You are on page 1of 24

MNS Low Voltage Switchgear

Safety Aspects

proactive value

innovative value

resourceful value

activate value

adaptable value

intelligent value

communicative value

ABB
MNS is a registered trademark of ABB Schaltanlagentechnik GmbH.

ABB assumes no responsibility for any errors that may appear in this document. In no event shall ABB be liable for direct,
indirect, special, incidental, or consequential damages of any nature or kind arising from the use of this document, nor
shall ABB be liable for incidental or consequential damages arising from use of any software or hardware described in this
document.
This document and parts thereof must not be reproduced or copied without ABB's written permission, and the contents
thereof must not be imparted to a third party nor be used for any unauthorized purpose. The software described in this
document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such
license.

All rights reserved.

Copyright 2006 © ABB Automation Products GmbH Ladenburg, Germany


MNS Low Voltage Switchgear
Safety Aspects

This compilation of Safety Aspects applies to the MNS family


of switchgear, from the industry standard conventional, to the
latest innovative design offered by MNS iS.

Explanatory technical information as well as lists of technical


data on the above products can be obtained from the follow-
ing documents:

MNS System Guide


publication no. 1TGC902030B0201

MNS iS System Guide


publication no. 1TGC910001B0203
Content

Content

Proven Safety “Plus” for Operators and Plant.....................6

Type Tested Switchgear Assembly


– Operators Advantage..........................................................8

Arc Fault Protection.............................................................10

Degrees of Protection provided


by enclosures (IP Code) . ....................................................16

Internal Separation . ............................................................18 

Earthquake, Vibration and Shock ......................................20

Neutral conductor dimensioning ........................................21


Safety "Plus"

Proven Safety “Plus” for Operators and Plant

Basic safety philosophy realized with MNS design

■ Universal rule to achieve a high safety level: The fulfillment of all instructions of IEC 60439-1
High protection of persons without com- assures a basic level for Personnel Protection
promise to the protection of the system and System Protection. ABB goes beyond this
standard in cases where a high degree of
■ Protection classification into 2 priorities: exposure is anticipated, or specific risks (e.g.
earthquake risk) have to be observed.
Priority 1:
Active Protection Thereby it was possible to reach an operational
The occurrence of a failure is avoided. availability of the installed MNS boards world-
wide of nearly 100%.
Priority 2: As illustrated in the schematic, additional meas-
Passive Protection ures are foreseen in these cases so that an
If a failure should occur it is limited to its even higher level of safety is reached to with-
place of occurrence, damage due to an arc stand the particular risks. This is guaranteed
is minimized e.g. by the use of optimized material or specific
constructions.

Switchboard MNS
safety level

IEC 60439-1

Level of Application
Safety "Plus"

Example: Development of the standards and tests concerning resistance to internal arcs

ABB can rely on its experience with approximately 400 internal arcing tests carried out to-date.
As early as 1979, ABB already performed the first internal arcing tests on MNS, which at that
time were still based on the medium-voltage standards VDE 0670 and IEC 60298 as well as
the PEHLA standards. Of central importance was pure personnel protection.

The first international standard regarding the performance of internal arcing tests in low-voltage
switchgear systems was published in 1996 (IEC 61641 - VDE 0660 Part 500, additional
sheet 2). The aim was to detect the effects of a possible internal arc on the safety of the
operating personnel. As early as 1979, ABB adopted internal testing regulations for internal
arcing tests which also referred to plant safety.


Type Tested Switchgear

Type Tested Switchgear Assembly – Operators Advantage

IEC 60439-1 classifies tests which verify the characteristics of an assembly into:
■ type tests (acc. paragraphs 8.1.1 and 8.2)

■ routine tests (acc. paragraphs 8.1.2 and 8.3).

Type tests

8.1.1 Type tests (see 8.2)


Type tests are intended to verify compliance with the requirements laid down in this standard
for a given type of ASSEMBLY.
Type tests will be carried out on a sample of such an ASSEMBLY or on such parts of
ASSEMBLIES manufactured to the same or a similar design.
They shall be carried out on the initiative of the manufacturer.

The MNS low-voltage switchgear system is tests are applicable to the various low-voltage
subjected to extensive type tests in compliance switchgear and control gear assemblies (TTA)
with the standards in order to ensure the high- (in accordance with IEC 60439-1; DIN EN
est possible degree of safety. 60439-1 / VDE 0660 Part 500).
These tests are based on the most critical rep- The safety level of the standard as well as a
resentative applications of the entire product or homogeneous quality are ensured in the way
performance range of the switchgear with re­­ that the corresponding design documents and
spect to the test standard. The results of these manufacturing instructions are strictly followed.


Type tests (related section of IEC 60439-1) Safety profit for operator and plant

Verification of temperature-rise limits (8.2.1) Extended life cycle of the switchboard and equipment.
Prevention of fire risks.

Verification of the dielectric properties (8.2.2) Avoidance of damage caused by over-voltage.


Verification of the short-circuit withstand strength (8.2.3) External influences can cause a short circuit.
The switchboard arrangement can withstand the mechanical
force of the short circuit. Limits the short circuit to the place
of initiation. Prevention of fire risks.

Verification of the effectiveness of the protective circuit Avoidance of fatal voltage at exposed conductive parts.
(8.2.4) Protection of personnel in case non current carrying parts
accidentally become live.

Verification of clearances and creepage distances (8.2.5) Environment influences can reduce the isolation quality (e.g.
polluted area). MNS can be used in severe atmosphere.

Verification of mechanical operation (8.2.6) Extended lifetime for moving components and equipments.
MNS far exceeds the standard requirements

Verification of the degree of protection (8.2.7) Protection against live parts. Protection against penetration
of liquid and solid elements. Ensures safe operation.
Type Tested Switchgear

Routine tests during production of MNS switchboards

8.1.2 Routine tests (see 8.3)


Routine tests are intended to detect faults in materials and workmanship. They are carried
out on every new ASSEMBLY after it has been assembled or on each transport unit. Another
routine test at the place of installation is not required.

8.3 Routine tests


8.3.1 Inspection of the ASSEMBLY including inspection of wiring and, if necessary, electrical
operation test.

8.3.2 Dielectric test


8.3.2.1 General
All electrical equipment of the ASSEMBLY shall be connected for the test, except those appa-
ratus which, according to the relevant specifications, are designed for a lower test voltage.

8.3.2.2 Application, duration and value of test voltage


a) The test voltage according to 8.2.2.4 shall be applied for 1 s.
b) The tests shall be made in accordance with 8.2.2.6.2 and 8.2.2.6.3.

8.3.2.3 Results to be obtained


Routine tests carried out consequently in the
factory ensure the quality of material and manu-
facturing. Guidelines like inspection instruction
and workshop checklist take into consideration
all relevant mechanical and electrical points.

Routine tests (related section of IEC 60439-1) Safety profit for operator and plant

Inspection of wiring and, if necessary, electrical operation Dielectric test or verification of insulation resistance.
test (8.3.1)

Dielectric test (8.3.2) The test is considered to have been passed if there
is no puncture or flashover.

Checking of protective measures and the electrical Assures protection against direct and indirect contact with
continuity of the protective circuits (8.3.3) live parts.
Arc Fault Protection

Arc Fault Protection

IEC 61641 Guide for testing under conditions of arcing due to internal fault:

This technical report applies to enclosed low-voltage switchgear and controlgear assem-
blies manufactured according to IEC 60439-1. This test is subject to an agreement
between manufacturer and user. It is not considered to be a type test.

The sole purpose of this test is to assess the ability to the assembly to limit the risk of
personal injury resulting from an internal arcing fault. It is intended to amend IEC 61641 to
cover plant protection, too. Currently only VDE 0660 part 500 (draft 2001 March) supple-
mentary sheet 2, already gives a testing guideline to limit the risk of a damage of the plant.

Despite the ever growing experience of the The resistance to internal arcs refers to two
manufacturers and operators of switchgear different aspects:
and control gear systems, there is some
residual risk of internal arc generation. ■ Personnel safety for the operator and
maintenance personnel
Internal arcs may be the result of: ■ Plant safety in order to limit the damage
■ external influences, e.g., tools forgotten within the system and to quench the internal
inside the system, or any remaining material arc within specific areas and functional
residues after maintenance or conversion compartments.
work.
■ conductive deposits on isolating supporting
10 elements under unfavorable environmental
conditions.

If the gases and decomposition products resul-


ting from the faults described are capable of
bridging the gap between two neighboring
phases, an arc will be fired with current intensi-
ties of several thousand amperes and tempera-
tures up to 10,000°C. These conditions will
result in a strong pressure build up inside the
switchgear.

Priorities for the arc fault protection in MNS

Priority 1 Priority 2
Active protection in MNS Passive protection in MNS
The basic ABB MNS principle is that an arc fault should be Limiting of the arc to the compartment where it occurs. This
prevented from occurring in the first place by designing and minimizes the consequences of an arc if it should occur.
dimensioning the equipment absolute reliable.
Arc Fault Protection

Constructional measures to achieve optimized active


and passive arc fault protection:

Subject IEC Specific solution in MNS assuring


high protection for Personnel and
System
Compartments for IEC 60439-1 Paragraph 7.7 Common compartment for the main
■ Busbars ■ Forms of internal separation and busbars system. A separate com-
■ Distribution bars Annex D, Figure D.1 partment for the distribution bars
■ Functional units ■ No separation between busbars embedded in the MNS MFW (Multi
and distribution bars is required Function Wall), single phase isolation
of distribution bars.
Busbars: Busbars are to be protected by The minimum degree of protection for
If forms of separation internal separation: internal separation is IP20
are required: The required degree of protection
■ Protection against shall be at least IP2X (or alternatively Option for maximum protection:
contact with IPXXB). The busbars are fully single phase
hazardous parts. insulated
■ Protection against Note:
the passage of solid IEC 60439-1 paragraph 7.7 Forms of
foreign bodies internal separation IP2X covers IPXXB

Main busbar
compartment

Distribution bar
compartment with
11
multifunction wall

Short circuit
protected
fault free zone

Gas sealed connections

Busbar The IEC 60439-1 does not give Maintenance free design by thread
■ fastening requirements in terms of maintenance locking screws and conical spring
■ connections and sealing of busbar fastening and washers.
connections Gas sealed connection between:
■ busbars and distribution bars

■ busbars and bars of other

functional units
Main contact system The IEC 60439-1 does Single phase isolated contacts.
not give requirements in terms of The contact housing gives a single
■ Single phase encapsulation phase casing prior to connection of
■ Main contact design the contacts
Arc Fault Protection

Constructional measures to achieve optimized active


and passive arc fault protection:

Subject IEC Specific solution in MNS assuring


high protection for Personnel and
System
Fault Free Zone IEC 60439-1 Fault free zone is provided by the
Paragraph 7.5.5.3 Multi Function Wall (MFW) and short
Selection and installation of non- circuit protected cable. Guarantees
protected active conductors (before higher safety between main busbars
the SCPD) to reduce the possibility and SCPD.
of short circuits

Main busbars

Distribution bar ”Fault free zone“


compartment Special requirements
to conductors and insulation

SCPD

12

Definition fault free zone:

The term fault free zone is used to describe the section within the cubicle consisting of the distribution
bars, the main contact, and the supply side of the functional unit being the connection to the SCPD.
According to IEC 60439-1 paragraph 7.5.5.3: "under normal operating conditions an internal short-
circuit between phases and/or earth is only a remote possibility".

This allows manufacturers to reduce the short-circuit strength for the components including the dis-
tribution bars to the load connection terminals of each functional device, to the value of the reduced
short circuit stress present on the load side of the SCPD.
Arc Fault Protection

Subject IEC Specific solution in MNS assuring


high protection for Personnel and
System
■ Comparative IEC 60439-1 MNS Standard: Material
Tracking Index CTI Paragraph 7.1.2.3.5 a) Group II = CTI value 400-600
■ Material groups for Minimum required:
Insulation purpose Material Group IIIb = CTI
value 100 –175

Clearances IEC 60439-1 Paragraph 7.1.2 Minimum clearance in MNS is


■ between busbars and table 14 20 mm.
■ between distribution

bars at a Rated Required clearance:


Impulse Withstand 14 mm minimum
Voltage (Uimp) 12 kV
Creepage distances IEC 60439-1 Paragraph Creepage distances in MNS main
between busbars 7.1.2 and table 16: busbar system are 30 mm.

Required distance minimum 14 mm


at Rated Insulation Voltage = 1000 V
Creepage distances IEC 60439-1 Paragraph Creepage distances in MNS
between distribution 7.1.2 and table 16: distribution bar system are 20 mm.
bars Required distance minimum 14 mm
at Rated Insulation Voltage = 1000 V

13
Clearance
Creepage distance

Conductor Conductor

Insulation material
Arc Fault Protection

Test criteria arc fault withstand

IEC 61641
Test criterion 1-5 for personnel protection:
Criterion
No.
1 whether correctly secured doors, covers, etc., do not open.
2 whether parts (of the assembly), which may cause a hazard, do not fly off.
3 whether arcing does not cause holes to develop in the freely accessible external
parts of the enclosure as a result of paint or stickers burning or other effects.
4 whether the indicators arranged vertically do not ignite (indicators ignited as a
result of paint or stickers burning are excluded from this assessment).
5 whether the equipotential bonding arrangement for accessible parts of the
enclosure is still effective.

VDE0660 part 500 (draft 2001 march supplementary sheet 2)


Test criteria for plant protection including system function protection
6 the arc must be limited to the defined area and must not re-ignite in the adjacent
areas.
7 an emergency operation of the switchgear and control gear assembly must be
possible when the fault has been repaired and/or the functional units of the
defined area have been isolated or removed. This requirement must be evidenced
by an insulation test carried out at 1.5 times the rated operating voltage for 1 min.
14

Test execution and results for MNS Note from IEC 61641 about the duration of the
The required values are selected for the equip- tests:
ment, which must be able to withstand the When the assembly is intended to be fed from
rated short circuit current for 0.3 s to the point a transformer, the permissible arc duration of
of fault arc ignition. the incoming switching device should in general
be 0.3 s to allow the operation of the high-volt-
Results for MNS: age protective equipment.
■ Test criterion 1-5 for personnel protection
is fulfilled
■ Test criterion 6-7 for system protection is
fulfilled
Arc Fault Protection

Points of arc fault ignition:


e

c
b

Note:
Arc fault test at ignition point b) and c) is not required
as they are located in the fault free zone. Refer to
IEC 60439-1 Clause 7.5.5.3. However MNS is fully
tested to meet this criteria.

Ignition point a ACB within adjusted tripping time. (less than 300 ms) of the
Outgoing side of the SCPD of the withdrawable module ACB. The fault arc is automatically extinguishing. The
(fuse or MCCB short circuit limiting breaker). The power is damage is kept on a low level.
switched off within the breaking time of the SCPD of 300 ms. Case d2)
In tests the time was between 2 -10 ms. The arc is self The fault arc is not limited by the ACB. The fault arc ignited
extinguishing. The switchboard remains in operation. on the incoming side (not protected side) of the ACB The 15
fault arc is inhibited to move to the outgoing side (protected
Ignition point b side) of the ACB. The components resist the fault arc at
Incoming side of the SCPD of the withdrawable module a duration of 300 ms. The current is switched off by the
(short circuit current not limited by the SCPD). The compo- test setup after 300 ms. The fault arc is automatically extin-
nents are tested to resist an arc fault duration of 300 ms. guishing.
The fault arc extinguishes automatically.
Ignition point e
Ignition point c Main busbars.
Distribution bars embedded in the Multi Function Wall.
The components are tested to resist an arc fault duration of Case e1)
300 ms. The fault arc extinguishes automatically. Fully insulated busbars, no root point: it is not possible to
ignite an arc fault
Ignition point d Case e2)
Incomer cubicle - before the ACB During this test the tripping device in the incomer cubicle is
The time for the duration of the fault arc is limited by the mechanical prevented to trip.
“test set up” (source) to 300 ms. To reduce damage, MNS The fault arc runs to the end of the busbars. The power
is designed as follows: switches off after max 300 ms. The fault arc extinguishes
automatically at the end of the switchgear.
Case d1) Case e3)
Type tests have confirmed following philosophy: During this test the ACB in the incomer cubicle is limiting
There is no fault arc barrier between the incoming and out- the short circuit current. The current is fast switched off by
going contacts of the ACB. the ACB within the adjusted tripping time of the ACB in less
An fault arc ignited on the incoming side (not protected than 300 ms. The fault arc is automatically extinguishing.
side) of the ACB moves to the outgoing side (protected The damage is kept on a low level.
side) of the ACB. The current is fast switched off by the
Degrees of Protection

Degrees of Protection provided by enclosures (IP Code)

The degree of protection provided by any assembly against contact with live parts, ingress of
solid foreign bodies and liquid is indicated by the designation IP... according to IEC 60529
(IEC 60439-1 Paragraph 7.2.1.1).
The degree of protection is also a criteria for type tests (IEC 60439-1 paragraph 8.2.7.). It is
subject to agreement between the manufacturer and user (IEC 60439-1 Annex E).

Definitions
Degrees of protection provided by enclosures 2. Protection of the equipment inside the enclo-
of electrical equipment in accordance with sure against ingress of solid foreign objects;
IEC 60529: 3. Protection of the equipment inside the enclo-
1. Protection of persons against access to sure against harmful effects due to the
hazardous parts inside the enclosure; ingress of water.

Designation for the degrees of protection:

IP 3 1 D

Code letters Additional letter


”International Protection” (optional)

1st characteristic numeral: 2nd characteristic numeral:


Protection against penetration by foreign Protection against ingress of water with
bodies and dust harmful effects

16
Remark
Where a characteristic numeral is not required to be specified,
it shall be replaced by the letter “X” (“XX” if both numerals are
omitted).

MNS – Available standard degrees of protection


As MNS is designed for indoor applications, no IP degrees covering water jetting and total water
immersion are foreseen.

Ventilated Non-ventilated
Ventilation grids in: Doors, covers and roof plate Sealed; no ventilation openings

IP30 IP40

IP31 IP41

IP32 IP42

IP54
Maximum heat dissipation Low heat dissipation
(by air convection) (heat emission via enclosure only)
Degrees of Protection

Protection of equipment Protection of persons

First characteristic numeral Protection against ingress of Protection against access


solid foreign objects to hazardous parts with:
2 ≥ 12.5 mm Diameter Finger
12,5

3 ≥ 2.5 mm Diameter Tool

4 ≥ 1.0 mm Diameter Wire

5 dust-protected Wire

Second characteristic Protection against ingress of


numeral water with harmful effects
0 No Protection

1 Water vertically dripping (e. g.


condensation water)

2 Water vertical dripping. The enclosure


is tilted at any angle up to 15" on
17
either side of the vertical
3 Water sprayed at an angle up to
60° on either side of the vertical

4 Water splashed against the
enclosure from any direction

Additional Letter (Optional) Protection against access
to hazardous parts with:
A Back of the hand
≥ 50 mm diameter

B Finger / Tool
≥ 12.5 mm diameter,
80 mm length

C Tool / Wire
≥ 2.5 mm diameter,
100 mm length

D Tool / Wire
≥ 1.0 mm diameter,
100 mm length
Internal Separation

Internal Separation

The internal separation is subject to agreement between the manufacturer and user
(IEC 60439-1 Annex E 7.7 Internal separation of assemblies by barriers or partitions).
Assemblies are divided by means of partitions or barriers (metallic or non-metallic) into separate
compartments or enclosed protected spaces.

Aim: Whenever access to a functional unit is Solution: The internal separation increases the
required (for extensions or maintenance), it safety for the personnel and the plant.
should be possible without de-energizing the Protection against direct contact can be
entire Low Voltage assembly. obtained by appropriate constructional meas-
ures on the assembly itself. The risk to cause
an internal arc failure is minimized.

Forms of separation

Form 1 Form 2b Form 4a Form 3b Form 4b

No separation Terminals not in the same


compartment as associated unit:
Form 4b
Separation

Separation of terminals for external conductors


Internal

18 from the functional units: Forms 3b, 4b


Separation of all functional units from another: Forms 4a, 3b, 4b
Separation of usbars including distribution bars from the functional units and terminals for
external conductors: Forms 2b, 4a, 3b, 4b

No protection Protection to terminals of the


when doors are neighbouring functional units:
open Form 4b
Protection of

Additional protection during work on the termi-


Persons

nals for external conductors: Forms 3b, 4b


Persons are protected against touch of neighbouring functional units dur-
ing work on a functional unit: Forms 4a, 3b, 4b
Persons are protected against touch of busbars and distribution bars during work on the
functional units: Forms 2b, 4a, 3b, 4b

No internal Protection against ingress of


protection foreign objects between single
terminal compartments: Form 4b
Protection of

Protection against ingress of foreign objects between


Equipment

functional units and common terminal compartment:


Forms 3b, 4b
Protection against ingress of foreign objects into any neighbouring
functional unit: Forms 4a, 3b, 4b
Protection against ingress of foreign objects between functional unit into the bus bar com-
partment: Forms 2b, 4a, 3b, 4b
Internal Separation

MNS technique complying with forms of separation

Form 1 Form 2b Form 4a Form 3b Form 4b

On behalf of safety, In addition MNS MNS provides a Each phase isolated At MNS withdrawable
MNS is only available provides a separate separate cubicle for as form 4b modules each phase
with higher protection compartment also for functional units with at the terminals for
MNS Solution

the distribution bars direct connection to external conductors


by the MNS Multi main busbars is isolated. 19
Function Wall

Special measures in MNS going Form 2b and 4a


beyond IEC regulations Switchboards with functional units which are directly
All separations fulfill the requirements of the degree of connected to the main busbars, mainly used for
protection IP20. incomers, bus ties (coupling) and outgoing feeders.
For switchboards with outgoing modules.
Form 2b through 4b
If internal separation is required MNS offers additional Form 3b and 4b
safety by the use of the Multifunction Wall (MFW). For switchboards with withdrawable modules.
The MFW is a separate compartment for the distribution
bars. It provides a “gas sealed” connection between the
main busbars and the distribution bars.

The degree of protection between the distribution bars


and equipment compartment (functional unit) using the
MFW is IP20 without the necessity of moving parts
(shutters etc.).
Earthquake, Vibration and Shock

Earthquake, Vibration and Shock

MNS was successfully tested according to:


■ IEC 60068-2-6 (Vibration)
■ IEC 60068-2-27 (Single shock)
■ Germanischer Lloyd, Lloyd’s Register of Shipping

Standard Execution Individual solutions


According to the standards listed above, the In the event of additional requirements con­
standard version of MNS (when erected with cerning the earthquake resistance of a plant in
20 floor connection, i.e. without any additional individual cases, the following data must be
reinforcement of the frame, the modules, etc.) provided for project engineering and, if neces-
is resistant to stress caused by vibration and sary, testing a specifically adjusted plant
shock up to 0.7 g (vertical, horizontal, diagonal). design:
■ the stress to be expected in the place
The functional safety of the equipment, con- of erection
tacts and connections in compliance with ■ the acceleration to be expected in the event
the standard is guaranteed within MNS. For of an earthquake
example, the screwed system connections ■ the frequency range and the response range
have been proven to resist con­tinuous stress of the building
resulting from vibration of excavators or on
ships, providing the recommended mainte- These increased demands can be met, e.g.:
nance intervals are observed. ■ by installing the system on shock absorbers
or alternatively
■ by using shock-proof equipment
■ by reinforcing the frame, the enclosure and
other system parts
Neutral conductor dimensioning

Neutral conductor dimensioning

No requirements are stipulated in IEC 60439-1 Annex E, "Items subject to agreement


between manufacturer and user“, with respect to the size of the neutral conductor. However,
ABB recommends to make an agreement concerning the neutral conductor design anyway,
in particular, if one or several of the operating conditions described below are present.

Various electrical components used today may A considerable load on the neutral conductor
cause undesirable neutral conductor currents. has to be expected based on the 3rd harmonic
These undesirable neutral conductor currents (150Hz in the 50Hz system) because the phase
result from harmonics and may even exceed currents of this frequency do not equal each 21
the value of the phase current. other out, but rather add up, flowing back to
the generator in the neutral conductor causing
This refers to, e.g.: overheating.
■ Rectifiers, especially if they are equipped with
power factor correction Recommended protective measures:
■ Power supply units without transformers, e.g. ■ MNS offers a 4-pole busbar system as a
switched-mode power supplies of computers standard option. Preferred neutral conductor
■ Lamps with electronic ballasts options include 50% or 100% of the phase
■ Phase-controlled inverters and controllers, conductor. In limited cases, it is also possible
e.g. frequency inverters to select a conductor rating up to 200%.
■ It should be checked if the neutral current
In reality the equipment mentioned above is can be reduced by using active ABB Third
often connected on the same network and uti- Harmonic Filters (THF). When properly rated,
lised simultaneously. these filters eliminate undesirable neutral
conductor currents from the system.
■ The inclusion of the N conductor in the safety
concept (overload trip) should be a matter-
of-course.
ABB
ABB Low Voltage Systems Publication No.: 1TGC900009B0201
Revision 01, June 2006
Local contacts:
www.abb.com/mns Editor:
ABB Automation Products
Dept. APR/RD-B
Wallstadter Str. 59
D-68526 Ladenburg, Germany

You might also like