REZUMAT
The results supplied by the analysis and processing of the experimental data obtained in CS 3
Bucharest solar house (INCERC) are also
presented; these results prove the theoretical ones
valid. The paper also includes a description of the
transient mathematical model specific to the
analysis of solar space system without air flow in
various constructive variants.
I. Introduction
Passive solar heating is presently a major
concern of Romania groups working on building
research and design. The first theoretical and
experimental research studies were worked out in
INCERC and used the following experimental bases:
the INCERC 1 solar cabin (1974), the Campina
solar houses (1976, 1977), the solar apartment
buildings in Medgidia (1981) and CS 3 Bucharest
solar house at INCERC (1982). Three passive solar
heating systems were analysed:
the INCERC system, similar to the
Trombe system with air flow through the
greenhouse space collecting solar radiation;
the Trombe system without air flow;
the direct gain system with triple glazing.
This paper introduces the theoretical and
experimental analysis of the first two systems which
are presently used in Romania typified projects for
dwelling and industrial buildings.
Nr. 1 / 2007
D. Constantinescu
x=
tG ) = Gcv (t g t ) + K g (tG te )
(1)
x=
t) + r (
x=
tG ) +
x=
(2)
for the heat carrier:
Gc pa (t
y = H ti )
P
= S p [ cv
(
x =
+ Gcv (tG t )]
t) +
(3)
Nr. 1 / 2007
V / S P = A1
x=
+ A2
t = B1 () y + ti
(4)
(5)
=0
(6)
=a
(8)
+ 4.74t + K G te + 17.70
r + 4.74 + K G
0.223
= 23.19 (
x=
= 23.19 (
x=
4.34)
(14)
x=
and x& =
, y& =
y
H
x&
x&
x=
( y, )) (13)
where:
(9)
(10)
x=
x=
Fo
t&)
+ 3.19
x=
x=
(12)
(7)
cv = 1.60 t 0.33
x=
3.41
B1 () =
x =0
2
x& 2
=0
x& = 0
+ 23.19
x& =1
=0
(15)
x& =1
Fo = 0
= f ( x& ) ( y& , 0)
where
= ( y& , Fo)
where:
t& = 0.16t E () + 0.84t + 3.11
Nr. 1 / 2007
(11)
D. Constantinescu
2
j
P (Fo s ) ds
Fo E ( s )
(18)
where
P (Fo) =
a0
b0
+
j
A( p j )
R( p j ) p j
exp ( p j Fo)
A( p ) = a j p j
j
R ( p) = b j p j
j
Fo ( y
&,
S)
Function
x& =1
exp [m 2j (Fo S )] dS
(16)
x& =1
j
mj (mj + sinmj cosmj )
Fo E (S )
0
S
(S)
Fo
x&=1
0.238 & (0) (Fo) +
(Fo S) dS
x=1
0
S
(17)
with the following solution:
1
& (Fo) =
x =1
b0
m 2j +
j
B(pj)
R( p j ) p j
exp ( p j Fo) +
x& =1
x&
Sp
(19)
x& =1
Nr. 1 / 2007
34
32
30
28
26
24
22
ti=8C
20
ti=14C
ti=20C
18
ti=22C
16
14
30
32
34
36
38
40
42
44
46
48
50
Nr. 1 / 2007
D. Constantinescu
x& =1
, ti ) resulted which is
Tabelul 1.
tes
ten
[C]
[C]
te
[C]
510
5.9
16.6
10.0
11.6
22.3
Month
I
n
[W / m2] [h / day]
ti
[C]
XI
463
2.5
7.2
3.9
4.3
15.3
XII
464
1.5
2.8
1.0
0.8
18.3
457
2.1
3.8
6.8
6.5
15.3
II
512
4.8
4.5
8.8
8.0
15.3
III
463
2.5
3.7
1.1
1.4
18.3
IV
454
7.1
18.5
12.3
14.1
20.3
AVE
480
3.3
6.1
0.2
0.67
10.3
75
80
75
70
65
60
qM = 0.897qC + 4.8716
2
R = 0.9985
55
50
45
qM
qC
Linear (q M)
40
35
30
30
35
40
45
50
55
60
65
70
(20)
where
10
c = 0.065 ( H / ) 1/ 9 Pr 1/ 3
Nr. 1 / 2007
q PI () = {t PI ()} { X } + {t PE ()} {Y }
(21)
q PE () = {t PE ()} { X } + {t PI ()} {Y }
Table 2.
Concrete collecting wall
Wall type
C-2GWP
0.2
0.2
0.2
0.2
0.2
0.2
2.88
13.68
15.07
6.00
9.54
10.89
[m]
0.3
0.3
0.3
0.3
0.3
0.3
2.94
12.6
13.79
4.09
9.32
10.54
[m]
2
C-2GP
C-2GRS
C-1GWP
C-1GP
C-1GRS
Table 3
ALC collecting wall
Wall type
ALC-2GWP
ALC-2GP
ALC-2GRS
ALC-1GWP
ALC-1GP
ALC-1GRS
[m]
0.2
0.2
0.2
0.2
0.2
0.2
5.36
10.11
11.02
1.77
6.96
7.82
[m]
qPI [kgcf / m year]
2
0.3
0.3
0.3
0.3
0.3
0.3
6.00
9.68
10.41
3.40
7.14
7.88
Nr. 1 / 2007
11
D. Constantinescu
V. Interpretation of results
The variant implying the highest energy gain is
concrete with double glazing and reflecting screen
protection, 0.20 m concrete thickness (qPI =
= 15.07 kgcf / m2 year; 1 kgcf = 21.506 kJ).
If automatic thermal protection is not
under service the energy gain is reduced up to
2.88 kgcf / m2 year. The influence of thermal
protection automatic control is rendered evident by
the following ration:
Rc(1) = 0.47
Rc( 2) = 0.73
where (1), (2) represent the glazing type.
In case of ALC the same ratios are:
(1)
RALC
= 0.76
( 2)
RALC
= 0.82
VI. Conclusions
a. This paper presents the analysis on mathematical models of two passive solar heating systems:
INCERC system with air natural flow in the
collecting greenhouse;
Trombe system without air flow.
b. Starting from the calculation models that
were worked out, the experimental data supplied
by CS 3 Bucharest solar house (at INCERC) were
analysed and processed.
c. The measured data (air volume flow-rate
values, convective and conductive heat flows) are
in accordance with those obtained by calculation.
d. The paper gives a description of the transient
mathematical model specific to the analysis of
unvented Trombe walls.
12
Symbols
tG glazing area temperature [C]
t air temperature in collecting greenhouse [C]
te outside temperature [C]
t
y=H
x=
Nr. 1 / 2007
REFERENCES