Electric Equipment General Catalog

Load Break Switches (LBS)

Contents
VTL Type

Auxiliaries &
Devices

Installation
Type

Circuit
Diagram

Outside
Drawing

Fuse Selection Official


Standard
Authentication Test
Exemption Certificate

D-6 D-8 D-10 D-12 D-13 D-15 D-17

Different grade of LBS

[Only VITZROTECH
s LBS is the only E3 class]

E3 class capacity
with 100A fuse
combination

E3 class capacity
with built in
lightning arrester

VITZROTECH LBS is the first and best E3 class LBS in the country.

Other

Performance comparison by class


according to IEC60265
Other companies
Other

D-2

VITZRO TECH LBS

Upgraded
Upgraded New
New Model
Model on
on a
a Differentiated
Differentiated Level!
Level!
Developed the countrys first LA-embedded LBS
Developed type tests for all types, in E3 class
Passed 100A fuse combination type test

E3 class capacity with


100A fuse combination
& built in LA

According to the development of 100A fuse-combined LBS that requires a performance three times higher
than the existing 63A device, the protection range for a transformer was extended up to 100A.
Maximum fuse capacity of fuse combination LBS

Transfer current breaking capacity of load


switch according to the fuse capacity

Other

Other

VITZRO

VITZRO

Electric Equipment General Catalog

D-3

[ Koreas first LA-Embedded LBS! ]


All you need is the LA-Embedded LBS!

LA Embedded LBS
The size of the switch panel can become smaller as
additional space for LAs is not necessary, so that cost
reduction can be realized.

Insulator Material
Excellent electrical and mechanical strength and
arc-resistance of the support insulator formed
with polysil (our patented product) and built-in LA,
and epoxy puffer insulator minimize the influence
to other devices
in the panel.

D-4

VITZRO TECH LBS

[ LA inside LBS ]
This product is the same size as existing LBS because LA is Embedded in the support insulator.

LA-embedded LBS
24kV 40kA

LA embedded inside
the support insulator
18kV 2.5kA

Main Circuit Section


Arcing blade

Dual contact structure by main blade and

Main blade

Arc chute

arcing blade prevents the damage on the


main blade
Pressurized air discharge maximizes the
instantaneous arc extinguishing capacity.

Fixed contact
Puffer insulator (Epoxy)

Electric Equipment General Catalog

D-5

VTL Type

KML Type

Auxiliaries &
Devices

Installation
Type

Circuit
Diagram

Outside
Drawing

Fuse selection
Standard

New E3 class High-Performance Model

Fuse-combrination type

Basic type

Embedded LA
100A fuse applied

Embedded LA

Type
VTL

Name
Operation type

LBS basic
VTL

LBS+LA embedded
VTL
VTL

24/630A1

24/630M1

Auto

Manual

LBS+fuse
VTLF
VTLF

24/630A1-LA1 24/630M1-LA1
Auto

Fuse-mounted

24/630A1

24/630A1

Auto

Manual

Manual

LBS+LA+fuse
VTLF
VTLF
24/630A1-LA1 24/630A1-LA1
Auto

No

LA-mounted

No

Manual

Yes
Yes

No

Rated voltage

Yes

24kV

Rated current

630A

Switch 630A/ Fuse 100A

Switch rating (IEC standard)

E3, M1 Class

Pole

3 poles

Rated frequency

60Hz

Rated short-time withstand current

20kA/1sec

Rated making current

52kAp

104kAp

Power frequency To ground

50kV/min

withstand voltage

Same phase

60kVmin

Lightning impulse

To ground

125kVp

withstand voltage

Same phase
Load current

Current
Loop current
switching
Cable
times

145kVp
630A

100 times

31.5A

20 times

630A

20 times

31.5A

10 times

Charging current 9.45A

10 times

Line charging current 1.5A

10 times

No-load switching

1,000 times

Rated breaking current

40kArms

Rated transfer current

1250Arms

Rated fuse current (Fuse-mounted type)

N/A

Up to 100A
1/5/10/16/20/25/31.5/40/50/63/80/100

Rated control voltage

110Vdc

110Vdc

110Vd

110Vdc

Rated control current

5A

5A

5A

5A

88kg

98kg

94kg

Manual operation cable length


Weight
) (LA-embedded type)
LA specification
Applied standard
D-6

VITZRO TECH LBS

Standard: 2.0m (Option: 1.5/2.6m)


68kg

64kg

74kg

70kg

92kg

* LA For LA-embedded type


1) Rated voltage : 18kV
2) Nominal discharge current: 2.5kA
3) Rated frequency: 60Hz
4) Power frequency withstand voltage: 50kV/1min
5) Lightning impulse withstand voltage: 125kVp
IEC60265-1, IEC62271-105, IEC60282-1

Load Break Switches

KML Type - 12kV Manual Operation-only


KML Type-12kV Manual Operation-only

Air Circuit Breakers

Load Break
Switches

D
Rated voltage

12 kV

Type

12KML-M

Pole

3 Pole

Rated current

630A

Rated frequency

50/60Hz

Power frequency withstand voltage

32kV

Impulse withstand voltage

85kV

Rated short-time current (1s)

20kA

Rated short circuit making current

52kA

Load current

Current switching
capacity

630A

Loop current

630A

Charging current

31.5A

Opening time

60ms

Operation type

Manual

Operating voltage

Operating current

Weight (Without fuse)

62.5kg

Manual operation cable lengt

Standard: 2.0m (Option: 1.5/2.6m)

Ordering codes
VTL

LA

100

Type
VTL
KML

Fuse-mounted

Operation type
Auto
A
Manual
M

LA-mounted
LA No
LA
Yes
-

Fuse capacity

Operating voltage

Manual operation cable length

F
N

Fuse Yes
Fuse No

Specify the
rated current
when necessary

A
B
C

DC110V
AC110V
AC220V

A
B
C

1.5M
1.8M
2.0M

* KML type is dedicated to 12kV manual operation.

Electric Equipment General Catalog

D-7

VTL Tyle

KML Type

Auxiliaries& Devices

Installation
Type

Circuit
Diagram

Outside
Drawing

Fuse selection
Standard

Striker

24/25.8kV Fuse Link


Rated current

Rated maximum Rated minimum

Model name

In
[A]

breaking current breaking current


[kA]
[A]

VTHF24001

VTHF24005

VTHF24010

10

VTHF24016

16

VTHF24020

20

VTHF24025

25

VTHF24032

31.5

VTHF24040

40

VTHF24050

50

VTHF24063

63

VTHF24080

80

VTHF25100

100

Rated voltage
[kV]

24

40

25.8

Dimension
e
[mm]

d
[mm]

Weight
[kg]

56

2.3

65

3.1

78

4.1

442

5In

Example of fuse-mounted LBS installation


This one line diagram is an example installation where the fuse
combination LBS applicable. The rated current of the power fuse
is chosen considering the capacity of power-receiving transformer
and the protection coordination with OCR.
VITZRO LBS is equipped with a fuse combined trip device that
automatically trips when one fuse is melted due to short circuit or
overcurrent, so that it operates quickly and accurately in case of
fault in any phase.

Incoming
LBS with Fuse combination

WHM
COS or PF

COS, PF or CB

Load

D-8

VITZRO TECH LBS

Load

Load

Load Break Switches

Auxiliaries& Devices

Electrically-Driven Operating Unit


This is used for remote On/Off control. The standard
rated voltage is DC 110V, but AC 110V/AC 220V are
also available by individual order.

Remote operation cable


Electricallydriven
operating unit

Manual Remote Operating Unit


Load Break
Switches

This is used for manual operation at the panel door,


and comprises a cable and a manual handle.

Manual
handle

Auxiliary Relay
This relay operates according to the main blade
operation, and is used in indicating the switch status and
controlling the switch.

D
Auxiliary relay

Shunt trip device

Shunt Trip Device


This device is equipped with a shunt coil to facilitate
quick trip operation by the signal from the relay in case
of fault.

Counter
This is a switching counter that indicates the number of
switching times of LBS

Fuse Combined Trip Device

Counter

Fuse melting trip device

This device provides trip operation to prevent open


phase operation in case one fuse out of three fuses is
melted due to a fault, which is clear and quick using
mechanical links.

Fuse Combined Indicator Contact


1a contact is provided to enable the remote
monitoring of fuse melting. (F1-F2)
P

F1

A1 A3 B1

B3

F2

A2 A4 B2

B4

Fuse melting indicator contact

Electric Equipment General Catalog

D-9

VTL Tyle

KML Type

Auxiliaries &
Devices

Installation Type

Circuit
Diagram

Outside
Drawing

Fuse Selection
Standard

LBS Main Body


Basic type

Fuse-mounted

Circuit diagram for


installation

Vertical installation

Horizontal Installation

* Check if the surface on which the device is installed is flat, to prevent the distortion of LBS

Manual remote operating unit

Fixed frame
(Switch cabinet door)

Above R150

Cable fixture

----- corresponds to the horizontal


installation.

Manual handle

Cable
1. The standard length is 2.0m, and 1.5/2.6m can also be manufactured by order.
2. The cable requires sufficient radius curvature above R150 for good operation.
3. The manual On/Off operation by cable is conducted by single direction turn (right turn).
4. Fix the cable with cable ties to the inside wall of switch cabinet considering the insulation distance.
5. Use the separately provided exclusive handle for manual operation.

D-10

VITZRO TECH LBS

Load Break Switches

Circuit
Circuit

Names by section
Base Frame

Support Insulator
Load Terminal
Load Break
Switches

Arcing Blade
Main Blade

Line Terminal

Arc Nozzle

Fixed Main Contact


Fixed Support Insulator
Operating Rod
Operating Mechanism
Manual Operation Cable
Geared Motor
Manual Handle
Support Insulator
Load Terminal

Current limiting Power Fuse


Fuse Trip Device

Electric Equipment General Catalog

D-11

VTL Tyle

Auxiliaries &
Devices

KML Type

Installation
Type

Circuit Diagram

Outside
Drawing

Fuse Selection
Standard

Automatic (Electrically-driven)

Control Circuit / Automatic

Control voltage(DC110V)

DC 110V

P : DC 110V ()
N : DC 110V ()
C : CLOSE
T : TRIP
SC : Trip Coil
M : Motor for closing
89X : Auxiliary relay for closing
Manual

Manual

Combination

AC 110V / AC 220V

Control voltage(DC110V)

P : AC 110V / AC 220V ()
N : AC 110V / AC 220V ()
C : CLOSE
T : TRIP
SC : Trip Coil
(DC 110V / DC 220V)
M : Motor for closing
DC 110V / DC 220V)
89X : Auxiliary relay for closing
Manual

D-12

VITZRO TECH LBS

Manual

Combination

Load Break Switches

Outside Drawing
Outside Drawing

VTL (E3 class) New Model


Basic Type/LA-Embedded Type (Auto/Manual)

Load Break
Switches

Fuse-Mounted Type/LA-Embedded Type (Auto/Manual)

Electric Equipment General Catalog

D-13

VTL Tyle

KML Type

Auxiliaries &
Devices

Installation
Type

Circuit
Diagram

Outside Drawing

Fuse selection
Standard

12KML-M
12kV, Manual-Exclusive

Installation dimension

Basic type and LA-embedded type (12KML-M)

D-14

VITZRO TECH LBS

Fuse-mounted type and LA-embedded type

Load Break Switches

Fuse Selection Standard


Fuse Selection Standard

Fuse Selection Standard by Usage


Power fuse for transformer circuit protection
Rated voltage
[kV]

Rated capacity of transformer [kVA] 3


7~15

PF

24

VTHF24001

36 ~ 76

VTHF24005

75 ~ 158

VTHF24010

141 ~ 276

VTHF24016

176 ~ 344

VTHF24020

220 ~ 431

VTHF24025

264 ~ 540

VTHF24032

466 ~ 990

VTHF24040

600 ~ 1238

VTHF24050

743 ~ 1585

VTHF24063

990 ~ 1981

VTHF24080

1585 ~ 2641

VTHF25100

2251 ~ 3301

VTHF24125

3522 ~ 4226

VTHF24160

Load Break
Switches

TR

Fuse link

<Detailed selection condition>


1. The inrush current of transformer was estimated by assuming 10 times the transformer full load current for 0.1s.
2. The rated fuse current was estimated so that 1.5 to 2 times the transformer rated current could be continuously conducted.
3. The transformer fuse was selected on the assumption that it could break in less than 2 seconds at 25 times the transformer
rated current in case of secondary short circuit.

Electric Equipment General Catalog

D-15