Flexi Power Rectifier FPRB

Installation Manual for


Surge Protective Device
Flexi Power Rectifier
FPRB

Manufactured by: Artesyn Embedded Technologies


Manufacturing PN: AA27540L
Visit us @ http://www.artesyn.com/

Installation Manual for SPD, Rev AC

Page 1 of 45

Flexi Power Rectifier FPRB


Manual Number: 970-009473-0000
Manual Issue: AC
Manual Status: Standard
Release Date: Jun 30, 2014
Copyright 2014 Artesyn Embedded Technologies
CONSIDER IT SOLVED
Published in China
This document, and the information it contains, are the property of Artesyn Embedded
Technologies Co., Ltd, and are protected by law. Both must be held in strictest confidence at all
times. Artesyn Embedded Technologies grants no license or right to copy, use or disclose either,
expressly or by implication.

Disclaimer
This document and the information contained herein are provided on an "AS IS" basis. Artesyn
Embedded Technologies may make improvements or changes in this documentation, at any
time and without notice and as it sees fit. The information in this documentation was prepared
by Artesyn Embedded Technologies with reasonable care and is believed to be accurate.
However, Artesyn Embedded Technologies shall not assume responsibility for losses or damages
resulting from any omissions, inaccuracies, or errors contained herein.

Installation Manual for SPD, Rev AC

Page 2 of 45

Flexi Power Rectifier FPRB


History
Date
DD-MM-YYY
30-06-2013

Version

Author

Change Note

AA

Ferdinand Sisracon

First release for FPRB


Release to be used as a common
SPD Instruction Manual for both
FPRA and FPRB

30-10-2013

AB

Ferdinand Sisracon

Added special instruction to


connect the N link cable for both
FPRA and FPRB

30-06-2014

AC

Alex Ding

Change the brand from Emerson


Network Power to Artesyn
Embedded Technologies

Installation Manual for SPD, Rev AC

Page 3 of 45

Flexi Power Rectifier FPRB

Table of Contents
History ...................................................................................................................3
Table of Contents ....................................................................................................4
List of Figures..........................................................................................................5
List of Tables ...........................................................................................................5
Preface...................................................................................................................9
Application of this manual ..................................................................................10
Chapter 1 Product Introduction.............................................................................11
1.1 General Description .................................................................................11
1.2 Main Specification of the SPD....................................................................11
1.3 Properties ...............................................................................................16
Chapter 2 Preparation ..........................................................................................18
2.1 Installation tools ......................................................................................18
2.2 Delivery contents .....................................................................................18
Chapter 3 SPD Installation ....................................................................................20
3.1 Make AC connection with the SPD .............................................................20
3.1.1 Preparation ................................................................................................... 21
3.1.2 Configure the Terminal Block ...................................................................... 27
3.1.3 3-phase star (3Y) AC connection with the SPD ........................................... 29
3.1.4 Single-phase (1) AC connection with the SPD.......................................... 35
3.1.5 2-phase AC connection with the SPD ........................................................ 38
3.1.6 3-phase delta (3) AC connection with the SPD ......................................... 40
3.2 Replace the SPD.......................................................................................44

Installation Manual for SPD, Rev AC

Page 4 of 45

Flexi Power Rectifier FPRB

List of Figures
Figure 1 Internal circuit diagram of the SPD .................................................................. 11
Figure 2 Structure of the SPD......................................................................................... 12
Figure 3 Dimension of the SPD top view..................................................................... 13
Figure 4 Dimension of the SPD side view.................................................................... 14
Figure 5 SPD configuration in a TN-S system ................................................................. 16
Figure 6 Checking failure of the SPD.............................................................................. 17
Figure 7 PDA rear internal chassis layout ...................................................................... 21
Figure 8 The AC cable connection chart ........................................................................ 27
Figure 9 AC terminal block configuration 1 and 2 Configuration ......................... 28
Figure 10 AC terminal block configuration 3 ............................................................ 28
Figure 11 AC terminal block configuration 3Y ............................................................ 29
Figure 12 Schematic diagram of AC connection with the SPD 3Y............................... 29
Figure 13 - Assemble the Link Cables to SPD .................................................................... 30
Figure 14 - AC Ground wire............................................................................................... 31
Figure 15 - Secure the SPD into the DIN rail ..................................................................... 31
Figure 16 - Connect the Link cables to Terminal Block ..................................................... 32
Figure 17 - Special Instruction for N Link Cable Installation ............................................. 33
Figure 18 AC connection with the SPD - 3Y ................................................................... 34
Figure 19 Schematic diagram of AC connection with the SPD 1.............................. 35
Figure 20 SPD configuration for single-phase AC connection ....................................... 36
Figure 21 - Connection of AC link cables from SPD to Terminal Block ............................. 37
Figure 22 Schematic diagram of AC connection with the SPD 2- Phase...................... 38
Figure 23 - AC connection with the SPD 2- Phase.......................................................... 39
Figure 24 Schematic diagram of AC connection with the SPD 3 .............................. 40
Figure 25 - Connection of AC link cables and SPD ground cables..................................... 41
Figure 26 Connecting the AC terminal block 3 ......................................................... 42
Figure 27 3-phase delta (3) AC connection with the SPD.............................................. 43
Figure 28 Removing the damaged OVP module from the SPD ..................................... 44
Figure 29 The OVP module and the SPD base ............................................................... 45
Figure 30 Fitting a new OVP module to the SPD ........................................................... 45
List of Tables
Table 1 Contents of this manual ...........................................................................................9
Table 2 Symbols in this manual ............................................................................................9
Table 3 Reference documents of the SPD .........................................................................10
Table 4 Main specification of the SPD ...............................................................................15
Table 5 Delivery contents of the SPD .................................................................................19
Table 6 Recommended preparation for AC mains cable ..................................................22
Table 7 AC connection with the SPD ..................................................................................23
Installation Manual for SPD, Rev AC

Page 5 of 45

Flexi Power Rectifier FPRB


Table 8 Schematic diagram of AC connection with the SPD ............................................25

List of Terms

Ampere

AC

Alternative current

AWG

American Wire Gauge

BAT

Battery

BR

Battery Return

BTS

Base Transceiver Station

CB

Circuit Breaker

CSA

Cross Section Area

CU

Control unit

DC

Direct current

EMC

Electromagnetic Compatibility

ESD

Electrostatic Discharge

FPRB

Flexi Power Rectifier

GND

Ground

GUI

Graphical User Interface

IE

Internet Explorer

IP

Internet Protocol

Live cable from the AC mains

LAN

Local Area Network

LED

Light Emitting Diode

LVD

Low Voltage Disconnect

MAC

Media Access Control

MCB

Miniature Circuit Breaker

Neutral cable from the AC mains

PC

Personal Computer

PCB

Printed Circuit Board

PDA

Power Distribution Assembly

PE

Protective earth

PSU

Power Supply Unit

Installation Manual for SPD, Rev AC

Page 6 of 45

Flexi Power Rectifier FPRB


SPD

Surge Protective Device

Volt

VPN

Virtual Private Network

Single-phase AC type

3Y

3-phase star AC type

3-phase delta AC type

Installation Manual for SPD, Rev AC

Page 7 of 45

Flexi Power Rectifier FPRB

This page left intentionally blank

Installation Manual for SPD, Rev AC

Page 8 of 45

Flexi Power Rectifier FPRB

Preface
About this manual
This manual provides all the necessary information to operate, install and maintain the
Surge Protective Device (SPD) used in the Flexi Power Rectifier (FPRB).
Table 1 lists the contents of this manual:
Table 1 Contents of this manual
Chapter

Title

Content

Product instruction

Describes the specifications and properties of the


SPD

Preparation

Describes the SPD installation preparations

SPD installation

Describes how to install and replace the SPD into the


FPRB

Terms and Symbols in this manual


These term and symbols in Table 2 might appear in the manual:
Table 2 Symbols in this manual
Symbol

Description
Warning statement identifies conditions or practices that could
result in bodily injury or loss of life.
It warns the reader to be extremely careful.
Caution statement identifies conditions or practices that could
result in damage to this product or devices connect to it.
It indicates that the reader must be careful.
Provides hints to the user for easier installation
The necessary supplementary of the article to let user be clearer.

Installation Manual for SPD, Rev AC

Page 9 of 45

Flexi Power Rectifier FPRB

Reference documents
Table 3 contains the reference documents of the SPD:
Table 3 Reference documents of the SPD
Document

Artesyn Embedded Technologies


File No.

Product Specification FPRB

970-009025-0000

FPRB Installation Manual for SPD (This manual)

970-009473-0000

FPRB User Manual

970-009474-0000

FPRB Installation Manual

970-009475-0000

FPRB Quick Start Guide for SPD

970-009476-0000

FPRB Quick Start Guide

970-009477-0000

Application of this manual


This manual is regarded as a substitution of the part Make AC connection without the SPD
(refer to section 3.4 of the Flexi Power Rectifier - Installation Manual, Artesyn File No. 970009475-0000).
This manual is based on the present SPD in use. Artesyn may change the SPD to a second
source in future. However Artesyn ensures the compatibility of the new SPD in the FPRB.
This manual supports all applications of the SPD that can be used in the FPRB.

Installation Manual for SPD, Rev AC

Page 10 of 45

Flexi Power Rectifier FPRB


Chapter 1 Product Introduction
1.1

General Description
The Flexi Power Rectifier (FPRX, Artesyn part number AA25020L/ CS7000013.XX for 6kW
and AA27540L/ CS7000030.XX for 9kW) is a 6kW or 9kW output power AC rectifier package
respectively. The Surge Protective Device (SPD, Artesyn part number AA25130L/
CS7000002.XX) is used to prevent damage to the FPRX caused by high input voltages or
surge.
The SPD consists of three equivalent OVP modules used between live cables and neutral
cable from the AC mains; one OVP module used between the neutral cable from the AC
mains and the earth; and one remote signaling contact.
The SPDs mentioned in this manual are applicable for both 6kW and 9kW system. The SPD
used is the same as the one we used in FPRA.

1.2

Main Specification of the SPD


The SPD illustrated in this manual is made by Phoenix Contact CO., Ltd (model number:
VAL-MS 230IT/3+1-FM), or SICHUAN ZHONGGUANG LIGHTNING (model number:
ZGG40-385(3+1)).
12 14

VAL-MS 230IT/3+1-FM

FM
11

VAL-MS 230 IT ST
L1

L2

L3

F-MS
12 ST

Figure 1 Internal circuit diagram of the SPD

Installation Manual for SPD, Rev AC

Page 11 of 45

Flexi Power Rectifier FPRB


The SPD (module name VAL-MS 230IT/3+1-FM) consists of three equivalent OVP
modules used between live cables and neutral cable from the AC mains (module name
VAL-MS 230 IT ST), one OVP module used between the neutral cable from the AC
mains and the earth (module name F-MS 12 ST) and one remote signaling contact
(module name VAL-MS 230IT-FM) (see Figure 1).
The four OVP modules and the remote signaling contact are all installed on the SPD base
and can be removed from the base. This structure leads to easier configuration and
replacement of the OVP modules (see
Figure 2).

F-MS12 ST

VAL-MS
230 IT ST

Base
VAL-MS
230IT-FM

Terminal

Figure 2 Structure of the SPD

Installation Manual for SPD, Rev AC

Page 12 of 45

Flexi Power Rectifier FPRB

Figure 3 and Figure 4 show the dimension of the SPD. The four OVP modules are of the
same dimensions.

17.5m

70m

17.5m

VAL-MS 230IT/3+1-FM

ZGG40-385(3+1)
Figure 3 Dimension of the SPD top view

Installation Manual for SPD, Rev AC

Page 13 of 45

Flexi Power Rectifier FPRB

VAL-MS 230IT/3+1-FM

ZGG40-385(3+1)

Figure 4 Dimension of the SPD side view

Installation Manual for SPD, Rev AC

Page 14 of 45

Flexi Power Rectifier FPRB


Table 4 lists the main specifications of the OVP modules.
Table 4 Main specification of the SPD
Module name

Parameter

Specification

Description

VAL-MS 230 IT
ST

UN (L-N / L-L)

230VAC / 400VAC

Rated voltage

UC (L-N)

385VAC

Clamping voltage

UP (L-N)

1.9kV

Protective voltage

In / Imax (8/20 S)

20kA / 40kA

Rated discharge current /


maximum discharge current

Screw thread / torque

M5 / 4.5Nm

F-MS 12 ST

UN (N-PE)

230 VAC

Rated voltage

(OVP module for


N-PE)

UC (N-PE)

260VAC

Clamping voltage

UP (N-PE)

1.0kV

Protective voltage

In / Imax (8/20 S)

20kA / 40kA

Rated discharge current /


maximum discharge current

Screw thread / torque

M5 / 4.5Nm

Imax

AC: 3A (125V)

(OVP module for


L-N)

VAL-MS 230ITFM
(Remote
signaling
contact)1

VAL-MS
230IT/3+1-FM
(The whole SPD
module)

0.75A (250V)
DC: 2A (30V)
Screw thread / torque

M2 / 0.25Nm

Temperature

-40C ~ +80C

IP-code

IP20

Class II

IEC 61643-1: 2005-01

Type 2

EN 61643-11: 2002-12

Installation Manual for SPD, Rev A


AC

Ingress Protection (IP)


degree

Page 15 of 45

Flexi Power Rectifier FPRB


Note:
1

Although the SPD remote signaling contact has three pins, only two are applied when
configured in the FPRB. Refer to Figure 13

1.3

Properties

Typical use
Figure 5 shows the configuration of the SPD in a TN-S system.

Figure 5 SPD configuration in a TN-S system


Note:
It is recommended to use the SPD with a mains utility offering the appropriate line
fuse protection.

Installation Manual for SPD, Rev AC

Page 16 of 45

Flexi Power Rectifier FPRB

Failure Detection

If any OVP module has been damaged, Artesyn will provide the user with the individual OVP
module but not the whole SPD for replacement.
In the event that any one of the four OVP modules is damaged, the PDA will send alarm
signal via the LCD.
After opening the rear top cover of the PDA (refer to section 3.4 of the Flexi Power
Rectifier Installation Manual, Artesyn File No. 970-009475-0000), the user can confirm
which OVP module is in failure.

Failure Indication
If the window is transparent, the OVP is OK; if the window is red, the OVP is damaged
and should be replaced in time (see Figure 6).

Window

Figure 6 Checking failure of the SPD

Installation Manual for SPD, Rev AC

Page 17 of 45

Flexi Power Rectifier FPRB


Chapter 2 Preparation
2.1 Installation tools
Tool kit:
Allen key (hex key): 8 mm (0.31 in.)
Allen key (hex key): 4 mm
Awl: diameter of 2mm
ESD wrist strap and cable
TORX screwdriver set: T10, T20, T25
Flat screwdriver
Cross screwdriver
Wrench 13 mm (0.51 in.)
Folding knife
Adjustable (monkey) wrench
Side cutters
Lint-free swab or wipe and 99% alcohol for cleaning optical connectors
Cable ties for routing cables
Tape measure
Flashlight, pocket lamp or torch
Hammer drill
Marker pen or comparable tool
Pliers
Wire-stripper
Test equipment:
Multi-meter

2.2 Delivery contents


The SPD is optional for the user and shipped independent from the FPRB.
Verify that all the material listed in Table 5 has been received and is in good condition.
Report any missing or damaged items to our Artesyn Embedded Technologies Service
Department.

Installation Manual for SPD, Rev AC

Page 18 of 45

Flexi Power Rectifier FPRB

Table 5 Delivery contents of the SPD


Part

SPD

Figure

Description

Usage

Surge Protective Device

Artesyn

Artesyn

Part Number

Module
Number

1 pc

440-0007000000

1 each

502-000496000X/

Manufacturer p/n:VAL-MS
230IT/3+1-FM
Manufacturer: PHOENIX
CONTACT (SEA), PTE. LTD.

Surge Protective Device


Manufacturer p/n: ZGG40385(3+1)
Manufacturer: SICHUAN
ZHONGGUANG LIGHTNING
PROTECTION TECHNOLOGIES
CO.,LTD.
SPD
Jumper

Short link for SPD terminals in


single-phase AC connection
(Color of plastic may vary)

L line
short link

L1/L2/L3 for three phase,

N line
short link

N for three phase star,

SPD
ground
link
SPD
sense
cable

500-0017690000
1

750-000984000X

750-000983000X

SPD ground link to Chassis

750-000988000X

SPD signal cable connecting to


the MCU

750-001004000X

L for single phase (AWG10)

N for single phase (10mm )

Installation Manual for SPD, Rev AC

Page 19 of 45

AA25130L

Flexi Power Rectifier FPRB


Chapter 3 SPD Installation
3.1 Make AC connection with the SPD

The AC power supply must be switched off prior to accessing the AC cable.

This manual concentrates on the AC connection with the SPD, and omits the steps prior
to the SPD installation, i.e. the AC terminal block configuration, etc. The user should
refer to Flexi Power Rectifier Installation Manual (Artesyn File No. 970-009475-0000)
for the relevant previous steps.
The colors of the AC mains wire used in this manual are for illustration purpose only.
However, the user should verify the AC mains referring to the color-coding in the
respective field or country of application.

Installation Manual for SPD, Rev AC

Page 20 of 45

Flexi Power Rectifier FPRB

3.1.1

Preparation

3.1.1.1

Detach the PDA rear top cover referring to Flexi Power Rectifier Installation
Manual (Artesyn File No. 970-009475-0000).

3.1.1.2

Loosen screws A, B and C as per attached photo with a TORX screwdriver (T20)

SPD
DIN Rail

AC
terminal
block

SPD ground
clamp

AC ground
clamp

PDA earth
cable

Strainrelief

SPD sensor
connection

F
Figure 7 PDA rear internal chassis layout

Installation Manual for SPD, Rev AC

Page 21 of 45

Flexi Power Rectifier FPRB

3.1.1.3

Preparing the AC mains cable. The color of the wires may vary depending on the
country where the SPD will be mounted.
Table 6 Recommended preparation for AC mains cable

(Tolerance: 3mm)
AC type

L1

L2

L3

PE

Single-phase

A (mm)

55

70

100

(1)

B (mm)

20

20

20

2-phase

A (mm)

55

100

N/A

B (mm)

20

20

N/A

3-phase delta

A (mm)

55

60

70

N/A

100

(3)

B (mm)

20

20

20

N/A

20

3-phase star

A (mm)

55

60

70

85

100

(3Y)

B (mm)

20

20

20

20

20

Installation Manual for SPD, Rev AC

Page 22 of 45

Flexi Power Rectifier FPRB

Table 7 AC connection with the SPD


AC type
AC
mains

AC terminal Chassis
block

N/A

L1

N/A

L1 for three-phase

L2

N/A

L2 for three-phase

N/A

L3

N/A

L3 for three-phase

N/A

N for single phase

PE

N/A

N/A

AC ground clamp

N/A

N/A

SPD ground clamp

SPD ground link

N/A

L1

N/A

L1 for three-phase

L1

L2

N/A

L2 for three-phase

N/A

L3

N/A

L3 for three-phase

L2

N/A

N for single phase

N/A

N/A

AC ground clamp

N/A

N/A

SPD ground clamp

SPD ground link

N/A

3Y

L1

L1

N/A

L1 for three-phase

L2

L2

N/A

L2 for three-phase

Installation Manual for SPD, Rev AC

AC terminal block

SPD configuration

Configuration (2)

(3)

SPD

N/A
2-Phase

Short link available (1)

Terminals connection

Page 23 of 45

Short terminals 1,2,3 and


4,5,6 respectively

Short terminals L1,


L2, L3

Short terminals 1,2,3 and


4,5,6 respectively

Short terminals L1,


L2, L3

Short terminals 1,2,3

N/A

Flexi Power Rectifier FPRB

L3

L3

N/A

L3 for three-phase

N/A

N for three-phase star

PE

N/A

N/A

AC ground clamp

N/A

N/A

SPD ground clamp

SPD ground link

N/A

L1

L1

N/A

L1 for three-phase

L2

L2

N/A

L2 for three-phase

L3

L3

N/A

L3 for three-phase

PE

N/A

N/A

AC ground clamp

N/A

N/A

SPD ground clamp

Short terminals 1,2 and 3,4


and 4,5 respectively

SPD ground link

Note:
(1) The short link names listed herein are in accordance with the actual labels on the short links.
(2) The AC terminal block should be configured before the AC connection. User shall refer to section 3.4 in
Flexi Power Rectifier Installation Manual (Artesyn file No.970-009475-0000) for more details

Installation Manual for SPD, Rev AC

Page 24 of 45

N/A

Flexi Power Rectifier FPRB

(3) Refer to Table 3for the corresponding clamps.


Table 8 Schematic diagram of AC connection with the SPD
AC
Type

Schematic diagram

Configuration of AC
terminal block
Short terminals 1,2,3

AC Terminal Block
SPD

L1

L2

L3

L1

L2

L3

3Y

PE

AC Mains

Short terminals 1,2,3;


4,5,6 respectively

AC Terminal Block

SPD
L1 L2

L3

PE

AC mains

Installation Manual for SPD, Rev AC

Page 25 of 45

Flexi Power Rectifier FPRB

AC Terminal Block
SPD

L1

L2

L3

L1

L2

L3

Short terminals 1,2; 3,4;


5,6 respectively

PE

AC mains

Short terminals 1,2,3;


4,5,6 respectively

2-phase

Installation Manual for SPD, Rev AC

Page 26 of 45

Flexi Power Rectifier FPRB

3.1.2

Configure the Terminal Block

Verify the AC power system types in field, and make sure the corresponding bridge
configuration is used.

The AC terminal block has been already configured for 3-phase star AC mains before
the shipment. Therefore the user has to change the AC terminal block configuration
if required referring to the actual AC type in field.

Insert the bridges and screws (provided as accessories) to the corresponding slots on
top of the AC terminal block referring to the AC CABLE CONNECTION CHART located
on the chassis (and reproduced in Figure 8).
Secure the screws with a flat screwdriver, tightening to 0.8Nm.

Figure 8 The AC cable connection chart


There are three AC power system types (see above Figure), and thus three AC
configurations of the AC terminal block.

Installation Manual for SPD, Rev AC

Page 27 of 45

Flexi Power Rectifier FPRB

Single-phase (1) and Two-phase (2 ) configuration


For Single- phase AC system, use two 3-pole bridges to short the terminals 1, 2,
3 and 4, 5, 6 respectively on the AC terminal block (see Figure 9)

Figure 9 AC terminal block configuration 1 and 2 Configuration

3- phase delta (3) configuration


For 3-phase delta AC system, use three 2-pole bridges to short the terminals 1, 2
and 3, 4 and 5, 6 respectively on the AC terminal block (see Figure 10 )

Figure 10 AC terminal block configuration 3

Installation Manual for SPD, Rev AC

Page 28 of 45

Flexi Power Rectifier FPRB

3- phase star (3Y) configuration


For 3-phase star AC system, use one 3-pole bridges to short the terminals 1, 2, 3
on the AC terminal block (see Figure 11)

Figure 11 AC terminal block configuration 3Y


3.1.3

3-phase star (3Y) AC connection with the SPD

AC Terminal Block
SPD

PE

L1

L2

L3

L1

L2

L3

AC Mains
Figure 12 Schematic diagram of AC connection with the SPD 3Y

Installation Manual for SPD, Rev AC

Page 29 of 45

Flexi Power Rectifier FPRB

The terminal marks in Figure 12 are in accordance with the actual SPD and AC
terminal block.
Use the indicated L or N short link for the AC mains as shown in Figure 12 and Table
7 referring to labels on the short links.
The terminals 1, 2, 3 on the AC terminal block should be shorted before the
connection. Refer to section 3.4 in Flexi Power Rectifier Installation Manual
(Artesyn file No.970-009475-0000) for details.
3.1.3.1

Detach the cable strain-relief from the chassis by loosening the screw C in
Figure 7 with a TORX screwdriver (T20). Insert the AC mains cable on the
strain relief.

3.1.3.2

Detach the AC ground clamp and SPD ground clamp from the chassis by
loosening the screws A and B with a TORX screwdriver (T20).

3.1.3.3

Prepare the AC mains of 3-phase star as per Table 6.

3.1.3.4

Assemble the Link cables, the AC mains cable, the SPD sensor cable and the
SPD grounding cable into the SPD. Refer to Figure 13

L1 for
threephase
L2 for
threephase

SPD
sense
cable

L3 for
threephase

N for
threephase
star

SPD
ground
cable
Figure 13 - Assemble the Link Cables to SPD

Installation Manual for SPD, Rev AC

Page 30 of 45

Flexi Power Rectifier FPRB

Insert the connector of the SPD sense cable into the left two contacts; otherwise it will
block the SPD from installing onto the chassis.

3.1.3.5

Fix the AC ground wire into the terminal lug.

.
Figure 14 - AC Ground wire
3.1.3.6

Secure the SPD into the SPD DIN rail. Connect the SPD sense cable to the
stand by mating connector. Connect the SPD grounding cable into the
terminal lug. Refer to Figure 15.

SPD
Grounding
cable

SPD

SPD
sense
cable

Figure 15 - Secure the SPD into the DIN rail

Installation Manual for SPD, Rev AC

Page 31 of 45

Flexi Power Rectifier FPRB


3.1.3.7

Connect the AC link cables from SPD to the Terminal Block. Assemble the
SPD grounding cable and the AC grounding cable into the PDA

SPD
grounding
cable lug

N link
cable
L3 link
cable
L2 link
cable

AC
grounding
cable lug

L1 link
cable

Figure 16 - Connect the Link cables to Terminal Block

1. Use the appropriate L and N short link referring to the label on the short links
and the indications in Figure 12 and Table 7.
2. Rotate the N link cable 90 degrees either clockwise or counter clockwise when
assembling the SPD on the FPRA due to the smaller slot of the terminal block.
Refer to Figure 17 - Special Instruction for N Link Cable Installation

Installation Manual for SPD, Rev AC

Page 32 of 45

Flexi Power Rectifier FPRB

Figure 17 - Special Instruction for N Link Cable Installation

It is recommended to clamp the AC wire and the corresponding short link with one
overlapping on another.

Installation Manual for SPD, Rev AC

Page 33 of 45

Flexi Power Rectifier FPRB


Below figure shows the PDA rear layout after completing the 3-phase star AC
connection with the SPD.

SPD ground
cable
N
N short link

L3

L1 short link

L2
L2 short link
L1

L3 short link

PE of AC
mains

SPD sense cable


Figure 18 AC connection with the SPD - 3Y

3.1.3.8

After finishing and checking the AC cable installation, re-install the PDA rear
cover referring to Flexi Power Rectifier Installation Manual (Artesyn File
No. 970-009475-0000).

After installation of the SPD kit has been completed, the installer should check the
installation against the steps outlined within this document, supported by a multimeter to check for wiring continuity.
Its strongly suggested that the insulation test (2.5kV Hi-pot) is carried out.

Installation Manual for SPD, Rev AC

Page 34 of 45

Flexi Power Rectifier FPRB


3.1.4

Single-phase (1) AC connection with the SPD

SPD ground link


SPD ground
clamp

N for single phase

AC Terminal Block

SPD
L1 L2

L3

L3 for three-phase
AC ground
clamp

PE

AC mains

L2 for three-phase
L1 for three-phase

Figure 19 Schematic diagram of AC connection with the SPD 1

The terminal marks in Figure 19 are in accordance with the actual SPD and AC
terminal block.
Use the indicated L or N short link for the AC mains as shown in Figure 19 and Table
7 referring to labels on the short links.
The terminals 1,2,3 and 4,5,6 on the AC terminal block should be shorted
respectively before the connection. Refer to section 3.4 in Flexi Power Rectifier
Installation Manual (Artesyn file No.970-009475-0000) for details.

3.1.4.1

Perform the same procedure in preparing the AC cables SPD grounding cables
and the SPD sense cables.

3.1.4.2

As indicated in Figure 19 and Table 7, the SPD terminals L1, L2 and L3 have to be
paralleled by the SPD jumper (see Figure 20).

Installation Manual for SPD, Rev AC

Page 35 of 45

Flexi Power Rectifier FPRB

The user should loosen the three terminal clamps of L1, L2 and L3, and hold the SPD
upside down. Thus the SPD jumper can be easily inserted into the parallel clamps.
The jumper should be fixed in the SPD together with the live cables of the AC mains
and L line short links.

SPD jumper

Figure 20 SPD configuration for single-phase AC connection


3.1.4.3

Connect the live cable from the AC mains and L2 short link into terminal L2 on
the SPD referring to Figure 19 and Table 7, tightening the top screw to 4.5Nm
with a cross screwdriver (see Figure 21).

Installation Manual for SPD, Rev AC

Page 36 of 45

Flexi Power Rectifier FPRB

N for single
phase

SPD
ground
link

L3 for
threephase

SPD ground
clamp

L2 for
threephase

AC ground
clamp

L1 for
threephase

Figure 21 - Connection of AC link cables from SPD to Terminal Block


3.1.4.4

After finishing and checking the AC cable installation, re-install the PDA rear
cover referring to section 3.4 in Flexi Power Rectifier Installation Manual
(Artesyn File No. 970-009475-0000).

Installation Manual for SPD, Rev AC

Page 37 of 45

Flexi Power Rectifier FPRB


3.1.5 2-phase AC connection with the SPD

SPD ground link


SPD ground
clamp

L3 for three-phase
AC ground
clamp

L2 for three-phase
L1 for three-phase

Figure 22 Schematic diagram of AC connection with the SPD 2- Phase

3.1.5.1

Perform the same procedure in preparing the AC cables SPD grounding cables
and the SPD sense cables

3.1.5.2

As indicated in Figure 19 and Table 7, the SPD terminals L1, L2 and L3 have to be
paralleled by the SPD jumper (see Figure 20).

Installation Manual for SPD, Rev AC

Page 38 of 45

Flexi Power Rectifier FPRB


3.1.5.3

Connect the AC link cables and the AC cables to the SPD and to terminal block.
Refer to Figure 23)
N for single
phase

SPD
ground
link

L3 for
threephase

SPD ground
clamp

L2 for
threephase

AC ground
clamp

L1 for
threephase
Figure 23 - AC connection with the SPD 2- Phase
3.1.5.4

After finishing and checking the AC cable installation, re-install the PDA rear
cover referring to section 3.4 in Flexi Power Rectifier Installation Manual
(Artesyn File No. 970-009475-0000).

After installation of the SPD kit has been completed, the installer should check the
installation against the steps outlined within this document, supported by a multimeter to check for wiring continuity.
Its strongly suggested that the insulation test (2.5kV Hi-pot) is carried out.

Use DMM to measure L1-L2 voltage


Ensure L1-L2 voltage between 180VAC-276VAC

Installation Manual for SPD, Rev AC

Page 39 of 45

Flexi Power Rectifier FPRB

The terminal marks in Figure 22 are in accordance with the actual SPD and AC
terminal block.
Refer to Single-phase (1) AC connection for details.

3.1.6

3-phase delta (3) AC connection with the SPD

SPD ground link

AC Terminal Block
SPD
L1

1
L2

L3

N
L3 for three-phase
L2 for three-phase

AC ground
clamp

L1 for three-phase

PE

L1

L2

L3

AC mains

SPD ground
clamp

Figure 24 Schematic diagram of AC connection with the SPD 3

The terminal marks in Figure 24 are in accordance with the actual SPD and AC
terminal block.
Use the indicated L or N short link for the AC mains as shown in Figure 24 and Table
7 referring to labels on the short links.
The terminals 1,2 and 3,4 and 5,6 on the AC terminal block should be shorted
respectively before the connection. Refer to section 3.4 in Flexi Power Rectifier
Installation Manual (Artesyn file No.970-009475-0000) for details.

Installation Manual for SPD, Rev AC

Page 40 of 45

Flexi Power Rectifier FPRB


3.1.6.1

Perform the same procedure in preparing the AC cables SPD grounding cables
and the SPD sense cables

3.1.6.2

Configure the terminal block as per Figure 10

3.1.6.3

Assemble the AC cables, AC link cables into the SPD.

3.1.6.4

Assemble the AC link cables into the Terminal Block.

SPD
grounding
cable
connected to
N terminal of
the SPD.
N connected
to Ground

Figure 25 - Connection of AC link cables and SPD ground cables

Installation Manual for SPD, Rev AC

Page 41 of 45

Flexi Power Rectifier FPRB


3.1.6.5

Connect the L1, L2 and L3 short links to terminals 5, 3, 1 on the AC terminal


block respectively referring to Figure 24 and Table 7,, tightening the top screws
to 1.5Nm with a Cross screwdriver (see Figure 26).

SPD
Sense
Cable
L3
short
link
SPD
ground
link

L2
short
link

L1
short
link
Figure 26 Connecting the AC terminal block 3

Installation Manual for SPD, Rev AC


A

Page 42 of 45

Flexi Power Rectifier FPRB


3.1.6.6

Figure 27 shows the PDA rear internal layout after completing the 3-phase delta
AC connection with the SPD.

SPD
ground
link
L3 for
threephase

SPD ground
clamp

L2 for
threephase

AC ground
clamp

L1 for
threephase

Figure 27 3-phase delta (3) AC connection with the SPD


3.1.6.7

After finishing and checking the AC cable installation, replace the PDA rear cover
referring to section 3.4 in Flexi Power Rectifier Installation Manual (Artesyn
File No. 970-009475-0000).

After installation of the SPD kit has been completed, the installer should check the
installation against the steps outlined within this document, supported by a multimeter to check for wiring continuity.
Its strongly suggested that the insulation test (2.5kV Hi-pot) is carried out.

Installation Manual for SPD, Rev AC

Page 43 of 45

Flexi Power Rectifier FPRB


3.2 Replace the SPD

The AC power supply must be switched off prior to accessing the SPD.

Ask Artesyn Embedded Technologies service people for help if any OVP module has
been damaged. Artesyn will provide the user with the individual OVP module but
not the whole SPD for replacement.
The user shall only replace the damaged OVP module of the SPD without removing
the whole SPD from the PDA chassis.
The user can verify which OVP module has been damaged Referring to section
Properties.
3.2.1 Hold the two sides of the damaged OVP module and pull
pull it out from the SPD
base (see Figure 28)

Figure 28 Removing the damaged OVP module from the SPD

Installation Manual for SPD, Rev AC


A

Page 44 of 45

Flexi Power Rectifier FPRB

3.2.2

The SPD base is designed such that the two kinds of OVP modules cannot be
mixed when installing onto it (see Figure 29).

Figure 29 The OVP module and the SPD base

3.2.3

Fit the new module into its position on the SPD base (see Figure 30).

Figure 30 Fitting a new OVP module to the SPD

Installation Manual for SPD, Rev AC

Page 45 of 45