5V DC)
65 mA (5V DC)
0 mA (24V DC)
0 mA (24V DC)
0 mA (24V DC)
0 mA (24V DC)
5 mA (5V DC)
5 mA (5V DC)
10 mA (5V DC)
5 mA (5V DC)
0 mA (24V DC)
0 mA (24V DC)
0 mA (24V DC)
0 mA (24V DC)
85g
100g
65g
100g
Input
4.3 k:
Input
15
Transition
Area
5
COM
OFF Area
0
1.2
4.2
7.0
Input Current (mA)
8.4
ON Area
When using the FC4A-N16B1 at 55C in the normal mounting direction, limit the
inputs which turn on simultaneously along line (1). At 45C, all inputs can be
turned on simultaneously at 28.8V DC as indicated with line (2).
When using the FC4A-N16B3 or -N32B3 at 55C, limit the inputs which turn on
simultaneously on each connector along line (3). At 30C, all inputs can be turned
on simultaneously at 28.8V DC as indicated with line (4).
When using the FC4A-N08B1, all inputs can be turned on simultaneously at 55C,
input voltage 28.8V DC.
15
(2) 45C
Transition
Area
OFF Area
0
3.2
5.3 6.4
0.9
Input Current (mA)
28.8
26.4
24.0
(1) 55C
(3) 55C
0
0
2-36
(4) 30C
28.8
26.4
Input Voltage (V DC)
24
28.8
100
70
Input Simultaneous ON Ratio (%)
50
70
90 100
Input Simultaneous ON Ratio (%)
2: MODULE SPECIFICATIONS
AC Input Module Specifications
Type No.
FC4A-N08A11
Terminal Arrangement
85 to 132V AC
Input Type
Input Impedance
Turn ON Time
25 ms
30 ms
Isolation
Not needed
Static
If any input exceeding the rated value is applied, permanent damage may be
caused.
All Inputs ON
60 mA (5V DC)
0 mA (24V DC)
30 mA (5V DC)
0 mA (24V DC)
Weight
Not isolated
Isolated
Photocoupler isolated
80g
The input operating range of the Type 1 and 2 (IEC 61131-2) input
module is shown below:
FC4A-N08A11
480 k:
220:
FC4A-N08A11
Internal Circuit
Input
0.33 F
132
100
COM
79
74
Transition
Area
OFF Area
20
0
1 2
4 5
13
Input Current (mA)
17
ON Area
102
0
0
100
50
Input Simultaneous ON Ratio (%)
2-37
2: MODULE SPECIFICATIONS
DC Input Module Terminal Arrangement and Wiring Diagrams
FC4A-N08B1 (8-point DC Input Module) Screw Terminal Type
Applicable Terminal Block:
FC4A-PMT10P (supplied with the input module)
DC.IN
2-wire Sensor
NPN
24V DC
+
0
1
Terminal No.
0
1
2
3
4
5
6
7
COM
COM
Input
I0
I1
I2
I3
I4
I5
I6
I7
COM
COM
2-wire Sensor
PNP
+
24V DC
Input
I0
I1
I2
I3
I4
I5
I6
I7
COM
COM
Terminal No.
0
1
2
3
4
5
6
7
COM
COM
Input
I0
I1
I2
I3
I4
I5
I6
I7
COM
COM
10
11
12
13
14
15
16
17
COM
COM
I10
I11
I12
I13
I14
I15
I16
I17
COM
COM
Terminal No.
0
1
2
3
4
5
6
7
COM
COM
3
4
5
6
7
COM COM
0
1
2
3
4
5
6
0
1
2
3
4
5
6
7
10
11
12
13
14
15
16
17
2-wire Sensor
NPN
7 COM COM
10
11
12
13
14
15
16
17 COM COM
NPN
24V DC
+
Input
I0
I1
I2
I3
I4
I5
I6
I7
COM
COM
2-wire Sensor
10
11
12
13
14
15
16
17
COM
COM
I10
I11
I12
I13
I14
I15
I16
I17
COM
COM
2-38
PNP
PNP
+ 24V DC
2: MODULE SPECIFICATIONS
FC4A-N16B3 (16-point DC Input Module) Connector Type
Applicable Connector:
FC4A-PMC20P (not supplied with the input module)
NPN
24V DC
+
Terminal No.
20
18
16
14
12
10
8
6
4
2
Input
I0
I1
I2
I3
I4
I5
I6
I7
COM
NC
Terminal No.
19
17
15
13
11
9
7
5
3
1
Input
I10
I11
I12
I13
I14
I15
I16
I17
COM
NC
2-wire Sensor
Terminal No.
20
18
16
14
12
10
8
6
4
2
Input
I0
I1
I2
I3
I4
I5
I6
I7
COM
NC
Terminal No.
19
17
15
13
11
9
7
5
3
1
Input
I10
I11
I12
I13
I14
I15
I16
I17
COM
NC
2-wire Sensor
NPN
24V DC
PNP
+ 24V DC
PNP
24V DC
2-39
2: MODULE SPECIFICATIONS
FC4A-N32B3 (32-point DC Input Module) Connector Type
Applicable Connector:
FC4A-PMC20P (not supplied with the input module)
NPN
24V DC
+
CN1
No.
20
18
16
14
12
10
8
6
4
2
Input
I0
I1
I2
I3
I4
I5
I6
I7
COM0
NC
No.
19
17
15
13
11
9
7
5
3
1
Input
I10
I11
I12
I13
I14
I15
I16
I17
COM0
NC
Input
I0
I1
I2
I3
I4
I5
I6
I7
COM0
NC
No.
19
17
15
13
11
9
7
5
3
1
Input
I10
I11
I12
I13
I14
I15
I16
I17
COM0
NC
CN2
No.
20
18
16
14
12
10
8
6
4
2
Input
I20
I21
I22
I23
I24
I25
I26
I27
COM1
NC
No.
19
17
15
13
11
9
7
5
3
1
Input
I30
I31
I32
I33
I34
I35
I36
I37
COM1
NC
2-wire Sensor
CN2
No.
2-wire Sensor
+
20
18
16
14
12
PNP
10
+
24V DC
8
6
4
2
Input
I20
I21
I22
I23
I24
I25
I26
I27
COM1
NC
No.
19
17
15
13
11
9
7
5
3
1
Input
I30
I31
I32
I33
I34
I35
I36
I37
COM1
NC
2-wire Sensor
2-wire Sensor
2-wire Sensor
NPN
24V DC
+
NPN
24V DC
+
NPN
24V DC
6
4
2
2-40
2-wire Sensor
PNP
+
24V DC
PNP
24V DC
2: MODULE SPECIFICATIONS
AC Input Module Terminal Arrangement and Wiring Diagrams
FC4A-N08A11 (8-point AC Input Module) Screw Terminal Type
Applicable Terminal Block:
FC4A-PMT11P (supplied with the input module)
AC.IN
0
1
2
3
4
5
6
7
AC
0
1
2
Terminal No.
0
1
2
3
COM0
NC
4
5
6
7
COM1
Output
I0
I1
I2
I3
COM0
NC
I4
I5
I6
I7
COM1
3 COM0 NC
AC
4
5
6
7
COM1
2-41