DataSheet
Features
HT311DS - 1201
Functional Description
The HI 311HART Serial Interface
provides a complete physical link between
a HART Field Instrument and any IBM
compatible personal computer. The
interface is fully self contained, and
requires no direct power supply.
The HI 311 is designed for use with
any software driver that meets the
conditions shown in Table 1, or with
SmarResearch's CONF 301 HART
Configuration Software.
WAVE SHAPER
TxD
RxD
INPUT LINE
RTS
CTS
DCD
DSR
MODEM
CIRCUIT
DTR
POWER
VCC
INPUT
FILTER
HT311DS - 1201
Signal Functions
TxD (pin #3)
TRANSMITTED DATA
HT311DS - 1201
Signal Levels
The table below defines the signal levels that should be present at the computers serial port
for proper operation of the HI 311.
Pin numbers reference the HI 311s female DB9 connector.
DB9
V+
min
Vmax
Z
max
TRANSMITTING TO A
HART LINE (FSK)
RECEIVING FROM
HART LINE (FSK)
TxD (3)
5V
1V
3K
DATA OUT
DON'T CARE
RxD (2)
4V
1V
200
DON'T CARE
DATA IN
RTS (7)
5V
1V
3K
TRUE
FALSE
CTS (8)
....
....
....
=RTS=TRUE
=RTS=FALSE
DSR (6)
....
....
....
=DTR=TRUE
=DTR=TRUE
GND (5)
REF
REF
REF
DIRECT CONNECTION
DIRECT CONNECTION
DCD (1)
4V
1V
200
LINE ACTIVITY
LINE ACTIVITY
DTR (4)
8V
0V
200
TRUE (V+)
TRUE (V+)
HT311DS - 1201
Signal Definitions
Figures 2 and 3 below give the
operating charecteristics of the HART
modulator at 1200 Hz and 2200 Hz. Both
were plotted using an HP digitizing
oscilloscope connected to a 24Vdc power
Frequency: 1200 Hz
500
300
100
0
-100
-300
0.36
0.72
-500
1.08
1.44
1.80
(ms)
Figure 2 - 1200 Hz
Frequency: 2200 Hz
500
300
100
0
-100
0.34
0.68
1.02
1.36
1.70
(ms)
Figure 3 - 2400 Hz
HT311DS - 1201
Connection Example
Serial
Cable
Optional
Intrinsically Safe
Barrier
250 Ohms
Vcc = 24Vdc
(35 Vdc MAX)
Instrument
Mechanical Specifications
Dimensions
Connections
Length:
Width:
Depth:
4.25
1.25
0.75
DB9
HT311DS - 1201
Smar Research reserves the right to make changes to design and functionality of any product without notice. Smar Research does not assume any liability arising out of the application or use of any product. Smar Research , Technology
Source, and the SRC logo are registered trademarks of Smar Research Corporation. The HART, Fieldbus, and Profibus
Foundation logos are trademarks of their respective owners.
HT311DS - 1201