BAE SECURA OPzS

Technical Specification for Stationary VLA - Cells


1. Application
BAE OPzS - Batteries belong to the most enduring lead
acid batteries. They are suitable for stand - by operations as well as for capacitive loads. They perfectly meet
requirements for bridging times between 1h and more
than 10 h.
Fields:
Telecommunications
Emergency lighting
Microwave radio systems
Power generation plants

2. Types, capacities, dimensions, mass


Type

C10
20 C

C5
20 C

C3
20 C

C1
C8
20 C 25 C

Ri
1)

Isc
2)

Ue
V/cell

Ah
1.80

Ah
1.77

Ah
1.75

Ah
1.67

4 OPzS 200
5 OPzS 250
6 OPzS 300

210
270
320

175
220
262

156
195
234

5 OPzS 350
6 OPzS 420
7 OPzS 490

400
490
570

336
400
470

6 OPzS 600
8 OPzS 800
10 OPzS 1000
12 OPzS 1200

670
890
1120
1340

12 OPzS 1500
16 OPzS 2000
20 OPzS 2500
24 OPzS 3000

1690
2250
2810
3380

Ah
1.75

m

kA

114
143
170

205
255
304

0.95
0.76
0.63

2.16
2.70
3.24

105
126
147

208
208
208

420
420
420

12.2
14.6
17.2

17.2
20.8
24.3

11.9
14.3
16.8

282
339
396

205
245
285

378
452
526

0.70
0.58
0.50

2.90
3.48
4.06

126
147
168

208
208
208

535
535
535

18.9
22.2
25.2

26.9
31.5
36.1

18.5
21.7
24.6

560
740
930
1100

474
633
789
948

330
440
550
660

657
880
1096
1312

0.47
0.35
0.28
0.23

4.32
5.76
7.20
8.64

147
215
215
215

208
193
235
277

710
710
710
710

31.9
44.2
52.3
62.1

44.8
61.3
74.5
88

31.2
43.2
51.1
60.7

1400
1850
2300
2800

1200
1600
2000
2400

820
1100
1375
1640

1672
2232
2792
3344

0.22
0.17
0.13
0.11

9.18
12.24
15.30
18.36

215
215
215
215

277
400
490
580

855
815
815
815

80.4
102.5
129.8
159.4

1, 2) internal resistance and short - circuit - current from IEC 60896-11

4 OPzS 200 to 6 OPzS 600

E N E R G Y

8 OPzS 800 to 12 OPzS 1500

F R O M

length width height mass mass lead


h
t
3)
4) mass
(max.)
mm
mm
mm
kg
kg
kg

3) dry-charged

16 OPzS 2000

114.3 78.6
151.5 100.0
193 127.0
234.5 156.0

4) filled and charged

20 OPzS 2500 to 24 OPzS 3000

B A T T E R I E S

BAE

Technical Specification for BAE SECURA OPZS

4. Charging
IU - characteristic

float current
boost charge
charging time up to 88%
5. Discharge characteristics
reference temperature
initial capacity
depth of discharge (DOD)
deep discharges

6. Maintenance
every 6 months
every 12 months
7. Operational data
operational life
water - refilling - interval
IEC 896-1 cycles
self-discharge
operational temperature
standard
tests according
safety standard, ventilation
transport

Imax without limitation


U = 2.23 V/cell 1%, between 10C and 55C
U/T = -0.003 V/K below 10C in the monthly average
15 mA/100 Ah, increasing to 30 mA/100 Ah at the end of life
U = 2.35 to 2.40 V/cell, time limited
6 h with 1.5 x I10 initial current, 2.23 V/cell, 80% C3 discharged
20C
100%
normally up to 80%
more than 80% DOD or discharges beyond final discharge
voltages (dependent on discharge current) have to be avoided

check battery voltage, pilot block voltage, temperature


record battery and block voltages and temperatures

20+ years in stand-by operation, float


more than 3 years at 20C
> 1500
approx. 3% per month at 20C
-20C to 55C
recommended 10C to 30C
DIN 40 736 part 1
IEC 60896 - 11
EN 50 272-2
Batteries are not subject to ADR (road transport), if the conditions of the special rule 598
(chapter 3.3) are observed.

BAE
in Germ

an

de

DIN EN ISO 9001:2000

BAE

BAE Batterien GmbH


Wilhelminenhofstrae 69/70
12459 Berlin Germany
P.O. Box 9 12442 Berlin Germany
Tel. +49 30 53001-647
Fax +49 30 53001-675
E-mail: international@bae-berlin.de
www.bae-berlin.de

Technical details may be subject to alterations.

connector screw
kind of protection

4804038

pole - bushing
kind of pole
connectors

04/2006

negative electrode
separation
electrolyte
container
lid
plugs

tubular - plate with a polyester gauntlet and solid grids in a corrosionresistant PbSb1.6SnSe - alloy
grid - plate in low antimony alloy with long - life expander material
microporous separator
sulphuric acid with a density of 1.24 kg/l,
high impact, transparent SAN (Styrol-Acryl-Nitril)
SAN in dark grey colour
labyrinth plugs for arresting aerosol, optional ceramic plugs or ceramic
funnel plugs according DIN 40 740
100% gas- and electrolyte-tight, sliding, injection-moulded Panzer pole
M10 brass insertion
insulated solid copper connectors with cross-section of 90, 150 or 300 mm2; on request:
flexible insulated copper cables with cross-section of 35, 50, 70, 95 or 120 mm2
M 10, steel, insulated
IP 25 regarding DIN 40 050, touch protected according VBG 4.

Ma

3. Design
positive electrode