Professional Documents
Culture Documents
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 1 of 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 2 of 75
Table of Contents
1
1.1
1.2
1.3
1.4
1.5
1.6
2
2.1
2.2
2.3
3
3.1
3.2
3.2.1
3.2.2
3.2.3
3.2.4
3.2.5
3.2.6
3.2.7
3.2.8
3.2.9
3.2.10
3.3
3.3.1
4
4.1
4.2
4.2.1
4.2.2
4.3
4.3.1
4.3.2
4.3.3
4.3.4
4.3.5
4.4
4.4.1
4.5
4.6
4.6.1
4.6.2
4.6.3
4.7
4.8
4.9
Introduction ..........................................................................................................................5
Background ..........................................................................................................................5
Purpose .................................................................................................................................5
Key Benefits .........................................................................................................................5
Glossary ................................................................................................................................ 6
Contact Information .............................................................................................................6
Additional Information .........................................................................................................6
Gas Availability and Meter Box Accessibility .....................................................................7
Determining Gas Availability ............................................................................................... 7
Accessibility .........................................................................................................................9
Pre-Laid Services with Retaining Walls ..............................................................................9
Meter Box Locations ..........................................................................................................11
Principal Frontage - Definition .......................................................................................... 11
Principal Frontage - Examples .......................................................................................... 12
Standard L-Shape House .....................................................................................................12
Standard L-Shape House with Corner Window ....................................................................13
Narrow Cottage Block ..........................................................................................................14
Rear Laneway (Must Determine Gas Availability) .................................................................15
Pre-Laid at Top of Stairs.......................................................................................................16
Elevated Lot with Retaining Walls ........................................................................................18
Carport .................................................................................................................................19
House with Perimeter Fence and Locked Gate ....................................................................20
House with Swimming Pool ..................................................................................................21
Property without Street Frontage or Gas Availability............................................................. 22
Designated Boundary Connection Areas .........................................................................24
Gas Services to Large Rural or Semi-Rural Lots ..................................................................24
Meter Box Installation Requirements ................................................................................25
Meter Box Dimensions .......................................................................................................25
Security for Gas Meter Box and Enclosure ......................................................................27
Viewing Apertures for Locked Enclosures ............................................................................27
Mandatory Lock Requirements ............................................................................................. 27
Recessed Gas Meter Box...................................................................................................28
AL8 Meter Box (Partially Recessed) .....................................................................................28
AL12 Meter Box (Partially Recessed) ...................................................................................28
AL8 Dual Gas and Electric Meter Box (Partially Recessed) ..................................................29
AL12 Dual Gas and Electric Meter Box (Partially Recessed) ................................................29
Meter Box (Fully Recessed) .................................................................................................30
Locating a Gas Meter Box Away from Openings into a Building ....................................31
Window Within Meter Box Exclusion Zone ...........................................................................31
Meter Boxes on NIB Walls (Recommended Alternate Meter Box Position)....................32
Gas Meter Boxes Mounted on Free Standing Walls .........................................................33
Protection for Gas Meters.....................................................................................................35
Gas Meter Boxes Mounted adjacent to Electrical Power Domes ..........................................37
Gas Service Riser and Footing Requirements ......................................................................38
Connection to Commercial Properties (AL8, AL12 or AL18 Gas Meters) .......................39
Meter Boxes Installed Inside a Commercial Building ......................................................39
Vent Line Requirements ....................................................................................................40
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 3 of 75
5
Meter Box Restrictions and Installation Responsibilities................................................41
5.1
Requirements of the Responsible Person ........................................................................41
5.1.1
Avoiding Delays in Gas Service Installation ..........................................................................42
5.1.2
Internal Property Reinstatement ........................................................................................... 42
5.2
Meter Box Location Restrictions (AS/NZS 4645) .............................................................. 43
5.3
Other Location Restrictions .............................................................................................. 43
5.3.1
Service Regulator Installation Restrictions (AS/NZS 4645) ...................................................43
5.3.2
Meter Box on Exterior Wall ...................................................................................................44
5.3.3
Meter Box Restrictions in Other Localities ............................................................................44
5.4
Obstructions (When Meter Boxes Cannot be Installed on Dwellings) ............................ 45
6
Connections to Residential Strata Titled Developments .................................................47
6.1
Open Trench Booking Process .........................................................................................47
6.1.1
AGA Minimum Plan Criteria ..................................................................................................48
6.2
Open Trench Prerequisites ................................................................................................ 51
6.3
Open Trench Criteria ..........................................................................................................51
6.4
Backfilling Open Trench ....................................................................................................52
6.5
Substandard Open Trench.................................................................................................53
7
Meter Banks and Enclosures............................................................................................. 55
7.1
Banks of Meter Boxes ........................................................................................................55
7.2
Meters in Recesses (Enclosures) ......................................................................................57
7.3
Banks of Meters Mounted on AGA Approved Brackets in Building Recesses ..............59
7.3.1
Depth and Height of Recesses ............................................................................................. 60
7.3.2
Inside the Recess .................................................................................................................60
7.4
Doors and Ventilation ........................................................................................................61
7.5
Floor Finishes .....................................................................................................................62
7.5.1
Security Access ....................................................................................................................62
7.5.2
Signage ................................................................................................................................ 62
8
Related Documents ............................................................................................................63
9
Disclaimer ........................................................................................................................... 65
Appendices ......................................................................................................................................67
Gas Connection Checklist ...............................................................................................................69
Gas Service Installation On Hold Form .......................................................................................... 71
SafetyGram.......................................................................................................................................73
Feedback Form ................................................................................................................................ 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 4 of 75
Introduction
This Handbook provides guidance for installing your natural gas meter box and service for
safe, reliable and efficient connection to ATCO Gas Australias (AGA) natural gas distribution
network. It is not to be used for guidance when referring to AGAs Albany Liquefied
Petroleum Gas (LPG) network due to specific issues with heavier than air LPG and allowable
meter box positions.
AGA aims to continuously improve its new connections process by outlining the installation
process and compliant meter positions to streamline the connection process and help avoid
delays or further additional work and costs being incurred by the requestor.
The Feedback Form, which is located in the Appendices at the end of this Handbook, can be
used to provide improvement suggestions to AGA.
This Handbook must be considered a live document and is therefore subject to change.
1.1
Background
The design and construction of developments in Western Australia has provided the gas
industry with many challenges in maintaining compliance with Australian Standards when
positioning customer gas meters. AGA wishes to work proactively with industry to find
resolutions and avoid confusion about gas services and metering apparatus.
New developments typically have buildings that occupy a larger portion of the block and
there are an increasing number of developments located in elevated positions. The changing
designs of these developments can compromise standard meter box locations. AGA wishes
to avoid delays by providing information to the industry at a design stage, eliminating costly
alterations and variations during construction.
1.2
Purpose
This Handbook will reduce the confusion and inefficiencies that may be experienced by
providing a clear point of reference for developers and the construction industry. It will also
assist the construction industry in designing the layout of buildings to accommodate a
compliant gas connection.
1.3
Key Benefits
Key benefits to the construction industry are:
Inclusion of Gas Service Installation On Hold Form to provide permission to lift paved
surfaces when required.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 5 of 75
1.4
1.5
Glossary
Term
Reference
AGA
Responsible Person
PLS
Pre-Laid Service
PLSS
Contact Information
Contact Information
ATCO Gas Australia enquiries:
Phone: 13 13 56
www.atcogas.com.au
Section
Phone
Email
scheduling@atcogas.com.au
Scheduling Centre:
13 13 56
Engineering Services:
1.6
engineering.services@atcogas.com.au
Additional Information
Refer to the Related Documents section (page 63) for a list of standards and legislation
Refer to the Appendices section (page 67) for the printable forms, checklists and other
information
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 6 of 75
2.1
In the majority of new subdivisions a PLS or PLSS is installed in a common trench to the
boundary line of a property when the subdivision is constructed.
Figure 1 shows a plan from the AGA Gas Network Information System, (available through
DBYD) and an example of a new subdivision where gas mains have been installed in road
reserves, including rear laneways, to both typical flat lots and elevated lots. The PLS symbol
indicates the side of the lot where the service has been installed with one PLS normally
supplying two lots. The meter position must allow direct (straight) access to the PLS
ensuring no part of the gas service is covered by a future building structure, (e.g. a carport or
garage).
Please be aware that unless there are measurements shown on the DBYD plans,
the PLS or PLSS will be installed as shown in Figure 2 Standard Lot Service
Locations (Flat Lots) Plan View and Figure 5 Pre-Laid Gas Services Installed
Under Stairways.
Please ensure consideration is given when installing the meter box in a position
where it is possible to connect the gas service.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 7 of 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 8 of 75
2.2
Accessibility
Accessibility to gas meter boxes must be maintained for the provision of:
Emergency shut-off
Maintenance
Meter reading
Inspection
A minimum 600mm clearance must be maintained in front of the gas meter box at all times.
2.3
The typical PLS alignment method had the gas service installed beneath the retaining
wall and looped back to service alignment. This method is no longer approved for
use and will not be accepted.
The PLSS method has the gas service installed beneath the retaining wall stairs,
terminating at top of stairs. Refer to figures in section 3.2.5 Pre-Laid at Top of Stairs.
The rear laneway method has the gas service installed from the rear laneway to the
typical PLS alignment.
The Responsible Person should determine the PLS or PLSS location on the lot being
developed when determining the meter box position on a new dwelling.
The AGA will only connect to the PLS or PLSS (if installed) located inside the lot boundary
as per the PLS or PLSS design which was installed to that lot at development stage.
The Responsible Person must ascertain the PLS or PLSS location and ensure accessibility
for gas service pipe installation to the meter box position.
If a gas meter box is located in a position which may become inaccessible, then the AGA will
not approve the connection to proceed.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 9 of 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 10 of 75
3.1
The line of service between the gas meter box and the gas connection point is to be
considered, ensuring the route is free from hazards/obstructions and is straight.
It is important that gas meter boxes are installed in a location on or within 1m of the principal
frontage of a property.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 11 of 75
3.2
3.2.1
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 12 of 75
3.2.2
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 13 of 75
3.2.3
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 14 of 75
3.2.4
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 15 of 75
3.2.5
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 16 of 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 17 of 75
3.2.6
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 18 of 75
3.2.7
Carport
Figure 14 Carport
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 19 of 75
3.2.8
Residential
Commercial
Document No.:
Revision:
Issue Date:
Meter boxes are not permitted behind a perimeter fence. If a perimeter gate is to be
installed and locked, preventing access, position F is the only option available.
NCN RF08
6
15/04/2013
Page 20 of 75
3.2.9
Document No.:
Revision:
Issue Date:
A gas service line must not travel through any part of a pool enclosure. Should any
future works position the gas service inside the pool area, the Responsible Person
must complete an Alter Gas Meter/Service Position Request Form.
NCN RF08
6
15/04/2013
Page 21 of 75
The meter box must be located on the boundary line or as close as reasonably practical
to where gas is available up to a maximum distance of 1m from the boundary line
Meter box position must remain readily accessible for emergency and maintenance
purposes
Obstructions and site conditions are to be taken into account as the above may not be
applicable in all scenarios
A Green Title subdivided block must have direct access to a gas main via direct street
frontage. Access via an easement or across another property is not acceptable
For a strata property requiring a gas connection in or through common property, written
approval from the Strata Company (Body Corporate) is required
For a strata property requiring a gas connection in or through an adjoining lot (in the
same strata scheme), an appropriate easement must be available and approval from
the Strata Company (Body Corporate) is required
If a gas mains extension is required, it will only be installed within public dedicated roads
or public dedicated right-of-ways. Installations will not be permitted within private roads
or private or right-of-ways. As a general rule, gas mains will not be installed within
existing roads or right-of-ways less than 6.01m wide unless there is no alternative route
or means of obtaining safe access as determined at the discretion of the AGA.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 22 of 75
The AGA will not install a new gas service line which crosses through an adjoining lot in
order to provide a service to subdivided property. However in some circumstances the AGA
may, at its absolute discretion, determine that a new gas service line can be installed where
it crosses another property.
Examples of factors that may be taken into consideration by the AGA:
Written agreement has been obtained from all affected Responsible Persons in relation
to the location of the service line
In an existing strata scheme, written agreement has been obtained from all affected land
owners in relation to the location of the gas service line
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 23 of 75
3.3
3.3.1
A suitable straight and direct trench is to be provided from the boundary to the meter
location by the Responsible Person
The route shall, as far as practicable, be at right angles to the gas main or as directed by
the AGA
The bed of the trench shall be soil that is free from rock or other sharp formation that
may cause damage to the Polyethylene (PE) gas service pipe
NCN RF08
6
15/04/2013
Page 24 of 75
4.1
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 25 of 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 26 of 75
4.2
4.2.1
4.2.2
2.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 27 of 75
4.3
4.3.1
4.3.2
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 28 of 75
4.3.3
Figure 26 AL8 Dual Gas and Electric Meter Box (Partially Recessed)
4.3.4
Figure 27 AL12 Combined Gas and Electric Meter Box (Partially Recessed)
Dual Gas and Electric Meter Boxes Dimension A height is set by the relevant power
authority.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 29 of 75
4.3.5
Conforming Installation
(recess sealed from cavity)
Non-Conforming Installation
(other services installed)
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 30 of 75
4.4
4.4.1
Permanently fixing the window closed with a minimum of two (2) rivets or non-retractable
screws in three (3) sides of the openable window portion. There must be a minimum
quantity of six (6) permanent fixtures.
Note:
A signed approval must be granted by the AGA before proceeding with any meter
positions within 1m of altered building windows or openings. Approval of acceptable
window fixing is at the discretion of the AGA.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 31 of 75
4.5
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 32 of 75
4.6
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 33 of 75
As noted in section 9 of this document, due care and caution should be exercised by
anyone working on or in the vicinity of walls, pillars and other constructions. Safe work
instructions and procedures should be followed at all times.
You should conduct your own independent due diligence checks and verifications, and
obtain your own independent design advice from relevant competent engineering experts
and other professionals. This includes ensuring the stability, structural integrity, support,
durability, performance, drainage, safety, quality, adequacy, fitness for any purpose and
compliance with all relevant laws, standards and codes. It applies to all Responsible
Person constructions including any wall or pillar location, footings, foundations,
protections, materials and any equipment, fittings, wires, cabling, pipes, conduits or
apparatus (including any meter-box) to be used, applied or installed in relation to those
construction; and for maintenance, upkeep, repair, monitoring and checking on an
ongoing basis of any such constructions.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 34 of 75
4.6.1
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 35 of 75
Caution should be exercised when installing bollards near existing underground utilities.
Always call Dial Before You Dig (phone1100) prior to any excavation works
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 36 of 75
4.6.2
A 600mm minimum distance exclusion zone applies above ground to any part of the
gas installation
A 500mm minimum distance exclusion zone applies below ground to any part of the
gas service including the service riser
Non-Conforming Installation
(dome too close to gas meter box)
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 37 of 75
4.6.3
The top of the footing is a minimum of 400mm below ground level, allowing offset of the
service riser on top of the footing
Specific attention must be given to the line of a service installation passing close to load
bearing structures or piers that could compromise structural integrity.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 38 of 75
4.7
4.8
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 39 of 75
4.9
Regulators must be vented when locating a meter box in a position that would affect the
installations operation or where a gas discharge would constitute a hazard. Vent line to
be minimum DN15mm, but larger diameter may be required depending on length and
creating no flow restriction to relief discharge.
Vent line to terminate downward facing with appropriate mesh to required standards
Vent line outlet must be 1m from opening, 3m from mechanical air intake, 1m from
source of ignition
Vent line outlet must not terminate under any roof, portico or veranda
Vent line to be level with bottom corner of meter box for connection to regulator
Vent line outlet to be minimum of 2.1m above ground level and terminating in a safe
position
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 40 of 75
5.1
Provide information and plans for any known location of soak wells, reticulation pipes or
other services
Arrange any reinstatement inside the property line including associated costs
Provide signed consent for any excavation inside the property line required to complete
the gas connection (i.e. Notice of Acceptance or Gas Service Installation On Hold
Form)
Ensure line of service is free from hazards or obstructions (e.g. building material and
vegetation)
Ensure gas meter box is installed entirely within the property boundary for the property
requiring the gas connection, unless other written arrangements have been accepted by
the AGA
After the AGA gas service is installed, a gas meter assembly will be fitted with a security disc
in the meter outlet. The consumers gas fitter is responsible to commission (introduce gas
into) their supply piping downstream of the gas meter.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 41 of 75
5.1.1
Paving or driveway is installed under meter boxes and permission is required in order to
remove or lift paving
Click here to go to
full size form
5.1.2
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 42 of 75
5.2
5.3
A bedroom
Gas meter boxes must not be located closer than one (1) meter from a source of
ignition. Sources of ignition include electrical devices such as the external unit of a split
system air conditioner, pool pumps, external power points, etc.
In an unventilated position
On or in the ground
Where subject to physical damage unless the meter is adequately protected. The
definition of adequate protection shall be determined by the AGA in all instances
5.3.1
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 43 of 75
(xii) In a cavity wall, unless installed in an adequately ventilated enclosure and the cavity is
sealed.
(xiii) On the ground.
(xiv) On a floor which is frequently wetted.
(xv) On a floor which contains material which may corrode the service regulator.
5.3.2
The location of a service regulator shall provide ready and safe access for authorised
persons carrying out maintenance.
5.3.3
Constructed of masonry
On a fence, unless the fence is constructed of masonry (refer to section 5.3.2 above)
Note: Local council by-laws prohibit fixing meter boxes to a neighbouring boundary
fence
In a position where any part of the gas service to supply the meter box has to pass
under any part of a building (i.e. carport, garage, etc.)
Where excavation alongside an unsupported wall or structure will compromise that wall
or structure
Ensure that the gas meter box is installed within the property boundary for the property
requiring the gas connection, unless other arrangements have been accepted by the AGA in
writing.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 44 of 75
5.4
Retaining walls
Meter boxes must remain readily accessible (e.g. not behind fencing)
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 45 of 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 46 of 75
Each unit has a gas hot water system installed (confirmation in writing must be given in
the Open Trench Booking form before installation of the gas service)
Project plans must be provided by the Responsible Person and all high rise installations
must be subject to consultation, and when required, a AGA on-site assessment for meter
locations.
6.1
There must be a minimum of 10 days notice given before the planned date of
installation
The trench must be open for the time and date specified
The gas service installer will endeavour to attend site and complete the service within
the four (4) hour time frame stated on the Open Trench Booking form
The four (4) hour time frame can be scheduled during normal business hours (8am-4pm).
State at time of booking, any occupational safety and health requirements to be met onsite (i.e. inductions, permit to dig)
Note:
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 47 of 75
6.1.1
House Behind House Submit clear and legible building site plan (minimum size A4) dimensions to permanent landmarks or boundaries must be included
Multiple Unit Site (2-15 units) Submit clear and legible building site plan
(minimum size A3) - dimensions to permanent landmarks or boundaries must be
included
Multiple Unit Site (16+ units) Contact Engineering Services to confirm requirements
via email to engineering.services@atcogas.com.au
Note: The AGA requires that a licensed surveyor must complete a site survey in GDA
94 projection format. A digital copy of the survey with recorded survey points must be
forwarded to the AGAs Drawing Office via drawing.office@atcogas.com.au. Any
questions about specific requirements of the GDA 94 survey must be directed to
drawing.office@atcogas.com.au.
Plans must:
Confirm that meter boxes are a minimum of 1m away from an opening to a building
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 48 of 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 49 of 75
Figure 41 Example of Site Plan (showing gas service and meter box locations)
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 50 of 75
6.2
Trenches must be provided with sufficient width to ensure the required minimum
separation of all utilities (gas/power/water/telco) is maintained
OR
2.
Trenches must be of sufficient depth to allow all other utilities to be installed first,
allowing the gas to be installed above them and ensuring access is maintained for gas
main and emergency purposes
3.
In 1 and 2 above, all other utilities must be installed prior to installing the gas service thereby
ensuring the gas service will:
6.3
Provide the AGA unrestricted and unobstructed access to the gas infrastructure for
emergency and maintenance purposes for the lifetime of the asset
Excavation to be provided in a straight line at right angles to the box where possible or
directed by the AGA
Trench must be arranged to ensure that other utilities and services will not be laid or
installed on top of gas service
If no open trench is provided, the gas meter connection will be installed on the front
boundary line
Where finished ground level cannot be determined, the AGA reserves the right to
request survey pegs be installed to determine such levels
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 51 of 75
6.4
It is the Responsible Persons duty to backfill and compact the open trench with a
minimum of 300mm clean fill or sand
Ground level must not be altered to a degree that would render the gas service a nonconforming depth
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 52 of 75
6.5
Should any part of the open trench not conform to the outlined criteria, the AGA will
refuse to install the gas infrastructure until such time as the minimum standards are met
Should any part of the gas service not conform to the minimum standards after
installation, the AGA reserves the right to isolate the gas supply until provision has been
made to correct any defect(s)
Note:
The Responsible Person shall ensure gas services remain free from damage and
ground levels do not significantly alter to affect the depth of cover of gas services.
Figure 43 shows an instance where other services have been placed on top of the gas
service. This is not acceptable. The service layer will refuse to install the gas service if the
trench is not wide enough to adequately separate the adjacent utility services.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 53 of 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 54 of 75
7.1
Figure 45 AL8 Standard Meter Bank Layout Meter Boxes (Preferred) No Charge
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 55 of 75
Figure 46 AL8 Non Standard Meter Bank Layout Meter Boxes - Charged
Manifold connections for bank of meters in meter boxes are recommended when supply
pipework cannot maintain underground separation distances from service pipework.
These are non-standard connections. Connection charges apply to install a manifold
connection and will be quoted on a project-by-project basis by the AGA. The following criteria
apply:
Meters may be installed in gas meter boxes on outside walls (if protected from vehicular
traffic)
Gas meter boxes must be supplied and installed by the Responsible Person and
mounted in accordance with dimensions as shown in Figure 45 and Figure 46
Each lateral branch must be controlled by a valve (greater than three (3) gas meters)
In all meter bank and enclosures, unit numbers are to be indicated in or on each meter
box or bracket prior to the gas connection taking place
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 56 of 75
7.2
Approval for meter recess location will be subject to final assessment and
determination by the AGA.
The location of the recess must provide clear unhindered access to the gas meter set,
provision of natural light and ventilation to the enclosure, and prevent:
Unauthorised access
Vandalism
Be fully sealed and constructed of materials that are of at least 2 hours fire rating
Have a secure fire retardant material seal between any openings adjoining a meter room
attached to the main building, (which is of cavity wall construction)
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 57 of 75
Note:
NCN RF08
6
15/04/2013
Page 58 of 75
7.3
Document No.:
Revision:
Issue Date:
Where multiple meters are installed, the Responsible Person must clearly mark
each meter box or bracket with permanent marker to indicate unit being supplied
prior to the gas connection taking place.
NCN RF08
6
15/04/2013
Page 59 of 75
7.3.1
7.3.2
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 60 of 75
7.4
Ventilation openings located so that adequate ventilation is achieved in all parts of the
enclosure (i.e. from floor to roof level)
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 61 of 75
7.5
Floor Finishes
Floor finishes shall be of 15mm blue metal (minimum 100mm thick) over plastic sheeting,
except where the meter set is located in a position where the floor of the recess is part of the
building. In this case, the meter riser shall be installed in a manner that will provide future
access to the gas service riser pipework both above and below ground.
7.5.1
Security Access
All meter enclosures must have approved Western Australian Services (WAS) locks installed
for maintenance and emergency access. For more information refer to section 4.2.2
Mandatory Lock Requirements.
7.5.2
Signage
Recesses enclosed with doors must have appropriate signage on the outside to indicate gas
meters are located inside.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 62 of 75
Related Documents
The following standards and legislation must also be referred to when positioning gas meter
boxes:
Standards and Legislation
Gas Standards [Gas Fitting and Consumer Gas Installations] Regulations 1999
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 63 of 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 64 of 75
Disclaimer
1.
The diagrams provided in this document are not intended to be used as advice of any
kind or a design for any construction or other purpose and must not be used or relied
upon as such.
2.
3.
Diagrams provided in this document cannot be used to ensure the stability, structural
integrity, support, durability, performance, drainage, safety, quality, adequacy, fitness for
purpose or compliance with any law, standard or code of any wall, pillar or other
construction or its location, footings, foundations, protections, materials or any
equipment, fittings, wires, cabling, pipes, conduits or apparatus (including any meterbox) used, applied or installed in relation to any construction.
4.
Due care and caution should be exercised by anyone working on or near walls, pillars
and other constructions. Safe work instructions and procedures should be followed at all
times.
5.
6.
You should conduct your own independent due diligence checks and verifications and
obtain your own independent design and advice from relevant competent engineering
experts and other professionals (including to ensure the stability, structural integrity,
support, durability, performance, drainage, safety, quality, adequacy, fitness for any
purpose and compliance with all relevant laws, standards and codes) for your own
constructions (including for any wall or pillar), their location, footings, foundations,
protections, materials and any equipment, fittings, wires, cabling, pipes, conduits or
apparatus (including any meter-box) to be used, applied or installed in relation to those
constructions; and for the maintenance, upkeep, repair, monitoring and checking on an
ongoing basis of any such constructions.
7.
To the maximum extent allowed by law, ATCO Gas Australia, its related bodies
corporate and officers, employees, agents or contractors are not liable in any way
whatsoever (including for negligence, recklessness or breach of any statutory duty) for
any loss, liability, cost or claim of any kind whatsoever (including any direct loss, indirect
loss, consequential loss, economic loss, loss of profit, loss of opportunity, death, illness,
injury or damage to reputation or goodwill) arising from or in relation to the use of or
reliance on diagrams in this document.
8.
ATCO Gas Australia reserves the right at any time (without giving any notice) modify,
supplement or withdraw diagrams or any other part of this document.
9.
In this document, including means including, but not limited to. Reference to this
diagram includes any part of it (including any information or drawing in it).
10. ATCO Gas Australia owns the copyright in the diagram referred to as Figure 32 and
does not give any license to copy or reproduce this diagram.
11. This Important Notice may not be altered, omitted, hidden or removed, except by ATCO
Gas Australia.
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 65 of 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 66 of 75
Appendices
The Appendices contains printable forms, checklists and other information referred to
throughout this document.
List of Appendices
Gas Connection Checklist
Gas Service Installation On Hold Form
SafetyGram
Feedback Form
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 67 of 75
Document No.:
Revision:
Issue Date:
NCN RF08
6
15/04/2013
Page 68 of 75
Yes
Have you referred to the ATCO Gas Australia Meter Box Location Handbook?
Check to ensure that no reinstatement paving has been laid (i.e. driveway under
meter box)
Signature
Date
No
ON HOLD
An ATCO Gas Australia Service laying contractor visited this site to connect the new gas service
Date:
Address:
ATCO Gas Australia job Notification number:
This service line is to be connected to the gas pre-laid service (adjacent to the water meter).
Connected in a straight line out to the boundary.
The gas service must be installed before the driveway and cross over is installed.
The gas pre-laid service (PLSS) is under the stairs, terminating at the top of the stairs.
Your gas service installation from the street to the meter box has been put on HOLD because:
This is a Designated Area: The meter box must be installed on boundary or an open trench provided.
There are building materials etc. on the line of service.
Scaffolding is in the way.
The meter box is in non-complying position.
Meter box recessed too far.
Meter box set too high / Low.
Footings protrude too far and need to be cut out from under meter box.
Permission is required to remove paving under the meter box. (Please sign below)
Please note: it is the builders or owners responsibility to replace any paving under the meter box or
driveway that may have to be lifted. The section at the bottom of this form can be used to grant permission
to lift paving or break out concrete. Please sign and leave in meter box.
Other:
When the above conditions have been rectified, and to reschedule the gas service installation:
please contact this number
(Contractor mobile phone) between 8am and 4pm or the ATCO Gas
Australia Call Centre on 13 13 56 between 7am and 6pm and quote the address, job notification number and the
reason (on this form) that was given for the service being put on hold.
Note: One call plans may need to be re-applied for. Allow 7 to 10 days for the installation of the gas service from
the date of contact to re-schedule the gas service installation. Line of service route to remain free from obstruction
for this period.
Date (dd/mm/yyyy):
SafetyGram
DOs
Determine gas locations in verge or inside property (DBYD, meter box sticker)
Close windows and doors to prevent gas entering building if gas is smelled outside
DONTs
Feedback Form
Please complete this form with your feedback. Detail only ONE request/suggestion per form.
Publication Information
Title:
NCN RF 08
Meter Box Location Handbook
Revision:
Issue
Date:
Paragraph
No:
Yes
No
Description
of Change:
Reason for
Change:
Your Information
Name:
Phone:
(daytime)
Address:
Signature:
Date: