SPECIFICATION GUIDE

SafeRing/SafePlus up to 24kV
IEC standard equipment
Date: 18 July 2014

1VDD006134 GB rev. B 07/2014

Page 1 of 13

Content:
1

SCOPE OF SUPPLY-------------------------------------------------------------------------------------------------------------- 3

STANDARDS AND REFERENCE DOCUMENTS ------------------------------------------------------------------------ 3


2.1

DESIGN CRITERIA -------------------------------------------------------------------------------------------------------------- 3


3.1
3.2

SERVICE CONDITIONS --------------------------------------------------------------------------------------------------------- 3


GENERAL STRUCTURAL AND MECHANICAL CONSTRUCTION -------------------------------------------------------------- 3

TECHNICAL DATA-------------------------------------------------------------------------------------------------------------- 5
4.1
4.2
4.3

CODES AND STANDARDS ------------------------------------------------------------------------------------------------------ 3

RING MAIN UNIT, ELECTRICAL DATA --------------------------------------------------------------------------------------- 5


COMPACT SWITCHGEAR, ELECTRICAL DATA ------------------------------------------------------------------------------- 6
RING MAIN UNIT AND COMPACT SWITCHGEAR, TECHNICAL DATA ----------------------------------------------------- 7

PANEL (MODULE) DESCRIPTION ----------------------------------------------------------------------------------------- 9


5.1.1
5.1.2
5.1.3

Incoming cable module ---------------------------------------------------------------------------------------------- 9


The T-off fuse protection module ---------------------------------------------------------------------------------- 9
The T-off circuit breaker module (200 A) and circuit breaker module (630 A) -------------------------- 9

OTHER MAIN FEATURES --------------------------------------------------------------------------------------------------- 10


6.1
BUSBARS----------------------------------------------------------------------------------------------------------------------- 10
6.2
THE CABLE SWITCH ----------------------------------------------------------------------------------------------------------- 10
6.3
EARTHING SWITCH ----------------------------------------------------------------------------------------------------------- 10
6.4
THE T-OFF SWITCH ----------------------------------------------------------------------------------------------------------- 10
6.5
THE MECHANISMS ------------------------------------------------------------------------------------------------------------ 10
6.6
ELECTRICAL BUSHINGS ------------------------------------------------------------------------------------------------------ 11
6.7
MECHANICAL BUSHINGS ----------------------------------------------------------------------------------------------------- 11
6.8
FRONT COVERS ---------------------------------------------------------------------------------------------------------------- 11
6.9
POSITION INDICATORS-------------------------------------------------------------------------------------------------------- 11
6.10 VOLTAGE INDICATOR -------------------------------------------------------------------------------------------------------- 11
6.11 CABLE COMPARTMENT ------------------------------------------------------------------------------------------------------- 11
6.11.1 Power connection, --------------------------------------------------------------------------------------------------- 12
6.12 INTERLOCKING------------------------------------------------------------------------------------------------------------ 12
6.13 OPTIONAL EQUIPMENT ------------------------------------------------------------------------------------------------------- 12
6.13.1 Current Transformers ----------------------------------------------------------------------------------------------- 12
6.13.2 Voltage Transformers ----------------------------------------------------------------------------------------------- 12
6.13.3 Auxiliaries -------------------------------------------------------------------------------------------------------------- 12
6.13.4 Low voltage compartment ------------------------------------------------------------------------------------------ 13

TESTING AND CERTIFICATION ------------------------------------------------------------------------------------------ 13


7.1
7.2

TYPE TESTS ----------------------------------------------------------------------------------------------------------------- 13


ROUTINE TESTS ----------------------------------------------------------------------------------------------------------- 13

DOCUMENTATION ------------------------------------------------------------------------------------------------------------ 13

TRAINING------------------------------------------------------------------------------------------------------------------------- 13

1VDD006134 GB rev. B 07/2014

Page 2 of 13

1 SCOPE OF SUPPLY
This specification describes the general requirements governing the design of 12-24 kV Metal
Enclosed Indoor Ring Main Units (RMU) and Compact Switch Gear (CSG) fully type tested
according to IEC 62271-200 standard.
The design of the switchgear shall be exclusive and specific responsibility of supplier and shall
comply with current good engineering practice, the relevant codes and recommendation, the project
specific requirements.

2 STANDARDS AND REFERENCE DOCUMENTS


2.1 Codes and Standards
The electrical switchgears and the relevant equipment shall be designed, manufactured and tested
according to the latest version of:
IEC 62271-1 Common specifications for high-voltage switchgear and controlgear standards
IEC 62271-200 A.C. metal-enclosed switchgear and controlgear for rated voltages above 1kV and
up to and including 72 kV and the IEC Code herein referred
IEC 62271-102 Alternating current disconnectors (isolators) and earthing switches
IEC 60529
Classification of degrees of protection provided by enclosures
IEC 62271-103 High-voltage switches-Part 1: Switches for rated voltages above 1 kV and less than
52 kV
IEC 62271-100 Circuit breakers
IEC 62271-105 High-voltage alternating current switch-fuse combinations
IEC 60044
Current transformers
IEC 60044
Voltage transformers
IEC 60255
Electrical relays

Any other codes recognized in the country of origin of equipment might be considered
provided that they fully comply with IEC standards.
The design of the switchgear shall be based on safety to personnel and equipment during operation
and maintenance, reliability of service, ease of maintenance, mechanical protection of equipment,
interchangeability of equipment and ready addition of future loads.

3 DESIGN CRITERIA
3.1 Service conditions
The switchgear and controlgear shall be suitable for continuous operation under the basic service
conditions indicated below. Installation shall be in normal indoor conditions in accordance with IEC
62271-1
Ambient temperature
Relative humidity
Altitude of installation

3.2

-25 oC to +40 oC
up to 95%
up to 1000m, IEC 62271-1

General structural and mechanical construction

The RMU and CSG units shall be of the fully arc proof metal enclosed, free standing, floor mounting,

1VDD006134 GB rev. B 07/2014

Page 3 of 13

flush fronted type, consisting of modules assembled into one or more units. Each unit is made of a
cubicle sealed-for life with SF6 and contains all high voltage components sealed off from the
environment. If a system requires use of several units a separate extension of the busbar shall form
a system with a common busbar.
The overall design of the switchgear shall be such that front access only is required. It shall be possible
to erect the switchboard against a substation wall, with HV and LV cables being terminated and
accessible from the front.
The units shall be constructed from 2.5 mm thick stainless steel sheets. The design of the units shall
be such that no permanent or harmful distortion occurs either when being lifted by eyebolts or when
moved into position by rollers.
The cubicle has a pressure relief device. In the rare case of an internal arc, the high pressure caused
by the arc will release it, and the hot gases are allowed to be exhausted out at the bottom of the
cubicle. A controlled direction of flow of the hot gas is achieved.
The switchgear and controlgear should have the minimum degree of protection (in accordance with
IEC 60529)
- IP 67 for the tank with high voltage components
- IP 2X for the front covers of the mechanism
- IP 3X for the cable connection covers
The switchgear must have optional possibility to be extendable in either direction.
Module dimensions will be as follows;
Height : 1336 mm (max 1806 with low voltage compartment)
Width : 325/371 mm module/single module (696 for metering module)
Depth : 765 mm
Each unit shall be supplied with the operating handle.

1VDD006134 GB rev. B 07/2014

Page 4 of 13

4 TECHNICAL DATA
Technical data sheet

4.1

Ring Main Unit, Electrical data

Electrical data and service conditions


No Rated voltage
12
15
17,5
24
1
Power frequency withstand voltage
kV
28
38
38
50
Impulse withstand voltage
2
kV
95
95
95
125
3
Rated frequency
Hz
50/60
50/60
50/60
50/60
4
Rated current busbars
A
630
630
630
630
5
Rated current (cable switch)
A
630
630
630
630
1
1
1
6
Rated current (T-off)
A
200
200
200
2001
Breaking capacities:
7
Active load
A
630
630
630
630
8
Closed loop (cable switch)
A
630
630
630
630
9
Off load cable charging (cable switch) A
135
135
135
135
10 Off load transformer (T-off fuse)
A
20
20
20
20
11 Earth fault (cable switch)
A
200
150
150
150
12 Earth fault cable charging (cable
A
115
87
87
87
switch)
13 Short circuit breaking current (T-off
kA
21
21
16
16
circuit breaker)
14 Rated making capacity
kA
52,52
52,52
402
402
15 Rated making capacity (downstream kA
12,5
12,5
12,5
12,5
fuse module)
16 Rated short time current 3 sec.
kA
21
21
16
16
17 Rated short time current 1 sec. kA
5
5
5
5
(downstream fuse module)
Service conditions for indoor equipment according IEC 62271-1
Ambient temperature3
18 Maximum value
+ 40
+ 40
+ 40
+ 40
C
19 Maximum value of 24 hour mean
+ 35
+ 35
+ 35
+ 35
C
20 Minimum value
25
25
25
- 25
C
4
21 Altitude for erection above sea level m
...1000 ...1000 ...1000 ...100
0
22 Relative humidity of 24h mean
95%
95%
95%
95%
Table 4-1 RMU Electrical data and service conditions

1)
2)
3)
4)

T-off fuse module: depending on the current rating of the fuse


T-off fuse module: limited by High Voltage Fuse Links
De-rating allows for higher maximum temperature
For greater altitude, reduced gas pressure is required

1VDD006134 GB rev. B 07/2014

Page 5 of 13

4.2

Compact Switchgear, Electrical data

Electrical data and service conditions


No Rated voltage
12
15
17,5
5
1
Power frequency withstand voltage
kV
28
38
38
2
Impulse withstand voltage
kV
95
95
95
3
Rated frequency
Hz
50/60
50/60
50/60
4
Rated current busbars
A
630
630
630
5
Rated current external busbars
A
1250
1250
1250
6
Rated current (cable switch)
A
630
630
630
7
Rated current (T-off)
A
6301
6301
6301
8
Breaking capacities:
9
Active load
A
630
630
630
10 Closed loop (cable switch)
A
630
630
630
11 Off load cable charging
A
135
135
135
(cable switch)
12 Off load transformer (T-off fuse)
A
20
20
20
13 Earth fault (cable switch)
A
200
150
150
14 Earth fault cable charging (cable
A
115
87
87
switch)
15 Rated Making capacity (V-module)
kA
52,5
52,5
40
16 Short circuit breaking current (T-off kA
21
21
16
circuit breaker)
17 Short circuit breaking current (V20- kA
25
25
25
module)
18 Rated making capacity (V20-module) kA
62,5 2
62,52
62,52
19 Rated making capacity (circuit
kA
62,5
breaker)
20 Breaking capacity (circuit breaker)
kA
25
21 Rated making capacity (downstream kA
12,5
12,5
12,5
fuse module)
22 Rated short time current 1 sec. (cable kA
25
21
21
switch)
23 Rated short time current 3 sec. (cable kA
21
21
21
switch)
24 Rated short time current 3 sec. (circuit kA
25
breaker CB-module)
25 Rated short time current 3 sec. (circuit kA
21
21
16
breaker V-module)
26 Rated short time current 3 sec. (circuit kA
21
21
21
breaker V20-module)
27 Rated short time current 1 sec. (circuit kA
25
25
25
breaker V20-module)
28 Rated short time current 1 sec. (circuit kA
21
21
16
breaker V-module)
29 Rated short time current 1 sec. kA
5
5
5
(downstream fuse module)
30 Service conditions for indoor equipment according IEC 62271-1
31 Ambient temperature3

1VDD006134 GB rev. B 07/2014

24
50
125
50/60
630
1250
630
6301
630
630
135
20
150
87
40
16
20
502
50
20
12,5
21
21
20
16
21
21
16
5

Page 6 of 13

32
33
34
35
36

Maximum value
Maximum value of 24 hour mean
Minimum value
Altitude for erection above sea level4
Relative humidity of 24h mean

C
C
C
m

+ 40
+ 35
- 25
...1000
95%

+ 40
+ 35
- 25
...1000
95%

+ 40
+ 35
- 25
...1000
95%

+ 40
+ 35
- 25
...1000
95%

Table 4-2 CSG Electrical data and service conditions

1)
2)
3)
4)
5)

T-off fuse module: depending on the current rating of the fuse


T-off fuse module: limited by High Voltage Fuse Links
Derating allows for higher maximum temperature
For greater altitude, reduced gas pressure is required
42 kV available for GOST applications

4.3 Ring Main Unit and Compact Switchgear, Technical data


No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

16
17
18

19
20
21

General data, enclosure and dimensions


Standard to which Switchgear
IEC
complies
Type of Ring Main Unit
Metal Enclosed
Number of phases
3
Whether RMU is type tested
Yes
Pressure test on equipment tank
2.64 bar abs
or containers
Whether facility is provided with
Yes
pressure relief
Insulating gas
SF6
Nominal operating gas pressure
1.4 bar abs. 20 C
Gas leakage rate / annum
%
0,075
Expected operating lifetime
30 years
Whether facilities are provided
Option
for gas pressure monitoring
Material used in tank
Stainless steel sheet
construction
Busbars:
Cu 240 mm2
Earth bar (external):
Cu 100 mm2
Earth bar bolt dimension:
M10
Overall dimensions of the fully
Height
Depth
assembled Ring Main Unit
2-way unit
mm 1336
765
3-way unit
mm 1336
765
4-way unit
mm 1336
765
Compact switchgear: (2,3,4 way unit as RMU) with additional
optional low voltage compartment(470mm)
1-way unit
mm 1336
765
5-way unit
mm 1336
765
Distance between units when
7 mm
external extension is used

Width
696
1021
1346
height for
371
1671

Table 4-3 General data, enclosure and dimensions

1VDD006134 GB rev. B 07/2014

Page 7 of 13

No
1
2
3

4
5

6
7
8
9

10
11

12
13
14
15

16
17

Operations, degree of protection and colours


Means of switch operation
separate handle or
remote control
Means of fuse switch/circuit
separate handle and push
breaker operation
buttons
Rated operating sequence of
O 0,3 s CO - 15 s - CO
Circuit Breaker (CB-module)
Rated operating sequence of
O 0,3 s CO - 3 min - CO
Circuit Breaker (V-module)
Total opening time of Circuit
approx. 45 ms
Breaker
Closing time of Circuit Breaker
approx. 40 ms
Tripping time of Circuit breaker
approx.
100 ms
Mechanical operations of switch CO 1000
Mechanical
operations
of CO 1000
earthing switch
Mechanical operations of circuit CO 2000
breaker
Principle switch / earth switch
3 position combined switch /
earth switch
Load break switch:
Rated operations on short circuit
5
current (class E3)
Rated operations mainly active
100
load
Degree of protection:
High Voltage live parts, SF6 tank
IP 67
Front cover mechanism
IP 2X
Cable covers
IP 3X
Protection
class
of
fuse
IP 67
compartment
Standard Colour:
Front cover
RAL 7035
Side and cable cover
RAL 7035

Table 4-4 Operations, degree of protection and colours

1VDD006134 GB rev. B 07/2014

Page 8 of 13

No

1
2
3
4
5
6
7

9
10
11
12

Fuses, cable box and auxiliary equipment


Standard fuse length
mm 442 Shorter fuses with fuse adapter
Standard dimensions
according to DIN 43625
Maximum size 12 kV
A
125
Maximum size 24 kV
A
63
Cable box for heat shrinkable termination:
Phase to phase clearance
mm 107
Phase to earth clearance
mm 54,5
Phase to earth over insulator surface mm 120
(creepage)
Type of cable termination adapters
Angle(elbow)
Whether facility is provided for
Yes
cable testing
Auxiliary equipment:
Short circuit indication
Option
Earth fault indication
Option
Auxiliary contact switch / earth /circuit Option
breaker position
Voltage indication
YES

Table 4-5 Fuses, cable box and auxiliary equipment

5 PANEL (MODULE) DESCRIPTION


5.1.1 Incoming cable module
It shall consist of an SF6 cubicle housing a switch disconnector and an earthing switch. Busbars and
all electrical connections are located inside the tank. The operating shafts for the switches shall have
rotary seals where they enter the SF6 cubicle. The operating mechanisms shall be located outside on
the front of the SF6 tank. Cable bushings of type interface C shall be located on the front of the SF6
cubicle in a separate cable compartment. Front covers containing the mimic diagram and having a
degree of protection IP2XC close the fronts.
5.1.2 The T-off fuse protection module
It shall consist of an SF6 cubicle housing a position switch-fuse combination and earthing switch. The
earthing switch shall be both upstream and downstream of the fuses and operated at the same time.
The fuses are separately located in sealed fuse canisters. Busbars and all electrical connections are
located inside the tank. The operating shafts for the switching devices shall have rotary seals where
they enter the SF6 cubicle. The operating mechanisms shall be located outside on the front of the
SF6 tank. Cable bushings interface A shall be located on the front of the SF6 cubicle in a separate
cable compartment. Front covers containing the mimic diagram and having a degree of protection
IP2XC close the fronts.
5.1.3 The T-off circuit breaker module (200 A) and circuit breaker module (630 A)
The T-off circuit breaker module shall consist of an SF6 cubicle housing a circuit breaker unit and a
disconnector-earthing switch. An integrated relay and related CTs is used for tripping of the circuit
breaker. Bus bars and all electrical connections are located inside the tank. The operating shafts for
the switches shall have rotary seals where they enter the SF6 cubicle. The operating mechanisms are
located outside on the front of the SF6 tank. Cable bushings interfaces are located on the front of the
SF6 cubicle in a separate cable compartment. Front covers containing the mimic diagram having a
degree of protection IP2XC seal off the fronts.

1VDD006134 GB rev. B 07/2014

Page 9 of 13

Circuit breaker T-offs use vacuum bottles as interrupters of the currents. The circuit breaker main
circuit is connected in series with a three-position disconnector-earthing switch, which has no
interrupting capacity. The operation between circuit breaker and disconnector-earthing is interlocked.

6 OTHER MAIN FEATURES


6.1 Busbars
Comprising the 3 single phases copper busbars and the connections to the switch or circuit
breaker. The busbar shall be integrated in the cubicle or made available for external
connection via a system with interface C.
Busbars shall be rated to withstand all dynamic and thermal stresses for the full length of the
switchgear.
6.2

The cable switch

It shall be a switch-disconnector and earthing switch using SF6 gas as an arc-quenching medium.
The switch positions are closed open earthed. In the open position the switch satisfies the
disconnector requirements.

6.3

Earthing Switch

Earthing switches shall be rated equal to the switchgear rating.


Earthing switches shall be quick make type.
Earthing switch shall be operated from the front of the cubicle by means of a removable handle.

6.4 The T-off switch


It shall be identical to the cable switch. By means of the fuse-tripping device it is operating as a switchfuse combination. There is a double earthing switch, which in the earthed position gives earth to both
sides of the fuses simultaneously. Both earthing switches are operated in one operation. The T-off
switch and earthing switch is interlocked to prevent hazardous access to the fuses.

6.5 The mechanisms


All mechanisms shall be situated in the mechanism compartment behind the front covers outside the
SF6-tank.
The mechanism for the switch and the earthing switch is operating both switches via one common
shaft. The mechanism provide independent manual operation for closing and opening of the switch,
independent closing of the earthing switch and dependent opening of the earthing switch.
The mechanism for the T-off switch and earthing switch is operating both switches via one common
shaft. The mechanism has stored spring energy and provide independent manual operation for closing
and opening of the switch, independent closing of the earthing switch and dependent opening of the
earthing switch. The mechanism has fuse tripping device.
The mechanism for the vacuum circuit breaker (VCB) and disconnector-earthing switch is operating
the VCB and the disconnector-earthing switch via to separate shafts. The mechanism for the VCB has
stored spring energy and provides independent manual operation for closing and opening of the VCB.
1VDD006134 GB rev. B 07/2014

Page 10 of 13

The mechanism has a relay with related CTs and/or remote tripping device. The mechanism for the
disconnector-earthing switch provide independent manual operation for closing and opening of the
disconnector, independent closing of the earthing switch and dependent opening of the earthing
switch.

6.6

Electrical bushings

The bushing for the incoming modules shall be made according to the interface C. The bushings for
the transformer connection shall be made according to the interface A. The bushings are made of cast
resin with molded electrical conductor in the center. In addition, a screen is moulded into the bushing.
This screen acts as the main capacitor supplying the voltage indicators. The bushings are sealed by
O-rings and fixed to the cubicle by a common supporting bracket.

6.7 Mechanical bushings


The mechanical bushings are the interface between the switches inside the cubicle, and the
mechanisms outside.
The mechanical bushing has a rotating shaft, which is connected to the shaft of the switch and to the
corresponding shaft of the mechanism.
The rotating shaft is sealed by a double set of radial simmering gas seals type BABSL 35-47-7. Orings type EPDM 65 x 5 provide the fixed sealing.

6.8 Front covers


The front cover contains the mimic diagram of the main circuit with the position indicators for the
switching devices. The voltage indicators are situated on the front panels. Access to the cable
bushings is in the lower part of each module.

6.9

Position indicators

The position indicators are visible through the front cover and are directly linked to the operating shaft
of the switching devices.

6.10 Voltage indicator


The voltage indicators are situated on the front cover, one for each module, and indicate the voltage
condition of each incoming cable. Identification of the phases is achieved with labels L1, L2 and L3
on the front of the voltage indicators. The voltage indicator satisfies the requirements of IEC61243-5.

6.11 Cable compartment


It shall be possible to terminate up to a maximum of two single core HV cables per phase.
The access to the compartment will be possible by removing the cable cover, bolted to the main frame.
Removable steel covers close the cable compartments. Arc proof cable covers shall be available as
option. Each module has a separate cable compartment that is segregated from each other by means
of a partition wall. A partition wall shall be fitted to divide the cable compartment from the rear side of
the switchgear. In case of an arc inside the tank, followed by the opening of the pressure relief, the
partition wall prevents the hot gases flowing out from the pressure relief to enter the cable
compartments. All covers are removable. The ground continuity is achieved when the covers are in
place by means of bolted connections.

1VDD006134 GB rev. B 07/2014

Page 11 of 13

6.11.1 Power connection,


The cables are installed in the dedicated compartment below the mimic front cover. The medium
voltage cables are connected to the unit through electrical bushings, interface C for the incoming
function and interface A for the transformer connection. The cable bushings shall be according to EN
50180 / 50181.
The bushings shall be fitted with a capacitor of approx 15 pF. This capacitor is the primary capacitor
used in the capacitive voltage divider, which is part of the permanent voltage indicator.
At the bottom of the cable compartment, an earthing bar system made of copper with a minimum cross
section of 100 mm2 shall be fitted. In each compartment the earthing bar shall be fitted with 4 screws
M10. The earthing system is connected to the tank by rear partition wall.

6.12 INTERLOCKING
The mechanism for the cable switch shall provide a built in interlocking system to prevent operation
of the switch when the earthing switch is closed, and to prevent operation of the earthing switch when
the switch is in the closed position.
The mechanism for the T-off switch shall provide a built in interlocking system to prevent operation of
the switch when the earthing switch is closed, and to prevent operation of the earthing switch when
the switch is in the closed position. In addition an interlocking device allows access to the fuses only
when the earthing switch is in the earthed position and opening of the earthing switch is only possible
when the fuse cover is closed and secured.
The mechanism for the VCB and the disconnector-earthing switch shall have a built in interlocking
system to prevent operation of the disconnector-earthing switch when the VCB is in the closed
position.

6.13 Optional equipment


6.13.1 Current Transformers
All current transformers shall comply with IEC 60044-1.
Current transformers shall be of dry type, with ratings and ratios as required.
Cable current transformers used in circuit breaker modules shall be maximum 100mm wide.
Current transformers used in metering cubicles shall have dimensions according to DIN 42600,
Narrow type.

6.13.2 Voltage Transformers


All voltage transformers shall comply with IEC 60044-2.
Voltage transformers shall be of dry type, with ratings and ratios as required.
Voltage transformers used in metering cubicles shall have dimensions according to DIN 42600,
Narrow type.
6.13.3 Auxiliaries
The switchgear shall be prepared for options like motor operation, auxiliary contacts and short-circuit
indicators. Necessary terminal blocks and wiring etc. shall be placed behind the front cover of each
module.

1VDD006134 GB rev. B 07/2014

Page 12 of 13

6.13.4 Low voltage compartment


Further additional low voltage equipment shall normally be contained in the low voltage compartment.
In particular:
Terminal blocks and wiring for interconnections between units connecting the auxiliary cables,
instruments, protection relay, metering devices, fuses etc.

7 TESTING AND CERTIFICATION


7.1

TYPE TESTS

Units shall be type tested in accordance with IEC standards 62271-100, 62271-102, 62271-103,
62271-200, 62271-105, IEC 62271-1, and 60529. The following type tests have been performed and
available if required
- Short time and peak withstand current test
- Temperature rise tests
- Dielectric tests
- Test of apparatus i.e. circuit breaker and earthing switch
- Arc fault test

7.2 ROUTINE TESTS


Routine tests shall be carried out in accordance with IEC 62271-200 standards. These tests shall
ensure the reliability of the unit.
Below listed test shall be performed as routine tests before the delivery of units;
- Withstand voltage at power frequency
- Measurement of the resistance of the main circuit
- Gas leakage test
- Withstand voltage on the auxiliary circuits
- Operation of functional locks, interlocks, signalling devices and auxiliary devices
- Suitability and correct operation of protections, control instruments and electrical connections
of the circuit breaker operating mechanism
- Verification of wiring
- Visual inspection

8 DOCUMENTATION
An instruction manual shall be provided with necessary information for receiving, handling, storage,
installation, operation and maintenance.
Routine test certificate shall follow each unit, and standard schematic drawings shall be delivered for
Ring Main Units. Compact Switchgear shall have drawings that consist of system single line drawings,
general arrangement and schematic drawings for order specific units.

TRAINING

Installation of the switchgear shall require no special tools. Optional product training shall be available
at the manufacturers facility.

1VDD006134 GB rev. B 07/2014

Page 13 of 13