Life of a transformer
Diagnostic testing
Thermal Stress
Develops across all assembly components. It ages the dielectric material
(even at rated temperatures). Stress to insulation worsened by high
temperature and repeated changes in temperature.
Mechanical Stress
Deforms/displaces assembly components. High shock events during shipping
displaces components. High current events deform the windings.
Chemical Stress
Oil additives have deteriorated insulation components.
Applicable Standards
IEEE C57.12.90
Standard test code
IEEE 62
Field test guide
Component
IEEE 62
by
Megger
Windings
Bushings
Insulating oil
Cellulose insulation
Load
Tap changers
De-energized
Core
Test
Resistance
Ratio/polarity
Excitation current
Short-circuit impedance
Frequency response analysis
Insulation resistance
Capacitance
Power factor/tan delta
Dielectric frequency response
Induced voltage/partial discharge
Capacitance
Power factor/tan delta
Dielectric frequency response
Partial discharge
Temperature (Infrared)
Water content
Dissolved gas
Dielectric strength
Particle count
Power factor/tan delta
Interfacial tension
Acidity
Visual
Color
Oxidation stability
Moisture content
Contact/winding resistance
Temperature (Infrared)
Ratio
Timing (make before break)
Motor current
Limit switch
Contact pressure (resistance test)
Centering
Ratio
Visual inspection
Insulation resistance
Frequency response analysis
Ground test
Megger products
MTO
TTR
Delta/TTR
MLR/FRAX
FRAX
S1
Delta/IDAX
Delta/IDAX
IDAX
Delta/IDAX
Delta/IDAX
IDAX
KF
OTS
IDAX/Delta
IDAX-MODS
MTO
TTR
MTO
MTO
TTR
6
MIT/S1
FRAX
MoM/DLRM
MTO
Winding resistance measurements
1 or 2-ch measurement
Single or dual current injection (HV and
LV simultaneously)
Tap-changer testing
Winding resistance/tap
Timing/Maker-before-break verification
Automatic demagnetization of
transformer core
Important to perform before all kinds on
excitation current tests (Delta, TTR,
FRAX)
Recommended in IEEE as standard
procedure before taking the transformer
in service
TTR
MIT/S1
DC insulation testing
Insulation resistance
Polarization index
Step voltage
Dielectric discharge
10
Delta
Winding winding
Winding tank
Bushings
Oil
11
IDAX
Insulation diagnostics
(DFR/FDS) from mHz to kHz
Tan delta/power factor and
capacitance
Winding winding
Winding tank
Bushings
Oil
12
MLR
Short-circuit impedance/leakage
reactance measurement @ 50/60
Hz
Capacitor bank testing
13
FRAX
14
Microohmmeters
15
Oil testing
16
17