You are on page 1of 65

KAWASAKI GPB30

This document is the property of Kawasaki


Gas Turbine Asia (KGA) . It has been
prepared exclusively for PPGJ GTG internal
use only. It contains confidential and
proprietary information of KGA and is not to
be disclosed to any person outside of PPGJ.
The reproduction of this document in any
manner or medium is strictly prohibited
without written authorization from KGA. Any
use made of this document, in whole or in
part, other than for evaluation purposes is
strictly prohibited without the express prior
written consent of KGA.

Warning: The purpose of this training is to provide basic information and principles of
Gas Turbine Generator (GTG) and its components. Under no circumstances, this
note is to be used as a reference during GTG maintenance or operation.

CONTENT
SYSTEM:
a.
GTG in General
b.
Enclosure and Inlet/Exhaust System
c.
Fuel System
d.
Lube Oil System
e.
Instrument Air System
f.
Electrical System
g.
Control System
OPERATING INSTRUCTION
a.
Pre-operation Check
b.
Starting Procedure
c.
Load Transfer Procedure
d.
Stopping Procedure
e.
Cranking
f.
Log and Operating Condition
TROUBLESHOOTING

GTG IN GENERAL AND SPECIFICATION


GPB30 Engine Arrangement and Specification

Engine Assembly: consists of 2 power sections, main reduction


gearbox and 2 accessory gearboxes.
Package Assembly: consists of engine assembly and generator.

POWER SECTION
Called Gas Turbine or GT
Consists of:- Two stages of CENTRIFUGAL Compressors
- Three stages of AXIAL Turbine
- Single CAN type combustor
- Double end supported BEARINGS
Speed: 21870 rpm
Weight: 1.19 ton

MAIN REDUCTION GEARBOX AND


ACCESSORY GEARBOX
Main Reduction Gearbox:- Type: Parallel
- Output Speed: 1,500 rpm (50Hz)
- Reduction Gear Ratio: 14.58

Accessory Gearbox
- Mounted to main reduction gearbox

GENERATOR
Type: Synchronous AC generator type
Capacity: 2812.5 kVA
Voltage: 6.6 kV
Frequency: 50 Hz
Number of poles: 4 poles

Enclosure and Inlet/Exhaust System


Enclosure Cooling Air
Turbine Inlet Air
Exhaust Air

FUEL SYSTEM
Engine Gas Fuel System
PT, FT, TE
Temperatur/Presure
compensation

PA

To Gas Exhaust

KHI/PLC

KHI/PLC

PT
FT

Gas fuel filter


differensial
presure high

EOV

PGV

TE

SSV1

SSV2

MGV

Gas Control
Valve

Gas Filter
SGV

FUEL SYSTEM
Engine Diesel Fuel System

PASSING

Pressurizing
Valve
Supply Fuel
Shutoff
Valve

Start Fuel
Pump
Main Fuel
Pump

Start Fuel
Valve
Fuel Control
Valve

Bypass Fuel
Valve

Main Fuel
Valve

Return to
service tank

DIESEL FUEL
LEAK

LUBE OIL SYSTEM


Engine Lube Oil System
LO Cooler

Oil mist separator

Vent

Manifold

Gas Turbine

Generator
Gearbox
LO Tank
160L
Main LO Pump
M

Pre Post
Pump

INSTRUMENT AIR SYSTEM


Engine Instrument Air System
Pressure for air starting: 0.9 1.0 MPa
Pressure for instrument: 0.6 MPa
P
G

P
G

P
G

Pressure
Control
Valve
Air for Starting
Pressure
Control
Valve
M

Instrumen
t Air Tank

Instrumen
t Air Tank

Fuel Line Purge


Air
Dryer

SSV-1 & SSV-2


Regulating
Valve

EOV
Intake Filter
JB Pressurizing
Gas Pressure Regulating
Valve

ELECTRICAL SYSTEM
Engine Electrical System
1. Ignition System
2. EGT Hardness
3. Speed Pick Up (Pulse)
4. Turning Motor

1. Ignition System
Ignition system is required to ignite the mixture of fuel and air inside the combustor during start up.

Ignition Plug:

Manufacturer: NGK Spark Plug Co.Ltd.

Ignition Exciter:

Manufacturer: Yamamoto Electric Works Co. Ltd.

Input voltage: DC24V

Discharge cycle: 3.5 sparks per seconds

Discharge specification: 1 Joule per spark

2. Exhaust Gas Temperature


(EGT) Hardness
EGT Hardness is required to measure result of the combustion of fuel before discharge into the atmosphere.
It is also used to compare and monitor the performance of the gas turbine.

Thermocouple type : K type, T1 bias

3. Speed Pickup Pulse


Speed Pickup Pulse is required to detect the rotation speed of the power section and gearbox by magnetic
pulse.
Speed Pickup Pulse for power section:

Manufacturer: Yamamoto Electric Works Co. Ltd.

Type: Magnetic detection

Voltage: 4.5 V p-p (output)

Speed Pickup Pulse for gearbox:

Manufacturer: Yamamoto Electric Works Co. Ltd.

Type: Magnetic detection

Voltage: 85-120 V p-p (output)

4. Turning Motor
Turning motor is required to rotate the turbine shaft slowly after shutdown to allow uniform cooling to
the turbine shaft.
The turning duration is controlled automatically by the gas turbine control panel.

Manufacturer: Sawamura Denki Kogyo Co.


Type
: DC Electrical motor
Rating
: 24 VDC, 0.5A

CONTROL SYSTEM
Engine Control System
1. Timing Schedule (Gas)
2. Timing Schedule (Diesel)
3. Alarm and Interlock
4. Operation Display Panel

TIMING CHART
Start
com
Gas Pressure
Established

Voltage
establish

Loading
completed

CB
close

95%

Stop
com

Stop

CB
open
95%
GTG cooling 5 min

55%

Fuel Changing

Unloading

4%

Loading

22%

3 min
Synchronizing

2 sec

Pre-excite

Fuel Changing

Pre Purge
Pre Purge
On
Off

55%

22%

4%

Starter Motor
Aux Machine
cooling 30 min

Ignition Exciter
Oil Cooler Fan
Encl Vent Fan
Turning Motor
Liquid Fuel Cooler Fan

Turning 10 hours

Pre Post LO Pump


Safety Shutoff Valve 1 (SSV1)
Safety Shutoff Valve 2 (SSV2)
Main Gas Valve (MGV)

1 sec

Start Gas Valve (SGV)


E. Open Valve Close (EOV)
Main Fuel Valve (MFV)

1 sec

1 sec

Start Fuel Valve (SFV)


Bypass Fuel Valve (BFV)
Purge Gas Valve (PGV)
Assist Air Valve (AAV)

30 sec
10 sec

TIMING CHART
Start
com
Gas Pressure
Established

Voltage
establish

Loading
completed

CB
close

95%

Stop
com

Stop

CB
open
95%
GTG cooling 5 min

55%

Fuel Changing

Unloading

Loading

22%

3 min
Synchronizing

4%

2 sec

Pre-excite

Fuel Changing

Pre Purge
Pre Purge
On
Off

55%

22%

4%

Starter Motor
Aux Machine
cooling 30 min

Ignition Exciter
Oil Cooler Fan
Encl Vent Fan
Turning Motor
Liquid Fuel Cooler Fan

Turning 10 hours

Pre Post LO Pump


Safety Shutoff Valve 1 (SSV1)
Safety Shutoff Valve 2 (SSV2)
Main Gas Valve (MGV)

1 sec

Start Gas Valve (SGV)


E. Open Valve Close (EOV)
Main Fuel Valve (MFV)

1 sec

1 sec

Start Fuel Valve (SFV)


Bypass Fuel Valve (BFV)
30 sec

Purge Gas Valve (PGV)


Assist Air Valve (AAV)

10 sec

TIMING CHART (DIESEL)


Start
com

Voltage
establish

Loading
completed

CB
close

95%

Stop
com

Stop

CB
open
95%
GTG cooling 5 min

55%

55%

Unloading

22%
Loading

5%

Pre-excite

22%

Synchronizing

2 sec

4%

Starter Motor
Ignition Exciter

Aux Machine
cooling 30 min

Oil Cooler Fan


Encl Vent Fan
Turning Motor
Liquid Fuel Cooler Fan

Turning 10 hours

Pre Post LO Pump


Safety Shutoff Valve 1 (SSV1)
Safety Shutoff Valve 2 (SSV2)
Main Gas Valve (MGV)
Start Gas Valve (SGV)
E. Open Valve Close (EOV)
Main Fuel Valve (MFV)
Start Fuel Valve (SFV)
Bypass Fuel Valve (BFV)
Purge Gas Valve (PGV)
Assist Air Valve (AAV)

30 sec

TIMING CHART (DIESEL)


Start
com

Voltage
establish

Loading
completed

CB
close

95%

Stop
com

Stop

CB
open
95%
GTG cooling 5 min

55%

55%

Unloading

22%
Loading

5%

Pre-excite

22%

Synchronizing

2 sec

4%

Starter Motor
Ignition Exciter

Aux Machine
cooling 30 min

Oil Cooler Fan


Encl Vent Fan
Turning Motor
Liquid Fuel Cooler Fan

Turning 10 hours

Pre Post LO Pump


Safety Shutoff Valve 1 (SSV1)
Safety Shutoff Valve 2 (SSV2)
Main Gas Valve (MGV)
Start Gas Valve (SGV)
E. Open Valve Close (EOV)
Main Fuel Valve (MFV)
Start Fuel Valve (SFV)
Bypass Fuel Valve (BFV)
Purge Gas Valve (PGV)
Assist Air Valve (AAV)

30 sec

ALARM AND INTERLOCK


Failure Description

Set Point

Major Fault

1.1

Start Failure 0-55%

352 seconds

1.2

Start Failure 55-95%

202 seconds

1.3

Over Speed

110+0, -2%

1.4

Under Speed 55-95%

54+0, -4%

1.5

Under Speed 95%~

94+0, -4%

1.6

LO Supply Temperature HH

905C

1.7

LO Supply Pressure LL (starting)

0.1+0.05, -0 MPa

1.8

LO Supply Pressure LL (running)

0.2+0.05, -0 MPa

1.9

Exhaust Gas Temperature HH (starting)

700+0, -40C

1.10

Exhaust Gas Temperature HH (running)

58010C

1.11

Emergency Shutdown

Push Button

1.12

Main Shaft Vibration HH

2D3m

1.13

Gearbox Vibration HH

2D0.5 mm/s

1.14

Flame Out

20010C

1.15

Miss Fire

1.16

GTG Package Gas Leak HH

10000 ppm

1.17

Generator Stator Winding Temperature HH

1502C

1.18

Generator Bearing Temperature HH

952C

1.19

Under Voltage (27G)

85V, 2 seconds

1.20

Over Voltage (59G)

130V, 2 seconds

1.21

Loss of Excitation (40G)

2 seconds

1.22

Generator Differential Protection (87G)

0.4A, 10%, instant

ALARM AND INTERLOCK


Failure Description

Set Point

1.23

Revolving Rectifier Failure (71G)

1.24

GTG Package Fire

1.25

Emergency Opening Valve Open

1.26

Pre-Post LO Supply Pressure L

1.27

Fuel Gas Valve Leak

1.28

PLC Major Fault

1.29

Control Power Fault

1.30

Supply Fuel Shutoff Valve Abnormal

1.31

Strainer Differential Pressure HH

1.32

Package Inlet Air Damper Close

1.33

Package Ventilation Air Damper Close

Middle Fault

2.1

Over Current (51G)

111%, M:1

2.2

Reverse Power (67PG)

10%, 10 seconds

2.3

Negative Sequence Current (46G)

M:10, 30%

2.4

Over Frequency (95HG)

54 Hz, 0.1 second

2.5

Under Frequency (95LG)

47.5 Hz, 0.1 second

2.6

Ground Over Current (51N)

2.7

AVR Failure

0.0150.0013 MPa

0.35 MPa

ALARM AND INTERLOCK


Failure Description

Set Point

Light Fault

3.1

Main Shaft Vibration H

1.5D3 m

3.2

Gearbox Vibration H

1.5D0.5 mm/s

3.3

GTG Package Gas Leak H

2500 ppm

3.4

Exhaust Gas Temperature H

56010C

3.5

LO Supply Temperature H

805C

3.6

LO Tank Level L

12010 L

3.7

LO Filter Differential Pressure H

0.240.04 MPa

3.8

LO Supply Pressure L

0.260.02 MPa

3.9

Sensor Failure

3.10

Turning Motor Power Failure

3.11

Pulse Filter Differential Pressure H

3.12

Intake Air Filter Differential Pressure H

3.13

Gas Fuel Control Valve Failure

3.14

GTG Oil Leak

3.15

Fuel Gas Pressure L (for fuel change)

3.16

Generator Stator Winding Temperature H

1352C

3.17

Generator Bearing temperature H

852C

3.18

Auxiliary Machine Failure

3.19

Fail to Syncoro

3.20

PLC Minor Fault

3.21

Display Failure

3.22

Starting Air Pressure L

0.7 kPa

2 minutes

ALARM AND INTERLOCK


Failure Description

Set Point

3.23

Strainer Differential Pressure L

0.3 MPa

3.24

Gas Fuel Filter Differential Pressure L

3.25

Liquid Fuel Filter Differential Pressure H

3.26

UPS Panel Failure

3.27

DC Battery Failure

3.28

Fire Extinguish Panel Failure

3.29

Ground Over Current (51N)

3.30

Fuel Gas Pressure LL

3.31

Supply Fuel Shutoff Valve Abnormal

3.32

Junction Box Air Pressure L

0.24 MPa

0.880.025 MPa

500 Pa

OPERATION INSTRUCTION
a.
b.
c.
d.
e.
f.

Pre-operation Check
Starting Procedure
Load Transfer Procedure
Stopping Procedure
Cranking
Log and Operating Condition

a. PRE OPERATION CHECKS


Following checks to be carried out prior to start GTG by Diesel Fuel Mode
NO

DESCRIPTION

CRITERIA

Intake Air Filter

Ensure security & no obstruction

GTG

Area

Ensure clear and no abnormality

GTG Ventilation Inlet Filter

Ensure security & no obstruction

Diesel Fuel System

Service Tank Outlet Supply Valve

Open

GTG Inlet Supply Valve

Open

GTG Outlet Return Valve

Open

FO Cooler Inlet Return Valve

Open

Service Tank Inlet Return Valve

Open

Service Tank Level

Confirm Full

Instrument Air

Supply

Confirm Supply Available

GTG Inlet Supply Valve

Open

Lubrication Oil (GTG)

Oil Tank Level

Confirm >120

Visual Inspection

No Leak

Oil Mist Vent

Confirm no obstruction

Power Supply

AC120V supply to TCP

confirm energize

DC24V supply to TCP

confirm all energize

JUDGEMENT

a. PRE OPERATION CHECKS


Following checks to be carried out prior to start GTG by Gas Fuel Mode
NO

DESCRIPTION

CRITERIA

Intake Air Filter

Ensure security & no obstruction

GTG
a

Area

Ensure clear and no abnormality

GTG Ventilation Inlet Filter

Ensure security & no obstruction

Lean Gas Fuel System


a

Lean Gas Fuel Valve

Open

Lean Gas Supply Pressure

> 1.323 MPa

Confirm Gas Filter Select

Valve Open

Diesel Fuel System


a

Service Tank Outlet Supply Valve

Open

GTG Inlet Supply Valve

Open

GTG Outlet Return Valve

Open

FO Cooler Inlet Return Valve

Open

Service Tank Inlet Return Valve

Open

Instrument Air
A

Supply

Confirm Supply Available

GTG Inlet Supply Valve

Open

Lubrication Oil (GTG)


A

Oil Tank Level

Confirm >120

Visual Inspection

No Leak

Oil Mist Vent

Confirm no obstruction

Power Supply
a

AC120V supply to TCP

confirm energize

DC24V supply to TCP

confirm all energize

JUDGEMENT

b. STARTING PROCEDURE
Starting and Loading in Manual Mode
1.
2.

3.

4.
5.

6.
7.
8.
9.
10.

On Operation page, select MANUAL mode and execute


If GTG starting in Diesel Mode, confirm following
On Operation page, select DIESEL and execute
If GTG starting in Gas Mode, confirm following
On Operation page, select GAS and execute
On Menu Bar, select READY
Confirm followings:
GTG Speed <5%
No Heavy Fault (GTG Trip Signal)
CB no Trip Signal
Generator CB Open
Starter Motor Ready to Start
On Operation page, select GAS TURBINE START and execute
Confirm Voltage Establish after GTG in RUNNING mode
On Operation page, select the SYNC DEVICE ON and execute
Manually adjust the voltage and GT speed
Manually CLOSE the generator CB when GTG frequency and voltage meet the criteria of
differential

b. STARTING PROCEDURE
Starting and Loading in Semi Auto Mode
1.
2.

3.

4.
5.

6.
7.
8.
9.
10.

On Operation page, select SEMI AUTO mode and execute


If GTG starting in Diesel Mode, confirm following
On Operation page, select DIESEL and execute
If GTG starting in Gas Mode, confirm following
On Operation page, select GAS and execute
On Menu Bar, select READY
Confirm followings:
GTG Speed <5%
No Heavy Fault (GTG Trip Signal)
CB no Trip Signal
Generator CB Open
Starter Motor Ready to Start
On Operation page, select GAS TURBINE START and execute
Confirm Voltage Establish after GTG in RUNNING mode
On Operation page, select the AUTO SYNCRO and execute
GTG will auto raise/reduce speed and voltage to meet the differential criteria
GTG will auto command to close the generator CB when frequency and voltage meet the
criteria of differential

b. STARTING PROCEDURE
Starting and Loading in Auto Mode
1.
2.

3.

4.
5.

6.
7.
8.
9.

On Operation page, select AUTO mode and execute


If GTG starting in Diesel Mode, confirm following
On Operation page, select DIESEL and execute
If GTG starting in Gas Mode, confirm following
On Operation page, select GAS and execute
On Menu Bar, select READY
Confirm followings:
GTG Speed <5%
No Heavy Fault (GTG Trip Signal)
CB no Trip Signal
Generator CB Open
Starter Motor Ready to Start
On Operation page, select GAS TURBINE START and execute
GTG will AUTO SYNC after voltage established
GTG will auto raise/reduce the speed and voltage to meet the differential criteria
GTG will auto close the generator CB when frequency and voltage meet the criteria of
differential

c. LOAD TRANSFER PROCEDURE


Load Transfer in Manual Mode
1.
2.
3.
4.
5.
6.

On Operation page, select MANUAL mode and execute


Start another GTG according to starting procedure
Synchronize another GTG to existing on load GTG for PARALLEL OPERATION
Manually raise another GTG speed and lower existing GTG speed
Observe the load (kW) is transferring to another GTG
Manually OPEN/TRIP the generator CB when load reduced to <80kW

c. LOAD TRANSFER PROCEDURE


Load Transfer in Semi Auto or Auto Mode
1.
2.
3.
4.
5.
6.

On Operation page, select SEMI AUTO or AUTO mode and execute


Start another GTG according to starting procedure
Synchronize another GTG to existing on load GTG for PARALLEL OPERATION
On Operation page of existing GTG, select AUTO UNLOAD and execute
Observe the load (kW) is transferring to another GTG
The generator CB will automatically OPEN/TRIP when load reduced to <80kW

d. GTG STOPPING PROCEDURE


Stopping in Manual Mode:

On Operation page, select MANUAL mode and execute.

Unload GTG according to manual unload manual.

Wait for 5 minutes for GTG cooling.

Carry out fuel change to DIESEL mode

After GTG cooling sequence completed, select the STOP on the Operation page and execute.

After GTG completely stopped, carry out inspection and verify for pre-post pump and turning motor operation.
Stopping in Semi Auto Mode:

On Operation page, select SEMI AUTO mode and execute.

Unload GTG according to semi auto unload manual.

GTG will auto fuel change to DIESEL mode after 3 minutes of cooling and resume another 2 minutes cooling
on DIESEL mode.

After GTG cooling sequence completed, select the STOP on the Operation page and execute.

After GTG completely stopped, carry out inspection and verify for pre-post pump and turning motor operation.
Stopping in Auto Mode:

On Operation page, select AUTO mode and execute.

Then select STOP on the Operation page and execute.

GTG will unload, cooling, fuel change and stop automatically.

After GTG completely stopped, carry out inspection and verify for pre-post pump and turning motor operation.

e. GTG MANUAL PURGING


(CRANKING)
On the Operation page, select PURGE,
push and hold the execute button.
Verify that GTG speed will rise up.
Cranking will stop if:
GTG speed > 25%
Release the execute button.

f. LOG AND OPERATION CONDITION


Description

Unit

Criteria

#1 Engine Speed

95~108

#2 Engine Speed

95~108

Gearbox Speed

95~108

#1 Intake Air Temp

#2 Intake Air Temp

#1 Exhaust Gas Temp (1)

<560

#1 Exhaust Gas Temp (2)

<560

#2 Exhaust Gas Temp (1)

<560

#2 Exhaust Gas Temp (2)

<560

#1 LO Supply Temp

<80

#2 LO Supply Temp

<80

#1 Main Shaft Vibration

<1.5D

#2 Main Shaft Vibration

<1.5D

Gearbox Vibration

mm/s

<1.5D

#1 Comp Discharge Press

MPa

#2 Comp Discharge Press

MPa

#1 LO Filter Inlet Press

MPa

#2 LO Filter Inlet Press

MPa

#1 LO Filter Outlet Press

MPa

#2 LO Filter Outlet Press

MPa

Time

Time

Time

Time

Time

f. LOG AND OPERATION CONDITION


Description

Unit

Criteria

#1 LO Supply Press (PP)

MPa

>0.015

#2 LO Supply Press (PP)

MPa

>0.015

Starting Air Pressure

MPa

Intake Air Filter Diff Press

kPa

<0.7

Fired Start Counter


Total Running Hour

Hr

#1 LO Outlet Temp (1)

#1 LO Outlet Temp (2)

#2 LO Outlet Temp (1)

#2 LO Outlet Temp (2)

#1 LO Supply Pressure

MPa

>0.26

#2 LO Supply Pressure

MPa

>0.26

#1 Strainer Inlet Pressure

MPa

#1 Strainer Outlet Pressure

MPa

#1 Strainer Diff Pressure

MPa

#2 Strainer Inlet Pressure

MPa

#2 Strainer Outlet Pressure

MPa

#2 Strainer Diff Pressure

MPa

<0.3

<0.3

Time

Time

Time

Time

Time

f. LOG AND OPERATION CONDITION


Description

Unit

Criteria

Generator Voltage (U-V)

400

Generator Voltage (V-W)

400

Generator Voltage (W-U)

400

Generator Current (U)

Generator Current (V)

Generator Current (W)

Generator Power Factor


Generator Frequency

Hz

50

Generator kWh

kWh

Generator kW

kW

Generator kVar

kVar

Excitation Voltage

Excitation Current

Gen Winding Temp (U)

<135

Gen Winding Temp (V)

<135

Gen Winding Temp (W)

<135

Gen Bearing Temp (DE)

<85

Gen Bearing Temp (NDE)

<85

Gas Governor Output

Liquid Governor Output

Time

Time

Time

Time

Time

f. LOG AND OPERATION CONDITION


Description

Unit

Gas Governor Actuator

Bus Voltage

400

Bus Frequency

Hz

50

Gas Fuel Flow

Nm3/h

Gas Fuel Pressure

MPa

Gas Fuel Temperature

Gas Fuel Flow (Pulse)

Nm3

Combustor Inlet Gas Fuel


Pressure

MPa

Accumulator Gas Fuel


Pressure

MPa

Gas Fuel Flow

MMSC
FD

Remarks

Criteria

Time

Time

Time

Time

Time

TROUBLESHOOTING
1.
2.
3.
4.
5.
6.

Large Vibration
High Exhaust Gas Temperature
Overspeed
Startup Failure
Low Lubrication Oil Pressure
High Lubrication Oil Temperature

1. Large Vibration
Vibration of gas turbine shaft is monitored to
detect Large Vibration. Specific alarm
value and trip value has been set in the
PLC.

1. Large Vibration
Possible causes of this problem are as
follows:
1. Defect of gas turbine itself: Abnormal
bearing or rotary part, etc.
2. External factor: Rubbing with foreign
matters entering through intake port.
3. Defect of control system: Abnormal
vibration system, etc.

1. Large Vibration
1.1 Simplified Inspection of Equipment
Gas Turbine
Inspection item 1
Visually check that engine (output shaft) is rotating smoothly as driven by turning motor
Objective
To confirm that rotor system is not on contact with stationary part and that foreign matter has not been
caught. If there is such abnormality, engine rotation is not smooth and generating friction sound.
Inspection item 2
Manually rotate engine by hand to check for abnormal rotation or abnormal rotating sound
Objective
This method is to be conducted if above inspection item 1 cannot be done by turning motor.
Inspection item 3
Study of data before occurrence of problem
Change in gas turbine shaft vibration value or reduction gear vibration value
Generator output
Lubrication oil temperature and pressure
Change in temperature for No.1, No.2 lube oil drain.
Objective
To obtain data useful to determine whether vibration increase is sudden or gradual as the result of
aged deterioration or false meter indication
To confirm that load is normal
To confirm that bearings are lubricated properly.

1. Large Vibration
1.2 Inspection of Individual Control Devices
Vibration System
Inspection item 1
Check monitor cable connection for looseness. If connection is loose or disconnect then connect cable
properly.
Objective
To confirm that signal is input properly to monitor
Inspection item 2
Check sensor wiring connection for looseness
Objective
To confirm that signal is output properly from sensor
Inspection item 3
Disconnect wire from sensor and measure DC resistance. Normal value is between 2.5-3.0 ohm
Objective
To confirm that wire is not broken

2. High Exhaust Gas Temperature


Exhaust gas temperature of gas turbine is
monitored to detect High Exhaust Gas
Temperature. Specific alarm value and
trip value have been set in the PLC.

2. High Exhaust Gas Temperature


Possible causes of this problem are as follows:
1. Defect of gas turbine itself: Deteriorated
performance of turbine, deteriorated
performance of compressor due to soil, etc.
2. External factor: Clogged intake/exhaust line,
overload, etc.
3. Defect of control system: Abnormal load
control, abnormal exhaust gas temperature
thermocouple, etc.

2. High Exhaust Gas Temperature


2.1 Simplified Inspection of Equipment
Gas Turbine
Inspection item 1
Visually check that engine (output shaft) is rotating smoothly as driven by turning motor.
Objective
To confirm that gas turbine itself and reduction gear are normal.
Inspection item 2
Manually rotate engine by hand to check for abnormal rotation or abnormal rotating sound
Objective
This method is to be conducted if above inspection item 1 cannot be done by turning motor.
Inspection item 3
Study of data before occurrence of problem
Gas turbine shaft vibration
Gas turbine intake air temperature and ambient temperature
Generator output
Compressor discharge pressure
Lubricating oil temperature
Operation mode: island or parallel with another GTG or Diesel Gen Set.
Objective
To confirm that gas turbine itself is normal
To confirm that air intake line is normal
To confirm that gas turbine is not operated under overload
To confirm that compressor is not soiled (check pressure data for the last one week or more)
To confirm that bearing is lubricated
To see if gas turbine is operated in island or parallel with other machines.

2. High Exhaust Gas Temperature


2.2 Inspection of Individual Control Devices
Instrumentation Devices
Inspection item 1
Inspection of exhaust gas temperature thermocouple for broken wire
Measure insulation resistance. Normal value is 1.5 ohm or higher as measured with a 500-V
megohmmeter at ordinary temperature
Objective
To confirm that thermocouple is not damaged
Inspection item 2
Heat up temperature sensing elements sequentially while checking if output voltage increases
Objective
To confirm that exhaust gas temperature is detected.
Inspection item 3
Inspection of rotation pickup for looseness
Objective
To confirm that connector or pickup is not loose
Inspection item 4
Disconnect cable from pickup and measure resistance. Normal value is 30050 ohm at 25 degC
Objective
To confirm that wire is not broken
Miscount during operation as interconnected with commercial power system can cause high exhaust
gas temperature.

3. Overspeed
Rotation of gas turbine power section is
monitored to detect Overspeed. Specific
trip value has been set in the sensor.

3. Overspeed
Possible causes of this problem are as
follows:
1. Defect of gas turbine itself: Broken
coupling of output shaft of power section
rotor system, etc.
2. External factor: Sticking fuel control
valve, etc.
3. Defect of control system: Abnormal
rotation pickup, etc.

3. Overspeed
3.1 Simplified Inspection of Equipment
Gas Turbine
Inspection item 1
Visually check that engine (output shaft) is rotating smoothly as driven by turning motor.
Objective
To confirm that gas turbine itself and reduction gear are normal
Inspection item 2
Manually rotate engine by hand to check for abnormal rotation or abnormal rotating sound
Objective
This method is to be conducted if above inspection item 1 cannot be done by turning motor.
Inspection item 3
Study of data before occurrence of problem
Gas turbine shaft vibration
Gas turbine speed
Whether any problem occurred at startup or during operation
If problem occurred during operation, check generator output for change
Operation mode: island or parallel with other GTG or Diesel Gen set.
Objective
To confirm that gas turbine itself is normal
To clarify the time of problem occurrence

3. Overspeed
3.2 Inspection of Individual Control Devices
Instrumentation Devices
Inspection item 1
Inspection of rotation pickup connector for looseness
Objective
To confirm the connector or pickup is not loose
Inspection item 2
Measure resistance for rotation pickup. Normal value is 30050 ohm at 25 degC
Objective
To confirm that sensor is normal

4. Startup Failure
Rotation and exhaust gas temperature of
gas turbine are monitored to detect
Startup Failure. Alarm signal is output
when specified conditions are not met.

4. Startup Failure
Possible causes of this problem are as
follows:
1. Defect of gas turbine itself: Defective fuel
nozzle, etc.
2. External factor: Abnormal starter
equipment, abnormal ignition system,
etc.
3. Defect of control system: Defective
rotation pickup, defective controller, etc.

4. Startup Failure
4.1 Simplified Inspection of Equipment
Gas Turbine
Inspection item 1
Visual check that engine (output shaft) is rotating smoothly as driven by turning motor.
Objective
To confirm that gas turbine itself and reduction gear are normal.
Inspection item 2
Manually rotate engine by hand to check for abnormal rotation or abnormal rotating sound
Objective
This method is to be conducted if above inspection item 1 cannot be done by turning motor.
Inspection item 3
Study of data before occurrence of problemIncrease in turbine speed
Increase in exhaust gas
Instrument air pressure 0.45MPa or higher
Fuel filter differential pressure indication
Objective
To confirm that gas turbine itself and reduction gear are normal
To confirm that fuel system is normal
To confirm that shutoff valve opening air pressure is normal

4. Startup Failure
4.1 Inspection of Individual Control Devices
Instrumentation Devices
Inspection item 1
Inspection of solenoid valve operation of starter valve unit
Objection
To confirm the integrity of starter air supply equipment
Inspection item 2
Inspection of exciter and ignition plug. Visual check for damage
Objective
To confirm that ignition system is normal
Inspection item 3
Inspection of exhaust gas temperature thermocouple for broken wire. Measure insulation resistance. Normal value is
1.5Mohm or higher as measured with a 500V megohmmeter at ordinary temperature
Objective
To confirm that thermocouple is not damaged
Inspection item 4
Inspection of rotation pickup for looseness. Disconnect cable from pickup and measure resistance. Normal value is
30050 ohm at 25 degC.
Objective
To confirm that pickup is not loose and wire is not broken.

5. Low Lubrication Oil Pressure


Lubrication oil pressure is monitored to
detect Low Lubrication Oil Pressure.
Specific alarm value and trip value have
been set in the sensor.

5. Low Lubrication Oil Pressure


Possible causes of this problem are as
follows:
1. Defect of gas turbine itself: Abnormal
lubrication oil pump, clogged filter
caused by abnormal bearing, etc.
2. External factor: Drop of lubrication oil
level, etc.
3. Defect of control system: Defective oil
pressure switch, etc.

5. Low Lubrication Oil Pressure

5.1 Simplified Inspection of Equipment

Gas Turbine
Inspection item 1
Visually check that engine (output shaft) is rotating smoothly as driven by turning motor.
Objective
To confirm that gas turbine itself and reduction gear are normal
Inspection item 2
Manually rotate engine by hand to check for abnormal rotation or abnormal rotating sound
Objective
This method is to be conducted if above inspection item 1 cannot be done by turning motor.
Inspection item 3
Check piping for any lubrication oil leakage.
Objective
To confirm that there is no oil leakage which can cause low oil pressure
Inspection item 4
Check oil level of lubrication oil tank.
Objective
To confirm that there is no oil level drop which can cause low oil pressure
Inspection item 5
Study of data before occurrence of problem
Lubrication oil temperature at bearing outlet.
Interval between alarm and trip.
Indication of clogged lubrication oil filter
Objective
To confirm that bearing are normal
To confirm that filter is free of foreign matters

5. Low Lubrication Oil Pressure


5.2 Inspection of Individual Control Devices
Instrumentation Devices
Inspection item 1
Inspection of lubrication oil pressure transmitter for looseness. Visual check for damage.
Objective
To confirm that the lubrication oil pressure transmitter is normal.

6. High Lubricating Oil


Temperature
Temperature of lubricating oil supplied to
gas turbine bearings is monitored to detect
High Lubricating Oil Temperature.
Specific alarm value has been set in the
PLC.

6. High Lubricating Oil


Temperature
Possible causes of this problem are as
follows:
1. Defect of gas turbine itself: Abnormal
bearing, etc.
2. External factor: Deteriorated oil cooler
performance, etc.
3. Defect of control system: Defective oil
temperature sensor, etc.

6. High Lubricating Oil


Temperature
6.1 Simplified Inspection of Equipment
Gas Turbine
Inspection item 1
Visually check that engine (output shaft) is rotating smoothly as driven by turning motor.
Objective
To confirm that gas turbine itself and reduction gear are normal
Inspection item 2
Manually rotate engine by hand to check for abnormal rotation or abnormal rotating sound
Objective
This method is to be conducted if above inspection item 1 cannot be done by turning motor.
Inspection item 3
Study of data before occurrence of problem
Lubricating oil temperature
Lubricating oil at bearing outlet
Objective
To confirm that bearing are normal

6. High Lubricating Oil


Temperature
6.2 Inspection of Individual Control Devices
Instrumentation Devices
Inspection item1
Inspection of lubrication oil temperature sensor (Pt 100-ohm resistance bulb). Measure resistance
value.
Objective
To confirm that sensor is normal.

You might also like