You are on page 1of 25

Introduction to

Doble Bushings Testing


Doble Engineering Diagnostics
Toolbox

 Capacitor/Condenser Type:
 Oil-Impregnated Paper Insulation
 Resin Bounded Paper Insulation
 Non-Condenser Type:
 Solid
 Alternate Layers of Solid and Liquid Insulation
 Gas-filled

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

Main Insulation C1

Center
Conductor

CA = CB = CC = CD = CE = CF= CG = CH = CI = CJ

V1 = V2 = V3 = V4 = V5 = V6 = V7 = V8 = V9= V10

CK

Grounded
Layer/Flange

Tap
Electrode

Line-to-Ground System Voltage

The Condenser type bushing allows an energized


conductor to penetrate a ground plane
Voltage is stressed equally across each layer of the
Condenser type bushing
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

CA

CENTER CONDUCTOR

CB
CC

Core Wind

CD
CE
CF
CG
CH
CI
CJ

CK

Tap Electrode
Grounded
Layer/Flange

Foil
C2 Plate

Grounded Layer/
Flange

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

CA

Herringbone Pattern

CENTER CONDUCTOR

CB
CC

Core Wind

CD
CE
CF
CG
CH
CI
CJ

CK

Tap Electrode
Grounded
Layer/Flange
C2 Plate

Grounded
Layer/Flange

Semi-Conducting Paper

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

Center Conductor
Sight-Glass
Liquid or Compound Filler
Insulating Weather Shed

Main Insulating Core


Tap Insulation
Tap Electrode
Mounting Flange
Ground Sleeve
Tapped Capacitance-Graded Layer
Lower Insulator

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

Center Conductor
Tapped Capacitance-Graded Core Layer
Liquid/Compound Filler
Main Insulating Core
Insulating Weathershed
Capacitance Graded
Core Layers
Tap Cover
Filler Plug
Connection to Tapped Core Layer
Tap Electrode
Tap Insulation
Mounting Flange
Permanently Grounded Core Layer
Ground Sleeve
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

Center Conductor
Tapped Capacitance-Graded Core Layer
Liquid/Compound Filler
Main Insulating Core
Insulating Weather shed
Capacitance Graded
Core Layers
Tap-Cover
Tap Insulation
Tap Electrode
Connection to Tapped
Core Layer
Mounting Flange
Ground Sleeve
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

10

 C1 Main Core Insulation (UST)


 Center Conductor to Tap

 C2 Tap Insulation Test (GST-guard)


 Tap to Flange

 Hot Collar Test


 Externally Applied Collar to Center Conductor

 Overall (typically for Spare Bushings)


 Center Conductor to Flange
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

11

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

12

Take advantage of the


Short Circuit in place
for the Overall test
(HV windings, LV
windings, and
Neutral Bushing
disconnected from
ground) to complete
Bushings tests.

High
Voltage
Windings

CHL

CH
CL
Low
Voltage
Windings

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

13

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

14

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

15

High-Voltage Cable

Test Includes
Main C1 Core Insulation

Test Mode: UST


Guard

Low Voltage Lead


Ground Lead
Bushing and
Apparatus Ground

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

16

Test Tap
Low-Voltage Lead

C1
C2

Test Mode: UST

Center Conductor

High Voltage Lead

Ground Lead

IC1
Guard
I & W Meter
Test Ground

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

17

Power Factor
 Modern Condenser Type Bushings in Acceptable condition
 Will depend on the manufacturer and type
 Generally the order of 0.5%
 Temperature correction to 20C

 Deteriorated Bushings
 Generally Between 0.5% to 1.0%

 Investigate Bushings
 Above 1.0%

Current/Capacitance
 Recommended Limits
 + 5% - Investigate
 + 10% - Investigate/Remove From Service
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

18

Description

Current (mA)

Watts

%PF

Typical Good
Bushing

1.08

0.03

.28

Same Bushing
Contaminated

1.09

0.06

.55

Same Bushing
Shorted
Condenser
layers

1.19

0.04

.34

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

19

Low Voltage Lead


Test Includes
 Tap Insulator
 Core Insulation between tapped layer and
Bushing ground sleeve
 Portion of liquid or compound filler
 Portion of Weather shed near flange
High Voltage Lead

Test Mode: GST-Guard


IC2
Guard
I & W Meter
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

20

Low Voltage Lead

C1
C2

Center Conductor

High Voltage Lead

Test Mode: GST-Guard


IC2
Guard

Test Ground
I & W Meter

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

21

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

22

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

23

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

24

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

25

When to perform Bushings Hot-Collar Tests







Compound-Filled Bushings
Solid Porcelain Bushings
Gas-Filled Bushings
Oil Filled Bushings not equipped with taps and Overall Test cannot be
performed
 Single Hot-Collar Test on small Bushings 15 KV and below
 Several single Hot-Collar Tests for Bushings rated above 15 KV

 To check Oil level on all liquid filled Bushings without liquid level
gauges or sight glass
 To check Bushings with liquid level gauges whenever the gauge is
suspect
 As supplementary tests when Overall, C1, C2 Tests indicate possible
problem

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

26

Low Voltage Lead


High Voltage Lead

Test Mode: GST-Ground


Ground Lead

Guard






Test Includes
Portion of insulating Weather shed
Sight-glass
Core insulation in upper area
Liquid or compound filler in the upper area
Surface leakage from Collar to LV lead and to
bushing flange

Bushing and
Apparatus Ground

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

27

Low Voltage Lead


High Voltage Lead

Test Mode: UST


Ground Lead
Guard
Test Includes
 Core Insulation in Upper Area
 Liquid or Compound Filler in the
Upper Area

Bushing and
Apparatus Ground

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

28

Low Voltage Lead


High Voltage Lead

Test Mode: GST-Guard


Ground Lead

Guard

Test Includes
 Portion of insulating Weather
shed sight-glass
 Surface leakage from Collar to LV
lead and to Bushing flange

Bushing and
Apparatus Ground

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

29

 Test Voltage 10 KV
 Recommended Acceptable Limits:
 Watts < = 0.1 Watts (100 mW)
 Current: similar for same type Bushings

Hot Collar Test Results Analysis


 Increased Watts
 Contamination of the Insulation

 Decreased Current (Amperes)


 Low liquid or compound level
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

30

Description

Current (mA)

Watts

Typical Good Bushing

.090

0.02

Same Bushings,
Contaminated

.095

0.31

Same Bushing,
Low Liquid Level

.070

0.02

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry







31

Dry Clean Cloth


Water & Soap
Colonite
Windex with Ammonia
Apply Heat to Fully Dry all Surfaces

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

32

Good Condition

General Contamination

Physical Changes (X2)

Defective Bushing (X3)

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

33

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

34

High-Voltage Cable
Test Includes
 Main C1 Core Insulation
 Insulating Weather shed
 Sight-glass
 Lower insulator
 Portion of liquid or compound filler
Guard
Ground Lead

Test Mode: GST-Ground


Bushing and
Apparatus Ground
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

35

 DO NOT test Bushings in wooden crate or stand


 Support Bushing on a metal stand if possible
 Slings may be used for tests, observe the
following:
 Cleanliness of sling may affect test results
 Sling should be kept clear of energized points

 Connect ground lead directly to Bushing flange


 Ground both test set and specimen to substation
ground
 Clean upper and lower surfaces before testing
89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

36

 Re-Check All Connections, Including Ground Lead


and Bushing Flange Ground
 Check Test Circuit Used
 Check Test Set and Test Set Leads
 Visually Inspect Bushing Sheds and Oil
 Clean and Dry All Surfaces

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

37

 Check all connections including ground lead and


Bushing flange ground
 Check test circuit used
 Check test set and test set leads
 Visually inspect Bushing and Oil (sight glass)
 Clean and dry all surfaces

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

38

 Compare and analyze results of identical Bushings


 Research Bushing history of flashovers or line Surges
 Verify temperature correction factor was used for C1
and Overall Tests *
 Verify the necessary fields in the nameplate were used
in order for DTA to identify the correct limit file
* Note: C2 Power factors are not temperature corrected

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

39

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

40

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

41

 IEEE Std 62 - 1995


 Guide for Diagnostic Field Testing of Electric Power
Apparatus Part 1: Oil Filled Power Transformers,
Regulators, and Reactors
 Section 3 Definitions
 3.2 Bushing - power and distribution transformer
 3.6 Power Factor - Dielectric

 Section 6 Tests and test techniques







6.2 Bushings
6.2.2 Visual Inspection
6.2.3 Oil Level
6.2.4 Capacitance, Power Factor, and Dissipation Factor

 Annex B (informative): Bushings Power Factor


measurements

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

42

DTA Bushings Tests Procedures


(Useful tips for DTA users)

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

43

 DTAF fields required To Activate temperature


Correction Factor
 Manufacturer
 Type
 Ambient Temperature (Probe)
 Apparatus Temperature
 Transformer - Oil Temperature
 Oil Circuit Breaker - Ambient Temperature

 DTA - Fields Required To Identify Correct Limit File


 Manufacturer
 Type
 KV rating

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

44

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

45

 The following pages provide information about


different Bushing Manufacturers and different
types of Bushings
 Use as Guidelines for test results analysis
 Please send your tests results to Doble for
further compilation and enhancement of
Bushings Database

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

46

Type
A*
A**
B*
D
F
L
LC
OF
S*

Description
Through Porcelain
High Current
Flexible Cable, Compound Filled
Oil Filled Upper Portion, Sealed
Oil Filled, Sealed
Oil Filled Upper Portion, Sealed
Oil Filled Upper Portion, Sealed
Oil Filled Expansion Chamber
Force C & CG, Rigid Core,
Compound Filled

Typical PF
3.0%
1.0%
5.0%
1.0%
0.7%
1.5%
0.8%
0.8%
1.5%

Questionable PF
5.0%
2.0%
12.0%
2.0%
1.5%
3.0%
2.0%
2.0%
6.0%

* Type S, Form F, DF & EF (flexible cable) redesigned as Types B, BD, and BE,
respectively. Type S, no Form letter (through porcelain) redesigned as Type A

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

Typical
C1
PF
Type ERC (Epoxy-Resin-Core, Plastic or Oil Filled)
Type PRC and PRC-A (Paper-Resin-Condenser Core)

0.8%
0.8%

47

Questionable
C1
PF
1.5%
1.5%

Typical C2 power factors for older PRC design range from 4-15% due to injected
compound used
during manufacturing.

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

48

Types

Typical %PF

Class LK-Type A, 23 to 69 kV
ODOF, Class G, and Class L Oil-Filled:
Prior to 1926 and
after 1938
Between 1926 and
1938

0.4

1.0

1.0-5.0

Change of 22%
from initial
Change of 16%
from initial

2.0-4.0

Type S, OS, and FS


On OCB and Inst. Trans. 69 kV and below
(except Types S, OS, and FS)

Questionable %PF

0.8
1.5

2.0
3.0

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

Typical %PF

Questionable %PF

On OCB and Inst. Trans. 92 kV to 139 kV


(except Types O, O-A1, OC and O Plus)

1.5

3.0

On Power and Dist Trans of all rating,


and OCB & Inst. Trans. 161 kV to 288 kV
(except Types O, O-A1, OC, and O Plus)

1.0

2.0

All Type D Transformer Bushings


( Semi-Condenser)

1.5

3.0

1.0

2.0

Type RJ
(Solid Porcelain)

49

89 Years of Diagnostic Instrumentation and Services for the Electric Power Industry

50