Current Loop Supply Alarm Setter Transmitter

FEATURES

 3 Digits Input Display -19.999.9%


 Input / Output / Set User Selectable
 Ultrathin Type, 27mm Width
 High Dielectric Strength ( AC 2KV/Min , between Input / Output / Power )

MODEL

TAS

INPUT
Setting Function
DC 4~20mA 2Wire A Hi-Lo Setting
EXT DC 22~28V
B Hi-Hi Setting
C Lo-Lo Setting
N NONE

A
B
C
D
E
F
Y

OUTPUT
DC 0~10mA
DC 0~20mA
DC 4~20mA
DC 0~5V
DC 1~5V
DC 0~10V
OTHER

AUX. POWER

C
F

DC 24V
AC 85~265V
DC 100~300V

OTHER

SPECIFICATIONS
AccuracyInput Accuracy 0.1FSOutput Accuracy 0.1RODisplay Accuracy 0.1FS 1C.
Display Range0.28 High Lightness, Red LED 3 Digits 19.999.9 Counts.(Input over100%, display shines)
Input ImpedanceVoltage Input 1M Current Input50
Insulation Resistance100M / DC 500V
Power SupplyDC 22~28V(without load)max DC 40mA
Output LoadDC Current Mode750 in Output 20mADC Voltage Mode10mA Maximum
Output CoordinationDigit Coordination
Dielectric StrengthAC 2KV / 1Minbetween Input / Output / Power. DIN IEC 688.
Setting FunctionTwo Units Alarm Joining. Hi / Lo User Selectable
Setting Range0 99.9 Counts Adjustable
Nonmoving Zone0 99.9 Counts Adjustable
Time Delay0 999 sec Adjustable
Relay ContactSPST AC 120V 5A ,250V 2.5A,DC 24V 3A PF=1
StabilityYear 0.2
Response Time1sec
Temperature Coefficient100ppm / From 060
Operation Condition-5+85 2095 RH Non-Condensed.
Storage Condition-10+105 2095 RH Non-Condensed.
Power Fluctuation RatePower Could Support AC 85265V or DC 24V 10
Aux. Power Effect0.03 / V
Housing MaterialNon-Combustible PC Products , Compliance With UL 94 CLASS V-O
MountingDIN Rail or Wall Mounting
Dimension27 W 119 H 70 L mm (Base)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM


S1

S2

Low Drift
Amplifier

Digital

Output

Driver

+
OUT

2
Computation

Isolation

S1

6
5

S.D

Circuit

9
10
11

S2

POWER

Current Loop Supply Alarm Setter Transmitter

EXTERNAL DIMENSIONS
mm (inch)
6
DIN RAIL
35mm wide
SD

3
6

6
2-4.2*5
MTG HOLE

70

59

72

2
4

+
output

8
3

S1

6
5

35.4

8
89

27

119

11-M3
SCREW

8
11

10
22

S2

9
10
11

POWER

29.5

TERMINAL CONNECTIONS :
Connect the unit as in the above diagram or refer to the connection diagram label on the side of the unit.

SETTING VALUE ADJUSTMENT


Key Description
UP (change enumeration)

S.DSELECT

RIGHT (move digit)

Function Key
51
54
57
58
59
59
59

S 1 setting value 0 99.9


5 2 S 1 nonmoving zone 0 99.9
5 3 S 1 moving time delay 0 999 sec.
S 2 setting value 0 99.9
5 5 S 2 nonmoving zone 0 99.9
5 6 S 2 moving time delay 0 999 sec.
S 1 S 2 setting type.(1=Hi. 0=Lo) Hi-Hi. Hi-Lo. Lo-Hi. Lo-Lo user selectable.
Start Delay Time 0 999, inputs start from zero, no alarming movement within the time.
72 SPAN digit adjustment (long press adjust roughshort press adjust detail)
73 ZERO digit adjustment (long press adjust roughshort press adjust detail)
99 Save.

Adjust output value SPANZERO.


Press "SD", enter 59, adjust display to "72" condition, operate "", adjust SPAN digit. (long / short press adjust
rough / detail)
Press "SD", enter 59, adjust display to "73" condition, operate "", adjust ZERO digit. (long / short press adjust
rough / detail)
Read output signals from terminal 7 and 8.

ANALOGY OUTPUT VOLTAGE CURRENT EXCHANGE


Disassemble box. Install and skip one pin as follows:
mA output

J1

V output

J1

CHECKING

Terminal wiringCheck that all cables are correctly connected according to the connection diagram.
Power input voltageCheck voltage of the terminal 1011.
InputCheck that the input signal is within 0-100.
OutputCheck alarming function movement meets the described specifications.

SETTING PROCEDURE

This unit is calibrated at the factory to meet the ordered specifications; therefore you usually do not need any
calibration.
30 sec. nonmoving key returns to normal display value.
For matching the signal to a receiving instrument, adjust the setting as explained.