SICAM microRTU

6MD203 Remote Terminal Unit

Power Automation
Catalog
SICAM 2.3.1 ⋅ 2001
SICAM microRTU SICAM microRTU Page

6MD2030 Remote Terminal Unit


Description 2

The SICAM microRTU belongs Make use of the advantages


to the family of SICAM devices offered by the
Scope of performance 3
notable for their combination of SICAM microRTU:
programmable controller and
telecontrol unit. n Attractively priced
Parameters 4 to 6
The SICAM microRTU is a n Useable for the automation of
telecontrol unit based on gas and hydro-electric stations
SIMATIC S7-200 and can be used as well as for the monitoring
Accessories 7
optimally for small volumes of in- and control of electrical energy
supply systems Handling
formation.
Up to 64 data points can be proc-
n Minimum space requirements
essed with the SICAM by virtue of compact design Technical data 7 and 8
microRTU.
The SICAM microRTU can be n Simplified installation thanks
used for general telecontrol tasks to the snap-on design onto
standard mounting rail and Selection and 9
in public and industrial power
connections with screw-type ordering data
supply systems such as for
contacts
conditioning and transmission of
indications, measured values, n Speedy commissioning by
metered values and furthermore
Accessories 10 and 11
practical pre-assigned parame-
for the output of pulse and ters
persistent commands.
n Maintenance-free, no calibra-
tion or adjustment required Spare parts 11

n Stocking of spare parts is kept


to a minimum as the same unit
Conditions of sale 12
can be used for gas/water and
energy areas and delivery

n Self-configuring to as large an
extent as possible by the auto- Catalog index 13
matic updating of the hardware
configuration
Fig. 1
n Easily adaptable to control cen-
SICAM microRTU
with expansion ters due to the internationally
module standardized IEC 60870-5-101
telecontrol protocol.

Supersedes Catalog
SICAM 2.3.1 ⋅ 1999

 Siemens AG 2001
SIP052f.tif

Siemens SICAM 2.3.1 ⋅ 2001 1


SICAM microRTU
6MD2030 Remote Terminal Unit
Description

n The system basis of the


SICAM microRTU is the
SIMATIC S7-200.
The S7-224 and S7-226
SIMATIC CPUs can be
used for the SICAM
microRTU.
The table below contains

SIP051f.tif
the most important data.
Fig. 2
SICAM microRTU
with mounting rail
modem

n S7-200-CPUs

Features S7-224 S7-226


Dimensions (w x h x d) 120.5 x 80 x 62 mm 196 x 80 x 62 mm
Power supply, integrated 24 V DC or 24 V DC or
110 / 230 V AC 110 / 230 V AC
Memory
Program (EEPROM) 8 K words 8 K words
User data 5 K words 5 K words
Inputs and outputs (I/O)
Inputs 14 DI: 24 V DC 24 DI: 24 V DC
Outputs 10 DO: 24 V DC, relays 16 DO: 24 V DC, relays
Communication
Number of interfaces 1 (RS485) 2 (RS485)
Supported protocols:
Interface 0 (Port 0) IEC 60870-5-101 IEC 60870-5-101
unbalanced mode unbalanced mode
Interface 1 (Port 1) – PPI

To control center

Remote
terminal unit
as “node”

Operator station
Modem

2-wire circuit

CPU CPU
Modem Modem

Fig. 3 Configuration with SICAM microRTU

2 Siemens SICAM 2.3.1 ⋅ 2001


Scope of performance

n Scope of performance 1 Function S7-224 S7-226 Transmission


acc. to IEC 60870-5-101
n The SICAM microRTU sup- Integrated digital inputs 14 24
ports the input/output func- Single point indications max. 14 max. 24 TK 1
tions listed in the table Double-point indications max. 7 max 12 TK 3
opposite: Metered values max. 4 max. 4 TK 15
Integrated digital outputs 10 16
Single commands max. 10 max. 16 TK 45
n Scope of performance 2 Double commands max. 5 max. 8 TK 46
Expansion modules
The processing functions
Digital inputs max. 16 max. 8
n Indications Single point indications max. 16 max. 8 TK 1
− Input filter Double-point indications max. 8 max. 4 TK 3
The first 16 digital inputs can Digital outputs max. 16 max. 16
be filtered: Range 0.2 ms to Single commands max. 16 max. 16 TK 45
12.8 ms adjustable with Double commands max. 8 max. 8 TK 46
STEP 7 Micro / Win. Analog inputs max. 16 max. 16
− Acquisition Measured values, normalized max. 16 max. 16 TK 9
The first 16 inputs are ac-
quired in the 10 ms scan and n Commands − TK 9: Measured value, nor- n Scope of performance 4
stored in the message malized value without time,
buffer in the correct sort or- − Outputs
quality identifications: “not n Operating mode control
der. Impulse (1 out of n-monitor- topical for module distur-
ing) or continuous output. This comprises:
− Transmission bances”.
Command messages of the − A high-priority message
The transmission is imple- − TK 15: Metered value with- buffer list for organizational
type TK45 / TK46 are ex- out time, quality identifica-
mented spontaneously or on pected for this purpose. De- information (start indica-
demand, using the tion: CA-”counter adjus- tion, acknowledgements)
pending on the qualifiers 0, ted”. After restoring, the
TK1 / TK3 message type. 1 and 2, it is possible to − A message buffer list for
metered value is deleted
n Metered values parameterize three com- process information (buffer
and then the CA bit will be
mand output times. Continu- depth >200 changes of in-
− Acquisition ous commands are possible
set.
dications)
Up to 4 metered values for a with qualifier 3 (only TK 45). n Process information in − Interrogation list group 0
maximum metering fre- the control direction (general interrogation) for
quency of 20 Hz. n Maximum expansion
− TK 45: single command indications and parame-
Optionally, a total of up to 32 terizable for metered and
− Restoring digital inputs and 32 digital − TK 46: double command measured values
The metered values can be outputs can be processed
relocated and transmitted by application of expansion n System information in − Interrogation list group 1
via an internal timer or modules. monitoring direction for measured values
TK101 metered-value inter- − TK 70: initialization end − Metered value interroga-
rogation command. It can be n Scope of performance 3 tion list
parameterized whether or n System information in
The SICAM microRTU is ca- control direction Each of the interrogation
not the metered value lists is acknowledged follow-
should be deleted after pable of implementing the − TK 100: general interroga-
IEC 60870-5-101 telecontrol ing activation; the content is
restoring. tion command transferred via the message
protocol in unbalanced
− Metered value mode. − TK 101: metered value in- buffer, and finally an ac-
terrogation command knowledgement message is
A 31 bit metered value The SICAM microRTU sent.
buffer is available for each − TK 103: time synchroniza-
supports the following func- tion.
metered value. tions: n Parameters
n Measured values n They are stored in the DB1
n Process information in data block and loaded into
− Monitoring of the analog the monitoring direction the SIMATIC CPU by the
modules − TK1: single-point indication PC in such a fashion that
Cyclic and/or on-demand without time, quality identi- no power failure can occur.
transmission using the TK9 fications not supported
message type. Module dis- − TK 3: Double-point indica-
turbances affect the NT (not tion without time, quality
topical) status of the mea- identifications not sup-
sured values messages. ported

Siemens SICAM 2.3.1 ⋅ 2001 3


SICAM microRTU
6MD203 Remote Terminal Unit
Parameters

n Parameter structure V2

// *** Parameters for SICAM microRTU version 2 and higher ***


//
// ****************************************************
//
// VB1O-VB17-> License number
// Input of license number (8 signs) in ASCI format:
e.g. ‘12345678’
// Please take your license number from your product card
//
// ****************************************************
//
// VB20 Baud rate
// 2 9600 Bd
// 3 4800 Bd
// 4 2400 Bd
// 5 1200 Bd
// 6 600 Bd
// 7 300 Bd
//
// ****************************************************
//
// VB21------> Message receive diagnosis and transmission output (RTS output)
// Bit 0 1: Q1.0 to be activated as RTS output, Q1.1 to be activated as receipt control
// 0: Q1.0 and Q1.1 not to be activated during message traffic usable as command output
//
// ****************************************************
//
// VB22------> RTS lead time
// 1-255 (*1Oms) corresponding to 10-2550 ms
//
// ****************************************************
//
// VB23------> RTS overtravel time
// 0-255 (*1Oms) without or corresponding to 10-2550 ms
//
// ****************************************************
//
// VB3O------> Length of link address
// permissible values are: 1,2 (octets)
//
// ****************************************************
//
// VW32------> Link address
// depending on the length of the link address (VB3O)
// L=1 octet: 1-254 (1-FEh)
// L=2 octets: 1-65534 (1-FFFEh)
//
// ****************************************************
//
// VB34------> Length of ASDU address (Application Service Data Unit)
// permissible values are: 1,2 (octets)
//
// ****************************************************
//
// VW36------> ASDU address
// depending on the length of the ASDU address (VB34)
// L=1 octet: 1-254 (1-FEh)
// L=2 octets: 1-65534 (1-FFFEh)
//
// ****************************************************
//
// VB38------> Length of information object address
// permissible values are: 1,2,3 (octets)
//
// ****************************************************
//
// VD40------> Basic address of process indications (SPI + DPI)
// depending on the length of the information object address (VB38)
// L=1 octet: 1-224
// L=2 octets: 1-65504
// L=3 octets: 1-16777184
//
// ****************************************************

4 Siemens SICAM 2.3.1 ⋅ 2001


n Parameter structure V2 (continued)

//
// VD44------> Basic address for internal indications
// Message buffer, buffer overflow -> indication is spontaneous, not listed in interrogation lists
// depending on the length of the information object address (VB38)
// L=1 octet 1-224
// L=2 octets: 1-65504
// L=3 octets: 1-16777184
//
//****************************************************
//
// VD48------> Basic address metered values
// depending on the length of the information object address (VB38)
// L=1 octet: 1-252
// L=2 octets: 1-65532
// L=3 octets: 1-16777212
//
// ***************************************************
//
// VD52------> Basic address measured values
// depending on the length of the information object address (VB38)
// L=1 octet: 1-240
// L=2 octets: 1-65520
// L=3 octets: 1-16777200
//
// ***************************************************
//
// VD56------> Basic address commands (single command + double command)
// depending on the length of the information object address (VB42)
// L=1 octet: 1-224
// L=2 octets: 1-65504
// L=3 octets: 1-16777184
//
// ***************************************************
//
// VB60-VB63-> Activated single point indications
// VB63: E0.0 - E0.7
// VB62: E1.0 - E1.7
// VB61: E2.0 - E2.7
// VB60: E3.0 - E3.7
//
// ***************************************************
//
// VB64------> SPI list parameter

// Reserved, must have 0 assigned to it


//
// ***************************************************
//
// VB66-VB69-> Activated double point indications
// VB69: E0.0 - E0.7
// VB68: E1.0 - E1.7
// VB67: E2.0 - E2.7
// VB66: E3.0 - E3.7
//
// ***************************************************
//
// VW70------> Fault position suppression DPI in 100 ms intervals
// 0 without
// 1-32767 0.1 - 3276.7 sec
// Accuracy +/-100 ms
//
// ***************************************************
//
// VB72------> DPI list parameter

// Reserved, must have 0 assigned to it.


//
// ***************************************************
//
// VB74------> Quantity of metered values
// 0 No metered values
// 1-4 Quantity of metered values (input 0.0-0.3)
//
// ***************************************************

Siemens SICAM 2.3.1 ⋅ 2001 5


SICAM microRTU
6MD203 Remote Terminal Unit
Parameters

n Parameter structure V2 (continued)

// VB75------> Internal restoring interval for metered values


// 0 No restoring
// Restoring interval in minutes: the following values are permitted:
// 1,2,3,4,5,6,10,12,15,20,30,60 min

//
// ***************************************************
//
// VB76------> Metered value list parameters
// Bit 0 -> Metered value transmitted spontaneously after restoring
// Bit 1 -> Metered value in interrogation group 0 (general interrogation)
//
// Bit 4 -> After restoring metered value is reset via internal timer
//
// ***************************************************
//
// VB78-VB79-> Measured values released for transmission
// VB78 MW 8-15
// VB79 MW 0-7
//
// ***************************************************
//
// VB80------> Cyclic measured value transmission (time-controlled)
// 0 No cyclical measured value transmission
// 1-255 Trigger in sec
//
// ***************************************************
//
// VB81------> Measured value list parameter

// Bit 0 -> Measured value in interrogation group 0 (general interrogation)


// Bit 1 -> Measured value in interrogation group 1
//
// ***************************************************
//
// VB82------> Allocation of time code to the command output time for qualifier 0
// 0 not permissible
// 1-255 100 ms-25.5 sec
//
// ***************************************************
//
// VB83------> Allocation of time code to the command output time for qualifier 1
// 0 not permissible
// 1-255 100 ms-25.5 sec
//
// ***************************************************
//
// VB84------> Allocation of time code to the command output time for qualifier 2
// 0 not permissible
// 1-255 100 ms-25.5 sec
//
// ***************************************************
//
// VW86------> Monitoring of time synchronization (in minutes)
// Free
// 0 without
// 1-255 1 - 255 min with accuracy x + 1min
//
// ***************************************************
//
// VB88------> Time stamp in indication messages
// Free
//
// *****************************************************

6 Siemens SICAM 2.3.1 ⋅ 2001


Accessories
Handling

n Modem n Commissioning (Fig. 4)

n A V.23 modem is available n Auxiliaries STEP 7-Micro/WIN


for the SICAM microRTU in Together with the required
accordance with the de- hardware such as S7-200
sign and the price of the components and modem,
unit. Possible modems are the following items are re-
e.g. Induline IL2K4 or MD2. quired for the commission- S7-200-CPU
In the control center, it is ing of SICAM microRTU. RS232
also possible, for example,
− Runtime software on dis-
to use an MD 100 modem.
kette
n The electrical level of the − STEP 7-Micro/WIN as of
communications interface version V2.1 Personal Computer RS485
on the S7-224/226 CPU is
− PC/PPI cable
RS485. The Induline IL2K4
and MD2 modem already in- − PC or PG.
corporates the RS485 inter- PC/PPI-cable
n Runtime software
face.
It is possible to obtain an in-
dividual license for this soft- Fig. 4 Communication
ware. The software may with SICAM microRTU
n Diagnosis,
trouble-shooting only be loaded once onto a
CPU. Each diskette is allo-
n LED displays cated its own registration
number which can be read
In addition to the LEDs on Technical data
from the CPU. In the event
the CPU and the expansion
of a malfunction, this num-
modules (see SIMATIC
ber is used to identify the
manual), two digital outputs
software.
are used as follows:
− RTS, message transmis- n Parameterizing
n General technical data
sion LED The parameters in the DB1
The output Q1.0 has a data block can be changed National and international directives
message transmission using STEP 7-Micro/WIN. The directives shown below were used for the definition of
control function. The parameters, their pur- the relevant performance characteristics and technical
− EK, message receive LED pose and the default set- data, as well as for the testing of the S7-200 product
The output Q1.1 has a tings are contained in the series.
message receive control SICAM microRTU manual.
− Underwriters Laboratories, Inc.: UL508 registered
function. When the func-
(Industrial Control Equipment)
tion is being applied, 2
command outputs can not n Supply configurations − Canadian Standards Association: CSA C22.2
be parameterized. Number 142, tested (Process Control Equipment)
This function should only The SICAM microRTU can − Factory Mutual Research: FM class 1, category 2,
be used with electronic be supplied in the following dangerous goods groups A, B, C and D, T4A
outputs. versions:
− VDE 0160: electronic devices for use in substations and
n Buffer overflow n SICAM microRTU power plants
Reaction of overflow of the product − EC directive on low voltages
internal buffers for the indi- The SICAM microRTU is − EN 61131-2: automation systems - requirements of the
cation acquisition. supplied in individual parts, devices
− Reset of the SICAM for example consisting of
microRTU CPU, expansion modules, n CE Conformity
modem and a diskette con-
− TK1 error message to taining the runtime software
control center This product is in conformity with the directives of the
(SICAM RTC for microRTU). Council of the European Communities on the approximati-
Note: metered value on of the laws of the Member States relating to electro-
processing remains unaf- n SICAM microRTU
system magnetic compatibility (EMC Council directive 89/336/EEC)
fected and concerning electrical equipment for use within speci-
The SICAM microRTU is
n Module disturbances fied voltage limits (low-voltage directive 72/23/EEC).
supplied as a complete
Analog input: device, consisting of The product conforms to the international standard
a housing with the CPU, IEC 60 255 and the national standard DIN 57 435/Part 303.
− Failure of external auxiliary
supply a modem, terminals and a The device is designed for use in an industrial environment
diskette containing the according to the EMC standard specification.
− Module fails (configuration runtime software (SICAM
error) Conformity is proved by tests performed by Siemens AG in
RTC for microRTU). line with article 10 of the Council Directives in accordance
Response: Optionally: expansion with the generic standards EN 50081 and EN 50082 for
− “NT bit” is set (not topical), module and buffer unit, EMC directive and EN 60 255-6 for the low-voltage directi-
measured value remains installation and testing. ve.
unchanged

Siemens SICAM 2.3.1 ⋅ 2001 7


SICAM microRTU
6MD203 Remote Terminal Unit
Technical data

n SICAM microRTU

Power supply
Rated voltage 24 V DC
– Voltage range 20.4 to 28.8 V DC
– Input current typically 85 mA, only CPU, maximum load current 900 mA
– Electrically isolated no
Rated voltage 110/230 V AC
– Voltage/frequency range 85 to 264 V AC / 47 to 63 Hz
– Input power typically 4.5 VA, only CPU, max. power 50 VA
– Electrically isolated yes, transformer, 1500 V AC, 1 min
Inputs
Voltage range for CLOSED 15 to 30 V DC, 35 V DC, voltage surge 500 ms
Rated voltage for CLOSED 24 V DC
Rated current 7 mA
Electrical isolation 500 V AC, 1 min
Electronic outputs
Voltage range 20.4 to 28.8 V DC
Maximum load current at 0 to 40 °C at 55 °C
– For each individual output 0.75 A 0.5 A
– For two adjacent outputs 1A 0.75 A
– Outputs overall 4A 3A
Surge current 4 A, 100 ms
Electrical isolation 500 V AC, 1 min
Short-circuit protection no
Relay outputs
Voltage range 5 to 30 V DC / 250 V AC
Max. load current 2 A / output, 8 A / conductor
Overvoltage surge 7 A when contacts are closed
Service life 10 000 000 switching cycles without load
100 000 switching cycles under load
Electrical isolation
– Coil to contact 1500 V AC, 1 min
– Contact to contact 750 V AC, 1 min
Degree of protection IP20
Ambient temperature
During continuous operation 0 to 55 °C, max. 95 % humidity without condensation
During transport/storage – 40 to + 70 °C

n Expansion module for measured values

Inputs
Maximum input voltage 30 V DC
Maximum input current 32 mA
Resolution 12 bit A/D conversion
Electrical isolation no
Power input 2W
Inputs and outputs 4 analog inputs with common potential
Dimensions (w x h x d) 46 x 80 x 62 mm
Weight Approx. 100 g
Configuration switch
Input ranges 0 to 5 V, 0 to 10 V, 0 to 20 mA

8 Siemens SICAM 2.3.1 ⋅ 2001


Selection and
ordering data

n no.
Order No. Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

SICAM microRTU Remote terminal unit including runtime software 6 MD 2 0 3 o - 0 o o 0 o - 2 A A 0


s s s s

Supply configuration
Product, supplied in individual parts 0
System, supplied in individual parts, additionally with housing and built-in components 1

S7-224 processor: 14 indications, 10 commands


S7-226 processor: 24 indications, 14 commands
6ES7 214-1AD21-0XB0, 24 V DC, 24 V DC inputs1), 24 V DC outputs, electronic B
6ES7 214-1BD21-0XB0, 110/230 V AC, 24 V DC inputs2), 24 V DC/250 V AC relay outputs C
6ES7 216-2AD21-0XB0, 24 V DC, 24 V DC inputs, 24 V DC outputs, electronic J
6ES7 216-2BD21-0XB0, 110/230 V AC, 24 V DC inputs, 24 V DC/250 V AC relay outputs K

Number of analog inputs (EM231)


without A
1 EM231 module (4 measured values) B
2 EM231 modules (8 measured values) C
3 EM231 modules (12 measured values) D
4 EM231 modules (16 measured values) E

Modem
without modem 0
IL2K4 RS485, V.23, 1200 bit/s, multidrop partyline, half-duplex, 2-wire with connection cable 1

STEP 7-Micro/WIN 32 V3.1 (32 bit version) 6ES7810-2BC01-0YX0

PC/PPI cable (RS232 RS485 converter) 6ES7901-3BF20-0XA0

Documentation
English
SICAM 2.3.1 Catalog SICAM microRTU E50001-K5602-A311-A3-7600
Manual SICAM microRTU E50417-H8976-C057-A1
System manual S7-200 6ES7298-8FA01-8BH0
German
SICAM 2.3.1 Catalog SICAM microRTU E50001-K5602-A311-A3
Manual SICAM microRTU E50417-H8900-C057-A1
System manual S7-200 6ES7298-8FA01-8AH0

1) Current-sinking
2) Current-sourcing

Siemens SICAM 2.3.1 ⋅ 2001 9


SICAM microRTU
6MD203 Remote Terminals Unit
Accessories

n SIMATIC modules Order No.

Expansion modules
Digital inputs
Module for S7-224/-226
EM221: Digital inputs, 8 x 24 V DC 6ES7 221-1BF21-0XA0
Digital outputs
Module for S7-224/-226
EM222: Digital outputs, 8 x relay outputs, 2 A 6ES7 222-1HF21-0XA0

Modem - CPU connecting cable


Modem - CPU connecting cable 6MD4301-0AD00

2.5 kV isolation with Phönix PLC relay (6.2 mm)


PLC-R-relay with gold-plated contacts for indications
PLC-RSC-24DC/21AU 24 V DC 29 66 26 5
PLC-RSC-48DC/21AU 48 V DC 29 66 12 6
PLC-RSC-60DC/21AU 60 V DC 29 66 14 2
PLC-RSC-120UC/21AU 110/120 V DC/AC 29 66 28 1
PLC-RSC-230UC/21 AU 220/230 V DC/AC 29 66 29 4
PLC system connection for inputs
PLC-V8/FLK14/IN, block for 8 inputs 22 96 55 3
System cable 0.5 m 22 88 90 1
System cable 1.0 m 22 88 91 4
PLC-R-relay with power contact
max. switching voltage 250 V DC/AC
max. breaking power at resistive load: 24 V DC at 140 W, 48 V DC at 20 W,
60 V DC at 18 W, 110 V DC at 23 W, 220 V DC at 40 W
PLC-RSC-24DC/21 24 V DC 29 66 17 1
PLC relay for high continuous current
max. switching voltage 250 V DC/AC
max. breaking power at resistive load: 24 V DC at 144 W, 48 V DC at 144 W,
60 V DC at 48 W, 110 V DC at 50 W, 220 V DC at 80 W
PLC-RSC-24DC/21HC 29 67 62 0
PLC system connection for outputs
PLC-V8/FLK14/OUT, block for 8 outputs 22 95 55 4
System cable 0.5 m 22 88 90 1
System cable 1.0 m 22 88 91 4

n Power supply

Power supply DC/DC, AC/DC


DC/DC converter 48/60/110 V DC, 24 V DC; 2 A 6EP1732-0AA00
AC/DC converter for UE: 110 to 230 V AC, 220 V DC, 24 V DC; 2.5 A 6EP1332-1SH12
Backup unit
AC/DC converter for UE: 120/230 V AC, 24 V DC; 5 A 6EP1333-2BA00
DC-USV module 15, input 24 V DC, output 24 V DC 6EP1931-2EC01
Battery module (lead-acid) for DC-USV module 15, 24 V DC, 7 Ah 6EP1935-6ME01

n Modem

Modem IL2K4 at the SICAM microRTU


IL2K4, V.23, 1200 bit/s, multidrop party line, RS485 6MD4500-0AB00
Modem MD 100 in the control center
MD100, V.23, 1200 bit/s, multidrop party line, RS232 6NH9810-2A

10 Siemens SICAM 2.3.1 ⋅ 2001


n Programming, test Order No.

Interface cable RS485 - RS232


For connection to the PPI interface of the S7-200 to a PC. The cable is used
for loading the CPU software into the S7-200 CPUs with STEP 7-Micro/WIN.
PC/PPI cable; 5 m long, RS232/RS485 6ES7 901-3BF20-0XA0
Configuring tool for S7-200 CPU
STEP 7-Micro/WIN runs under WIN 95 or NT. It can be connected to
the S7-200 via the COM interface of a PC by means of the PC/PPI cable.
Operation via PG 7xx and MPI interface is also possible.
STEP 7-Micro/WIN 32 V3.1, individual license, CD-ROM 6ES7810-2BC01-0YX0
Upgrade to V3.1, CD-ROM 6ES7810-2BC01-0YX3

Spare parts

Modem IL2K4 at the SICAM microRTU


IL2K4, V.23, 1200 bit/s, multidrop party line, RS485 6MD4500-0AB00
Analog module EM231
S7-224/-226: AI 4 x 12 bit, 0 to 20 mA, 0 to 5 V, 0 to 10 V 6ES7 231-0HC20-0XA0

Siemens SICAM 2.3.1 ⋅ 2001 11


Conditions of
sale and delivery

n Conditions of Sale and Delivery

Subject to the
General Conditions of Supply and Delivery for Products
~The technical data, di-
mensions and weights
and Services of the Electrical and Electronic Industry and
to any other conditions agreed upon with the recipients of are subject to change
catalogs. unless otherwise stated
on the individual pages
n Export Regulations
of this catalog.
In accordance with the present provisions of the German
Export List and the US Commercial Control List, export
licences are not required for the products listed in this The illustrations are for
catalog. reference only.
An export licence may however be required due to country-
specific application and final destination of the products.
We reserve the right to
Relevant are the export criteria stated in the delivery note
and the invoice regarding a possible export and reexport adjust the prices and
licence. shall charge the price
Subject to change without notice.
applying on the date of
n Dimensions delivery. }
All dimensions in this catalog are given in mm.

n Trademarks

All product designations used are trademarks or product


names of Siemens AG or of other suppliers.

Responsible for:
Technical contents: Manfred Krautschneider
Siemens AG, PTD PA 27, Nürnberg
General editing: Claudia Kühn-Sutiono
Siemens AG, PTD CC T, Erlangen

12 Siemens SICAM 2.3.1 ⋅ 2001 Order No.: E50001-K5602-A311-A3-7600


Printed in Germany
KGK 0501 12 En 102266 6101/D6171
Catalog index

n Catalog index of the Power Transmission and Distribution (Power Automation Division)

Title Designation- Order No.


Numerical Protection Systems and Bay Control Units
Operation and Evaluation Software for Numerical Protection Devices LSA 2.0.2 E50001-K5702-A121-A1-7600
Relay Selection Guide LSA 2.0.3 E50001-K5702-A031-A2-7600
7SJ41 Definite-Time Overcurrent Protection Relay LSA 2.1.10 E50001-K5712-A201-A2-7600
7SJ511 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.3 E50001-K5712-A131-A2-7600
7SJ512 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.4 E50001-K5712-A141-A3-7600
7SJ512 Numerical Feeder Protection (Version V3.6) LSA 2.1.30 E50001-K5712-A411-A1-4A00
SIPROTEC 7SJ531 Numerical Line and Motor Protection with Control Function LSA 2.1.9 E50001-K5712-A191-A4-7600
7SJ551 Multi-Function Protection Relay LSA 2.4.2 E50001-K5742-A121-A3-7600
SIPROTEC 4 - 7SJ61/62/63 6MD63 Multifunction Protection Relay and Bay Controller SIP 3.1 E50001-K4403-A111-A1-4A00
SIPROTEC 7SJ600 Numerical Overcurrent, Motor and Overload Protection Relay SIP 3.2 E50001-K4403-A121-A1-7600
SIPROTEC 7SJ602 Numerical Overcurrent, Motor and Overload Protection Relay SIP 3.3 E50001-K4403-A131-A1-7600
SIPROTEC 7SJ601 Overcurrent Protection LSA 2.1.16 E50001-K5712-A261-A1-7600
SIPROTEC 7SA511 Distance Protection Relay (Version V3) LSA 2.1.11 E50001-K5712-A211-A2-7600
7SA513 Line Protection Relay (Version V3) LSA 2.1.12 E50001-K5712-A221-A1-7600
7SA518/519 Overhead Control-Line Protection Relay (Version V3) LSA 2.1.14 E50001-K5712-A241-A2-7600
SIPROTEC 4 - 7SA6 Distance Protection Relay for all Voltage Levels SIP 4.3 E50001-K4404-A131-A1-7600
3VU13 Miniature Circuit-Breaker LSA 2.1.8 E50001-K5712-A181-A2-7600
7SD502 Line Differential Protection with Two Pilot Wires LSA 2.2.1 E50001-K5722-A111-A2-7600
7SD503 Line Differential Protection with Three Pilot Wires LSA 2.2.2 E50001-K5722-A121-A2-7600
7SD511/512 Current Comparison Protection Relay (Version V3)
for Overhead Lines and Cables LSA 2.2.3 E50001-K5722-A131-A2-7600
7UT512/513 Differential Protection Relay (Version V3)
for Transformers, Generators and Motors LSA 2.2.4 E50001-K5722-A141-A2-7600
SIPROTEC 7RW600 Numerical Voltage, Frequency and Overexcitation Relay SIP 2.1 E50001-K4402-A111-A1-7600
SIPROTEC 7SS50 Version V1.2 Busbar/Circuit-Breaker
Failure Protection Relay (Summation Current Transformer Version) SIPROTEC 5.1 E50001-K4405-A111-A1-7600
SIPROTEC 7SD60 Numerical Current Differential Protection Relay
for Two Pilot-Wire Link SIP 5.2 E50001-K4405-A121-A2-7600
SIPROTEC 4 - 7SD610 Universal Differential Protection Relay for Two Line Ends SIP 5.4 E50001-K4405-A141-A1-7600
SIPROTEC 7SS52 Distributed Numerical Busbar and Circuit-Breaker
Failure Protection Relay LSA 2.2.7 E50001-K5722-A171-A1-7600
Auxiliary Current Transformers 4AM50, 4AM51, 4AM52
and Isolating Transformers 7XR95 LSA 2.2.6 E50001-K5722-A161-A1-7600
Introduction to Earth-Fault Detection LSA 2.3.1 E50001-K5732-A111-A2-7600
7SN71 Transient Earth-Fault Relay LSA 2.3.2 E50001-K5732-A121-A1-7600
7XR96 Toroidal Current Transformer LSA 2.3.3 E50001-K5732-A131-A1-7600
7VC1637 Earth-Leakage Monitor LSA 2.3.4 E50001-K5732-A141-A1-7600
Introduction to Generator Protection LSA 2.5.1 E50001-K5752-A111-A1-7600
7SK52 Motor Protection LSA 2.4.1 E50001-K5742-A111-A1-7600
7UM511 Generator Protection Relay (Version V3) LSA 2.5.2 E50001-K5752-A121-A2-7600
7UM512 Generator Protection Relay (Version V3) LSA 2.5.3 E50001-K5752-A131-A2-7600
7UM515 Generator Protection Relay (Version V3) LSA 2.5.4 E50001-K5752-A141-A2-7600
7UM516 Generator Protection Relay (Version V3) LSA 2.5.5 E50001-K5752-A151-A1-7600
SIPROTEC 4 - 7UM611/612 Multifunction Generator Protection Relay SIP 6.1 E50001-K4406-A111-A1-7600
SIPROTEC 4 - 7UM62 Multifunction Generator, Motor & Transformer
Protection Relay SIP 6.2 E50001-K4406-A121-A1-7600
7VE51 Synchronizing Unit LSA 2.5.7 E50001-K5752-A171-A1-7600
7VK512 Numerical Auto-Reclose/Check-Synchronism Relay LSA 2.7.3 E50001-K5772-A131-A1-7600
7SV7220 Power Supply Unit LSA 2.7.9 E50001-K5772-A191-A1-7600
7SV50 Numerical Circuit-Breaker Failure Protection Relay LSA 2.7.1 E50001-K5772-A111-A1-7600
7SV512 Numerical Circuit-Breaker Failure Protection Relay LSA 2.7.2 E50001-K5772-A121-A1-7600
7XV72 Test Switch LSA 2.6.2 E50001-K5762-A121-A1-7600
7VP151 Three-Phase Portable Test Set (Omicron CMC56) LSA 2.6.1 E50001-K5762-A111-A2-7600
Communication for Protection Devices
Centralized and Remote Control of Siemens Protection Relays (Overview) SIPROTEC 8.1 E50001-K4408-A111-A1-7600
Operating and Analysis Software DIGSI V3 LSA 2.8.2 E50001-K5782-A121-A1-7600
DIGSI 4 - Software for Configuration and Operation of SIPROTEC 4 units SIP 8.2 E50001-K4408-A121-A1-7600
DIGRA 4 - Software for the Visualization and Analysis of Fault Records SIP 8.3 E50001-K4408-A131-A1-7600
6MB252 Mini Bay Unit for Energy Automation with SICAM SIPROTEC 7.1 E50001-K4407-A111-A1-7600
SIPROTEC 4 - 6MD66 Bay Control Unit SIP 7.2 E50001-K4407-A121-A1-7600
Energy Automation
Substation SICAM RTU System SICAM 2.1.1 E50001-K5602-A111-A1-7600
SICAM miniRTU 6MD202 Remote Terminal Unit SICAM 2.2.1 E50001-K5602-A211-A2-7600
SICAM microRTU 6MD2030 Remote Terminal Unit SICAM 2.3.1 E50001-K5602-A311-A3-7600
SICAM SAS Substation Automation System SICAM 3.1.1 E50001-K5603-A111-A1-7600
PS20A-6EP8090 Power Supply Module SICAM 5.1.1 E50001-K5605-A111-A1-7600
DI32-6MD1021 Digital Input Functional Module SICAM 5.2.1 E50001-K5605-A211-A1-7600
AI32-6MD1031 Analog Input Functional Module SICAM 5.2.2 E50001-K5605-A221-A1-7600
AI16-6MD1032 Analog Input Functional Module SICAM 5.2.3 E50001-K5605-A231-A1-7600
Visualization System for SICAM SAS: SICAM WinCC SICAM 6.1.1 E50001-K5606-A111-A1-7600
SICAM plusTOOLS Configuration System SICAM 6.2.1 E50001-K5606-A211-A1-7600

Siemens SICAM 2.3.1 ⋅ 2001 13


Published by
Siemens AG
Power Transmission and Distribution
Power Automation Division
Postfach 48 06
90026 Nürnberg
Germany

www.ev.siemens.de Order No.: E50001-K5602-A311-A3-7600