You are on page 1of 8

Test And Drain Valve

A61

FEMALE x FEMALE

CERTIFICATIONS

Standard equipment:
Female NPT inlet and outlet, forged
brass body, brass finish ball
with teflon seats.

LISTED 36Y7
FM approved at 300 psi *
UL listed

a
c

C
H

PORT

SPECIFY THREAD

A61

a/b (Orifice - K factor)

c (plug)

PORT

1(3/8-2.8)*

1/4

1-1/16

5-1/32

2-43/64

5-11/32

4-27/64

1-57/64

1(7/16- 4.2)*

1/4

1-1/16

5-1/32

2-43/64

5-11/32

4-27/64

1-57/64

1 (1/2-5.6) *

1/4

1-1/16

5-1/32

2-43/64

5-11/32

4-27/64

1-57/64

1(17/32- 8) *

1/4

1-1/16

5-1/32

2-43/64

5-11/32

4-27/64

1-57/64

1-1/4 (3/8-2.8)*

1/4

1-1/16

5-1/32

2-43/64

5-11/32

4-27/64

1-57/64

1-1/4 (7/16-4.2)*

1/4

1-1/16

5-1/32

2-43/64

5-11/32

4-27/64

1-57/64

1-1/4 (1/2-5.6) *

1/4

1-1/16

5-1/32

2-43/64

5-11/32

4-27/64

1-57/64

1-1/4(17/32- 8) *

1/4

1-1/16

5-1/32

2-43/64

5-11/32

4-27/64

1-57/64

1-1/4 (5/8-11.2)*

1/4

1-1/16

5-1/32

2-43/64

5-11/32

4-27/64

1-57/64

1-1/4 (3/4-14)*

1/4

1-1/16

5-1/32

2-43/64

5-11/32

4-27/64

1-57/64

GROOVE X GROOVE

CERTIFICATIONS

Standard equipment:
GROOVE inlet and outlet, forged
brass body, brass finish ball with
teflon seats.

FM approved at 300 psi

a
c

a/b (Orifice - K factor) c (plug)

C
H

PORT

SPECIFY THREAD

42

PORT

1-1/4 (3/8 - 2.8)

1/4

1-1/16

6-13/32

2-43/64

5-11/32

4-27/64 1-1/4groove

1-1/4 (7/16 - 4.2)

1/4

1-1/16

6-13/32

2-43/64

5-11/32

4-27/64 1-1/4groove

1-1/4 (1/2 - 5.6)

1/4

1-1/16

6-13/32

2-43/64

5-11/32

4-27/64 1-1/4groove

1-1/4 (17/32 - 8)

1/4

1-1/16

6-13/32

2-43/64

5-11/32

4-27/64 1-1/4groove

1-1/4 (5/8 - 11.2)

1/4

1-1/16

6-13/32

2-43/64

5-11/32

4-27/64 1-1/4groove

1-1/4 (3/4 - 14)

1/4

1-1/16

6-13/32

2-43/64

5-11/32

4-27/64 1-1/4groove

(Technical communication n A039)

A61 Test and Drain


valve
Standard equipment
Female NPT inlet and outlet, forged brass body,
chrome plated ball with teflon seats.

Products
Test and drain valve
Female x Female
1" (orifice 1/2")
1 1/4"(orifice 1/2")
1" (orifice 17/32")
1 1/4" (orifice 17/32")

Thread

A61Y005
A61Y006
A61Y015
A61Y016

1" NPT (orifice 1/2")


1 1/4" NPT (orifice 1/2")
1" NPT (orifice 17/32")
1 1/4" (orifice 17/32")

Dimensions
PORT

1" (orifice 1/2)

1 7/64" 5 1/32"

1" (orifice 17/32")

1 7/64" 5 1/32"

1 1/4" (orifice 1/2")

1 7/64" 5 1/32"

1 1/4" (orifice
17/32")

1 7/64" 5 1/32"

B
2
45/64"
2
45/64"
2
45/64"
2
45/64"

C
5
11/32"
5
11/32"
5
11/32"
511/32"

Inspection and test of the wet pipe sprinkler


system
System Test Connections
The initial test required on a wet pipe automatic
sprinkler system is the hydrostatic test at not
less that 200 psi for two hours, or 50 psi in
excess of the static pressure, when the
maximum static pressure exceeds 150 psi.
During the hydrostatic test there should be no
visible leakage from the sprinkler system
piping.
The underground mains leading to the sprinkler
system should always be thoroughly flushed
before the mains are connected to the system.
A weekly inspection of all water control valves
and alarm control valves is recommended to be
certain they remain open. (Giacomini A200
valves have green indicator to see their open or
closed position from 50 ft distance)

Wet Systems
A test connection not less than 1 in. (25 mm) in
diameter, terminating a smooth bore corrosion
resistant orifice, given a flow equivalent to one
sprinkler of a type having the smallest orifice
installed on the particular system, shall be
provided to test each waterflow alarm device for
each system. The test connection valve shall be
readily accessible. The discharge shall be to the
outside, to a drain connection capable of
accepting full flow under system pressure or to
another location where water damage will not
result.

Drainage
All sprinkler pipes and fittings shall be so
installed that the system may be drained
Giacomini Test and Drain valve merges in one
valve the above two functions of testing and
draining the system.
Connections to the branch line (a and b) 1" and
1 1/4"
Orifice 1/2" or 5/8" size

The valves will be available for two orifices:


inch and 5/8"
Special patented construction allows the ball to
be supported at the flow inlet side by a special
plastic housing.
By rotation of the lever handle the valve can be
set at:
OFF position
Test position
Drain position

Stem seals: two "O" rings with stem inserted


from inside of the valve.

The intent of this section is to require


inspector's test connection located in a manner
which will provide for the testing of all water
flow alarm devices.

It permits both an electrically operated alarm


and a water motor alarm supplied from an alarm
valve to be tested through a single test pipe.

Pressure

In multistory buildings where waterflow alarm


devices are provided at each floor or where
more than one alarm device is provided in one
sprinkler system, a test type pipe shall be
provided for

VEHZ.EX4430 - Drain Fittings, Special Type

1 de 1

http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpag...

VEHZ.EX4430
Drain Fittings, Special Type
Page Bottom

Drain Fittings, Special Type


See General Information for Drain Fittings, Special Type
GIACOMINI SPA

EX4430

VIA PER ALZO 39


28017 S MAURIZIO D'OPAGLIO, NOVARA ITALY
Model A61 Test and Drain fitting, 1 in. and 1-1/4 in. NPT size simulating a 2.8, 4.2, 5.6, 8.0, 11.2 and 14.0 K-factor, for installation in threaded steel
pipe where pressures do not exceed 300 psig.
Model A61 Test and Drain fitting, 2 in. NPT size simulating a 4.2, 5.6, 8.0, 11.2, 14.0, 16.8, 22.4 and 25.2 K-factors, for installation in threaded or
grooved steel pipe where pressures do not exceed 300 psig.
This fitting is intended for installation on sprinkler systems in accordance with the Standard for Installation of Sprinkler Systems, NFPA 13.
Last Updated on 2009-09-28
Questions?

Print this page

Notice of Disclaimer

Page Top
Copyright 2010 Underwriters Laboratories Inc.

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data
(or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must
appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright
2010 Underwriters Laboratories Inc."

19/07/2010 02:37 p.m.

Sprinkler System Alarm Testers


Each separate sprinkler system must be equipped with a separate waterflow alarm. In a high rise building, the system for each floor
must be separately alarmed. Where pressure reducing valves are used, a dual alarm and drain piping arrangement is required. The
alarm testers listed below combine test and drain valves, a waterflow sight glass, and a calibrated flow orifice in a single assembly to
simplify the piping required for such arrangements.

Model A61
Model Designation

Size, inches NPS

Nominal
K-factor(s)

Rated working
pressure,
psi (kPa)

Remarks

A61

2.8, 4.2, 5.6, 8.0

300 (2070)

A61

1 14

2.8, 4.2, 5.6, 8.0, 11.2,


14.0

300 (2070)

a, b

A61

4.2, 5.6, 8.0, 11.2,


14.0, 16.8, 22.4, and
25.2

300 (2070)

a, b

Remarks:
a. Devices supplied with female NPT threaded end connections.
b. Devices supplied with grooved end connections.

Company Name: Giacomini SpA


Company Address: Strada Per Alzo 39, 28017 S Maurizio d'Opaglio, Italy
Company Website: http://www.giacomini.com
Listing Country: Italy
Certification Type: FM Approved

2007-2010 FM Approvals. All rights reserved.

1 of 1

You might also like