0 INTRODUCTION
Power transmission lines are designed to transmit large values of power between even
far points. Generally power plants are created where an energy source is available. Then
these plants will serve all users located in industrial areas.
The operating voltage is choosing according to minimize joule effect losses. It can
immediately by realized that sources will be reduced when current it reduced, but when
huge volumes of power have to be sent, energy will be exclusively transmitted with high
voltages. All that will lead to consider also the accessories that are step up transformers at
the origin and the respective step down transformers at the destination of the lines.
The parameter of capacitance is directly proportional the length of the transformer line,
its concentrated into an equivalent total of capacitance only for easier study. Actually the
parameter of a transmission line (capacitance and resistance in this particular case) are
distributed crossing to line resistor the capacitance current will produce power losses
occurring even when the transmission line is in no load condition.
2.0 EXPERIMENT OBJECTIVES

Measurement of the voltage increase and charging power in lines of different lengths in

no load operation.
Different performance characteristics of overhead transmission line and cable.

3.0 METHODOLOGY
1. The circuit is assembled as shown in figure 5.
2. The secondary side voltage of the three-phase transformer is set to U N -10% using the
bridging plugs.
3. The connection of the bridging plugs made for this experiment means that the shortest
possible transmission line length, 144km, has been selected.
4. The voltage between the two outer conductors at the beginning and end of the line is
measured, as well as the reactive power consumed by one of the phases.
5. The line length is changed to 216km by reconnecting the bridging plugs as shown in
figure 6 and the measurement is repeated.
6. The line length is changed to 360km by reconnecting the bridging plugs as shown in
figure 7 and the measurement is repeated.
7. To demonstrate the concept of operating capacitance, the circuit in figure 8 is
assembled.

8. The voltage at the three-phase transformer is set to the value U N -10%, all bridging plug
is removed, and the capacitances is connected to the transmission line model.
9. The voltage between the two outer conductors at the beginning and end of each line is
measured, as well as the reactive power consumed by a phase.
10. The difference between the performance of a cable and the performance of an overhead
transmission line in no-load operation is demonstrated by the connection shown in figure
9.
11. The operating capacitance of the transmission line model is doubled by connecting the
two (artificial) line capacitances. The voltage increase effect at the line end is thus
amplified.
12. The voltage between two outer conductors at the beginning and end of each line is
measured as well the reactive power consumed by a phase.
4.0 RESULTS

LINE LENGTH (KM)


144
216
360

U1 / V
380
380
385

RATIO
U2 / U 1
1.03
1.05
1.09

U2 / V
390
400
420

QC / Var
30
40
80

Table 1: The characteristics of a transmission lines in no-load.

CONDITIONS
OPERATING CAPACITANCE

U1 / V

U2 / V

RATIO
U2 / U 1

QC / Var

380

420

1.11

40

390

470

1.21

170

INCREASED OPERATING
CAPACITANCE

Table 2: The characteristics of transmission line model with operating capacitance and increased operating
capacitance.

5.0 DISCUSSION

The secondary-side voltage of the three-phase transformer is set to U N -10%, using the
bridging plugs. The connection of the bridging plugs is made for the shortest possible
transmission line length 144km. The voltage between the two outer conductors at the
beginning and end of the line is measured. The charging reactive power QC is measured.
The ratio of U2 to U1 is calculated. This step is repeated for transmission line length
216km and 360km. The result is shown in table 1.

Based on the result in table1, the Q/Var against 1/% graph and U2/U1 against 1/% is
plotted. From the graph1, the charging reactive power is increasing exponentially with
the line length. From the graph2, the ratio U2/U1 is increasing with the line length. The
transmission line required active power in no-load operation because of the increase in
the charging reactive power QC will cause increasing in active power.

The circuit is connected as shown in figure 8 to demonstrate the concept of operating


capacitance. The voltage at the three-phase transformer is set to the value UN-10%, all
bridging plugs are removed and the capacitances are connected to the transmission line
model. Compare the result with that for the transmission line model at a length of 100%,
transmission line model at length at 100% will be slightly affected due to the capacitive
coupling that produced by the equivalent capacitance.

The transmission line is connected as shown in figure 9 to figure out the difference
between the performance of a cable and the performance of an overhead transmission
line in no-load operation. Compare the result with those for a line length of 100% but
3

without additional capacitances, the reactive power become increase due to the double
operating capacitance of the transmission line model.

6.0 CONCLUSION
The objectives of this experiment were achieved. The measurement of the voltage increases
and the charging power in lines of different length in no-load operation. Besides that, the length
line shows that the different performance characteristics of overhead line and cable which is the
charging reactive power is increasing exponentially with the line length and it will cause
increasing in active power.