You are on page 1of 108

Low Voltage

Catalogue2013

Source
changeover
systems
Compact NSX100-630, Compact NS630b-1600,
Compact INS/INV, Masterpact

Efficient energy
management and
continuity of service with
source-changeover system
To ensure continuity of service for critical applications,
LV electrical installations need to be connected to
at least two independent power sources:

1
2

A normal

The source-changeover

source (N)

system switches the


load (partly or fully)

And a replacement

between these
two sources.

source (R)*

used to supply energy to the installation


when the normal source unavailable, or,
for instance, when its quality and/or availability
is no longer guaranteed.

A few basics on source-changeover systems


> A source-changeover
system can be
automated to manage
transfers according
to external
conditions.

> Switching from

> A source-changeover
a main power source to system comprises
a replacement source circuit breakers,
can be performed
either manually or
automatically.

switch-disconnectors
or contactors.

* The replacement source (R) can be: a second power source (with possibly different
characteristics from the normal source) or an electrical generator
I

ways

to switch the load to meet


your needs
Manual source-changeover system
(or MTSE: Manual Transfer Switching Equipment)
The simplest way to switch the load. It is controlled manually by an operator.
The time required to switch from the N source to R source can vary.

System

2 or 3 mechanically interlocked manuallyoperated circuit breakers or 2 switchdisconnectors.

Applications

Buildings and infrastructure where the need

for continuity of service is significant but not


a priority: offices, small and medium-sized
businesses.

Remote-operated source-changeover system


(or RTSE: Remote Transfer Switching Equipment)
The most commonly used system for devices with high ratings. No direct human
intervention is required. Source-changeover is controlled electrically.

System

2 or 3 circuit breakers that may have different


configurations, linked by an electrical
interlocking system. In addition, a mechanical
interlocking system protects against electrical
malfunctions or incorrect manual operations.

Applications

Industry (assembly lines, engine rooms on

ships, critical auxiliaries in thermal


powerstations, etc.); Infrastructure (port and
railway installations, runway lighting systems,
control systems on military sites, etc.).

Automatic source-changeover system


(or ATSE: Automatic Transfer Switching Equipment)
An automatic controller may be added to a remote-operated source-changeover system. It is

possible to automatically control source transfer according to programmed (dedicated controllers) or


programmable (PLC) operating modes. These solutions ensure optimum energy management.

System

2 or 3 circuit breakers that may have different


configurations, linked by an electrical interlocking
system. A mechanical interlocking system
protects against electrical malfunctions or
incorrect manual operations, with an automatic
control system (dedicated controllers or PLC).

II

Applications

Commercial and service sector (operating

rooms in hospitals, safety systems for


buildings, computer rooms for banks and
insurance companies, lighting and emergency
lighting systems in malls, etc.), industry and
infrastructure.

Whatever the system,


you benefit from our expertise!
> MTSE range

Our expertise and support come together


with the source-changeover system you
choose for your LV electrical installation.

Compact INS
From 40 A to 630 A

With Compact INS, Compact NSX


and Masterpact NT and NW, we offer
a complete range of solutions, designed
around key values:

> RTSE range

Maximum continuity
of service

> Energy availability is ensured whatever

the external requirements (e.g. high


power demand).
> Maintenance and replacement of the sources
(N or R) can be done with no interruption
of service.
You can maintain a continuous level of service
and customer satisfaction.
Compact NSX
From 100 A to 630 A

Masterpact NT / NW
From 630 A to 6300 A

> ATSE range

Maximum safety

For LV electrical installations where safety and


continuity of service are critical for people
and/or equipment such as hospitals, airports,
banks, malls, etc.

Optimized energy
management

> Transfer the load to a replacement source

according to external requirements.

> Manage power sources according to power

quality and power costs.

> Perform system regulation.


> Switch to an emergency replacement source.

You are no longer dependent on your power


supply (and supplier)!

Simplicity and reliability

UA Controller

Compact NSX
From 100 A to 630 A

> Simple installation on LV switchboard.


> Optimized size of the switchboard.
> System based on pre-tested components.
> Compliance with IEC 60947-6-1.

III

For critical applications


in particular

For all others


in general

A source-changeover system is indispensable


for applications that need a continuous supply
of electric power (hospitals, airports, banks,
government facilities, etc.).
But a source-changeover system is also
suitable for all LV electrical installations
exposed to:
> Nominal voltage loss or dip (when there
is high demand for electric power)
> Unpredictable power quality
> Frequent power cuts.

IV

These factors, and many others, can damage the


continuity of service of your electrical installation.
For infrastructure managers, a sourcechangeover system gives direct economic
benefits: it is possible to select your source based
on power cost.
In this case, the replacement source (R) is used
as an alternative, more economical source.

Managing
energy
efciently
Power Cost
Safety

Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Compact INS/INV, Masterpact

General content

Presentation

Functions and characteristics

A-1

Dimensions

B-1

Electrical diagrams

C-1

Catalogue numbers
and order forms

D-1

For maximum continuity


of service...

Presentation

Db101543.eps

PB105109.eps

Incoming feeders and main LV switchboards

Currents
From 630 to 6300 A.

PD390385_SE_R_35.eps

Power distribution

Currents
From 250 to 3200 A.

PB111556.eps

Loads

Currents
From 40 to 400 A.

... in a wide range of applications

QN
0
1
0

QR

QS1

QC

QS2

0
0
0
1
0
1
1
1
0
0
1
1
1
0
0 (1)
0
0
1 (1)
(1) possible by forcing
operation.

0
0
1

2 normal sources
1 replacement source
Db101540.eps

Db101539.eps

2 sources with coupler on


busbars

Db101538.eps

1 normal source
1 replacement source

QN1
0
1
0
1
0

QN2

QR

0
1
0
0
1

0
0
1
0
0

Generator or permanent
source
Db101541.eps

QN
0
1
0

0
0
1

Typical applications:
b continuous production processes
b operating rooms
b computer rooms...

Generator or permanent
source
Db101544.eps

Db101541.eps

Generator or permanent
source

QR

QN
0
1
0

QR
0
0
1

Typical applications:
b large electrical installations (e.g. airports)
b refrigeration units
b special electricity tariffs
b pumping stations...

TOOLS
Ecodial
Ecodial software is dedicated to LV electrical installation
calculation in accordance with the IEC60364
international standard or national standards.
This 4th generation, "Ecodial Advance Calculation 4",
offers a new ergonomic and new features:
p operating mode that allows easy calculation in case
of installation with different type of sources
(parallel transformers, back-up generators)
p discrimination analysis associating curves checking
and discrimination tables
p direct access to protection settings including residual
current protections
p easy selection of alternate solutions or manual
selection of a product.

Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Compact INS/INV, Masterpact

Functions and characteristics

Presentation

Overview of solutions
Manual source-changeover systems Compact INS/INV 40 to 630 A,
Compact NSX100/630
Manual source-changeover systems Compact NS
and Masterpact NT/NW 630 A to 6300 A
Remote-operated source-changeover systems
Compact NSX100/630, Compact NS630b/1600 A
Remote-operated source-changeover systems
Masterpact NT/NW 630 A to 6300 A

A-2
A-3
A-4
A-5

Manual source-changeover systems


Possible combinations

A-6

Remote-operated source-changeover systems


Mechanical interlocking Compact NSX, Compact NS or Masterpact NT/NW
Mechanical interlocking Compact NS or Masterpact NT/NW
General characteristics Compact NSX
General characteristics Compact NS, Masterpact NT/NW
Mech. and elect. durability
Connection and insulation accessories for Compact NSX and INS y 630 A
Electrical interlocking
6WDQGDUGFRQJXUDWLRQV

A-10
A-11
A-12
A-13
A-14
A-15
A-16
$

Associated controllers
Controller selection
Controller installation
BA controller
BA controller, Operating sequences
UA controller
UA controller, Operating sequences, Forced operation mode
UA controller, Operating sequences, Special-tariff mode
UA controller, Operating sequences , Test mode and automatic operation

A-18
A-19
A-20
A-21
A-22
A-23
A-24
A-25

Operating sequences
IVE unit
%$8$FRQWUROOHU

COM communications option


Dimensions
Electrical diagrams
Catalogue numbers and order forms

A-26
$

A-28
B-1
C-1
D-1

A-1

Functions
and characteristics

Range

Overview of solutions
Manual source-changeover systems
Compact INS/INV 40 to 630 A, Compact
NSX100/630
Compact

Models

Compact

INS40 to INS80
INS100 to INS160
40 to 160
Switch-disconnectors with
extended handles

Rating (A)
Type of device

INS250 to INS630
INV250 to INV630
100 to 630
Switch-disconnectors

NSX100 to NSX250
NSX400 to NSX630
100 to 630
N/H/L circuit breakers
NA switch-disconnectors

Manual source-changeover systems


Db101545.eps

DB126589.eps

Interlocking via toggles

2 devices side-by-side.

3 devices side-by-side.

Db101548.eps

'EHSV

Db101546.eps

.4

DB126590.eps

Interlocking via rotary handles


ON
I

ON
I
O
OFF

2 devices side-by-side.

O
OFF

Db101550.eps

Db101549.eps

DB126588.eps

Interlocking via keylocks with captive keys

A number of different devices.

Db101551.eps

'%HSV

Interlocking on a base plate

2 devices side-by-side.

DB126586.eps

'%HSV

Complete source-changeover assemblies

2 devices side-by-side.

A-2

Manual source-changeover systems


Compact NS and Masterpact NT/NW
630 A to 6300 A
Range
Models
Rating (A)
Type of device

Compact

Masterpact

NS630b to NS1600
630 to 1600
N/H/L circuit breakers
NA switch-disconnectors

NT06 to NT16
630 to 1600
H1/L1 circuit breakers
HA switch-disconnectors

NW08 to NW63
800 to 6300
N1/H1/H2/H3/L1 circuit
breakers
NA/HA/HF switchdisconnectors

Manual source-changeover systems


Db101553.eps

DB126590.eps

Interlocking via extended rotary handles

2 devices side-by-side.

I ON

OOFF

push

push

discharged

O OFF

Db101556.eps

Db101555.eps

Db101554.eps

DB126588.eps

Interlocking via keylocks with captive keys

I ON

OOFF

push

push

discharged

O OFF

A number of different devices.

sup

degr
ahcs
id

Db101559.eps

NO h

Db101562.eps

hsup

Db101558.eps

FFO

FFO

Db101561.eps

'EHSV

DB126585.eps

Mechanical interlocking using connecting rods

FFO

hsup

NO h
sup

FFO

O
degr
ahcs
id

2 devices one above the other.


(1)

Db101560.eps

DB126584.eps

Mechanical interlocking using cables

DB126583.eps

2 or 3 devices one above the other.

(1)

2 or 3 devices side-by-side.

(2)

DB126580.eps

For this case and other cases, please consult us

(1) Implemented with NS630b to NS1600 electrically-operated devices only.


(2) )RUVRXUFHFKDQJHRYHUV\VWHPVXVLQJFDEOHVDOZD\VUHVSHFWWKHLQVWDOODWLRQFRQGLWLRQVVSHFLHGRQpage A-13.

A-3

Functions
and characteristics

Overview of solutions

Range

Compact

Models
Rating (A)
Type of device

Remote-operated source-changeover
systems Compact NSX100/630,
Compact NS630b/1600 A
NSX100 to NSX630
100 to 630
N/H/L circuit breakers
NA switch-disconnectors

NS630b to NS1600
630 to 1600
N/H/L circuit breakers
NA switch-disconnectors

Remote-operated source-changeover system


'%HSV

Db101563.eps

Mechanical interlocking on base plate + electrical interlocking

2 electrically-operated devices side-by-side combined


with an electrical interlocking system.

'EHSV

DB126585.eps

Mechanical interlocking using connecting rods + electrical interlocking

FFO

hsup

NO h
s

up

FFO

O
degr
a

hcsi
d

FFO

hsup

NO h
sup

FFO

O
degr
a

hcsi
d

2 electrically-operated devices one above


the other combined with an electrical interlocking system.

Db101560.eps

DB126581.eps

Mechanical interlocking using cables + electrical interlocking

DB126582.eps

2 electrically-operated devices one above


the other combined with an electrical interlocking system.

2 electrically-operated devices side-by-side combined


with an electrical interlocking system.

(1)

Automatic source-changeover systems


DB126581.eps

The automatic controller


operates the devices
depending on external
parameters.

DB404439.eps

Remote-operated source-changeover system combined with an automatic-control system

UA: Controller that also


manages engine generator
sets.

BA controller

DB404440.eps

DB126582.eps

BA: Simple controller that


manages the changeover
function.

UA150: UA controller with a


communication option.
UA and UA150 controller
(1) )RUVRXUFHFKDQJHRYHUV\VWHPVXVLQJFDEOHVDOZD\VUHVSHFWWKHLQVWDOODWLRQFRQGLWLRQVVSHFLHGRQpage A-13.

A-4

Remote-operated source-changeover
systems Masterpact NT/NW
630 A to 6300 A
Range

Masterpact

Models
Rating (A)
Type of device

NT06 to NT16
630 to 1600
H1/L1 circuit breakers
HA switch-disconnectors

NW08 to NW63
800 to 6300
N1/H1/H2/H3/L1 circuit breakers
NA/HA/HF switch-disconnectors

Remote-operated source-changeover system


Db101559.eps

DB126585.eps

Db101558.eps

Mechanical interlocking using connecting rods + electrical interlocking

2 electrically-operated devices side-by-side combined


with an electrical interlocking system.

Db101562.eps

Db101561.eps

DB126584.eps

Mechanical interlocking using cables + electrical interlocking

DB126583.eps

2 or 3 electrically-operated devices one above the other


combined with an electrical interlocking system (1).

2 or 3 electrically-operated devices side-by-side combined with


an electrical interlocking system (1).
(2)

Automatic source-changeover systems


DB404439.eps

The automatic controller


operates the devices
depending on external
parameters.
BA: Simple controller that
manages the changeover
function.
UA: Controller that also
manages engine generator
sets.

BA controller
DB404440.eps

DB126582.eps

DB126581.eps

Remote-operated source-changeover system combined with an automatic-control system

UA150: UA controller with a


communication option.

UA and UA150 controller

(1) Three devices with Masterpact NW only.


(2) )RUVRXUFHFKDQJHRYHUV\VWHPVXVLQJFDEOHVDOZD\VUHVSHFWWKHLQVWDOODWLRQFRQGLWLRQVVSHFLHGRQpage A-13.
For other cases, please consult us.

A-5

Functions
and characteristics

Manual source-changeover
systems
Possible combinations

A manual source-changeover system can be installed


on two or three manually-operated and mechanically
interlocked circuit breakers or switch-disconnectors.
Interlocks prevent connection to both sources at the
same time, even momentarily.

All possibilities for manual source-changeover systems


Type of device

Type of interlocking for two devices

Complete
assembly
Compact switch-disconnectors

Keylock

Direct rotary
handle

Extended
rotary handle

INS40 to INS160
b

INS250-100 to INS630
INV100 to 630

b r

b r

b r

b rr

b
INS/INV630b to 2500
Legend:
r Possible but visible break function disabled.
r 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.

Type of device

Type of interlocking for two devices


Toggle

Keylock

Direct rotary
handle

Extended rotary
handle

On base plate
On base plate
(toggle or direct extended (motor mechanism)
rotary control)

&RPSDFW[HGRUZLWKGUDZDEOHFLUFXLWEUHDNHUV
NSX100 to 250

bb

bbp

bb

bb

bbb

bbb

NSX400 to NS630

bb

bbp

bb

bb

bbb

bbb

bbp

bbp

bbp

bbbp

bbbp

NSX100 to 630

bb
NS630b to 1600 with
bbp
rotary handle
Legend:
b Fixed devices only.
b Fixed or withdrawable devices.
b 'HYLFHVPXVWEHHLWKHUERWK[HGRUERWKZLWKGUDZDEOH
p With NSX400/630 rotary handle interlocking system.
p Possible with NSX400/630 base plate + NSX100-250 adaptation kit.
p Devices equipped with rotary handles.

Type of device

bb

7\SHRILQWHUORFNLQJIRUHLWKHUDOO[HGRUDOOZLWKGUDZDEOHGHYLFHV

Cable-type,
Cable-type,
Cable-type,
2 devices one
3 devices
2 devices
above the other
side-by-side
side-by-side
&RPSDFW[HGRUZLWKGUDZDEOHFLUFXLWEUHDNHUVRUVZLWKGLVFRQQHFWRUVZLWKPRWRUPHFKDQLVP
Keylock

Cable-type,
3 devices one
above another

b
b
b
NS630b to 1600
0DVWHUSDFW[HGRUZLWKGUDZDEOHFLUFXLWEUHDNHUVRUVZLWKGLVFRQQHFWRUVPDQXDORSHUDWLRQRUZLWKPRWRUPHFKDQLVP
NT06 to 16

NW08 to 63

NT06 to NW63

A-6

b
b

b
b

Rod-type,
3 devices one
above another

b
b

Possible combinations
Complete source-changeover assembly for two switch-disconnectors
All possibilities for manual source-changeover systems
'%HSV

These assemblies provide an easy way to implement source changeover functions


with:
b a single 3-position rotary handle that controls the two switch-disconnectors
(Normal source ON, OFF, Replacement source ON)
b a smaller size, taking up less room in the switchboard.
A complete source changeover assembly can be ordered with a single catalogue
number.

Normal N

Replacement R
INS250-100

INS250-100
Ratings 100 A
INS250-160
Ratings 160 A
INS200-200
Ratings 200 A
INS250-250
Ratings 250 A
INS320
Ratings 320 A
INS400
Ratings 400 A
INS500
Ratings 500 A
INS630
Ratings 630 A

INS250-160

INS200-200

INS250-250

INS320

INS400

INS500

INS630

b
b
b
b
b
b
b
b

Interlocking of two or three toggle-controlled devices


Db101566.eps

Possible combinations of Normal and Replacement source circuit breakers

Two devices can be interlocked using this system. Two identical interlocking systems
can be used to interlock three devices installed side by side, in which case one
device is in the ON position and the two others are in the OFF position. Devices must
DOOKDYHWKHVDPHFRQJXUDWLRQLH[HGSOXJLQZLWKGUDZDEOHRUGUDZRXW
The system is locked using one or two padlocks (shackle diameter 5 to 8 mm).
Two interlocking system models are available for:
b Compact NSX100 to 250
b Compact NSX400 to 630.

Normal N
NSX100
Ratings 16... 100 A
NSX160
Ratings 80...160 A
NSX250
Ratings 125...250 A
NSX400
Ratings 150... 400 A
NSX630
Ratings 630 A

Replacement R
NSX100

NSX160

NSX250

NSX400

NSX630

$

Functions
and characteristics

Manual source-changeover
systems
Possible combinations

Interlocking of a number of devices using keylocks (captive keys)


Combination of Normal and Replacement devices
Db101569.eps

All Compact and Masterpact circuit breakers and Compact switch-disconnectors


from 100 to 6300 A with rotary handles or motor mechanisms can be interlocked.
Interlocking is based on two identical keylocks with a single key and a keylock
adapter (different for each device). This solution enables interlocking between two
devices that are physically distant or that have very different characteristics, for
example between a low and a medium-voltage device, or between Compact NSX
circuit breakers and switch-disconnectors.
A system of wall-mounted captive key boxes makes possible a large number of
combinations between many devices.

Interlocking of two devices with rotary handles


Possible combinations of Normal and Replacement source circuit breakers
Db101568.eps

The direct or extended rotary handles are padlocked with the devices in the OFF
position. The mechanism prevents simultaneous closing of the devices, but allows
them to be opened.
ON
I

ON
I
O
OFF

O
OFF

Normal N
Compact NSX100/630 (1)

Replacement R
NSX100

NSX160

NSX250

NSX400

NSX630

NSX100
Ratings 16... 100 A
b
b
b
v
v
NSX160
Ratings 80...160 A
b
b
b
v
v
NSX250
Ratings 125...250 A
b
b
b
v
v
NSX400
Ratings 160... 400 A
v
v
v
b
b
NSX630
Ratings 630 A
v
v
v
b
b
v 250 A and 630 A ratings can be mixed by using NSX400/630 rotary handle interlocking
system.

Normal N
Replacement R
NS800
Compact NS630b/1600 (1) NS630b

NS1000

NS1200

NS1600

NS630b
Ratings 250... 630 A
b
b
b
b
b
NS800
Ratings 320... 800 A
b
b
b
b
b
NS1000
Ratings 400... 1000 A
b
b
b
b
b
NS1200
Ratings 480... 1200 A
b
b
b
b
b
NS1600
Ratings 640... 1600 A
b
b
b
b
b
(1) When mixing NSX100/250 and NSX400/630 circuit breakers, use the NSX400/630
interlocking system.

A-8

Possible combinations
Interlocking of two devices with rotary handles
Possible combinations of Normal and Replacement source switch-disconnectors
'%HSV

The direct or extended rotary handles are padlocked with the devices in the OFF
position. The mechanism prevents simultaneous closing of the devices, but allows
them to be opened.
Normal N
Compact INS (1)

Replacement R

INS40
INS63
INS80
INS100
INS40
Ratings 40 A
b
b
b
b
INS63
Ratings 63 A
b
b
b
b
INS80
Ratings 80 A
b
b
b
b
INS100
Ratings 100 A
b
b
b
b
INS125
Ratings 125 A
b
b
b
b
INS160
Ratings 160 A
b
b
b
b
(1) With extended rotary handles only.
(2) 3RVVLEOHZLWK,19EXWYLVLEOHEUHDNIXQFWLRQLVVLJQLFDQWO\LPSDLUHG

Normal N
Compact INS /INV (2)

INS125

INS160

Replacement R
INS250-100/
INV100

INS250-160/
INV160

INS250-200/
INV200

INS250-250/
INV250

INS250-100/INV100
Ratings 100 A
b
b
b
b
INS250-160/INV160
Ratings 160 A
b
b
b
b
INS250-200/INV200
Ratings 200 A
b
b
b
b
INS250-250/INV250
Ratings 250 A
b
b
b
b
INS320/INV320
Ratings 320 A
v
v
INS400/INV400
Ratings 400 A
INS500/INV500
Ratings 500 A
INS630/INV630
Ratings 630 A
v
v
v 250 A and 630 A ratings can be mixed by using INS320/630 rotary handle interlocking system.

INS320/
INV320

INS400/
INV400

INS500/
INV500

INS630/
INV630

Interlocking of two devices on a base plate


Possible combinations of Compact NSX Normal and Replacement source circuit breakers
DB414891.eps

A base plate is available for mechanical interlocking of two manually-operated


Compact NSX100 to 630 circuit breakers or switch-disconnectors.
Normal N
NSX100
Ratings 16... 100 A
NSX160
Ratings 80... 160 A
NSX250
Ratings 125... 250 A
NSX400
Ratings 150... 400 A
NSX630
Ratings 630 A

Replacement R
NSX100

NSX160

NSX250

NSX400

NSX630

Interlocking of a number of devices using keylocks (captive keys)


Db101903.eps

Combination of Masterpact devices

Interlocking uses two identical keylocks with a single key. This solution enables
LQWHUORFNLQJEHWZHHQWZRGHYLFHVWKDWDUHSK\VLFDOO\GLVWDQWRUWKDWKDYHVLJQLFDQWO\
different characteristics.

A-9

Functions
and characteristics

Remote-operated
source-changeover systems
Mechanical interlocking Compact NSX,
Compact NS or Masterpact NT/NW

PB105106_50.eps

Mechanical interlocking of two or three devices is used


to create a remote-operated source-changeover
system. A basic mechanical interlocking system
enhances the reliability of system operation.

Interlocking of two Compact NSX100 to 630 devices using a


base plate
A base plate designed for two Compact circuit breakers can be installed horizontally
or vertically on a mounting rail. Interlocking is carried out on the base plate by a
mechanism located behind the breakers. Access to the circuit breaker controls and
WULSXQLWVLVFRQVHUYHG&LUFXLWEUHDNHUVPXVWEH[HGRUSOXJLQYHUVLRQVZLWKRU
without earth-leakage protection or measurement modules. The base plate and the
circuit breakers are supplied separately.
b Base plate for Compact NSX100 to 250 devices
This base plate is intended for two Compact NSX100 to 250 devices.
b Base plate for Compact NSX400 to 630 devices
This base plate is intended for two Compact NSX400 to 630 devices. It may also be
XVHGZLWKRXWDQ\PRGLFDWLRQVWRLQWHUORFND[HG&RPSDFW16;WRZLWKD
Compact NSX400 or 630 device.
An adapter kit is required for plug-in versions of the Compact NSX100 to 250
devices.
&RPSDFW16;WRGHYLFHVLQERWK[HGDQGSOXJLQYHUVLRQVPD\EH
equipped with spreaders.
Possible combinations of Normal and Replacement Compact NSX source circuit
breakers

Interlocking of two electrically-operated Compact NSX


circuit breakers using a base plate.

Normal N

DB126268.eps

NSX100
Ratings 12,5... 100 A
NSX160
Ratings 12,5...160 A
NSX250
Ratings 12,5...250 A
NSX400
Ratings 160... 400 A
NSX630
Ratings 250... 630 A

Replacement R
NSX100

NSX160

NSX250

NSX400

NSX630

Interlocking of two Compact NS630b to 1600 or two Masterpact


NT and NW devices using connecting rods
7KHWZRGHYLFHVPXVWEHPRXQWHGRQHDERYHWKHRWKHU HLWKHU[HGRU
2 withdrawable/drawout devices).
Combinations are possible between Compact NS630b to NS1600 devices and
between Masterpact NT and Masterpact NW devices.
Installation
This function requires:
b DQDGDSWDWLRQ[WXUHRQWKHULJKWVLGHRIHDFKFLUFXLWEUHDNHURUVZLWFK
disconnector
b a set of connecting rods with no-slip adjustments.
7KHDGDSWDWLRQ[WXUHVFRQQHFWLQJURGVDQGFLUFXLWEUHDNHUVRUVZLWFK
disconnectors are supplied separately, ready for assembly by the customer.
7KHPD[LPXPYHUWLFDOGLVWDQFHEHWZHHQWKH[LQJSODQHVLVPP
Possible combinations of Normal and Replacement source circuit breakers

Normal N

Replacement R
NS630b to
NS1600

Interlocking of two Masterpact NT or NW circuit breakers using


connecting rods.

A-10

NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A

NT06 to NT16

NW08 to
NW40

NW40b to
NW63

PB100842_68_SE.eps

Mechanical interlocking
Compact NS or Masterpact NT/NW
Interlocking of two Compact NS630b to 1600 or two Masterpact
NT/NW or up to three Masterpact NW devices using cables
For cable interlocking, the circuit breakers may be mounted one above the other or
side-by-side.
7KHLQWHUORFNHGGHYLFHVPD\EH[HGRUGUDZRXWWKUHHSROHRUIRXUSROHDQGKDYH
different ratings and sizes.
Interlocking between two devices (Compact NS630b to 1600 or Masterpact NT
and NW)
This function requires:
b DQDGDSWDWLRQ[WXUHRQWKHULJKWVLGHRIHDFKGHYLFH
b a set of cables with no-slip adjustments.
7KHPD[LPXPGLVWDQFHEHWZHHQWKH[LQJSODQHV YHUWLFDORUKRUL]RQWDO LVPP

Interlocking of two Masterpact circuit breakers using cables.

Interlocking between three devices (Masterpact NW only)


This function requires:
b DVSHFLFDGDSWDWLRQ[WXUHIRUHDFKW\SHRILQWHUORFNLQJLQVWDOOHGRQWKHULJKWVLGH
of each device
b two or three sets of cables with no-slip adjustments.
7KHPD[LPXPGLVWDQFHEHWZHHQWKH[LQJSODQHV YHUWLFDORUKRUL]RQWDO LVPP
Installation
7KHDGDSWDWLRQ[WXUHVVHWVRIFDEOHVDQGFLUFXLWEUHDNHUVRUVZLWFKGLVFRQQHFWRUV
are supplied separately, ready for assembly by the customer.
Installation conditions for cable interlocking systems:
b cable length: 2.5 m
b radius of curvature: 100 mm
b maximum number of curves: 3.
Possible combinations of Normal and Replacement source circuit breakers

Normal N

Replacement R
NS630b to
NS1600

NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A

NT06 to NT16

NW08 to
NW40

NW40b to
NW63

It is not possible to combine Compact NS630b to 1600 and Masterpact NT


(or Masterpact NW) devices.
All combinations of two Masterpact NT and Masterpact NW devices are possible,
whatever the rating or size of the devices.
Possible combinations of three device

Normal N

Replacement R
NS630b to
NS1600

NS630b to NS1600
Ratings 250... 1600 A
NT06 to NT16
Ratings 250... 1600 A
NW08 to NW40
Ratings 320... 4000 A
NW40b to NW63
Ratings 4000... 6300 A

NT06 to NT16

NW08 to
NW40

NW40b to
NW63

Only Masterpact NW may be used for three-device combinations.

Types of mechanical interlocking and combinations


See page A-4 to page A-9.

A-11

Remote-operated
source-changeover systems

Functions
and characteristics

General characteristics
Compact NSX
Range

Compact NSX

Types of devices
Types of circuit breakers
Switch-disconnector version
Mixing possibilities

NSX100 to NSX250
N/H/L
NA
all devices
NS100 to NS250
N/H/L/NA
[HGRUSOXJLQ

NSX400 to NSX630
N/H/L
NA
all devices
NS100 to NS630
N/H/L/NA
[HGRUSOXJLQ

Rating
Insulating voltage Ui (V AC)
Positive break indication
Number of poles
(N and R devices must have the same number of poles)

15 to 250 A

b
3, 4

15 to 630 A

b

Electrical durability
Operating temperature

See page A-14


&WR& &IRU9+]

Electrical characteristics

Control characteristics
Control voltage

AC

Maximum consumption

DC
AC
DC

Minimum switching time

48 V - 50 Hz
110/130, 220/240, 380/440 V - 50/60 Hz
24-250 V
500 VA
500 W
800 ms

48 V - 50 Hz
110/130, 220/240, 380/440 V - 50/60 Hz
24-250 V
500 VA
500 W
800 ms

b
b
1 OF + 1 SDE

b
b
1 OF + 1 SDE

b
b
b

b
b
b
b
b
b

OF + SD (+ SDV)
b
b
b
b
b
b

3 OF + SD (+ SDV)
b
b
b
b
b
b

Interlocking
Mechanical (see page A-10)
Electrical
by diagram (without IVE)
with IVE unit
auxiliary contacts used by circuit breaker

Protection and measurement


Overload protection
Short-circuit protection
Earth-fault protection
Zone selective interlocking (ZSI)
Earth-leakage protection

long time
short time
instantaneous

by Vigi module
by control unit
by add-on Vigirex relay

Current measurements
Voltage, frequency, power measurements, etc.

Indication and control auxiliaries


Available auxiliary indication contacts
Voltage releases
MX shunt
MN undervoltage
Voltage presence indicator
Voltage transformer
Ammeter module
Insulation monitoring module

Source-changeover controller
With permanent replacement source
With standby generator set

b BA controller
b UA controller

Remote communication via bus


Device status indications
Device remote control
Transmission of settings
,QGLFDWLRQDQGLGHQWLFDWLRQRISURWHFWLRQVWDWXVDQGDODUPV
Transmission of measurements

b
b
b

b
b
b

b (long rear connections)


b (plug-in on base)

b (long rear connections)


b (plug-in on base)

b
b
b

b
b
b
b
b
b
b

Installation and connection


Fixed front connected
Fixed rear connected
Withdrawable, plug-in or drawout

Installation and connection accessories


Downstream coupling accessory
Bare-cable connectors
Terminal extensions
Terminal shields and inter-phase barriers
Locking
by padlock
by keylock
Front panel escutcheons

A-12

b
b
b

General characteristics
Compact NS, Masterpact NT/NW
Compact NS

Masterpact

NS630b to NS1600
N/H/L
NA
all devices
NS630b to 1600
N/H/L/NA
[HGRUSOXJLQ

NT06 to 16
N1 / H1 / H2 / H3 / L1
NA / HA / HF
all mixing possibilities
[HGGUDZRXWRU[HGGUDZRXW 
N1/H1/H2/H3/L1/NA/HA/HF

NW08 to 63
N1 / H1 / H2 / H3 / L1
NA / HA / HF
all mixing possibilities
[HGGUDZRXWRU[HGGUDZRXW 
N1/H1/H2/H3/L1/NA/HA/HF

250 to 1600 A


600 to 1600 A
1000
b
3, 4

800 to 6300 A
1000
b

See page A-14


&WR& &IRU9+]

24-250 V
180 VA
180 W
800 ms

48 to 415 V - 50/60 Hz
440 V - 60 Hz
24-250 V
180 VA
180 W
800 ms

24-250 V
180 VA
180 W
800 ms

b
b
1 OF + 1 CE (+ SDE)

b
only with UA or BA
1 OF + 1 CE + 1 PF

b
only with UA or BA
1 OF + 1 CE + 1 PF

b
b
b
b
b

b
b
b
b
b

b
b
b
b
b

b
b
b

b
b
b
b

b
b
b
b

2 OF + SD
b
b

2 OF + SD
b
b
b
b
b
b

2 OF + SD
b
b
b
b
b
b

b BA controller
b UA controller
b

b
b
b

b
b
b

b
b
b

b (vertical or horizontal)
b (drawout)

b (vertical or horizontal)
b (drawout)

b (vertical or horizontal)
b (drawout)

b
b
b

b
b
b

b
b
b
b
b

A-13

Remote-operated
source-changeover systems

Functions
and characteristics

Mech. and elect. durability Compact INS,


Compact NSX, NS, Masterpact NT/NW
Compact INS switch-disconnectors
INS250-100
INS250-160
INS250-200
Number of poles
Conventional thermal current (A)
Rated operational current (A)

Durability (category A)
(ON-CR-OR-CN cycles)

Number of poles
Conventional thermal current (A)
Rated operational current (A)

Durability (category A)
(ON-CR-OR-CN cycles)

lth at 60 C
Ie Electrical AC, 50/60 Hz
440-480 V
660-690 V
Mechanical
Electrical AC, 50/60 Hz
440-480 V
660-690 V

lth
Ie

at 60 C
Electrical AC, 50/60 Hz
440-480 V
660-690 V
Mechanical
Electrical AC, 50/60 Hz
440-480 V
660-690 V

3, 4
100
AC22A
100
100
15000
AC22A
1500
1500

AC23A
100
100
AC23A
1500
1500

3, 4
160
AC22A
160
160
15000
AC22A
1500
1500

AC23A
160
160
AC23A
1500
1500

3, 4
200
AC22A
200
200
15000
AC22A
1500
1500

AC23A
200
200
AC23A
1500
1500

INS250
3, 4
250
AC22A
250
250
15000
AC22A
1500
1500

INS320

INS400

INS500

INS630

3, 4
320
AC22A
320
320
10000
AC22A
1500
1500

3, 4
400
AC22A
400
400
10000
AC22A
1500
1500

3, 4
500
AC22A
500
500
10000
AC22A
1500
1500

3, 4
630
AC22A
630
630
10000
AC22A
1500
1500

AC23A
320
320
AC23A
1500
1500

AC23A
400
400
AC23A
1500
1500

AC23A
500
500
AC23A
1500
1500

AC23A
250
250
AC23A
1500
1500

AC23A
630
630
AC23A
1500
1500

Compact NSX100-630, Compact NS630b-1600


NSX100-250
NSX400-630
NS630bNS1600
Number of poles
Rated current In (A)
Mechanical durability
(ON-CR-OR-CN cycles)

3, 4
100 to 250
20000 - 40000 50000

Electrical durability at In 10000 - 20000 30000


(ON-CR-OR-CN cycles)
for y 440 V and 480 V
NEMA (2)
Electrical durability at In 
(ON-CR-OR-CN cycles)
for U = 500 V to 690 V (2)

3, 4
400 to 630
15000

3, 4
630 to 1600
8000

4000 - 6000

2000

2000 - 3000

1500

Masterpact NT06-NT16/NW08-NW63 (1)


NT06- NT12- NW08- NW20 NW25- NW50NT10 NT16
NW16
NW40 NW63
Number of poles
Rated current In (A)
Mechanical durability
(ON-CR-OR-CN cycles)

3, 4
630 to
1600
8000

3, 4
1250 to
1600
8000

3, 4
800 to
1600
10000

3, 4
2000
10000

3, 4
2500 to
4000
10000

3, 4
5000 to
6300
5000

10000
8000
5000
1500
6000
Electrical durability at In 6000
NT16:
(ON-CR-OR-CN cycles)
for y 440 V and 480 V
3000
NEMA (2)
Electrical durability at In 3000
10000
6000
2500
1500
2000
(ON-CR-OR-CN cycles)
NT16:
(2)
for U = 500 V to 690 V
1000
(1) Mechanical and electrical durability not applicable to Masterpact H3 and L versions.
(2) Electrical durability tests carried out with a power factor of 0.8 as per IEC 947-2.
Note:
ON: opening of Normal source
CR: closing of Replacement source
OR: opening of Replacement source
CN: closing of Normal source

A-14

DB413568.eps

Connection and insulation accessories


for Compact NSX and INS y 630 A
1

Downstream coupling accessory


7KLVDFFHVVRU\VLPSOLHVFRQQHFWLRQWREDUVDQGFDEOHVZLWKOXJV
It may be used to couple two circuit breakers (Compact NSX100 to 630) or switchdisconnectors (Compact INS/INV100 to 630) of the same size.
Pitch between outgoing terminals:
b Compact INS250 and INV100 to 250: 35 mm
b Compact INS/INV320 to 630: 45 mm
b Compact NSX100 to 250: 35 mm
b Compact NSX400 to 630: 45 mm.
For Compact NSX circuit breakers, the downstream coupling accessory can be used
only with [HGYHUVLRQV.

Connection and insulation accessories


3

7KHFRXSOLQJDFFHVVRU\FDQEHWWHGZLWKWKHVDPHFRQQHFWLRQDQGLQVXODWLRQ
accessories as the circuit breakers and switch-disconnectors.

Possible uses

Downstream coupling
Possible
mounting

Outgoing pitch
(mm)

b
b
b
b
b
b

35
35
35
45
45
45

b
b

35
45

b
b

35
45

Manual source-changeover systems


4

1
2
3
4

Short terminal shields


Terminals
Interphase barriers
Long terminal shields

INS250 (100 to 250 A) with rotary handle


NSX100/250 with rotary handle
NSX100/250 on base plate with toggle control
INS400/630 (320 to 630 A) with rotary handle
NSX400/630 with rotary handle
NSX400/630 on base plate with toggle control

Complete source-changeover assembly


INS250 (100 to 250 A)
INS400/630 (320 to 630 A)

Remote-operated source-changeover systems


NSX100/250
NSX400/630

A-15

Remote-operated
source-changeover systems

Functions
and characteristics

Electrical interlocking
Electrical interlocking is used with a mechanical
interlocking system.
An automatic controller may be added to take into
account information from the distribution system.

Electrical interlocking is carried out by an electrical control device.


For Compact NSX up to 630 A, electrical interlocking is implemented by the IVE unit
integrating control circuits and an external terminal block in accordance with the
pages C-5 to C-4 of the chapter Electric diagrams of this catalogue.
The integrated control circuits implement the time delays required for correct source
transfer.
For Compact NS630b to 1600 and Masterpact, this function can be implemented
in one of two ways:
b using the IVE unit
b by an electrician based on the diagrams in accordance with the pages C-9 to C-14
of the chapter Electric diagrams of this catalogue.

Morover, the relays controlling the closing


order to the Normal and Replacement
circuit-breakers must be mechanically and/or
electrically interlocked to prevent them from
giving simultaneous closing commands.

Characteristics of the IVE unit

'EHSV

b External connection terminal block:


v inputs: circuit breaker control signals
v outputs: status of the SDE contacts on the Normal and Replacement source
circuit breakers.
b 2 connectors for the two Normal and Replacement source circuit breakers:
v inputs:
- status of the OF contacts on each circuit breaker (ON or OFF)
- status of the SDE contacts on the Normal and Replacement source circuit breakers
v outputs: power supply for operating mechanisms.
b Control voltage:
v 24 to 250 V DC
v 48 to 415 V 50/60 Hz - 440 V 60 Hz.
The IVE unit control voltage must be same as that of the circuit breaker operating
mechanisms.

IVE unit.

Necessary equipment
For Compact NSX100 to 630, each circuit breaker must be equipped with:
b a motor mechanism
b an OF contact
b an SDE contact.
The components are supplied ready for assembly and the circuit breakers prewired.
7KHSUHZLULQJPXVWQRWEHPRGLHG
For Compact NS630b to 1600, each circuit breaker must be equipped with:
b a motor mechanism
b an available OF contact
b a CE connected-position contact (carriage switch) on withdrawable circuit breakers
b an SDE contact.
For Masterpact NT and NW, each circuit breaker must be equipped with:
b a remote-operation system made up of:
v MCH gear motor
v MX or MN opening release
v XF closing release
v PF ready to close contact
b an available OF contact
b one to three CE connected-position contacts (carriage switches) on drawout
circuit breakers (depending on the installation).

A-16

Standard configurations

Compact NS, Masterpact NT and NW


Types of mechanical interlocking

Possible combinations Typical electrical diagrams

Diagram no.

'EHSV

2 devices
QN

QR

Compact NSX100 to 630:

b electrical interlocking without emergency


power off (EPO) auxiliaries:

51201177

v with EPO by MN

51201178

v with EPO by MX

51201179

Compact NS630b to 1600:


b electrical interlocking with lockout after fault:
v permanent replacement source (with IVE)

51201183

v with EPO by MX (with IVE)

51201184

v with EPO by MN (with IVE)

51201185

Masterpact NT and NW:


b electrical interlocking with lockout after fault:
v permanent replacement source (with IVE)

51201142

v with EPO by MX (with IVE)

51201143

v with EPO by MN (with IVE)

51201144

b automatic control with lockout after fault:


v permanent replacement source (with IVE)

51156904

v engine generator set (with IVE)

51156905

b BA/UA controller (with IVE)

51156903

Masterpact NW only
Types of mechanical interlocking

Possible combinations Typical electrical diagrams

Diagram no.

'EHSV

3 devices: 2 Normal sources and 1 Replacement source


QN1

QN2

QR

b electrical interlocking:

v without lockout after fault

51156906

v with lockout after fault

51156907

'EHSV

3 devices: 2 Normal sources and 1 Replacement source with source selection


QN1

QN2

QR

b automatic control with engine generator set:

v without lockout after fault (with MN)

51156908

v with lockout after fault (with MN)

51156909

QS1

QS2

QS3

b electrical interlocking:

v without lockout after fault

51156910

v with lockout after fault

51156911

QS1

QC

QS2

b electrical interlocking:

v without lockout after fault

51156912

v with lockout after fault

51156913

b automatic control with lockout after fault

51156914

(1)

(1)

'EHSV

3 devices: 3 sources, only one device

'EHSV

3 devices: 2 sources + 1 coupling

(1) possible by forcing


operation
Lockout after fault option. This option makes it necessary to manually reset the device following fault tripping.

$

Functions
and characteristics

By combining a remote-operated source-changeover


system with an integrated BA or UA automatic
controller, it is possible to automatically control source
transfer according to user-selected sequences.
These controllers can be used on source-changeover
systems comprising 2 circuit breakers.
For source-changeover systems comprising 3 circuit
breakers, the automatic control diagram must be
prepared by the installer as a complement to to
diagrams provided in the electrical diagrams section
of this catalogue.

Associated controllers
Controller selection

Controller

BA

Compatible circuit breakers

UA

All Compact NS,


Compact NSX and
Masterpact circuit breakers

4-position switch
Automatic operation
Forced operation on Normal source
Forced operation on Replacement source
Stop (both Normal and Replacement sources off)

b
b
b
b

b
b
b
b

b
b
b
b
b

Automatic operation
Monitoring of the Normal source and automatic transfer
Generator set startup control
Delayed shutdown (adjustable) of generator set
Load shedding and reconnection of non-priority circuits
Transfer to the Replacement source if one of the phases
of the Normal phase is absent

Test
DB403809.eps

By opening the P25M circuit breaker supplying the controller


By pressing the test button on the front of the controller

b
b

Indications
Circuit breaker status indication on the front of the controller:
on, off, fault trip
Automatic mode indicating contact

Other functions

BA controller.

Selection of type of Normal source


(single-phase or three-phase) (1)
Voluntary transfer to Replacement source
(e.g. energy management commands)
During peak-tariff periods (energy management commands)
forced operation on Normal sourceif Replacement source
not operational
Additional contact (not part of controller).
Transfer to Replacement source only if contact is closed
(e.g. used to test the frequency of UR).
Setting of maximum startup time for the replacement source

b
b

b
b

DB403810.eps

Options
Communication option

Power supply
Control voltages (2)

110 V
220 to 240 V 50/60 Hz
380 to 415 V 50/60 Hz
and 440 V 60 Hz

b
b
b

b
b
b

0.35 Un y voltage y8Q


0.5 Un y voltage y8Q
voltage u 0.85 Un

b
b
b

Operating thresholds
Undervoltage
Phase failure
Voltage presence

IP degree of protection (EN 60529) and IK degree of protection against


external mechanical impacts (EN 50102)

UA controller.

Front
Side
Connectors
Front

IP40
IP30
IP20
,.

b
b
b
b

b
b
b
b

Characteristics of output contacts (dry, volt-free contacts)


Rated thermal current (A)
8
Minimum load
10 mA at 12 V
Output contacts:
Position of the Auto/Stop switch
b
b
Load shedding and reconnection order
b
Generator set start order.
b
AC
DC
8WLOLVDWLRQFDWHJRU\ ,(&
AC12 AC13 AC14 AC15 DC12 DC13
Operational current (A)
24 V
8

5
5
8
2
48 V
8

5
5
2
110 V
8
6
4
4
0.6
220/240 V
8
6
4
3
250 V
0.4
380/415 V
5
440 V
4
660/690 V
(1) For example, 220 V single-phase or 220 V three-phase.
(2) The controller is powered by the ACP control plate. The same voltage must be used for the ACP
plate, the IVE unit and the circuit breaker operating mechanisms. If this voltage is the same as
the source voltage, then the Normal and Replacement sources can be used directly for the
power supply. If not, an isolation transformer must be used.
A-18

3%B6(HSV

Controller installation

ACP control plate


The control plate provides in a single unit:
b protection for the BA or UA controller with two highly limiting P25M circuit breakers
LQQLWHEUHDNLQJFDSDFLW\ IRUSRZHUGUDZQIURPWKH$&VRXUFH
b control of circuit-breaker ON and OFF functions via two relay contactors
b connection of the circuit breakers to the BA or UA controller via a built-in terminal
block.
Control voltages
b 110 V 50/60 Hz.
b 220 to 240 V 50/60 Hz.
b 380 to 415 V 50/60 Hz and 440 V 60 Hz.
The same voltage must be used for the ACP control plate, the controller and the
circuit breaker operating mechanisms.
Installation
Connection between the ACP control plate and the IVE unit may use:
b wiring done by the installer
b prefabricated wiring (optional).

Installation of the BA and UA controllers


The BA and UA controllers may be installed in one of two manners:
b directly mounted on the ACP control plate
b mounted on the front panel of the switchboard
b if the length of the connection between the controller and the control plate (ACP) is
less than or equal to 1 m, the connecting cable ref. 29368 can be ordered as an
optional extra. Cables longer than 1 m, but not longer than 2 m will be the
responsibility of the installer.
DB126269.eps

ACP control plate.

'%HSV

Mounting on the ACP control plate.

Mounting on the front panel of the switchboard.

A-19

Functions
and characteristics

The BA controller is used to create simple sourcechangeover systems that switch from one source to
another depending on the presence of voltage UN on
the Normal source.
It is generally used to manage two permanent sources
and can control Compact NS, Compact NSX and
Masterpact NT/NW circuit breakers and switchdisconnectors.

Associated controllers
BA controller

Operating modes
A four-position switch may be used to select:
b automatic operation
b forced operation on the Normal source
b forced operation on the Replacement source
b stop (both Normal and Replacement sources off).

Setting the time delays

DB403841.eps

Time delays are set on the front of the controller.


t1. delay between detection that the Normal source has failed and the transmission
of the order to open the Normal source circuit breaker (adjustable from 0.1 to
30 seconds).
t2. delay between detection that the Normal source has returned and the
transmission of the order to open the Replacement source circuit breaker
(adjustable from 0.1 to 240 seconds).

Circuit breaker commands and status indications


The status of the circuit breakers is indicated on the front of the controller.
b ON, OFF, fault.
A built-in terminal block may be used to connect the following input/output signals:
b inputs:
v voluntary order to transfer to source R (e.g. for special tariffs, etc.)
v additional control contact (not part of the controller). Transfer to the Replacement
source takes place only if the contact is closed (e.g. used to test the frequency of UR,
etc.)
b outputs:
v indication of operation in automatic or stop mode via changeover contacts.

Test

DB403838.eps

It is possible to test the operation of the BA controller by turning OFF (opening)


the P25M circuit breaker for the Normal source and thus simulating a failure of
voltage UN.

BA Controller

Front of the BA controller.

A-20

BA controller
Operating sequences

Switch set to the N position (forced


operation on the Normal source)

'%HSV

DB126548.eps

Switch set to Auto (automatic operation and special-tariff mode)

Switch set to the Stop position


DB126550.eps

DB126549.eps

Switch set to the R position


(forced operation on the Replacement source)

Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker

WAITING 7KHV\VWHPH[LWVWKLVPRGHZKHQWKHRSHUDWLQJPRGHLVPRGLHGRU
when an external event occurs (e.g. failure or return of UN).

1
1 The number sends to the indicated step when
the condition is true.

A-21

Functions
and characteristics

DB403842.eps

The UA controller is used to create a sourcechangeover system integrating the following automatic
functions:
b transfer from one source to another depending on
the presence of voltage UN on the Normal source
b startup of an engine generator set
b shedding and reconnection of non-priority circuits
b transfer to the Replacement source if one of the
phases on the Normal source fails.
The UA controller can control Compact NS,
Compact NSX and Masterpact NT/NW devices.

Associated controllers
UA controller

Operating modes
A four-position switch may be used to select:
b automatic operation
b forced operation on the Normal source
b forced operation on the Replacement source
b stop (both Normal and Replacement sources off, then manual operation).

Setting the time delays


Time delays are set on the front of the controller.
t1. delay between detection that the Normal source has failed and the transmission
of the order to open the Normal source circuit breaker (adjustable from 0.1
to 30 seconds).
t2. delay between detection that the Normal source has returned and the
transmission of the order to open the Replacement source circuit breaker
(adjustable from 0.1 to 240 seconds).
t3. delay following opening of QN with load shedding and before closing of QR
(adjustable from 0.5 to 30 seconds).
t4. delay following opening of QR with load reconnection and before closing of QN
(adjustable from 0.5 to 30 seconds).
t5.GHOD\IRUFRQUPDWLRQWKDW81LVSUHVHQWEHIRUHVKXWWLQJGRZQWKHHQJLQH
generator set (adjustable from 60 to 600 seconds).
t6. delay before startup of the engine generator set (120 or 180 seconds).

Commands and indications


Circuit breaker status indications on the front of the controller:
b ON, OFF, fault.
A built-in terminal block may be used to connect the following input/output signals:
b inputs:
v voluntary order to transfer to source R (e.g. for special tariffs, etc.)
v additional control contact (not part of the controller). Transfer to the Replacement
source takes place only if the contact is closed (e.g. used to test the frequency of UR,
etc.)
b outputs:
v control of an engine generator set (ON / OFF)
v shedding of non-priority circuits
v indication of operation in automatic mode via changeover contacts.

'%HSV

Distribution-system settings

UA Controller

Three switches are used to:


b select the type of Normal source, whether single-phase or three-phase
(e.g. 240 V single-phase or 240 V three-phase)
b select whether to remain (or not) on the Normal source if the Replacement
source is not operational during operation on special tariffs
b select the maximum permissible startup time for the engine generator set during
operation on special tariffs (120 or 180 seconds).

Test
A pushbutton on the front of the controller may be used to test transfer from the
Normal source to the Replacement source, then the return to the Normal source.
The test lasts approximately three minutes.

COM communications option

Front of the UA controller.

A-22

Using the internal bus protocol, this option may be used to remote the following
information:
b circuit breaker status (ON, OFF, fault trip)
b presence of the Normal and Replacement voltages
b presence of an order for forced operation (e.g. special tariffs)
b VHWWLQJVDQGFRQJXUDWLRQLQIRUPDWLRQ
b status of non-priority circuits (loads shed or not)
b position of the switch (stop, auto, forced operation on the Normal source, forced
operation on the Replacement source).

UA controller
Operating sequences
Forced operation mode
Switch set to the N position (forced operation on
the Normal source)
DB126552.eps

DB126551.eps

Switch set to the R position (forced operation on the Replacement source)

DB126553.eps

Switch set to the Stop position

WAITING The system exits this mode when the


RSHUDWLQJPRGHLVPRGLHGRUZKHQDQ
external event occurs (e.g. failure or return
of UN).
When the UA controller is not energised, the output for
generator set startup is activated).
Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker

A-23

Functions
and characteristics

DB126554.eps

Switch set to the Auto position (special-tariff mode)


WAITING The system exits this mode when the
RSHUDWLQJPRGHLVPRGLHGRUZKHQDQ
external event occurs (e.g. failure or return
of UN).
When the UA controller is not energised, the output for
generator set startup is activated).

Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker
B : Penalties accepted (N ON), i.e. B = 1

The number sends to the indicated step when


the condition is true.

A-24

Associated controllers
UA controller
Operating sequences
Special-tariff mode

UA controller
Operating sequences
Test mode and automatic operation
DB126555.eps

Switch set to the Auto position (automatic operation and test mode).

WAITING The system exits this mode when the


RSHUDWLQJPRGHLVPRGLHGRUZKHQDQ
external event occurs (e.g. failure or return
of UN).
When the UA controller is not energised, the output for
generator set startup is activated).
Key
UN : Normal source voltage
UR : Replacement source voltage
N : Normal source circuit breaker
R : Replacement source circuit breaker
B : Penalties accepted (N ON), i.e. B = 1
(*) The test lasts 180 seconds.

The number sends to the indicated step when


the condition is true.

A-25

Functions
and characteristics

Operating sequences
IVE unit

Db126594.eps

IVE unit

Symbols
QN : Normal Compact circuit breaker equipped
for remote operation (motor mechanism)
QR : Replacement Compact circuit breaker
equipped for remote operation (motor
mechanism)
ON : Circuit breaker QN opening order
OR : Circuit breaker QR opening order
IN : Circuit breaker QN closing order
IR : Circuit breaker QR closing order
L1 : Faulty Normal indication LED
L2 : Faulty Replacement indication LED

Key
O: OFF (circuit open)
I: ON (circuit closed
: either ON or OFF.

A-26

Note: following all trips (overload, short-circuit, earth-leakage fault, voluntary trip), a manual
reset on the front of the motor mechanism is required.

BA/UA controller

Db126595.eps

BA controller

Inputs
UN : Normal source voltage
UR : Replacement source voltage
KT : order for forced-operation on R
KR : additional check before transfer
Outputs
QN : Normal source circuit breaker
QR : Replacement source circuit breaker

Db126599.eps

UA controller

Inputs
UN : Normal source voltage
UR : Replacement source voltage
KT : order for forced-operation on R
KR : additional check before transfer
Outputs
KG : order to the genset
SH : load-shedding order
QN : Normal source circuit breaker
QR : Replacement source circuit breaker

Key
O: OFF (circuit open)
I: ON (circuit closed
: either ON or OFF.

Important
If UR is not ON when the transfer order is issued (KT or UN), the sequence is not carried out.
If KR status is not ON when the transfer order is issued (KT or UN), the transfer sequence is
carried out later when KR status becomes I.

$

COM communications option

'%HSV

Functions
and characteristics

Electrical-installation management

Communication
interface
RS 232, Ethernet

RS 485

Communications option for Compact NS u 630 A


and Masterpact NT/NW
The COM communications option is compatible with all the source-changeover
systems for Compact NS630b-1600 and Masterpact NT/NW circuit breakers and
switch-disconnectors.
It can be used to remote status information. It may not be used to operate the circuit
breakers (only possible locally on the front of the UA150 controller).
Masterpact and Compact NS630b to 1600 circuit breakers and switch-disconnectors
are compatible with the Modbus ECO COM option.
Depending on the trip units or control units used, the COM option may also be used
to analyse distribution-system parameters required for the operating and
maintenance assistance.

Circuit breaker communication


SwitchCircuit breaker
disconnector

Compact NS630b-1600 status indications

Communication bus

ON / OFF
Fault trip
Connected / disconnected position
BBus

JBus

OK

com.

com.

error

24V

error

9600
19200
3

N1

N2

1
15
3

9
13
5

1
15

N1

7
9

13

N2

b
b
b

Masterpact NT/NW status indications

N
DC150

DC150 data
concentrator

ON / OFF
Fault trip
Connected / disconnected position

b
b

b
b
b

Operating and maintenance assistance


Operating and maintenance aids

Devices

N
R

IVE

A-28

Masterpact

Masterpact

Modbus

Measurement
Current
A
E
P
Voltages, power...
E
P
Frequency
P
Power quality: fundamental, harmonics
Programming of demand metering
E
P
Fault readings
Type of fault
A
E
P
Interrupted current
P
Waveform capture
On faults
On demand or programmed
Histories and logs
Trip history
E
P
Alarm history
P
Event logs
P
Indicators
Counter operation
A
E
P
Contact wear
P
Maintenance register
P
Note: see the description of the Micrologic control units for further details on protection and
alarms, measurements, waveform capture, histories, logs and maintenance indicators.

H
H
H
H
H
H
H
H
H
H
H
H
H
H
H

COM communications option

Controller

UA150

Status indications
Normal source
ON / OFF
Circuit breaker ON
Fault trip (SDE)
Voltage presence
Replacement source
Circuit breaker ON
Fault trip (SDE)
Voltage presence
Status of R voltage contact
Controller
Automatic mode
Normal mode
Replacement mode
Stop mode
Testing
Replacement engine generator set
Genset failure
Genset OFF
Genset ON
Shedding of non-priority circuits
Reconnection of non-priority circuits

b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b
b

'%HSV

Settings
Time delay t1 for validation of UN absence

Time delay t2 for validation of UN return


Time delay t3 for wait between opening of N and closing of R
Time delay t4 for wait between opening of R and closing of N
Time delay t5 for wait between return of UN and order for genset shutdown
Time delay t6 for wait before declaring genset failure
Penalties accepted to avoid special tariff transfer

b
b
b
b
b
b

DC150 data concentrator


The DC150 data concentrator is designed to centralise the information provided
by the communicating switchgear of the Digipact range and to make this information
accessible to a supervisor or PLC under the MODBUS/JBUS protocol.

N
DC150

BBus

JBus

OK

com.

com.

error

24V

error

9600
19200
3

N1

N2

1
15
3

9
13
5

1
15

N1

Main characteristics
b Power supply:
110 V AC to 240 V AC
115 V DC to 125 V DC.
b Weight: 1.5 kg.
b Installation: on panel with the DC150 box which must be earthed on metal part of
the installation.
b Over dimensions H x W x D (mm): 138.5 x 100 x 192.8.

7
9

N2

13

A-29

TOOLS
schneider-electric.com

This international site allows you


to access all the Schneider Electric
Solution and Product information via :
p comprehensive descriptions
p range data sheets
p a download area
p product selectors
p ...
You can also access the information
dedicated to your business and get
in touch with your Schneider Electric
country support.

Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Compact INS/INV, Masterpact

Dimensions

Presentation
Functions and characteristics

2
A-1

Manual source-changeover systems


Interlocking of direct rotary handles
Interlocking of extended rotary handles
Interlocking of toggles
Complete source-changeover assembly
'RZQVWUHDPFRXSOLQJDFFHVVRU\

B-2
B-3
B-5
B-6
%

Remote-operated source-changeover systems


Interlocking on a base plate
Interlocking using connecting rods
Interlocking using cables
IVE unit, BA and UA automatic controllers
Electrical diagrams
Catalogue numbers and order forms

B-9
B-13
B-15
B-20
C-1
D-1

B-1

Manual source-changeover
systems

Dimensions

Interlocking of direct rotary handles


Compact NSX100 to 630
'%HSV

DB404483.eps

Front-panel cutout
DB126608.eps

Dimensions

Dimensions (mm)
Type
NSX100/160/250
NSX400/630

A
325
416

B
90
115

C

100

D

200

F
156
210

G
133


H
9.25
5

J
9
24.6

K
295
386

L

100

M
150


N



P
155


Compact INS/INV250 - 100 to 250 / Compact INS/INV320/400/500/630


Db101611.eps

Front-panel cutout
Db101610.eps

Db101609.eps

Dimensions

Dimensions (mm)
Type
A
B
C
INS/INV250 - 100/160/200/250 325
90

INS/INV320/400/500/630
416
115
100
Note: X and Y are the symmetry planes for a 3-pole device.

B-2

D

200

F
156
210

G
106
130

H

22.5

K
295
386

L

100

M
150


N



P
131
160.4

Interlocking of extended rotary handles


Compact NSX100 to 630
DB404482.eps

Front-panel cutout
DB126608.eps

DB126610.eps

Dimensions

Dimensions (mm)
Type
NSX100/160/250
NSX400/630

A
325
416

B
90
115

C

100

D

200

F
156
210

G min

195

G max
600
600

H
9.25
5

J
9
24.6

P
25.5
30.8

Q
25.5
30.8

Compact INS40/63/80/100/125/160 / Compact INS/INV250 - 100 to 250 / Compact INS/INV320/400/500/630


'EHSV

Front-panel cutout
Db101615.eps

Db101614.eps

Dimensions

Dimensions (mm)
Type
INS40/63/80
INS100/125/160
INS/INV250 - 100/160/200/250
INS320/400/500/630

A
325
325
325
416

B
90
90
90
115

C



100

D



200

F
156
156
156
210

G min
155
200
185
204

G max
396
441
600
600

H
0
0

22.5

P
25.5
25.5
25.5
30.8

Q
25.5
25.5
25.5
30.8

B-3

Manual source-changeover
systems

Dimensions

Interlocking of extended rotary handles


Compact NS630b to 1600
'EHSV

DB101618.eps

Dimensions

Db101619.eps

Front-panel cutout

Dimensions (mm)
Type
NS630b/800/1000/1200/1600

B-4

A
411

B
63.5

C
98

D


F
280

G min
218

G max
605

H
25

J
24

P
25.5

Q
25.5

R
64

Interlocking of toggles
Compact NSX100 to 630
4 poles

4 poles on left
Db101624.eps

3 poles on left
Db101623.eps

Front-panel cutout

DB126614.EPS

3 poles
DB126613.EPS

DB126612.EPS

Dimensions

Dimensions (mm)
Type
NSX100/160/250
NSX400/630

C2
54
92.5

C3
108
182

L
52.5


L16
140
185

L17
245
325

L18
280


R2
54


R18
89
116.5

R19
140
185

P5
83


P
120
150

B-5

Manual source-changeover
systems

Dimensions

Complete source-changeover assembly


Assembly for INS250 - 100 to 250 / Assembly for INS320/400/500/630
Db101626.eps

Db101625.eps

Dimensions

'EHSV

Front-panel cutout

Dimensions (mm)
Type
INS250 - 100/160/200/250
INS320/400/500/630

A
60.4
82.5

B
130.4


C
296
395

D
68
102.5

E
136
205

F
131
155

G
61.8


H



I
42
64

J
84
128

K
156
210

L
186.5
213

M
5.5
8

N
50
50

'%HSV

Db101650.eps

Db101651.eps

Dimensions of the complete source-changeover assembly with an extended handle

Dimensions (mm)
Type
A
INS250 - 100/160/200/250 60.4
INS320/400/500/630
82.5

B
130.4


C
295
395

E
136
205

K
156
210

L
138.5
162.5

Dimensions (mm)
Type
P
INS250 - 100/160/200/250 100
INS320/400/500/630
150

Mmax Mmin
 195
593
220.5

Q
64
64

Note: lines X and Y indicate the axes of symmetry of the switch-disconnector.


Reference plane Z corresponds to the back of the switch-disconnector.

B-6

M
631
658

N
50


Downstream coupling accessory


Compact NSX100 to NSX630 RQO\IRU&RPSDFW16;[HGGHYLFHV
'%HSV

DB413282.eps

Dimensions

DB413569.eps

Connection

DB413280.eps

Dimensions

Dimensions (mm)
Type
NSX100/160/250
NSX400/630

G2
118
165.9

G3
181.5


G28
244.5


G29
96
143.5

G30
152.5
220.5

G52



K1
35
45

K2
35
45

K3
51


K4
156
210

K8

113.5

K9



K16
8
15

L28
320
425

L29
99.5
130

L30
300
400

L31
89.5


L32

5.15

L33
130.5


L34
139.5


L35

98.5

L36
19.5
26

L37

115

L39
9.5
9.85

L40
140


T
6
6

Dimensions (mm)
Type
NSX100/160/250
NSX400/630

Note: FRXSOLQJDFFHVVRU\RQO\IRUFKDQJHRYHUV\VWHPVXVLQJ[HGYHUVLRQVRI&RPSDFW16;FLUFXLWEUHDNHUV

%

Manual source-changeover
systems

Dimensions

Downstream coupling accessory


Compact INS250 - 100 to 250 / Compact INS320/400/500/630
'%HSV

DB413283.eps

DB413286.eps

Dimensions

Connection

DB413284.eps

'%HSV

Dimensions

Dimensions (mm)
Type
INS250-100/160/200/250
INS320/400/500/630

G2
105.5
141

G3
169


G28
232
313

G29
83.5
119

G30
140
195.6

G52
165.5
240

K1
35
45

K2
35
45

K3
51


K4
156
210

K8

88.5

K9



K16
25.5


L28
320
425

L29
83


L30
300
400

L31

95

L32
12.8


L33
130.5


L34
139.5


L35

98.5

L36
21.5
26

L37

92.5

L39
8.5
12.65

L40
140


T
6
6

Dimensions (mm)
Type
INS250-100/160/200/250
INS320/400/500/630

B-8

Remote-operated
source-changeover systems
Interlocking on a base plate
Compact NSX100 to 250
Fixed device

Withdrawable device
DB126619.EPS

'%HSV

DB413288.eps

Dimensions, 3 or 4 poles

(*) Short terminal shields are


mandatory.

Horizontal mounting
Db101638.eps

'EHSV

Vertical mounting

Dimensions (mm)
Type
NSX100/160/250
NSX400/630

G50

180

G51
285
360

H20
62.5
100

H21

152

H22
45.5
83

H23

123

H42
60
60

H43
120
120

H44
144.5
189

H45
300


H46



K25
156
210

K35
210.5
282.5

L31
110.5
150.5

L32
354
466

P7
25
25

P8
45
45

P9

100

P32
182
256

P33
143
215

P50
25
25

P52
99.5
123

P54
21
21

T9
9
9

T10
6
6

U
y 32
y 32

K36
300
400

Dimensions (mm)
Type
NSX100/160/250
NSX400/630

Note: FRXSOLQJDFFHVVRU\RQO\IRUFKDQJHRYHUV\VWHPVXVLQJ[HGYHUVLRQVRI&RPSDFW16;FLUFXLWEUHDNHUV

B-9

Remote-operated
source-changeover systems

Dimensions

Interlocking on a base plate


Compact NSX400 to 630
DB413290.eps

Fixed device

DB413289.eps

Dimensions, 3 or 4 poles

DB126622.EPS

Withdrawable device

Note: FRXSOLQJDFFHVVRU\RQO\IRUFKDQJHRYHUV\VWHPVXVLQJ[HGYHUVLRQVRI&RPSDFW16;
circuit breakers.

Horizontal mounting
Db101638.eps

'EHSV

Dimensions
Vertical mounting

Note: dimensions see page B-9.

B-10

(*) Short terminal shields are mandatory.

Normal and Replacement source devices: NSX100 to NSX250


Front-panel cutout

DB413291.eps

DB404134.eps

Dimensions

95

95

47.5

47.5

77
29.5

NSX100
to
NSX250

156

NSX100
to
NSX250

145
177

Normal and Replacement source devices: NSX400 to NSX630


DB404135.eps

Front-panel cutout

DB413300.eps

Dimensions

127

127
63.5

63.5

127
42

NSX400
to
NSX630

210

NSX400
to
NSX630

217
249

Note for Compact NSX:


For dimensions with the accessories (IP40 escutcheons and Vigi escutcheon protection collars), see Catalogue Compact.

B-11

Remote-operated
source-changeover systems

Dimensions

Interlocking on a base plate


NSX400 to NSX630 as the Normal device, NSX100 to NSX250 as the Replacement device
Front-panel cutout
DB404136.eps

DB126623.EPS

Dimensions

NSX400
to
NSX630

B-12

NSX100
to
NSX250

Interlocking using connecting rods


Two Compact NS630b to NS1600 devices one above the other
Withdrawable devices
Db101655.eps

'%HSV

Fixed devices

Two Masterpact NT devices one above the other


Withdrawable devices
Db101655.eps

Db101656.eps

Fixed devices

B-13

Dimensions

Remote-operated
source-changeover systems
Interlocking using connecting rods

Two Masterpact NW devices one above the other


Withdrawable devices
'%HSV

'%HSV

Fixed devices

B-14

Interlocking using cables


Two Compact NS630b to NS1600 devices side-by-side
Withdrawable devices

Db101661.eps

Db101662.eps

Fixed devices

Two Masterpact NT devices side-by-side


Drawout devices
Db101662.eps

Db101663.eps

Fixed devices

Combination of two Masterpact NT and NW devices side-by-side


Drawout devices
'%HSV

Db101664.eps

Fixed devices

B-15

Dimensions

Remote-operated
source-changeover systems
Interlocking using cables

Two Masterpact NW devices side-by-side


Drawout devices
'EHSV

Db101666.eps

Fixed devices

Three Masterpact NW devices side-by-side


Db101668.eps

Fixed devices

Db101669.eps

Drawout devices

B-16

Two Compact NS630b to NS1600 devices one above the other


Withdrawable devices
'EHSV

'%HSV

Fixed devices

Two Masterpact NT devices one above the other


Drawout devices
'EHSV

'EHSV

Fixed devices

%

Dimensions

Remote-operated
source-changeover systems
Interlocking using cables

Two Masterpact NW devices one above the other


Drawout devices
'%HSV

'%HSV

Fixed devices

Two Masterpact NT and NW devices one above the other


Drawout devices
DB404148.eps

'%HSV

Fixed devices

B-18

Dimensions

Remote-operated
source-changeover systems
Interlocking using cables

Three Masterpact NW devices one above the other


Drawout devices
'%HSV

'%HSV

Fixed devices

B-19

Remote-operated
source-changeover systems

Dimensions

IVE unit, BA and UA automatic controllers

'EHSV

Door cutout for BA/UA controllers


Db101682.eps

Db101681.eps

Db101680.eps

ACP control plate and BA/UA controllers

DB101683.eps

'EHSV

IVE unit

(1) Cutout according DIN 43700 standard.

B-20

Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Compact INS/INV, Masterpact

Electrical diagrams

Presentation
Functions and characteristics
Dimensions

2
A-1
B-1

Remote-operated source-changeover systems


2 Compact NSX100/630 devices
2 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices

C-2
C-5

Source-changeover systems with automatic controllers


2 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices
&RQWUROOHUVHWWLQJV
2 Compact NSX100/630, NS630b/1600 or Masterpact NT/NW devices

C-6
&
C-8

Remote-operated source-changeover systems


2 Compact NS630b/1600 devices
2 Masterpact NT or NW devices
0DVWHUSDFW1:GHYLFHV

C-9
C-12
&

Source-changeover systems with automatic controllers


2 Masterpact NT or NW devices
Catalogue numbers and order forms

C-26
D-1

C-1

Electrical diagrams

Remote-operated
source-changeover systems
2 Compact NSX100/630 devices
Diagram no. 51201177

Source-changeover system without automatic-control system


Local reset

Db401805.eps

Db101659.eps

Without auxiliaries for emergency off

Db101660.eps

Voluntary remote reset

Automatic reset

(1)3UHIDEULFDWHGZLULQJFDQQRWEHPRGLHG

Legends
QN Normal source Compact NSX equipped with motor mechanism
QR Replacement source Compact NSX equipped with motor
mechanism
SDE fault-trip indication contact
IVE electrical interlocking and terminal block unit
MT motor mechanism
OF2 breaker ON/OFF indication contact
RN reset order for breaker QN
RR reset order for breaker QR

C-2

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: diagram shown with circuits de-energised, circuit breakers
open and relays in normal position.

Electrical diagrams

Remote-operated
source-changeover systems
2 Compact NSX100/630 devices
Diagram no. 51201178

Source-changeover system without automatic-control system


DB415114.eps

With emergency off by MN release and automatic reset

KA5

KA5

Automatic reset

KA5

KA5

(1) Prefabricated wiring supplied.


(2) Independent auxiliary source.

Legends
QN Normal source Compact NSX equipped with
motormechanism
QR Replacement source Compact NSX equipped with motor
mechanism
MN undervoltage release
OF2 breaker ON/OFF indication contact
SDE fault-trip indication contact
MT motor mechanism
IVE electrical interlocking and terminal block unit
BP emergency off button with latching
KA5 auxiliary relay
F1 auxiliary power supply circuit breaker

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: after a fault trip, the breaker must be reset manually by
pressing its reset button.
Diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.

C-3

Electrical diagrams

Remote-operated
source-changeover systems
2 Compact NSX100/630 devices
Diagram no. 51201179

Source-changeover system without automatic-control system


DB415115.eps

With emergency off by MX release and automatic reset

Automatic reset

(1) Prefabricated wiring supplied


(2) This source can be:
b the source present in the case of voltage monitoring
b an independent source.
In this case, the MX release must be protected.
(3) The reset orders must be delayed by 0.3 seconds.
Legends
QN Normal source Compact NSX equipped with motor
mechanism
QR Replacement source Compact NSX equipped with motor
mechanism
SDE fault-trip indication contact
OF2 breaker ON/OFF indication contact
MX shunt release
MT motor mechanism
IVE electrical interlocking and terminal block unit
KA5 time-delayed auxiliary relays
KA6 time-delayed auxiliary relays
F1 auxiliary power supply circuit breaker
F2 auxiliary power supply circuit breaker

C-4

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: after a fault trip, the breaker must be reset manually by
pressing its reset button.
Diagram shown with circuits de-energised, circuit breakers open
and relays in normal position.

Remote-operated
source-changeover systems

Electrical diagrams

2 Compact NSX100/630, NS630b/1600


or Masterpact NT/NW devices
Electrical interlocking by the IVE unit
Simultaneous order to Normal/Replacement source
DB415113.eps

DB415112.eps

Independent order to Normal/Replacement source

CN CR

CN CR

Closure order to
"Replacement" source (1)

KA1
KA1

Closure order to
"Normal" source (1)

KA2
KA3

Opening order to
"Replacement" source

KA4

KA1
KA1

Order for transfer to


"Normal" source (1)

KA2
KA2

KA2

Opening order to
"Normal" source

Order for transfer to


"Replacement" source (1)

KA3

KA4

Controlling each circuit breaker independently.

Control of two circuit breakers by common transfer order.

(1) See section IMPORTANT here after.


(2) Operating diagram: the SDE fault-trip signals are transmitted to the IVE unit. The SDE auxiliary contacts are mounted in the circuit breakers.

IMPORTANT
The relays controlling the closing order to the Normal and Replacement circuit breakers must be mechanically and/or electrically
interlocked to prevent them from giving simultaneous closing commands.
It is recommended to use Tesys K relays from Schneider Electric reference LC2-K06010pp. These relays are mechanically and electrically
interlocked.

Legends
ON Normal source opening order
OR Replacement source opening order
CN Normal source closing order
CR Replacement source closing order
KA1 auxiliary relay
KA2 auxiliary relay
KA3 auxiliary relay
KA4 auxiliary relay
L1
Normal source fault-trip signal
L2
Replacement source fault-trip signal
N
Normal source auxiliary wiring connector
R
Replacement source auxiliary wiring connector

Note: diagram shown with circuits de-energised, circuit breakers


open and relays in normal position.

C-5

Electrical diagrams

Source-changeover systems
with automatic controllers
2 Compact NSX100/630, NS630b/1600
or Masterpact NT/NW devices

Source-changeover system with UA controller


'%HSV

'%HSV

Load shedding and genset management

'%HSV

Transfer conditions

Terminals 20 and 21:


additional control contact (not part of
controller).

'%HSV

Tests on Normal and Replacement


source voltages
Normal source voltage UN test

Replacement source voltage UR test


The single-phase check for UR is
implemented across terminals 1 and 5
of circuit breaker Q2.

Legends
Q1
circuit breaker supplying and protecting the automaticcontrol circuits for the Normal source
Q2
circuit breaker supplying and protecting the automaticcontrol circuits for the Replacement source
ACP control plate
UA
automatic controller
IVE
electrical interlocking and terminal block unit

C-6

Note: diagram shown with circuits de-energised, circuit breakers


open and relays in normal position.

Source-changeover systems
with automatic controllers

Electrical diagrams

Controller settings
Source changeover system with UA controller
Using communication functions
'%HSV

'%HSV

Controller settings

Tests on Normal source voltage


A = 0 single-phase test,
A = 1 three-phase test.

The address of the UA 150 controller is set using


the two BBus dials.

Voluntary transfert (e.g. for energy management)


b action in the event of genset failure
B = 0 circuit breaker N opens,
B = 1 circuit breaker N remains closed.
b maximum permissible genset startup time (T6)
C = 0 T = 120 s,
C = 1 T = 180 s.
After this time has elapsed, the genset is considered to
have failed.

&

Electrical diagrams

Source-changeover systems
with automatic controllers
2 Compact NSX100/630, NS630b/1600
or Masterpact NT/NW devices

Source-changeover system with BA controller


'%HSV

'%HSV

Coupling

'%HSV

Transfer conditions

Terminals 20 and 21:


additional control contact (not part of
controller).

Tests on Normal and Replacement


source voltages
The single-phase check for UN and UR
is implemented across terminals 1 and 5
of circuit breakers Q1 and Q2.

Legends
Q1
circuit breaker supplying and protecting the automaticcontrol circuits for the Normal source
Q2
circuit breaker supplying and protecting the automaticcontrol circuits for the Replacement source
ACP control plate
BA
automatic controller
IVE
electrical interlocking and terminal block unit

C-8

Note: diagram shown with circuits de-energised, circuit breakers


open and relays in normal position.

Remote-operated
source-changeover systems

Electrical diagrams

2 Compact NS630b/1600 devices


Diagram no. 51201183

DB415209.eps

Electrical interlocking by IVE unit

IVE

* IVE connection see pages C5, C6 or C8

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN
Normal source Compact NS630b to 1600
QR
Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
IVE
electrical interlocking and terminal block unit
ON
Normal source opening order
OR
Replacement source opening order
CN
Normal source closing order (0.25 second delay)
CR
Replacement source closing order (0.25 second delay)
MT
Motor Mechanism

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1)1RWWREHZLUHGRQ[HGYHUVLRQ
(2) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: after a fault trip, the breaker must be reset manually by
pressing its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MT...).

C-9

Remote-operated
source-changeover systems

Electrical diagrams

2 Compact NS630b/1600 devices


Diagram no. 51201184

DB415210.eps

Electrical interlocking by IVE unit with emergency off by shunt release

KA5

CN CR

Interlocking by IVE see page C5:


- Independent Order to
Normal/Replacement source
- Simultaneous Order to
Normal/Replacement source

KA5

KA5

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN
Normal source Compact NS630b to 1600
QR
Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
IVE
electrical interlocking and terminal block unit
MX
shunt release
BP
emergency off button with latching
KA5 auxiliary relay
ON
Normal source opening order
OR
Replacement source opening order
Normal source closing order (0.25 second delay)
CN
CR
Replacement source closing order (0.25 second delay)
MT
Motor Mechanism

Wiring colour codes


RD

GN

BK

VT

YE

red

green

black

violet

yellow grey

C-10

GY

WH

BN

white

brown

(1)1RWWREHZLUHGRQ[HGYHUVLRQ
(2) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: after a fault trip, the breaker must be reset manually by
pressing its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation, MX,
MT...).

Remote-operated
source-changeover systems

Electrical diagrams

2 Compact NS630b/1600 devices


Diagram no. 51201185

DB415211.eps

Electrical interlocking by IVE unit with emergency off by undervoltage release

KA5

CN CR

Interlocking by IVE see page C5:


- Independent Order to
Normal/Replacement source
- Simultaneous Order to
Normal/Replacement source

KA5

KA5

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN
Normal source Compact NS630b to 1600
QR
Replacement source Compact NS630b to 1600
OF... breaker ON/OFF indication contact
SDE fault-trip indication contact
CE1 connected-position indication contact (carriage switch)
F1
auxiliary power supply circuit breaker
IVE
electrical interlocking and terminal block unit
MN
undervoltage release
BP
emergency off button with latching
KA5 auxiliary relay
ON
Normal source opening order
OR
Replacement source opening order
CN
Normal source closing order (0.25 second delay)
CR
Replacement source closing order (0.25 second delay)
MT
Motor Mechanism

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1)1RWWREHZLUHGRQ[HGYHUVLRQ
(2) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: after a fault trip, the breaker must be reset manually by
pressing its reset button.
Diagram shown with circuit breakers in connected position, open,
charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation, MN,
MT...).

C-11

Remote-operated
source-changeover systems

Electrical diagrams

2 Masterpact NT or NW devices
Diagram no. 51201142

DB415212.eps

Electrical interlocking by IVE unit with lockout after a fault

IVE

* IVE connection see pages C5, C6 or C8

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN
Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
F1
auxiliary power supply circuit breaker
ON
Normal source opening order
OR
Replacement source opening order
CN
Normal source closing order (0.25 second delay)
CR
Replacement source closing order (0.25 second delay)

Wiring colour codes


RD
red

C-12

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, XF...).

Remote-operated
source-changeover systems

Electrical diagrams

2 Masterpact NT or NW devices
Diagram no. 51201143

DB415213.eps

Electrical interlocking by IVE unit with lockout after a fault and emergency off by shunt release

KA5

CN CR

Interlocking by IVE see page C5:


- Independent Order to
Normal/Replacement source
- Simultaneous Order to
Normal/Replacement source

KA5

KA5

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
Normal source Masterpact NT or NW
QN
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
KA5 auxiliary relay
F1
auxiliary power supply circuit breaker
BP
emergency off button with latching
ON
Normal source opening order
OR
Replacement source opening order
CN
Normal source closing order (0.25 second delay)
CR
Replacement source closing order (0.25 second delay)

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, XF...).

BN
brown

C-13

Remote-operated
source-changeover systems

Electrical diagrams

2 Masterpact NT or NW devices
Diagram no. 51201144

DB415214.eps

Electrical interlocking by IVE unit with lockout after a fault and emergency off by undervoltage release

KA5

CN CR

Interlocking by IVE see page C5:


- Independent Order to
Normal/Replacement source
- Simultaneous Order to
Normal/Replacement source

KA5

KA5

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN
Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
KA5 auxiliary relay
F1
auxiliary power supply circuit breaker
BP
emergency off button with latching
ON
Normal source opening order
OR
Replacement source opening order
CN
Normal source closing order (0.25 second delay)
CR
Replacement source closing order (0.25 second delay)

Wiring colour codes


RD
red

C-14

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, MN, XF...).

Remote-operated
source-changeover systems

Electrical diagrams

2 Masterpact NT or NW devices
Diagram no. 51156904

DB414899.eps

Automatic-control system for permanent replacement source with lockout after a fault (with MN)

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.

IMPORTANT
The relays controlling the closing order to the Normal and Replacement circuit breakers must be mechanically and/or electrically
interlocked to prevent them from giving simultaneous closing commands.
It is recommended to use Tesys K relays from Schneider Electric reference LC2-K06010pp. These relays are mechanically and electrically
interlocked.
Legends
QN
Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
F1
auxiliary power supply circuit breaker
F2
circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays

Wiring colour codes


RD
red

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MN, XF...).

C-15

Remote-operated
source-changeover systems

Electrical diagrams

2 Masterpact NT or NW devices
Diagram no. 51156905

DB414900.eps

Automatic-control system for replacement source generator set with lockout after a fault (with MN)

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.

IMPORTANT
The relays controlling the closing order to the Normal and Replacement circuit breakers must be mechanically and/or electrically
interlocked to prevent them from giving simultaneous closing commands.
It is recommended to use Tesys K relays from Schneider Electric reference LC2-K06010pp. These relays are mechanically and electrically
interlocked.
Legends
QN
Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
IVE
electrical interlocking and terminal block unit
F1
auxiliary power supply circuit breaker
F2
circuit breaker (high breaking capacity)
S1
control switches
KA1 auxiliary relay
KA2 time delay for genset startup order to avoid starting
the genset for transient UN disturbances
KA3 auxiliary relay

Wiring colour codes


RD
red

C-16

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MN, XF...).

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156906

'EHSV

2 normal sources and 1 replacement source: electrical interlocking without lockout after a fault

Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE
connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
order for transfer from R to N1 + N2
(QN1 and QN2 closing time delay = 0.25 sec. minimum)
t2
order for transfer from N1 + N2 to R
(QR closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system


Normal 1
Normal 2
Replacement
0
0
0
1
1
0
0
0
1
1
0
0
0
1
0
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, XF...).

&

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156907

'EHSV

2 normal sources and 1 replacement source: electrical interlocking with lockout after a fault

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
S1
control switches
S2
source selection switches
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
t1
order for transfer from R to N1 + N2
(QN1 and QN2 closing time delay = 0.25 sec. minimum)
t2
order for transfer from N1 + N2 to R
(QR closing time delay = 0.25 sec. minimumm)

C-18

States permitted by mechanical interlocking system


Normal 1
Normal 2
Replacement
0
0
0
1
1
0
0
0
1
1
0
0
0
1
0
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, XF...).

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156908

'EHSV

2 normal sources and 1 replacement source: automatic-control system for generator set without lockout
after a fault (with MN)

Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
S2
source selection switches
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
KA3 auxiliary relays with 0.1 to 30 sec. time delay
KA4 auxiliary relay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay

States permitted by mechanical interlocking system


and with associated automatism
Normal 1
Normal 2
Replacement
0
0
0
1
1
0
0
0
1
1
0
0
0
1
0
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MN, XF...).

C-19

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156909

'EHSV

2 normal sources and 1 replacement source: automatic-control system for generator set with lockout
after a fault (with MN)

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QN... Normal source Masterpact NW
QR
Replacement source Masterpact NW
MCH spring-charging motor
XF
standard closing voltage release
MN
undervoltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
S2
source selection switches
KA1 auxiliary relay
KA2 auxiliary relays with 10 to 180 sec. time delay
KA3 auxiliary relays with 0.1 to 30 sec. time delay
KA4 auxiliary relay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay
KA7 auxiliary relay
KA8 auxiliary relay

C-20

States permitted by mechanical interlocking system


and with associated automatism
Normal 1
Normal 2
Replacement
0
0
0
1
1
0
0
0
1
1
0
0
0
1
0
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MN, XF...).

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156910

'EHSV

3 sources with only 1 device closed: electrical interlocking without lockout after a fault

Legends
QS... Source Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
order for transfer to Source 1
(QS1 closing time delay = 0.25 sec. minimum)
t2
order for transfer to Source 2
(QS2 closing time delay = 0.25 sec. minimum)
t3
order for transfer to Source 3
(QS3 closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system


Source 1
Source 2
Source 3
0
0
0
1
0
0
0
1
0
0
0
1
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, XF...).

C-21

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156911

'EHSV

3 sources with only 1 device closed: electrical interlocking with lockout after a fault

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QS... Source Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
order for transfer to Source 1
(QS1 closing time delay = 0.25 sec. minimum)
t2
order for transfer to Source 2
(QS2 closing time delay = 0.25 sec. minimum)
t3
order for transfer to Source 3
(QS3 closing time delay = 0.25 sec. minimum)
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays

C-22

States permitted by mechanical interlocking system


Source 1
Source 2
Source 3
0
0
0
1
0
0
0
1
0
0
0
1
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, XF...).

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156912

'EHSV

2 sources and 1 coupling: electrical interlocking without lockout after a fault

Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
coupling order for Source 1 failure
(QC closing time delay = 0.25 sec. minimum)
t2
coupling order for Source 2 failure
(QC closing time delay = 0.25 sec. minimum)
t3
coupling order for Source 1 restored
(QS1 closing time delay = 0.25 sec. minimum)
t4
coupling order for Source 2 restored
(QS2 closing time delay = 0.25 sec. minimum)

States permitted by mechanical interlocking system


Source 1
Source 2
Coupling
0
0
0
1
1
0
1
0
1
0
1
1
1
0
0
0
1
0
0
0
1
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, XF...).

C-23

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156913

'EHSV

2 sources and 1 coupling: electrical interlocking with lockout after a fault

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
t1
coupling order for Source 1 failure
(QC closing time delay = 0.25 sec. minimum)
t2
coupling order for Source 2 failure
(QC closing time delay = 0.25 sec. minimum)
t3
coupling order for Source 1 restored
(QS1 closing time delay = 0.25 sec. minimum)
t4
coupling order for Source 2 restored
(QS2 closing time delay = 0.25 sec. minimum)
KA1 auxiliary relays
KA2 auxiliary relays
KA3 auxiliary relays

C-24

States permitted by mechanical interlocking system


Source 1
Source 2
Coupling
0
0
0
1
1
0
1
0
1
0
1
1
1
0
0
0
1
0
0
0
1
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, XF...).

Electrical diagrams

Remote-operated
source-changeover systems
3 Masterpact NW devices
Diagram no. 51156914

'EHSV

2 sources and 1 coupling: automatic-control system with lockout after a fault

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
the SDE to terminals 81 and 84.

Legends
QS... Source Masterpact NW
QC
Coupling Masterpact NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault trip indication contact
PF
ready-to-close contact
CE... connected-position indication contact (carriage switch)
CH
springs charged indication contact
F1
auxiliary power supply circuit breaker
F2/F3 circuit breaker (high breaking capacity)
S1
control switches
S2
source selection switches
KA1 auxiliary relays with 10 to 180 sec. time delay
KA2 auxiliary relays with 0.1 to 30 sec. time delay
KA3 auxiliary relays with 10 to 180 sec. time delay
KA4 auxiliary relays with 0.1 to 30 sec. time delay
KA5 auxiliary relays with 0.25 sec. time delay
KA6 auxiliary relays with 0.25 sec. time delay
KA7 auxiliary relays with 0.25 sec. time delay

States permitted by mechanical interlocking system


and with associated automatism
Source 1
Source 2
Coupling
0
0
0
1
1
0
1
0
1
0
1
1
1
0
0
0
1
0
0
0
1
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.
Auxiliary power supply = supply voltage of auxiliary relays (KA...)
= supply voltage of electrical auxiliaries (electrical operation,
MCH, MX, XF...).

C-25

Source-changeover systems
with automatic controllers

Electrical diagrams

2 Masterpact NT or NW devices
Diagram no. 51156903

DB415120.eps

Electrical interlocking with lockout after a fault

ATTENTION
The diagram shows the electrical wiring for circuit breakers.
When wiring the SDE with switch-disconnectors, connect
wire BK to terminal 82.

Legends
QN
Normal source Masterpact NT or NW
QR
Replacement source Masterpact NT or NW
MCH spring-charging motor
MX
standard opening voltage release
XF
standard closing voltage release
OF... breaker ON/OFF indication contact
SDE1 fault-trip indication contact
PF
ready-to-close contact
CE1 connected-position indication contact (carriage switch)
CH
springs charged indication contact

Wiring colour codes


RD
red

C-26

GN
green

BK
black

VT
violet

YE
GY
yellow grey

WH
white

BN
brown

(1) Not to be wired for the without lockout after a fault solution.
(2) 1RWWREHZLUHGRQ[HGYHUVLRQ
(3) Prefabricated wiring supplied.

States permitted by mechanical interlocking system


Normal
Replacement
0
0
1
0
0
1
Note: diagram shown with circuit breakers in connected position,
open, charged, and ready to close.

Source-changeover systems
Compact NSX100-630,
Compact NS630b-1600,
Compact INS/INV, Masterpact

Catalogue numbers
and order forms

Presentation
Functions and characteristics
Dimensions
Electrical diagrams

2
A-1
B-1
C-1

Source-changeover systems for 2 devices


Compact INS40 to INS2500 and INV100 to INV2500
Compact NSX100 to NSX630
Compact NS630b to NS1600 circuit breakers and switch-disconnectors
0DVWHUSDFW17FLUFXLWEUHDNHUVDQGVZLWFKGLVFRQQHFWRUV

D-2
D-3
D-5
'

Source-changeover systems for 2 or 3 devices


Masterpact NW circuit breakers and switch-disconnectors

D-8

Source-changeover systems for 2 devices


Compact INS40 to INS630 switch-disconnectors
Compact NSX100 to NSX630 / circuit breakers and switch-disconnectors
Compact NS630b to NS1600 / circuit breakers and switch-disconnectors
Masterpact NT or NW / circuit breakers and switch-disconnectors

D-10
D-12
D-14
D-16

Source-changeover systems for 3 devices


Masterpact NW / circuit breakers and switch-disconnectors

D-18

D-1

Catalogue numbers
and order forms

Source-changeover systems
for 2 devices
Compact INS40 to INS2500
and INV100 to INV2500

Manual source-changeover systems Compact INS40 to INS630 and INV100 to INV630


'%HSV

Interlocking for rotary handle


3/4P
28953

'%HSV

Mechanical device for INS40 to INS160


equipped with an extended rotary handle

5...8

31073

Mechanical device for INS250-100 to INS250/INV100 to INV250


equipped with a direct or extended rotary handle
Mechanical device for INS/INV320 to INS/INV630
equipped with a direct or extended rotary handle

31074

Complete assembly source-changeover systems Compact INS250 to INS630

'%HSV

'%HSV

'%HSV

3P
With Compact INS250-100A
31140
With Compact INS250-160A
31144
With Compact INS250-200A
31142
With Compact INS250
31146
With Compact INS320
31148
With Compact INS400
31150
With Compact INS500
31152
With Compact INS630
31154
Locking for INS complete source changeover assembly
Handle locking by 1 to 3 padlocks (in OFF position)
By keylock
Keylocking device
+ Ronis 1351B.500 keylock
or + Profalux KS5 B24 D4Z keylock

4P
31141
31145
31143
31147
31149
31151
31153
31155
Built in
31097
41940
42888

Rotary handle
Extended front control for complete source changeover assembly

31055

Manual source-changeover systems Compact INS250 to INS2500 and INV250 to INV2500 by keylock

DB404080.eps

Db101549.eps

Interlocking
Locking device for Ronis/Profalux keylocks
on INS250-100 to INS250/INV100 to INV250
Locking device for Ronis/Profalux keylocks
on INS/INV320 to INS/INV630

2x

3/4P
31087

2x

31088

Locking device for Ronis/Profalux keylocks


on INS/INV630b to INS/INV2500

2x

31291

41950
42878

+ Ronis 1351B.500 keylock (2 keylocks / 1 key)


or + Profalux KS5 B24 D4Z keylock (2 keylocks / 1 key)

Connection accessories
Downstream coupling accessories
DB101062.eps

Short terminal shields (1 pair) + normal source/replacement source

DB413292.eps

3/4P
LV429359
LV432620

INS250/INS250
INS320 to INS630/INS320 to INS630

Db403921.eps

Long terminal shields (1 piece)


INS250 long terminal shield
INS320 to INS630

LV429518

Long terminal shield, 45 mm (1 piece)

LV432594

Long terminal shield for spreaders, 52.5 mm (1 piece)

LV432596

DB115652.eps

Terminal extensions
Spreaders

D-2

52.5 mm

4P

LV432491

Source-changeover systems
for 2 devices

Catalogue numbers
and order forms

Compact NSX100 to NSX630


Manual source changeover
DB404083.eps

For toggle controlled circuit breakers

NSX100...250
NSX400...630

LV429354
LV432614

DB404084.eps

Mechanical interlocking

For rotary handled circuit breakers

NSX100...250
NSX400...630

LV429369
LV432621

Key lock interlocking


DB404085.eps

For rotary handled or remote controlled circuit breakers


2 locks, 1 key
Ronis 1351B.500
Profalux KS5 B24 D4Z

41950
42878

Remote controlled source changeover


Plate + IVE unit
DB404086.eps

Source normal/source replacement (identical voltages)


NSX100...250/NSX100...250
Plate + IVE unit (1)
Plate
IVE unit
Auxiliary switches 2 OF + 2 SDE
Spare wiring system (device/IVE unit)
Back sockets option add:
Only long RC
Plug in base option add:
Plug in kit
NSX400...630/NSX100...630
Plate + IVE unit (1)
Plate
IVE unit
Auxiliary switches 2 OF + 2 SDE
Spare wiring system (device/IVE unit)
Back sockets option add:
Only long RC
Plug in base option add:
Plug in kit
Adaptator kit for NSX100...250

24 to 250 V DC

48 to 415 V AC 50/60 Hz
440 V 60 Hz

29351
29349
29356
4 x 29450
29365

29350
29349
29352
4 x 29450
29365

(2)

(2)

(2)

(2)

32611
32609
29356
4 x 29450
29365

32610
32609
29352
4 x 29450
29365

(2)

(2)

(2)

(2)

1 x 32618

1 x 32618

'%HSV

Control unit option


110/127 V AC 50/60 Hz
GERIN
MERLIN
multi

GERIN
MERLIN
multi

0 . OFF

220/240 V AC 50/60 Hz
29470
29363
29376
29472
29363
29378
29474
29363
29379

380/415 V AC 50/60 Hz
440 V 60 Hz
29471
29364
29377
29473
29364
29380
29475
29364
29381

29368

29368

0 . OFF

ACP + controller BA (1)


Plate ACP
Controller BA
ACP + controller UA (1)
29448
Plate ACP
29447
Controller UA
29446
ACP + controller UA150 (1) (communication option)
Plate ACP
Controller UA150

P25M
660V
AC3-IEC292-1

P25M
660V
AC3-IEC292-1

Test

Test

Wiring cable between BA/UA and ACP/IVE


Wiring cable (1.5 meter)

Communication module
DB403922.eps

DC150 data concentrator


110-240 V AC / 115-125 V DC

50823

N
DC150

com.

OK
error

BBus

com.
error

24V

JBus

9600
19200
N 1

N 2

3 5 7

N1

15 13
3 5 7
1
9 N2
15 13

(1) The supply voltages BA/UA controller, ACP plate, IVE unit and the remote control must be identical whatever the source changeover type.
(2) See products pages.

D-3

Source-changeover systems
for 2 devices

Catalogue numbers
and order forms

Compact NSX100 to NSX630 (cont.)


Connection accessories
DB101062.eps

Downstream coupling accessories


Short terminal shields (1 pair) + normal source/replacement source
3P
NSX100...250/NSX100...250 / 250 A LV429358
NSX400...630/NSX400...630 / 630 A LV432619

'%HSV

4P
LV429359
LV432620

Db403921.eps

Long terminal shields (1 piece)


NSX100...250 long terminal shield
NSX400...630
Long terminal shield, 45 mm (1 piece)
Long terminal shield for spreaders,
52.5 mm (1 piece)

3/4P
LV429518
LV432594
LV432596

DB115652.eps

Terminal extensions
Spreaders

52.5 mm

4P LV432491

Typical composition of remote controlled source changeover


DB413426.eps

Remote controlled source changeover

1 normal device N (1)


+ 1 replacement device R (2)
+ 2 remote controls (3)
+ 1 plate with interlocking (4) with IVE (5) and its wiring (8)
+ 2 plug-in kits (if plug-in version)
+ 1 adaptor kit for NSX100...250 plug-in (if NSX400...630 with NSX100...250)
+ auxilary switches (6)
2 x (1 OF + 1 SDE) for Compact NSX100...630
GRZQVWUHDPFRXSOLQJDFFHVVRU\  IRU&RPSDFW16; RSWLRQ
+ long RC (if back connection)

IVE voltages and remote controls are identical.


DB403059.eps

Associated control unit


0 . OFF
0 . OFF

1 source changeover without associated control unit


+ 1 ACP (9) with BA control unit (10)
Or + 1 ACP (9) with UA control unit (11)
Or + 1 ACP (9) with UA150 control unit (11)
+ extension (12) for remote UA/BA connection on front of switchboard

IVE voltages + remote control + ACP + BA or UA are identical.

D-4

Catalogue numbers
and order forms

Source-changeover systems
for 2 devices
Compact NS630b to NS1600
circuit breakers and switch-disconnectors

Interlocking for source-changeover systems


DB404090.eps

Mechanical interlocking
For 2 devices with extended rotary handles

33890

Interlocking using connecting rods for Compact electrically-operated devices


DB404091.eps

&RPSOHWHDVVHPEO\ZLWKDGDSWDWLRQ[WXUHVURGV
&RPSDFW[HGGHYLFHV
2 Compact withdrawable devices

33910
33913

FFO
hsu p

NO h

FFO

sup

O
degr

ahcs
i

F FO

hsup

NO h
sup

FFO

O
degr

ahcs
i

Interlocking using cables for Compact electrically-operated devices


DB404092.eps

&RPSOHWHDVVHPEO\ZLWKDGDSWDWLRQ[WXUHVFDEOHV
&RPSDFW[HGGHYLFHV
2 Compact withdrawable devices
&RPSDFW[HG&RPSDFWZLWKGUDZDEOHGHYLFH

FFO

hsup

NO h

FFO

33911
33914
33915

sup

O
degr
ah

csid

F FO

hsup

NO h
sup

FFO

O
degr
ah

csid

D-5

Catalogue numbers
and order forms

Source-changeover systems
for 2 devices
Compact NS630b to NS1600 circuit
breakers and switch-disconnectors (cont.)

Associated controller
The automatic-control option includes:
b an IVE electrical-interlocking unit
b an ACP control plate
b a BA or UA controller, depending on the required functions
b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

IVE electrical-interlocking unit

24 to 250 V DC

DB404093.eps

For 2 devices
29356
:LULQJNLWIRUFRQQHFWLRQRI[HGZLWKGUDZDEOHGHYLFHVWRWKH,9(XQLW

'%HSV

Control unit option

GERIN
MERLIN
multi

110/127 V AC 50/60 Hz
ACP + controller BA (1)
Plate ACP
Controller BA
29448
ACP + controller UA (1)
Plate ACP
29447
Controller UA
29446
ACP + controller UA150 (1) (communication option)
Plate ACP
Controller UA150

0 . OFF

P25M

GERIN
MERLIN
multi

0 . OFF

660V
AC3-IEC292-1

P25M
660V
AC3-IEC292-1

Test

Test

48/415 V AC 50/60 Hz
440 V 60 Hz
29352
54655

220/240 V AC 50/60 Hz

380/415 V AC 50/60 Hz
440 V 60 Hz

29470
29363
29376
29472
29363
29378
29474
29363
29379

29471
29364
29377
29473
29364
29380
29475
29364
29381

DB403922.eps

Communication module
DC150 data concentrator
110-240 V AC / 115-125 V DC

50823

N
DC150

com.

OK
error

BBus

com.
error

24V

JBus

9600
19200
N1

N2

3 5 7

N1

15 13
3 5 7
1
9 N2
15 13

(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of sourcechangeover system.

D-6

Catalogue numbers
and order forms

Source-changeover systems
for 2 devices
Masterpact NT circuit breakers
and switch-disconnectors

Interlocking for source-changeover systems


Interlocking using connecting rods
DB404094.eps

&RPSOHWHDVVHPEO\ZLWKDGDSWDWLRQ[WXUHVURGV
0DVWHUSDFW17[HGGHYLFHV
2 Masterpact NT drawout devices

33912
33913

Interlocking using cables (*)


&KRRVHDGDSWDWLRQ[WXUHV IRUHDFKEUHDNHUVHWRIFDEOHV
DGDSWDWLRQ[WXUHIRU0DVWHUSDFW17[HGGHYLFHV
DGDSWDWLRQ[WXUHIRU0DVWHUSDFW17GUDZRXWGHYLFHV
1 set of 2 cables
(*) &DQEHXVHGZLWKDQ\FRPELQDWLRQRI17RU1:[HGRUGUDZRXWGHYLFHV

33200
33201
33209

Associated controller
The automatic-control option includes:
b an IVE electrical-interlocking unit
b an ACP control plate
b a BA or UA controller, depending on the required functions
b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

DB404093.eps

IVE electrical-interlocking unit


For 2 devices
:LULQJNLWIRUFRQQHFWLRQRI[HGGUDZRXWGHYLFHVWRWKH,9(XQLW

'%HSV

Control unit option

GERIN
MERLIN
multi

110/127 V AC 50/60 Hz
ACP + controller BA (1)
Plate ACP
Controller BA
29448
ACP + controller UA (1)
Plate ACP
29447
Controller UA
29446
ACP + controller UA150 (1) (communication option)
Plate ACP
Controller UA150

0 . OFF

P25M

GERIN
MERLIN
multi

0 . OFF

660V
AC3-IEC292-1

P25M
660V
AC3-IEC292-1

Test

Test

24 to 250 V DC

48/415 V AC 50/60 Hz
440 V 60 Hz

29356

29352
54655

220/240 V AC 50/60 Hz

380/415 V AC 50/60 Hz
440 V 60 Hz

29470
29363
29376
29472
29363
29378
29474
29363
29379

29471
29364
29377
29473
29364
29380
29475
29364
29381

Communication module
DB403922.eps

DC150 data concentrator


110-240 V AC / 115-125 V DC

50823

N
DC150

com.

OK
error

BBus

com.
error

24V

JBus

9600
19200
N 1

N 2

3 5 7

N1

15 13
3 5 7
1
9 N2
15 13

(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type
of source-changeover system.

'

Catalogue numbers
and order forms

Source-changeover systems
for 2 or 3 devices
Masterpact NW circuit breakers
and switch-disconnectors

Interlocking for source-changeover systems for 2 devices


Interlocking of 2 devices using connecting rods
DB404095.eps

&RPSOHWHDVVHPEO\ZLWKDGDSWDWLRQ[WXUHVURGV
0DVWHUSDFW1:[HGGHYLFHV
2 Masterpact NW drawout devices
&DQEHXVHGZLWK1:[HG1:GUDZRXW

48612
48612

Interlocking of 2 devices using cables (*)


&KRRVHDGDSWDWLRQ[WXUHV IRUHDFKEUHDNHUVHWRIFDEOHV
DGDSWDWLRQ[WXUHIRU0DVWHUSDFW1:[HGGHYLFHV
DGDSWDWLRQ[WXUHIRU0DVWHUSDFW1:GUDZRXWGHYLFHV
1 set of 2 cables
(*) &DQEHXVHGZLWKDQ\FRPELQDWLRQRI17RU1:[HGRUGUDZRXWGHYLFHV

47926
47926
33209

Associated controller for 2 devices


The automatic-control option includes:
b an IVE electrical-interlocking unit
b an ACP control plate
b a BA or UA controller, depending on the required functions
b a UA/BA adapter kit.
Note: the circuit breaker auxiliaries (MCH, MX, XF) and the automatic-control components (IVE, ACP, UA or BA) must have the same voltages.

IVE electrical-interlocking unit


DB404093.eps

For 2 devices
29356
:LULQJNLWIRUFRQQHFWLRQRI[HGGUDZRXWGHYLFHVWRWKH,9(XQLW

Control unit option


'%HSV

24 to 250 V DC

110/127 V AC 50/60 Hz

220/240 V AC 50/60 Hz

48/415 V AC 50/60 Hz
440 V 60 Hz
29352
54655

380/415 V AC 50/60 Hz
440 V 60 Hz

ACP + controller BA (1)


29470
29471
Plate ACP
29363
29364
Controller BA
29376
29377
29448
29472
29473
ACP + controller UA (1)
Plate ACP
29447
29363
29364
Controller UA
29446
29378
29380
29474
29475
ACP + controller UA150 (1) (communication option)
Plate ACP
29363
29364
Controller UA150
29379
29381
(1) The supply voltages of the BA/UA controller, ACP plate, IVE unit and circuit breaker operating mechanism must be identical whatever the type of sourcechangeover system.
GERIN

MERLIN
multi

P25M

GERIN

MERLIN
multi

0 . OFF

660V
AC3-IEC292-1

P25M

660V
AC3-IEC292-1

Test

Test

D-8

0 . OFF

Catalogue numbers
and order forms

Source-changeover systems
for 2 or 3 devices
Masterpact NW circuit breakers
and switch-disconnectors

Communication module
DB403922.eps

DC150 data concentrator


110-240 V AC / 115-125 V DC

50823

N
DC150

com.

OK
error

BBus

com.
error

24V

JBus

9600
19200
N 1

N 2

3 5 7

N1

15 13
3 5 7
1
9 N2
15 13

Interlocking for source-changeover systems for 3 devices


Interlocking of 3 devices using cables
&KRRVHDGDSWDWLRQ[WXUHV FRPSOHWHVHWZLWKDGDSWDWLRQ[WXUHVFDEOHV 
VRXUFHVRQO\GHYLFHFORVHG[HGRUGUDZRXWGHYLFHV
VRXUFHVFRXSOLQJ[HGRUGUDZRXWGHYLFHV
QRUPDOUHSODFHPHQWVRXUFH[HGRUGUDZRXWGHYLFHV

48610
48609
48608

D-9

Catalogue numbers
and order forms

Source-changeover systems
for 2 devices
Compact INS40 to INS630
Switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.

and enter the

Mechanical interlocking of two INS40 to INS630 devices


Devices with front rotary handles, mounted side by side
Two devices with direct rotary handles
INS250

INS320/400/500/630

Two devices with extended rotary handles


INS40/63/80

INS100/125/160

INS250

INS320/400/500/630

Downstream coupling
accessory

INS250

INS320/400/500/630

Long terminal shields

INS250

INS320/400/500/630

Complete source-changeover assembly

D-10

INS250-100 A

INS250-160 A

INS250-200 A

INS250-250 A

INS320

INS400

INS500

INS630

Source-changeover systems
for 2 devices

Catalogue numbers
and order forms

Compact INS40 to INS630


Switch-disconnectors
To indicate your choices, check the applicable square
boxes
and enter the appropriate information in the
rectangles
.

Indication and measurements


4P ammeter module

For INS250

Rating

100 A
150 A

(one sheet per device, make copies if necessary)

250 A

'HYLFHLGHQWLFDWLRQ
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Switch-disconnector

Adaptation kit required for direct handles


Rating

400 A

For INS250

Rating

100 A

600 A
4P current-transformer
module

INS40/63/80

Compact type

For INS320/630

150 A

INS100/125/160

250 A

INS250

For INS320/630

Rating

400 A

For INS40/160

1OF/CAF/CAO

Standard

For INS250/630

1 OF/CAM

Standard

INS320/400/500/630
Rating

Number of poles

3 or 4

600 A
Auxiliary contact

Low level

Connections
Front connection Standard

Low level

Rotary handles

Rear connection

2 short

INS40/80
connectors

Distribution 3x16v rigid/10vH[LEOH

INS100/160
connectors
INS250
connectors

2 long

INS40 to INS160

Black

INS250

Black

Red on yellow front

Snap-on y 95v

INS320 to INS630

Black

Red on yellow front

Distribution 4x25v rigid/16vH[LEOH

For complete changeover assembly

Snap-on 1.5v to 95v (< 160 A)

Clips for connectors

Red on yellow front

INS250
INS320/630

Snap-on 10v to 185v (< 250 A)

Locking of rotary handles

Voltage tap connector for 185v


connector

Padlocking

1 to 3 padlocks (in OFF position)

Keylocking

Keylock adapter (keylock not included)

Set of 10

Distribution 6x1.5v to 35v rigid


with interphase barriers
INS320/630
connectors

Extended front handles

Keylocks Ronis 1351B.500

Profalux KS5 B24 D4Z

Installation accessories
Front-panel escutcheon

1 cable 35v to 300v

For switch-disconnectors
For ammeter module, IP40

2 cables 35v to 240v


Voltage tap connector for 185v
connector

Distribution
blocks

Linergy DX
4P

125 A

160 A

1P

160 A

Linergy BS
(multi stage)

160 A

250 A

Linergy DP

250 A

Rt-angle extension Set of 3 or 4

250 A

630 A

Straight extension INS250


Edgewise ext.

INS630

Spreader

INS250 (45 mm)


Front alignment base

Cu cable lugs
supplied with
2 or 3 inter-phase
barriers

INS320/630

52.5 mm

PP

One-piece

INS250

INS630

INS100/160

For 95v cable

INS250

For 120v cable


For 150v cable
For 185v cable

INS320/630

For 240v cable

INS250

For 150v cable

For 300v cable


Al cable lugs
supplied with
2 or 3 inter-phase
barriers

For 185v cable


INS320/630

For 240v cable

Terminal shrouds

INS40/63/80

INS100/125/160

Terminal shields

INS40/63/80

INS100/125/160

For 300v cable

INS250

Long

INS320/630

Long

Long for 52.5 mm spreaders


Interphase
barriers

INS100/160

Set of 6

INS250

Set of 6

INS320/630

Set of 6

D-11

Catalogue numbers
and order forms

Source-changeover systems
for 2 devices
Compact NSX100 to NSX630 / Circuit
breakers and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.

and enter the

Diagram for two Compact NSX devices


Without automatic control, without emergency off auxiliaries

QR

Without automatic control, with emergency off by MN

QR

Without automatic control, with emergency off by MX

QR

Mechanical interlocking of two NSX100 to NSX630 devices


[HGSOXJLQRUZLWKGUDZDEOH
Manually operated devices, mounted side by side:
Two devices with toggles
Two devices with rotary handles

Mechanical and electrical interlocking of two NSX100 to NSX630 devices


[HGRUSOXJLQ
Electrically operated devices, mounted side by side:
Select 1 base plate + IVE unit, the 4 auxiliary contacts and the options / accessories
Base plate + IVE unit

Identical voltages:

48 to 415 V AC 50/60 Hz

24 to 250 V DC

440/480 V AC 60 Hz

Normal NSX100/250

Replacement NSX100/250

Normal NSX400/630

Replacement NSX400/630

Normal NSX400/630

Replacement NSX100/250

Adapter kit for NSX400/630 with NSX100/250 (plug-in)


Auxiliary contacts

2 OF + 2 SDE (mandatory)

Options

Long rear connections

Downstream coupling accessory


Prefabricated wiring

Quantity
Plug-in base

3P

NSX100/250

4P

NSX400/630

Between device and IVE

Quantity

Automatic-control option
Power supply 220/240 V - 50/60 Hz:

ACP + BA controller
ACP + UA controller
ACP + UA150 controller

Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz:

ACP + BA controller
ACP + UA controller
ACP + UA150 controller

D-12

Source-changeover systems
for 2 devices

Catalogue numbers
and order forms

Compact NSX100 to NSX630 / Circuit


breakers and switch-disconnectors
(One sheet per device, make copies if necessary)
Name of customer:
Address for delivery:
Requested delivery date:
Customer order no.:
To indicate your choices, check the applicable square boxes
and enter the appropriate information in the rectangles
Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE
Circuit breaker or switch disconnector
Compact type
NSX100/160/250
Rating
A
Circuit breaker B, F, N, H, S, L
Switch-discon. NA
No. of poles
2, 3 or 4
No. of poles
2d, 3d or 4d
protected
Fixed device
Plug-in/withdr.
Earth-leakage
protection
Vigi module
Trip unit
Thermal-mag.

Plug-in
ME, MH, MB

NSX400/630

Front connections
Withdrawable

Voltage
4P option on 3P NSX

Indication and measurement


Ammeter module
Standard
I max
Current-transformer module
Current-transformer module + TCU
Insulation-monitoring module
Voltage-presence indicator
Auxiliary contact
OF
SD
OF
SD
SDE adapter (TM, MA or Micrologic 2 trip units)
SDX module
Remote operation
Electrical operation
Motor mechanism
Voltage releases
Instantaneous MX
Instantaneous MN
Fixed time delay MN
Adjust. time delay MN
Rotary handles
Direct
Black

Extended

TMD rating (16 250 A)


TMG rating (16 63 A)
MA rating (2.5 220 A)
Electronic
Micrologic 2.2
Micrologic 2.3
Micrologic 2.2 G
Micrologic 2.3 AB
Micrologic 2.2 AB
Micrologic 5.3 A
Micrologic 5.2 A
Micrologic 5.3 E
Micrologic 5.2 E
Micrologic 5.3 A-Z
Micrologic 5.2 A-Z
Micrologic 6.3 A
Micrologic 6.2 A
Micrologic 6.3 E
Micrologic 6.2 E
Micrologic 1.3 M
Micrologic 2.2 M
Micrologic 2.3 M
Micrologic 6.2 E-M
Micrologic 6.3 E-M
SDTAM module
External neutral CT
24 V DC power supply connector
ZSI wiring accessory for NS630b NW/NT
48-60 V DC
External power 24-30 V DC
supply module 100-125 V AC
110-130 V AC
24 V DC
200-240 V AC
380-415 V AC
Battery module
Connection
Rear-connection Short
Long
kit
Mixed
NSX100/250
Snap-on 1.5v to 95v (< 160 A)
connectors
Snap-on 25v to 95v (< 250 A)
Snap-on 120v to 185v (< 250 A)
Distribution 6 x 1.5v to 35v
Aluminium 2 cables 50v to 120v
NSX400/630
1 cable 35v to 300v
connectors
2 cables 35v to 240v
Right-angle terminal extensions
Straight extensions
NSX100/250
Edgewise extensions
Dbl.-L term. ext.
45 term. ext.
Spreader
NSX100/250 (one piece)
(45 mm)
NSX400/630 (52.5 mm)
PP
150v
185v
Cu cable lugs
NSX100/250
120v
NSX400/630
240v
300v
Al cable lugs
NSX100/250
150v
185v
NSX400/630
240v
300v
V mesrt Input for For lugs NSX100/250 y 185v
connector
For lugs NSX400/630
Terminal shields NSX100/250
Long
NSX400/630
Long
Long for 52.5 mm spreaders
Interphase barriers
Set of 6
2 insulating scrn. NSX100/250
NSX400/630 SLWFK
Test tool
Pocket battery for Micrologic
Maintenance case
USB maintenance interface
Power supply 110-240 V AC
Spare Micrologic cord

3P
3P
3P
3P
3P

4P

SDE
SDE

SDV
SDV

Standard
Low level

AC
AC
AC
AC
AC

DC
DC
DC
DC
DC

4P
4P
4P

V
V
V
V
V

Red and yellow front

MCC conversion access.


CNOMO conversion access.
Black
Red and yellow front
Telescopic handle for withdrawable device

Indication auxiliary
1 early-break switch
2 early-make switches
Locking
Toggle (1 to 3 padlocks) Removable
Fixed
Rotary handle
Keylock adapter (keylock not included)
Keylocks Ronis 1351B.500
Profalux KS5 B24 D4Z
Motor mechanism
Keylock adapter + keylock Ronis (special)
NSX100/250
Keylock adapter (keylock not included)
NSX400/630
Keylocks Ronis 1351B.500
Profalux KS5 B24 D4Z
Interlocking
Mechanical
Toggle operated
Rotary Handle
By key (2 keylocks,
Locking kit without locks
1 key) for rotary handle Keylocks Ronis 1351B.500
Profalux KS5 B24 D4Z
Installation accessories
IP30 escutcheon for all types (toggle/rotary handle/motor mechanism)
IP30 escutcheon (with access to toggle + trip unit)
IP30 escutcheon for Vigi module
IP40 escutcheon for all types (toggle/rotary handle/motor mechanism)
IP40 escutcheon for Vigi module
IP40 escutcheon for Vigi or ammeter module
Toggle cover
Sealing accessories
DIN rail adapter
3P 60 mm busbar adapter
3OXJLQZLWKGUDZDEOHFRQJXUDWLRQDFFHVVRULHV
Auxiliary connections
DXWRPDWLFFRQQHFWRU[HGSDUWZLWKZLUHV IRUEDVH
1 automatic connector moving part with 9 wires (for circuit breaker)
1 sup. for 3 auto. conn. moving parts
1 sup. for 2 auto. conn.
ZLUHPDQXDODX[LOLDU\FRQQHFWRU [HGPRYLQJ
Plug-in base
Long insulated terminals
Set of 2
accessories
2 IP4 shutters for base
Chassis accessories
Escutcheon collar
Toggle
Vigi
Locking kit (keylock not included)
2 carriage switches (conn./disconnected position indication)
Parts or plug-in
Plug-in base FC/RC
2P
3P
4P
Withdrawable kits
Set of two power connections
Standard
Vigi
Safety trip for advanced opening
For 3P/4P chassis
Moving part
Fixed part
Adaptater for plug-in base (for terminal shield or interphase barriers)
Communication
NSX Cord L = 0.35 m
NSX Cord L = 1.3 m
NSX Cord U > 480 V AC L = 0.35 m
NSX Cord L = 3 m
BSCM (NSX400/630)
Communicating motor mechanism 220-240 V
Switchboard front display module FDM121
FDM mounting accessory
Modbus interface
Stacking accessory
ULP line termination
RJ45 connectors
Wire length RJ45 L = 0.3 m
Wire length RJ45 L = 0.6 m
female/female
Wire length RJ45 L = 1 m
Wire length RJ45 L = 2 m
Wire length RJ45 L = 3 m
Wire length RJ45 L = 5 m

D-13

Catalogue numbers
and order forms

Source-changeover systems
for 2 devices
Compact NS630b to NS1600 / Circuit
breakers and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.

and enter the

Diagram for two Compact NS devices


Electrical interlocking with lockout after fault:
Permanent replacement source (with IVE unit)

(no. 51201183)

With emergency off by MX (with IVE unit)

(no. 51201184)

With emergency off by MN (with IVE unit)

(no. 51201185)

Interlocking using connecting rods between two NS630b to NS1600 devices


Manually operated devices installed side-by-side:
)RUWZR[HG16GHYLFHVZLWKH[WHQGHGURWDU\KDQGOHV
Electrically operated devices installed one above the other:
6HOHFWDFRPSOHWHVHWLQFOXGLQJWZRDGDSWDWLRQ[WXUHVDQGWKHFRQQHFWLQJURGV
Complete set for:

[HG16GHYLFHV
2 withdrawable NS devices

Interlocking using cables between two NS630b to NS1600 devices


Electrically operated devices installed one above the other or side-by-side:
6HOHFWDFRPSOHWHVHWLQFOXGLQJWZRDGDSWDWLRQ[WXUHVDQGWKHFDEOHV
Complete set for:

[HG16GHYLFHV
2 withdrawable NS devices
[HG16GHYLFHZLWKGUDZDEOH16GHYLFH

Electrical interlocking between two NS630b to NS1600 devices


1 IVE unit 48/415 V - 50/60 Hz and 440 V - 60 Hz
ZLULQJNLWIRUFRQQHFWLRQEHWZHHQ[HGZLWKGUDZDEOHGHYLFHVWRWKH,9(XQLW

Automatic-control option
Power supply 110 V - 50/60 Hz:

ACP + BA controller
ACP + UA controller
ACP + UA150 controller

Power supply 220/240 V - 50/60 Hz:

ACP + BA controller
ACP + UA controller
ACP + UA150 controller

Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz:

ACP + BA controller
ACP + UA controller
ACP + UA150 controller

D-14

Source-changeover systems
for 2 devices

Catalogue numbers
and order forms

Compact NS630b to NS1600 / Circuit


breakers and switch-disconnectors
Indication contacts

(One sheet per device, make copies if necessary)


Name of customer:

SD trip indication (maximum 1)

Address for delivery:

6 A-240 V AC

Low level

SDE fault-trip indication (maximum 1) (SDE integrated in electrically operated devices)


Requested delivery date:

6 A-240 V AC

Customer order no.:

Low level

OF ON/OFF indication contacts (maximum 3)


6 A-240 V AC

qty

Carriage switches (possible combinations: 3 CE, 2 CD, 1 CT)


qty
CE - connected position
6 A-240 V AC
Low level

Device iGHQWLFDWLRQ

CD - disconnected position

6 A-240 V AC

qty

Q 1 - NORMAL SOURCE

CT - test position

6 A-240 V AC

qty

Q 2 - REPLACEMENT SOURCE

Auxiliary terminals for chassis alone

Circuit breaker or switch disconnector


Compact type

qty

Low level

qty

3-wire terminal (30 parts)

6-wire terminal (10 parts)

Remote operation

NS630b to NS1600

Rating

A
N, H, L

Switch-disconnector

NA

Number of poles

3 or 4

Device

Fixed

MN delay unit

Electrical operation
Voltage releases

Standard

Communicating
V

Power supply

AC

DC

MX

AC

DC

MN

AC

DC

Adjustable

Non-adjustable

5RWDU\KDQGOHVIRU[HGDQGZLWKGUDZDEOHGHYLFH

Withdr. with chassis

Direct

Withdr. without chassis

Black

Red on yellow front


CNOMO conversion access.

(moving part only)

Extended

Chassis alone without connections

Micrologic control unit

Black

Red on yellow front

Telescopic handle for withdrawable device

Basic protection

2.0

5.0

6.0

A - ammeter

2.0

5.0

6.0

E - energy meter

2.0

5.0

6.0

5.0

6.0

P - power meter
AD - external power-supply module

Indication auxiliary

6 A-240 V AC

2 early-break switches
Locking

7.0
V

Toggle (1 to 3 padlocks)

Removable system

Rotary handle using


a keylock

OFF position

ON and OFF positions

Ronis 1351B.500

Profalux KS5 B24 D4Z

For electrically operated


devices

VBP - ON/OFF pushbutton locking

Standard 0.4 to 1 Ir

OFF position locking:

Low setting 0.4 to 0.8 Ir

VCPO - by padlocks

High setting 0.8 to 1 Ir

VSPO - by keylocks

LT OFF

Communication
Device

Front Display Module (FDM121)


Breaker ULP cord

Fixed system

Keylock kit (without keylock)

280 x 115 mm

TCW - external sensor for SGR protection

Eco COM module Modbus

2 early-make switches

7.0

TCE - external sensor (CT) for neutral protection

LR - long-time rating plug

qty

Low level
Jumpers (set of 10)

Circuit breaker

Rectangular sensor

qty

Low level

and enter the appropriate information in the rectangles

To indicate your choices, check the applicable square boxes

Chassis
Mounting accessory

Profalux

Ronis

Profalux

Ronis

2 identical keylocks, 1 key

Profalux

Ronis

Profalux

Ronis

Chassis locking in disconnected position:


VSPD - by keylocks

L = 0.35 m

Keylock kit (w/o keylock)


1 keylock

Keylock kit (w/o keylock)

Kirk

Castell

1 keylock

Profalux

Ronis

L = 1.3 m
L=3m

Connections

2 identical keylocks, 1 key

Profalux

Ronis

Horizontal rear connections

Top

Bottom

2 keylocks, different keys

Profalux

Ronis

Vertical rear connections

Top

Bottom

Optional connected/disconnected/test position locking

Front connections

Top

Bottom

4x240v bare cable connectors

16)&[HG

VPEC - door interlock

On right-hand side of chassis


On left-hand side of chassis

VPOC - racking interlock

+ shields
Long connection shields

16)&[HG

Vertical-connection adapters

16)&[HGZLWKGU

Cable-lug adapters

16)&[HGZLWKGU

CDM - mechanical operation counter

Arc chute screen

16)&[HG

CDP - escutcheon

Interphase barriers

16)&[HGZLWKGU

CP - transparent cover for escutcheon

Spreaders

16)&[HGZLWKGU

OP - blanking plate for escutcheon

VO - safety shutters on chassis 16)&[HG

VDC - mismatch protection


Accessories

0RXQWLQJEUDFNHWVIRU[HG16
Test kits

For mounting on horizontal plane


Mini test kit

Portable test kit

D-15

Catalogue numbers
and order forms

Source-changeover systems
for 2 devices
Masterpact NT or NW / Circuit breakers
and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.

and enter the

Diagram for 2 Masterpact NT/NW devices


Electrical interlocking with lockout after fault:
Permanent replacement source (with IVE unit)

(no. 51201142)

With emergency off by MX (with IVE unit)

(no. 51201143)

With emergency off by MN (with IVE unit)

(no. 51201144)

Automatic control with lockout after fault:


Permanent replacement source (with IVE unit)

(no. 51156904)

Engine generator set (with IVE unit)

(no. 51156905)

BA/UA controller (with IVE unit)

(no. 51156903)

Interlocking using connecting rods (NT/NW devices one above the other)
6HOHFWDFRPSOHWHVHWLQFOXGLQJWZRDGDSWDWLRQ[WXUHVDQGWKHFRQQHFWLQJURGV
Complete set for:

2 drawout NT devices

[HG17GHYLFHV

2 drawout NW devices

[HG1:GHYLFHV

[HG17GHYLFH[HG1:GHYLFH
1 drawout NT device + 1 drawout NW device

Interlocking using cables (NT/NW devices one above the other or side-by-side)
6HOHFWWZRDGDSWDWLRQ[WXUHV RQHIRUHDFKGHYLFH DQGDVHWRIWZRFDEOHV
$GDSWDWLRQ[WXUHIRU
[HG17GHYLFH
171:[HGDQGGUDZRXW 1 drawout NT device
devices may be mixed)
[HG1:GHYLFH

qty
qty
qty

1 drawout NW device

qty

1 set of 2 cables (for two devices)

Electrical interlocking 2 Masterpact NT/NW devices


1 IVE unit 48/415 V - 50/60 Hz and 440 V - 60 Hz
ZLULQJNLWIRUFRQQHFWLRQEHWZHHQ[HGZLWKGUDZDEOHGHYLFHVWRWKH,9(XQLW

Automatic-control option
Power supply 220/240 V - 50/60 Hz:

ACP + BA controller
ACP + UA controller
ACP + UA150 controller

Power supply 380/415 V - 50/60 Hz and 440 V - 60 Hz:

ACP + BA controller
ACP + UA controller
ACP + UA150 controller

D-16

Source-changeover systems
for 2 devices

Catalogue numbers
and order forms

Masterpact NT or NW / Circuit breakers


and switch-disconnectors
Indication contacts

(One sheet per device, make copies if necessary)

OF - ON/OFF indication contacts

Name of customer:
Address for delivery:

Standard

4 OF 6 A-240 V AC (10 A-240 V AC and low-level for NW)

Additional

1 block of 4 OF for NW

max. 2

qty

EF - combined connected/closed contacts

Requested delivery date:


Customer order no.:

1 EF 6 A-240 V AC for NW

max. 8

qty

1 EF low-level for NW

max. 8

qty

SDE - fault-trip indication contact

To indicate your choices, check the applicable square boxes


and enter the appropriate information in the rectangles

Standard

1 SDE 6 A-240 V AC

Device iGHQWLFDWLRQ

Additional

1 SDE 6 A-240 V AC

Q 1 - NORMAL SOURCE

Programmable contacts

2 M2C contacts

Q 2 - REPLACEMENT SOURCE

Carriage switches

6 A-240 V AC

CE - connected position

max. 3 for NW / NT

qty

CD - disconnected position

max. 3 for NW, 2 for NT

qty

max. 3 for NW, 1 for NT

Circuit breaker or switch disconnector


NT

Masterpact type

NW

1 SDE Low level


6 M6C contacts
Low level

Rating

CT - test position

Sensor rating

AC - NW actuator for 6 CE - 3 CD - 0 CT additional carriage switches

Circuit breaker

N1, H1, H2, H3, L1

Switch-disconnector

NA, HA, HF, ES, HA10 (NW)

Number of poles

3 or 4

qty
qty

Remote operation
Remote ON/OFF

MCH - gear motor

XF - closing voltage release

Option: neutral on right side

MX - opening voltage release

Device

PF - ready to close contact

Fixed

Low level
6 A-240 V AC

Withdr. with chassis

BPFE - electrical closing pushbutton

Withdr. without chassis

Res - electrical reset option

(moving part only)

RAR - automatic reset option

Chassis alone without connections


Remote tripping

Micrologic control unit


A - ammeter

2.0

5.0

6.0

E - energy meter

2.0

Rr - adjustable delay unit

5.0

6.0

P - power meter

5.0

6.0

7.0

H - harmonic meter

5.0

6.0

7.0

AD - external power-supply module

MN - undervoltage release
R - delay unit (non-adjustable)

7.0

2nd MX - shunt release

Locking
VBP - ON/OFF pushbutton locking (by transparent cover + padlocks)

TCE - external sensor (CT) for neutral protection

OFF position locking:

Rectangular sensor for

NT (280 x 115 mm)

VCPO - by padlocks

earth-leakage protection

1: [PP

VSPO - by keylocks

Keylock kit (w/o keylock)

LR - long-time rating plug Standard 0.4 to 1 Ir

Profalux

Castell

Low setting 0.4 to 0.8 Ir

1 keylock

Profalux

Ronis

High setting 0.8 to 1 Ir

2 identical keylocks, 1 key

Profalux

Ronis

LT OFF

2 keylocks, different keys (NW)

Profalux

Ronis

Profalux

Ronis

Chassis locking in disconnected position:

PTE - external voltage measurement input (required for reverse


supply)

VSPD - by keylocks

Keylock kit (w/o keylock)

BAT - battery module


Communication
Eco COM module Modbus

Device

Front Display Module (FDM121)


Breaker ULP cord

Chassis
Mounting accessory

Kirk

Castell

1 keylock

Profalux

Ronis

2 identical keylocks, 1 key

Profalux

Ronis

2 keylocks, different keys

Profalux

Ronis

Optional connected/disconnected/test position locking

L = 0.35 m
VPEC - door interlock

L = 1.3 m

On right-hand side of chassis


On left-hand side of chassis

L=3m
VPOC - racking interlock

Connections
Horizontal

Top

Bottom

IPA - cable-type door interlock

Vertical

Top

Bottom

IBPO - racking interlock between crank and OFF pushbutton for NW

Front

Top

Bottom

Vertical-connection adapters

17)&[HGGUDZ

Cable-lug adapters

17)&[HGGUDZ

Arc chute screen

17)&[HG

CDM - mechanical operation counter

Interphase barriers

171:[HGGUDZ

CB - auxiliary terminal shield for chassis

Spreaders

17[HGGUDZRXW

CDP - escutcheon

Disconnectable front

1:[HG

DAE - automatic spring discharge before breaker removal for NW


VDC - mismatch protection device - chassis
Accessories

CP - transparent cover for escutcheon


OP - blanking plate for escutcheon

connection adapter
Lugs for 240v or 300v cables

%UDFNHWVIRUPRXQWLQJ1:[HG

1:[HGGUDZRXW

VO - safety shutters on chassis NT, NW


VIVC - shutter position

Ronis

Kirk

Test kits

On backplates
Mini test kit

Portable test kit

NW

indication and locking

'

Catalogue numbers
and order forms

Source-changeover systems
for 3 devices
Masterpact NW / Circuit breakers
and switch-disconnectors
To indicate your choices, check the applicable square boxes
appropriate information in the rectangles
.

and enter the

Diagram for 3 Masterpact NW devices


2 Normal sources + 1 Replacement source:
Electrical interlocking without lockout after fault

(no. 51156906)

Electrical interlocking with lockout after fault

QR

2 Normal sources + 1 Replacement source with source selection:


Automatic control w/ engine generator set w/o lockout after fault

(no. 51156908)

Automatic control w/ engine generator set w/ lockout after fault

(no. 51156909)

3 sources, only 1 device ON:


Electrical interlocking without lockout after fault

(no. 51156910)

Electrical interlocking with lockout after fault

(no. 51156911)

2 Normal sources + 1 coupling:


Electrical interlocking without lockout after fault

(no. 51156912)

Electrical interlocking with lockout after fault

(no. 51156913)

Automatic control with lockout after fault:

(no. 51156914)

Interlocking using cables (NW devices one above the other or side-by-side)
6HOHFWDFRPSOHWHVHWLQFOXGLQJWKUHHDGDSWDWLRQ[WXUHVDQGWKHFDEOHV
1 complete set for:

VRXUFHVGHYLFH21[HGRUGUDZRXW
VRXUFHVFRXSOLQJ[HGRUGUDZRXW
VRXUFHVUHSODFHPHQWVRXUFH[HGRUGUDZRXW

D-18

Source-changeover systems
for 3 devices

Catalogue numbers
and order forms

Masterpact NW / Circuit breakers


and switch-disconnectors
To indicate your choices, check the applicable square
boxes and enter the appropriate information in the
rectangles
.
(one sheet per device, make copies if necessary)

Q 1 - NORMAL SOURCE
Q 2 - REPLACEMENT SOURCE

Circuit breaker or switch-disconnector


A
A
N1, H1, H2, H3, L1
NA, HA, HF
3 or 4

qty
qty

Remote operation
Remote ON/OFF

7.0

max. 8
max. 8

1 SDE Low level


6 M6C contacts
Low level
qty
qty
qty
AC - NW actuator for 6 CE - 3 CD - 0 CT additional carriage switches
qty

MCH - gear motor


XF - closing voltage release
MX - opening voltage release
PF - ready to close contact Low level

V
V
V

6 A-240 V AC

7.0
7.0

Remote tripping

Rectangular sensor
470 x 160 mm
for earth-leakage protection
TCW - external sensor for SGR protection
LR - long-time rating plug Standard 0.4 to 1 Ir
Low setting 0.4 to 0.8 Ir
High setting 0.8 to 1 Ir
LT OFF
PTE - external voltage measurement input (required for
reverse supply)
BAT - battery module

BPFE - electrical closing pushbutton


Res - electrical reset option
RAR - automatic reset option
MN - undervoltage release
R - delay unit (non-adjustable)
Rr - adjustable delay unit
2eme MX - shunt release

Locking
VBP - ON/OFF pushbutton locking (by transparent cover + padlocks)
OFF position locking:
VCPO - by padlocks
VSPO - by keylocks
Keylock kit (w/o keylock)
Profalux

Kirk
1 keylock
Profalux
2 identical keylocks, 1 key
Profalux
2 keylocks, different keys (NW) Profalux

Communication
Eco COM module Modbus

Chassis locking in disconnected position:


VSPD - by keylocks
Keylock kit (w/o keylock)

Device
Chassis
Front Display Module (FDM121)
Mounting accessory
Breaker ULP cord
L = 0.35 m
L = 1.3 m
L=3m

Interphase barriers
Disconnectable front
connection adapter
VO - safety shutters on chassis
VIVC - shutter position indication and locking

1 EF 6 A-240 V AC
1 EF low-level

1 SDE 6 A-240 V AC
1 SDE 6 A-240 V AC
Programmable contacts 2 M2C contacts
Carriage switches
6 A-240 V AC
CE - connected position Max. 3
CD - disconnected position Max. 3
CT - test position
Max. 3

Fixed
Drawout with chassis
Drawout without chassis
(moving part only)
Chassis alone without connections

Top
Top
Top
Fixed, drawout
Fixed

qty

Standard
Additional

Device

Connections
Horizontal
Vertical
Front

4 OF 6 A-240 V AC (10 A-240 V AC and low-level)


1 block of 4 OF
max. 2

SDE - fault-trip indication contact

NW

2SWLRQQHXWUDORQULJKWVLGH

Micrologic control unit


A - ammeter
2.0
5.0
6.0
E - energy meter
2.0
5.0
6.0
P - power meter
5.0
6.0
H - harmonic meter
5.0
6.0
AD - external power-supply module
TCE - external sensor (CT) for neutral protection

Standard
Additional

EF - combined connected/closed contacts

'HYLFHLGHQWLFDWLRQ

Masterpact type
Rating
Sensor rating
Circuit breaker
Switch-disconnector
Number of poles

Indication contacts
OF - ON/OFF indication contacts

Bottom
Bottom
Bottom

VPEC - door interlock

V
V
V

Ronis
Castell
Ronis
Ronis
Ronis

Profalux
Ronis
Kirk
Castell
1 keylock
Profalux
Ronis
2 identical keylocks, 1 key
Profalux
Ronis
2 keylocks, different keys
Profalux
Ronis
Optional connected/disconnected/test position locking
On right-hand side of chassis
On left-hand side of chassis

VPOC - racking interlock


IPA - cable-type door interlock
IBPO - racking interlock between crank and OFF pushbutton for NW
DAE - automatic spring discharge before breaker removal for NW
VDC - mismatch protection
Accessories
CDM - mechanical operation counter
CB - auxiliary terminal shield for chassis
CDP - escutcheon
CP - transparent cover for escutcheon
OP - blanking plate for escutcheon

Brackets for mounting 1:[HG


Test kits

Mini test kit

On backplates
Portable test kit

D-19

D-20

35, rue Joseph Monier


CS 30323
92506 Rueil Malmaison Cedex
France
RCS Nanterre 954 503 439
Capital social 896 313 776
www.schneider-electric.com
LVPED211022EN

$VVWDQGDUGVVSHFLFDWLRQVDQGGHVLJQVFKDQJHIURP
WLPHWRWLPHSOHDVHDVNIRUFRQUPDWLRQRIWKH
LQIRUPDWLRQJLYHQLQWKLVSXEOLFDWLRQ

Publication: Schneider Electric Industries SAS


Photos: Schneider Electric
Publishing: Altavia St Etienne

10-31-1247

This document has been


printed on ecological paper.

ART960666 2013 - Schneider Electric - All rights reserved.

Schneider Electric Industries SAS

04-2013