Professional Documents
Culture Documents
INTRODUCTION
The
insulations
of
electrical
equipment
in
generating
stations,
OVERVOLTAGES
Over voltages are classified as:
2.1
40
The lightning
impulse is one which more or less rises to its peak or crest value in 1.2
microseconds and it is half the crest value in 50 microseconds.
It was originally felt that the lightning stroke was substantially a single
impulse. Later data has shown that 50% of all strokes were multiple in
character; that is after the first discharge has subsided a second and
subsequent discharge occurred.
41
42
2.3
3.0
43
4.1
44
potential of the tower itself can rise to a value sufficient to flash the
insulator string from tower to line conductor, which is equally as bad, if
the flash-over was in the reverse direction. A reasonable value for the
tower footing impedance is a value of less than 10 ohms.
The tower footing impedance depends upon the soil in which the tower
is located. In swampy wet ground, clay soils or garden soils values as
45
resistance is encountered, it can be reduced in several ways such as:1. Driving ground rods around the base of the tower to be connected
electrically to the tower leg.
2. Running lateral wires buried in the ground from each tower leg and
generally called crow-foot arrangement.
3. Placing a counter-phase of one or more wires or rods in the ground and
extending under the line between the towers.
4.2
Protection to Equipment
The protection to equipment is essentially made by the following
Lightning Arresters
4.3.1 Requirements:
The basic requirement of a lightning arrester is that:a) It should behave as a perfect insulator for the highest system voltage
to ground
b) It should discharge any over voltage into the ground safely.
46
3 to 15KV
b) Line type
20 to 72KV
c) Station type
prevailing.
network
A second method of classification is by the characteristic that is, as to
whether it is linear or non linear. A linear characteristic is described by
a lightning arrester
which discharges into the ground when the voltage reaches a preset
value and the resistance offered to the voltage is the same irrespective
of the magnitude of the voltage. On the other hand, in a non-linear
type, the resistance decreases as the magnitude of the voltage
increases.
47
terminal, the space between the spark gap will have recovered its di-
48
electric properties.
reason the arrester is open at its lower end to permit the gases to
escape; hence the name Expulsion type.
resistor which has the property of offering a low resistance to the flow
of heavy currents and high resistances to the power frequency follow
current.
49
some of which are flat and some of special design with pressed out
projections.
The resistance elements are generally made up in the form of
cylindrical blocks.
Station type: - Most expensive, very efficient and used for all voltage
ratings in substations.
ii.
50
selection and use. Thus the various terms connected with the same
are described below.
4.3.6 Rated Voltage
It is the voltage to which the characteristics of the L.A. are referred. It
is the designated maximum permissible R.M.S value of power
frequency voltage which it can support across its line and earth
terminals while still carrying out effectively and without damage, the
automatic extinction of the follow up current. (The follow up current is
explained in paragraph 4.3.4).
A lightning arrester is often called upon to operate for an earth fault
elsewhere in the system. The voltage rating must therefore be higher
than the sound phase to ground voltage as otherwise the arrester may
draw too high a follow up current which may lead to thermal
overloading and failure.
already
in
been
explained
earlier
the
handout
on
instrument
transformers.
4.3.7 Co-efficient of Earthing
It is defined as the ratio of the highest R.M.S. voltage to earth of sound
phase or phases at the point of application of an arrester during a line
51
the ratio Ro/X1 is less than 1 and Xo/X1 is less than 3, the voltage from
line to earth on healthy phases, will not, in practice, exceed 80% of the
line to line voltage. Here R o is the zero sequence resistance, X o the
zero sequence reactance and X1 is the positive sequence reactance of
the system up to the point of installation of the lightning arrester.
For example, in a 132KV effectively earthed system for which the
highest system voltage is 145KV, the voltage rating of the lightning
arrester will be 145 x 0.8 = 116KV. However in practice a margin is
allowed and 85% line voltage is selected i.e. (123KV L.A. for 132KV
system).
b) Non-Effectively Earthed System
52
voltages of 66KV and above. Ratings of 5KA are for system voltages of
11KV and below. Field studies have indicated that 95% of the surges
are within the 10KA range.
4.3.9 Rated frequency
53
power frequency is fixed, which as per B.S.S. is 1.6 times the rated
voltage of the lightning arresters.
For example if an 80% L.A. is used, then it will not discharge for a
system voltage equal to or less than 2.43 times the normal line to
ground voltage as shown below:
1.6 x (KVr) x 1.1 x 0.8
KV/3
Where
2.43
For example in BS
54
2ei ea
Z
ia
Discharge Current
ei
ea
55
This current is
56
Generally
57
ii.
iii.
To determine the ratio Ro/X1 and Xo/X1 at the point of installation and
also the Co-efficient of Earthing. This is to decide the voltage rating of
the L.A.
58
iv.
(viii) is completed.
v.
vi.
vii.
viii.
ix.
59
It is
reflected back at almost twice its value if the line dead ends or
terminates at a transformer. This reflected wave travels back to the
L.A. and a negative reflected wave travels from the L.A. back to the
transformer.
Where
Et
ea + 2 de x L___
dt 1000
ea
de
=
second
dt
An
KV
2
For arresters located close to within 30ft of a transformer, the
protection level is given by:
1.15 x Residual Voltage + 30.
60
132KV
145KV
145 x 0.80 =
116KV
145 x 0.85 =
123.25KV
123 x 3.6
=
442.8
443 KV peak
123 x 1.6
196.8
197 KV (R.M.S.)
2(860) 443
400
3.1925 KA
It is
10KA
61
539 KV peak
=
123 x 3.6
443 KV peak.
443 x 1.25
553.75 KV peak
Thus the 123 KV L.A. will protect a transformer if the B.I.L of the
transformer is greater than 553.75 KV. The nearest B.I.L for 132 KV to
correspond to 553.75KV is 650KV.
Protective margin =
650___
553.75
1.17
That is 117% for switching and lightning and for temporary overvoltages
4.4
Rod Gaps
This type of protective device is simple and robust.
It does not;
62
Rod gaps are used as a sort of back up protection to L.As and are also
referred to as Spark gaps or Coordinating gaps.
provide adequate protection. On the other hand, if the gaps are set to
provide protection for these waves, their minimum spark-over voltages
will be too low and there may be outages even for normal switching
over-voltages and minor lightning surges. The practical gap setting is
63
therefore a compromise.
insulator should also be not less than about one third of the gap length
in order to prevent the arc from being blown on to the insulator.
The gaps on line and bus-bar insulator strings are used for the
following in addition to what has been mentioned earlier
a) To equalise the potential gradient over the string and to produce a
more uniform field.
b) To provide an alternative path for flash-overs to avoid damage to
insulator strings.
4.5
Protector tubes
These are gas filled tubes with two or three electrodes, one of which is
connected to the ground. The gas is a rare gas such as Neon, Argon,
etc. They are connected between the line and ground in case of a two
electrode gas tube or shunted across a line in case of a three electrode
tube as shown:
64
65
66
One or all of the above methods are employed to reduce the overvoltage factor due to switching to less than 2.0 and the temporary
over-voltage factor to less than 1.5.
Tests on L.As
The following tests are prescribed for L.As in almost all of the national
and international specifications.
a) Type tests
b) Sample tests
c) Routine tests
5.1
Type Tests
(i)
67
(ii)
(iii)
(iv)
(v)
(vi)
5.2
Sample tests
(i)
(ii)
5.3
Routine tests
(i)
(ii)
(iii)
68