BAE Secura PVS solar

Technical Specification for Vented Lead-Acid Batteries (VLA)


1. Application
BAE Secura PVS solar batteries need only low maintenance and are
used to store electric energy in medium and large solar photovoltaic
installations.
Due to the robust tubular plate design BAE PVS batteries are excellent
suited for highest requirements regarding cycling ability and long lifetime.

2. Technical data (Reference temperature 20 C)





Type

Ue
V/cell

2 PVS 140
3 PVS 210
4 PVS 280
5 PVS 350
6 PVS 420

5 PVS 550
6 PVS 660
7 PVS 770

6 PVS 900
7 PVS 1050
8 PVS 1200
9 PVS 1350
10 PVS 1500
11 PVS 1650
12 PVS 1800

11 PVS 2090
12 PVS 2280
13 PVS 2470
14 PVS 2660
15 PVS 2850
16 PVS 3040
17 PVS 3230
18 PVS 3420
19 PVS 3610
20 PVS 3800
22 PVS 4180
24 PVS 4560
26 PVS 4940

C1 h
Ah

C10 h
Ah

C20 h
Ah

C72 h
Ah

C100 h
Ah

C120 h C240 h
Ah
Ah


1.67


1.80


1.80


1.80


1.80


1.80

127
191
254
318
382

432
518
604

748
872
996
1,116
1,240
1,362
1,486

1,636
1,784
1,938
2,080
2,220
2,380
2,540
2,680
2,840
2,980
3,280
3,560
3,860

141
211
282
352
424

486
583
681

856
993
1,137
1,274
1,418
1,555
1,699

1,836
2,001
2,174
2,332
2,498
2,664
2,858
3,024
3,189
3,355
3,686
4,010
4,341

143
215
287
359
431

496
595
694

877
1,020
1,160
1,300
1,450
1,590
1,740

1,870
2,040
2,210
2,380
2,550
2,710
2,910
3,080
3,250
3,420
3,750
4,090
4,420

144
217
289
361
434

500
601
700

888
1,033
1,178
1,320
1,464
1,608
1,752

1,884
2,052
2,232
2,400
2,568
2,736
2,940
3,108
3,276
3,444
3,780
4,128
4,464

63 111
95 167
127 223
159 279
191 334


223 389
267 467
310 544


352 665
415 777
473 886
522 992
585 1,100
635 1,210
698 1,320


790 1,470
869 1,600
978 1,740
1,051 1,880
1,123 2,010
1,195 2,140
1,280 2,290
1,352 2,420
1,425 2,560
1,496 2,690
1,635 2,950
1,777 3,220
1,917 3,480


1.80

148
222
295
369
444

513
616
720

916
1,065
1,216
1,365
1,516
1,665
1,816

1,941
2,116
2,292
2,448
2,640
2,808
3,000
3,192
3,360
3,528
3,888
4,224
4,584

Ri
1)
mV
1.52
1.06
0.84
0.70
0.60

0.57
0.49
0.44

0.47
0.36
0.32
0.33
0.28
0.28
0.24

0.24
0.22
0.16
0.15
0.14
0.13
0.12
0.11
0.11
0.11
0.10
0.09
0.09

Ik Length Width Height Weight Weight


2)
(L)
(W)
(H)
dry filled
kA mm mm
mm
kg
kg
1.37
1.96
2.46
2.98
3.47

3.61
4.18
4.69

4.41
5.66
6.36
6.20
7.25
7.36
8.41

8.38
9.48
13.03
13.82
14.43
15.20
16.91
17.55
18.36
18.92
19.92
21.26
22.49

105
105
105
126
147

126
147
168

147
215
215
215
215
215
215

215
215
215
215
215
215
215
215
215
215
215
215
215

208
208
208
208
208

208
208
208

208
193
193
235
235
277
277

277
277
400
400
400
400
490
490
490
490
580
580
580

420
420
420
420
420

535
535
535

710
710
710
710
710
710
710

855
855
815
815
815
815
815
815
815
815
815
815
815

9.1
11.2
12.8
15.3
18.1

14.5
16.4
18.0
21.7
25.7

20.0
23.5
26.8

28.8
34.0
39.1

33.0
42.1
46.6
51.4
56.0
61.0
65.4

47.4
61.5
65.4
75.4
79.4
89.6
93.4

72.7
77.4
90.8
95.3
100.2
105.4
117.7
121.9
126.8
132.0
145.4
155.2
165.0

105.9
110.4
137.8
142.4
146.9
151.6
175.1
179.1
183.6
188.3
213.9
223.0
232.0

1, 2) Internal resistance Ri and short circuit current Ik according to IEC 60896-11


Height (H) is the maximum height between container bottom and top of the bolts in assembled condition.
BAE Secura PVS solar batteries are also available as dry pre-charged version. They are titled with additional TG, e.g. 4 PVS 280 TG.
All values given in the table correspond to 100 % DOD without voltage drop of connectors. Please consider item 7.

3. Terminal positions

2 PVS 140 to 6 PVS 900

7 PVS 1050 to 12 PVS 2280

13 PVS 2470 to 16 PVS 3040

17 PVS 3230 to 26 PVS 4940

Terminals are designed as female poles with brass inlay M10 for flexible insulated copper cables with cross-section 25, 35, 50, 70, 95 or
120 mm2 or insulated solid copper connectors with cross-section 90, 150 or 300 mm2.

Technical Specification for BAE Secura PVS solar


4. Design
Positive electrode

Negative electrode
Separation
Electrolyte
Container
Lid

Plugs

Pole-bushing
Kind of protection

tubular-plate with a woven polyester gauntlet and solid grids in a corrosion-resistant


PbSbSnSe-low antimony alloy
grid-plate in a low antimony alloy with long-life expander material
microporous separator
sulphuric acid with a density of 1.24 kg/l at 20 C (68 F)
high impact, transparent SAN (Styrol-Acrylic-Nitrile), UL-94 rating: HB
high impact SAN in dark grey colour (colour may vary slightly from given image),
UL-94 rating: HB
labyrinth plugs for arresting aerosols,
optional ceramic plugs or ceramic funnel plugs according to DIN 40740
100 % gas- and electrolyte-tight, sliding, plastic-coated Panzerpol
IP 25 regarding EN 60529, touch protected according to VBG 4

5. Installation

BAE Secura PVS solar batteries are designed for indoor applications.
For outdoor applications please contact BAE.

6. Maintenance
Every 6 months
Every 12 months
Every 3 years

check battery voltage, pilot cell voltages, temperatures


check connections, record battery voltage, cell voltages and temperatures
average water-refilling interval (depending on utilization and ambient temperature)
16500

Zyklen

7. Operational data
15000
Depth of discharge (DOD)
max.
80 % (Ue = 1.91 V/cell for discharge times >10 h; 1.74 V/cell for 1 h)
13500
12000

deep
discharges of more than 80 % DOD have to be avoided
10500
Initial charge current
unlimited,
the minimal charge current has to be 5 A/100 Ah C10
9000
(I or bulk phase)
7500
Charge voltage at cyclic operation restricted
from 2.30 V to 2.40 V per cell, operating instruction is to be observed
Float voltage/non cyclic voltage 2.236000V/cell
4500
Adjustment of charge voltage no adjustment
necessary if battery temperature is between 10 C and 30 C

(503000
F and 86 F) in the monthly average,
1500

otherwise
DU/DT = -0.003 V/cell per K
Recharge to 100 %
within0 a0 period
of 120up to 304 weeks
10
40
50
60
70
80
90
IEC 61427 cycles
3,150 (A+B) at 40 C (104
F) (DOD) in %
Entladetiefe
Battery temperature
-20 C to 55 C (-4 F to 131 F),

recommended temperature range 10 C to 30 C (50 F to 86 F)
Self-discharge
approx. 3 % per month at 20 C (68 F)
8. Number of cycles
as function of
Depth of discharge

16500
15000
13500
12000

Cycles

10500
9000
7500
6000
4500

1500
0
0

10

20

30

40

50

60

70

80

90

Depth of discharge (DOD) in %

9. Transport




10. Standards
Test standards
Safety standard, ventilation

BAE Batterien GmbH


Wilhelminenhofstrae 69/70
12459 Berlin
Germany

Batteries are not subject to ADR (road transport), if the conditions of Special Provision
598 (Chapter 3.3) are observed.
These cells/batteries are dangerous goods on sea transport. Declaration and packaging
must comply with the requirements of IMDG-Codes.
IEC 60896-11, IEC 61427
EN 50272-2

Tel.: +49 (0)30 53001-661


Fax: +49 (0)30 53001-667
E-Mail: info@bae-berlin.de
www.bae-berlin.de

12/2012 4805220 Technical details may be subject to alterations.