P-100H
TEMPERATURE CONTROLLER
(User's Manual)

DIGITAL KOREA Co.,Ltd


http://www.poard.co.kr
991-21 Geomsa-dong, Dong-gu, Daegu, Korea / Tel : +82.53.964.0475 / Fax : +82.53.964.1906
Notice about safety

Before using, certainly read the guideline for correct use and use it correctly.
Please let the operating manual carried to the final user and a good repair chief.
After reading the operation manual, Please keep it at a place for a person using a product to be
able to always see well.

CONTENT

The guideline
for correct use

-----------------------

Summary

-----------------------

Characteristic

-----------------------

Appearance

-----------------------

Set-up method

-----------------------

-----------------------

-----------------------

-----------------------

10

In-put/Out-put
specific

Function &
Movement explain

Terminal connection
diagram

SIZE

-----------------------

10

Sensor specific

-----------------------

10

FAN wiring diagram

-----------------------

11

10

Page 2

The guideline for correct use

Thank you for buying P-100H.

P-100H is Transformer Digital Temperature Controllr.


"For Correct Use" is a indication about operation or emergency measures that we produce. Therefore
this guide book is enough familiar before use as it is to use safely and please prepare in case of a
product disorder.

Things to be careful about during installation


1 Make sure the indicator is installed only indoors or in a closed place.

2 Do not fasten the case engagements too tightly.


3 Do not install the indicator in a place exposed to.
Corrosive gases
Moisture or high humidity
Vibration or heat
Dust
High radio frequencies
Poor ventilation or air circulation
The place where the detonating gas occurs
A notice is classified by warning and caution, an electric shocks.
If there is the following symbol, you read carefully to avoid the dangerous occurrence, and you shoul
obey it in indication
Warning

- If you violated instructions, serious injury or


death can occur.

Caution

- If you violated instructions, slight injury or


product damage can occur.

Electric
shocks

- As there is possibility of an electric shock


under specific condition, the symbol indicate to pay
attention.

Page 3

Warning

Don't disassemble, assemble or remodel P-100H optional. If trouble is occurrde to the product and
it is needed maintenance work, you should work the operation power and the usual power after doing

OFF And before solving the problem, don't do re-closing P-100H power.

Caution

- Please P-100H not install close dangerous substances and firearms.


- Please be careful not to enter a bolt, metal or flammability in the product inside.
- Don't install in the place that shine the direct ray of the sun or can be affectde by the direct effect
of the rain.
- Please do not use a softer volt than defined length and tighten it to a limitde torque. If you give
force forcibly, a nut for fixing can drop.
- In case of electric wiring, we wish that you"ll wire to fit terminal number to the rear terminal.

Caution

Electric shocks

- As the operation power supplies voltage above

AC220V or DC110V,

you should pay attention in

electric shock.
- Please supply the power the product operation power to fit polarity and standard spec to a
power terminal[No.12,NO.13]
- As output terminal of Warning
supplies woltage above

[No.8,No.9],

AC220V or DC110V,

Fault [No.10,No.11], FAN[No.6,No.7]


you should pay attention in electric shock.

- Please use the terminal in case of electric wiring and don't use the damaged cable.
- Please don't use the terminal, when the power is input or while operating.

Caution

Electric shocks

When you ground P-100H, you should ground voltage not to be risen in the panel as
electric safety rules.

The inside except the outside of P-100H never disassemble it. Please obey it in
indication as I contact you by head office quality control teams.
Tel : +82.53.964.0475

Fax : +82.53.964.1906

Page 4

1. Summary
P-100H

is a meter with temperature sensor(PT-100), which is used for the purpose of transformer

temperature watch and control. It measures a temperature and the damage which is caused by at
temperature prevents. Also it minimize power loss with cooling fan control.
Using analog communication(4~20mA), because it has a networking which is connected
with several meters, it is possible to check its function in a long range.

2. Characteristic
2-1 It receives the input of the Temperature sensor(PT-100) and it operate.
2-2 Peak value memory and display mode : It remember temperature that was the highest and indicate
a temperature value to SND disply to a Peak value.
2-3 It can measure accurately because it is not using former analog compensation mode but using
digital compensation mode.
2-4 It applies the Hi, Hi-Hi a notion WARNING(Alarm1) and FAULT(Alarm2). Therefore it is possible a
flexible disposal.
- WARNING(Alarm1)

action

: When measure temperature passes overAlarm1(Hi) setting value,

it sends LED-lighting and WARNING RELAY output.

- FAULT(Alarm2) action : When measure temperature passes over Alarm2(Hi-Hi) setting value,

it sends LED-lighting and FAULT RELAY output.

2-5 FAN/MAN Key : We can do ON/OFF FAN by manual operate.


(It is done ON/OFF automatically in normal times state)
2-6 When sensor is connected wrong and is damaged(a breakdown), it displays
Initial setting value
Analog value output range : 0.0 ~ 200.0,
Warning 110, Fault 130, FAN ON 90, FAN OFF 70

Page 5

3. Appearance

3-1 DISPLAY

Indication
department

Output
department

PEAK FND

Present temperature /
Set temperature indicate
Maximum temperature display

WARNING LED

Alarm 1 occurrence

FAULT LED

Alarm 2 occurrence
Display present FAN a condition that is
ON automatically
Display present FAN a condition that is
ON manually
Display the condition, if sensor is wrong
connected and is damaged
ERROR operations and alarm 1, alarm 2
operation at the time of indications

FND

FAN/ON AUTO LED


FAN/ON MANUAL LED
ERROR LED
BUZZER. STOP LED

3-2 CONTROL Key

Move set mode / Save setting value

Move from set mode to present temperature

Increase setting value(INC)

display mode / OFF Buzzer manually

Decrease setting value(DEC)


CPU RESET

Use FAN ON / OFF manually

When a meter will not be operated normally, operate

Key with a pin.

Page 6

4. Set-up method
When

Key is pressed, move to the setting mode. If you pressed

Key, a present

temperature display is indicated.


(If you pressed

Key after settings value is changed [

] in the set mode,

changed settings value is saved and you hear long buzzer.)

Present temperature display

PEAK value display

Key : PEAK value Clear

WARNING(Alarm1) value setting display

FAULT(Alarm2) value setting display

Device number setting display(P-100HD)

WARNING(Alarm1), FAULT(Alarm2) Buzzer ON/OFF setting display

Page 7

Test display : WARNING, FAULT, FAN Relay and indication LED

Manual operation. [ON : INC Key and OFF : DEC Key] operated
with compulsion
(When continuously is to this mode and normally does not
become the control operation)

4 ~ 20mA out-put High temperature setting display

4 ~ 20mA out-put Low temperature setting display


(Temperature that's 0 or lower is not applicable)

FAN ON temperature setting display

FAN OFF temperature setting display

Present temperature display

When moving between items by

key, buzzer is heard.

If you heard a long buzzer, changed settings value are saved.

If you exit by

value is not saved.

key after settings value is changed, changed settings

Page 8

5. In-put/Out-put specific
5-1 Sensor Input : PT-100 3Wires
5-10 Operating environment
5-2 A line resistance : 10/LINE below
Action temperature and humidity : -10~70, 10%~90%
5-3 Measurement and indicate a cycle : 200ms/channel Conservation temperature and humidity : -20~70, 5%~95%
5-4 Precision : 0.5(Full Scale)
5-11 Electric Current output : DC 4~20mA(Load resistance 600 less)
5-5 Measuring range : -25 ~ 230
5-12 Temperature display : Current temperature, Peak temperature
5-6 Temperature indication : 0.1
5-13 Size : 153(W) 92(H) 148(D)
5-9 Relay Output contact
5-14 Use voltage : AC 80~265V(50/60), DC 100~300V
- FAN MOTOR Control Relay
5-15 Use electric power : 5VA(Max)
(10A 250VAC, 5A 30VDC(Max.)
5-16 Weight : 660 g
- WARNING Relay, FAULT Relay
5-17 CMRR(Common Mode Rejection Ratio) : 120db more
(10A 250VAC, 5A 30VDC(Max.)
5-18 NMRR(Normal Mode Rejection Ratio) : 50db more

6. Function & Movement explain


6-1 WARNING(Alarm1), FAULT(Alarm2) Function
When the present temperature is over setting value, it Out-put RELAY with Buzzer voice and then
display LED (As WARNING Buzzer voice and FAULT Buzzer voice are different, it can take management)
6-2 FAN AUTO / MANUAL Function
You can operate the FAN(ON/OFF) manually.
When manually operated, FAN(MAN) LED is turned on.
Normal FAN(ON/OFF) operation is automatically.
6-3 TEMP. PEAK Function

Present temperature display

Push the

Key, display PEAK value

Display the highest temperature which is measured till now.


( If you want to delete PEAK value, push the

Key)

Page 9

6-4 Alarm Function - Buzzer


When WARNING and FAULT happen, Buzzer is heard.
Press the

Key, when you want to stop the Buzzer.

6-5 Analog communication function - 4~20mA

If you set the value of


0 is output in 4mA, 200 is output in 20mA.

7. Terminal connection diagram

8. SIZE

9. Sensor specific

Page 10

10. FAN wiring diagram

Page 11