Okken
High dependability
http://www.panelbuilders.schneider-electric.com
Contents
Presentation 2
Solution overview
10
Functional units
14
Cubicles 32
Example 50
Installation 52
Okken performances
54
Fields of applications
Presentation
Petroleum, gas,
petrochemical
Mines, metallurgy,
cement works
Food-processing
Requirements
Continuity of supply
and safety
Solutions
Nuclear
Water treatment
Requirements
Continuity of supply
and safety
Continuity of supply
and environment
Solutions
Fields of applications
Presentation
Functions
Motor control
Electrical distribution
Presentation
Okken solution
Okken solution
Presentation
MotorSysTM iPMCC
solutions integrate
perfectly into your site
network infrastructure,
whatever the
communication
protocol, but also into
energy management
control systems
and process
control systems
Example of a
MotorSysTM iPMCC
solution integrated
into a site
infrastructure
Okken solution
Presentation
Innovation
70-M cubicles
Distribution busbar
ic
tr
lec
E
r
e
eid tent
n
h
Sc
pa
tric
The tightening screw devices used to secure the connection go through the gap
between the horizontal bars.
ec
r El
e
d
nei ent
Sch pat
Auxiliaries connection
tric
ec
r El
e
d
nei ent
Sch pat
The innovative mechanism guarantees that the control contacts are connected
when the drawer is in service or test position.
Presentation
Okken solution
Innovation
Drawer positions
Drawers operation is very simple. Using the indexing pushbutton, the operator
can simply move the drawer in the draw-in, test, draw-out positions.
Each position are mechanically marked with a mechanical indicator on the
drawer sides.
Draw-in
Test
bb The functional unit is not operational.
bb Only auxiliaries are connected.
bb Allow padlocking.
bb It allows the functional unit verification.
bb Allow maintenance on the process.
Draw out
bb The functional unit is not operational.
bb Power and auxiliaries are disconnected.
bb Allow maintenance on the process.
Withdrawn
bb The drawer can be fully extracted.
bb Allow quick replacement.
bb Allow switchboard live change.
The Polyfast supports the active portion of the moulded circuit breaker housing.
Presentation
Okken solution
Implementation
Continuity of supply
Type tested
Okken is totally type-tested in accordance with
IEC 61439-2
bb Certified by independant labs:
LOVAG, ASEFA, CESI and VIRLAB.
bb As well as by a permanent control in Schneider Electric
test laboratories.
bb Type-tests are carried out:
vv temperature-rise limit,
vv dielectric properties,
vv short-circuit withstand,
vv effectiveness of the protective circuit,
vv conformity of the clearance and creepage distances,
vv mechanical operation,
vv degree of protection.
Okken solution
Presentation
Implementation
4 specific compliances
Standard
1 option
2G & 5G
Marine
Forced
ventilation
DEP shell
Cubicle partitioning
Connection accessories
5 levels of service
Service Index 211
212
233
223
333
Operation
Shutting down the whole switchboard.
Maintenance
Evolution
Shutting
down the
whole
switchboard.
Addition of a
functional unit in
pre-equiped spare
slots.
2b
3b
4a
4b
Solution overview
wer
igh po
Very h
ers
s/feed
r
e
m
o
inc
cubicle
ower
High p
eders
ers/fe
m
o
c
in
cubicle
Mixed
eders
ers/fe
m
o
c
in
cubicle
Type of cubicle
230
115
115 / 70-2
In distribution
busbar
4500/7300 A
1750/4000 A
1750 / 3200 A
Incomers
NW40b/63b
NT08-16/NS800-1600
NT08-16/NS800-1600
NW08-40
NW08-32
NT08-16/NS800-1600
NT08-16/NS800-1600
NW08-40
NW08-32
Feeders
Distribution
> 630A
10
NW40b/63b
y 630A
disconnectable Polyfast
plug-in Polyfast
drawer
Solution overview
r
h powe
ed hig
iz
im
s
t
r
Op
ede
ers/fe
incom
cubicle
ower
high p
d
e
iz
Optim
eders
ers/fe
incom
cubicle
n
nsatio
Compe
onic
& harm
g
filterin
185
Single NW
Single NT / NS
1600 / 3200 A
800 / 1600 A
NW08-32
NT08-16/NS800-1600
NW08-32
NT08-16/NS800-1600
witch
Fuse-s
le
s cubic
feeder
PFC
Power factor
compensation
630 / 1500 A
Jean Mller
11
Solution overview
al
Electric n
utio
distrib s
r
drawe
al
Electric
ution
distrib
le
s cubic
feeder
Type of cubicle
70-2
70-F
In distribution
busbar
1000/2100 A
2100 A
Incomers
NT08-16/NS800-1600
NT08-16
NT08-16/NS800-1600
NT08-16
Feeders
y 630A
disconnectable Polyfast
plug-in Polyfast
drawer
MCC
Distribution
> 630A
Okken 70-2
12
Solution overview
r
ized fo
Optim
rawers
MCC d
eders
ers/fe
m
o
c
In
cubicle
70-M
70-2
2000 A
1000/2100 A
d
le spee
Variab
t
f
so
drive &
bicle
u
c
starter
VSD - SS
-
drawer y 250 kW
b disconnectable mounting
plate y 37 kW
b
drawer y 250 kW
Okken 70-M
Functional units
Operation
The switchboard
must permit
Checking
Cleaning
Repairing
Setting
Locking
Padlocking
Evolution
Addition
Modifications
Expansion
The applications
continuity of service is:
Not required
Wanted
Essential
Addition of a functional
unit in pre-equiped spare
slots
Addition of a functional
unit without shutting
down the swwitchboard,
free addition in
non-equiped spare slots
Examples
I want to determine the
consequences of mechanical
padlocking or electrical locking on
my switchboard:
OPERATION
MAINTENANCE
EVOLUTION
2
2
14
3
2
3
3
plug-in feeder
disconnectable feeder
withdrawable drawer
Functional units
Compact NSX
fixed on mounting plate
Compact NSX
disconnectable
on Polyfast: SI=223
Compact NSX
withdrawable
in drawer SI=233
15
Functional units
Electrical distribution
In > 630 A
Combinations
Q2
Q1
Q2
Q3
Q1
Q2
Q3
16
Electrical distribution
Functional units
In > 630 A
Coupling
bb Coupling in Okken has many possibilities, regarding the devices used and the
type of connection.
Coupling
devices
Type of connection
TDC
BDC
RC
top
bottom
115 cubicle
Masterpact NW08-32
Masterpact NT08-16
Compact NS800-1600
Masterpact NW40
230 cubicle
Masterpact NW40b-63
17
Electrical distribution
Functional units
In > 630 A
150
NW40b-63b
100
NW40
NW20-32
NW08-16
NW08-32
100
NT08-16
NS 800-1600 A
80
NT08-16
NS 800-1600 A
Cubicle
230
4000
115-3
4000
115-2
1600 < In < 3200
100
3200
115-1
3200
Single NW
800 < In < 1600
2100
70-2
70-F
2100
Single NT/NS
18
Electrical distribution
Functional units
In y 630 A
In (A)
Device
Drawer
In < 63
iC60
In < 63
iC60
NG125
NSX100
NSX160
NSX 250-400
NSX630
Disconnectable
mounting plate
SI = 223
In < 63
iC60
Disconnectable Polyfast
SI = 223
In < 400
NSX100-250
7 modules
NSX400-630
9 modules
Plug-in on Polyfast
In < 400
NSX100-250
7 modules
SI = 233
NSX400-630
9 modules
Fixed
In < 400
NSX100-250
8 modules
SI = 211 - 212
NSX400-630
10 modules
Cubicle
SI = 333
70-M
70 - M
70-2
6 modules
70-2
70-2
70-2
70-F
(1) depending on Iq
In (A)
Device
Drawer
In < 100
NS100L
8 modules
SI = 333
NS400L
12 modules
Cubicle
70 - M
70-2
19
Functional units
Selection
U max = 690 V
U max = 415 V
Varpact
few
polluted
network
Classic
Custom
polluted
network
very
polluted
network
Comfort
Harmony
few
polluted
network
Custom
very
polluted
network
polluted
network
few
polluted
network
polluted
network
Varplusbox
components
Pollution rate
occasionally
Classic
Comfort
Harmony
Gh / Sn y 15 %
Automotive
Water treatment
Mines & Minerals
Infrastructures
Tertiary
Marine & Off-shore
Agri-food
Sn: apparent power of the transformer.
Gh: apparent power of harmonics-generating loads (variable speed motors, static converters,
power electronics, etc.).
20
Cos
250
400
630
1000
1600
0.5
125
200
315
500
800
0.7
175
280
441
700
1120
0.9
225
360
567
900
1440
0.95
238
380
598
950
1520
Functional units
Selection of cubicle
Rated
Type
voltage (Ue)
Power
(kVAR)
qty
height
(mm)
width
(mm)
Qty of
mounting
plates
415 V
up to 500
2200
650
2350
650
2200
650
2350
650
2200
650
2350
650
2200
650
2350
650
2200
650
2350
650
without self
with integrated self
separated self
690 V
without self
separated self
up to 250
up to 125
up to 500
up to 250
Cubicles
21
Functional units
Motor control
> Based on architectures that have been pretested and pre-validated for an integration in the
leading communication protocols used in process
industry and infrastructures, our solutions help
you rapidly and efficiently optimise the energy
efficiency of your assets.
Example of an Ethernet
communication architecture of a
MotorSysTM iPMCC solution, at
a process unit level
Innovation
Bypass switch in a
Daisy Chain Loop
for an optimum
dependability
22
Functional units
Motor control
iPMCC
MCC
Protection
Short-circuit, Thermal overload, Overcurrent, Ground current
Current phase imbalance & phase loss
Current phase reversal
Undercurrent
Long start (stall) & Jam (locked rotor)
Motor temperature sensor
Rapid cycle lockout
Load shedding
Voltage phase imbalance, phase loss, & phase reversal
Undervoltage & Overvoltage, Underpower & Overpower, Under & Over power factor
Measurements
Line currents, Ground current, Average current, Current phase imbalance, Thermal
capacity level
Motor temperature sensor
Frequency
Line-to-line voltage, Line voltage imbalance, Average voltage
Active & Reactive power, Power factor, Active & Reactive power consumption
interop. tested
interop. tested
Operational modes
Consignment
Starters test position
Maintenance & Upgrade live
Control at motor level
PC set-up
Remote management
Local HMI
"Nominal current only" set-up (screwdriver)
(1) PLC: Programmable Logic Controller
Standard
Optional
23
Functional units
Motor control
24
Motor control
Functional units
Selection of the functional unit -MotorSys iMCC 1 component - Ue = 415 V - 50 / 60 Hz - IP31 / 35C
Iq Circuit
(A) breaker or
fuses
Power kW
0.06 0.75 1.1
1.5 2.2 3
5.5 7.5 9
TeSys U
4M half to 4M full
100 TeSys U
4M half to 4M full
15
18.5 22
30 37
45
55
75 90 110
Cubicle
Direct On Line
50
11
70 - M
Selection of the functional unit -MotorSys MCC 2 components - rated 415 V - 50 / 60Hz - IP31 / 35C
Star Delta
Reverse
Direct On Line
Iq Circuit
(A) breaker or
fuses
50
Power kW
0.06 0.75 1.1
1.5 2.2 3
5.5 7.5 9
11
15
Cubicle
8M half to
8M full
8M half to 8M full
70 - M
8M full
GV2P
12M full
GV3P
100 GV2P
75 90 110
8M half to 8M full
GV3P
50
55
4M half to 8M half
GV2P
100 GV2P
45
4M to 8M
full
GV3P
50
30 37
4M half to 8M half
GV2P
100 GV2P
18.5 22
8M full
25
Motor control
Functional units
Selection of the functional unit -MotorSys MCC 3 components - rated 415 V - 50 / 60 Hz - IP31 / 35C
Iq Circuit
(A) breaker or
fuses
50
Power kW
0.06 0.75 1.1
1.5 2.2 3
5.5 7.5 9
11
15
45
55
75 90 110
8M to 12M full
8M to
12M full
NSX160
Direct On Line
NSX250
12M to
16M full
NSX400
20M to 24M
full
4M half to 4M full
4M full
8M
full
GS2F
8M to 12M full
GS2J
12M to
16M full
GS2L
16M full
GS2N
24M full
GS2QQ
50
70
Reverse
70 - M
20M
full
NSX630
Vario V2 +
DF14
Vario V3 +
DF14
8M half to 8M full
GV2L
GV3L
8M half to
8M full
NS80
8M to 12M full
100 GV2L
8M half to 8M full
12M to 16M full
NSX100
12M to
16M full
NSX160
NSX250
20M
full
NSX400
8M full
GV2L
12M full
GV3L
70
NSX100
NSX160
NSX250
26
NS80
100 GV2L
24M
full
24M
full
NSX630
50
Cubicle
4M half to 8M half
NSX100
Star Delta
4M to 8M
full
8M half to 8M
full
NS80
100 GV2L
30 37
4M half to 8M half
GV2L
GV3L
70
18.5 22
8M full
16M full
16M
full
24M
full
Functional units
Selection of the functional unit - MotorSys iMCC 3 components - rated 415 V - 50 / 60 Hz - IP31 / 35C
Iq Circuit
(A) breaker or
fuses
50
Power kW
0.06 0.75 1.1
1.5 2.2 3
5.5 7.5 9
11
15
45
55
75 90 110
8M full
4M half to 8M full
8M to 12M full
NSX100
8M to
12M full
NSX160
12M to
16M full
NSX250
70 - M
20 M
full
NSX400
20M to
24M full
NSX630
Vario V2 +
DF14
Vario V3 +
DF14
4M half to 4M full
4M full
8M
full
GS2F
8M to 12 M full
Direct On Line
GS2J
12M to
16M full
GS2L
20M full
GS2N
24M full
GS2QQ
50
GV2
3M to 4M
4M
GV3
70
6M
NS80
6M
100 NSX100
6M
NSX160
12M
NSX250
18M
NSX400
70-2
18M
NSX630
GS2F
GS2J
GS2L
GS2N
GS2QQ
Cubicle
8M half
to 8M full
NS80
100 GV2L
30 37
4M half to 4M full
GV2L
GV3L
70
18.5 22
6M
6M to 12M
12M
12M
24M
27
Motor control
Functional units
Selection of the functional unit - MotorSys iMCC 3 components - rated 415 V - 50 / 60 Hz - IP31 / 35C
Iq Circuit
(A) breaker
50
Power kW
0.06 0.75 1.1
1.5 2.2 3
5.5 7.5 9
11
18.5 22
45
55
75 90 110
8M half to 8M full
12M to 16M full
12M to
16M full
NSX160
70 - M
20M full
NSX250
24 M
full
NSX400
24M
full
NSX630
50
6M
GV2
6M
GV3
70
6 M to 12M
NS80
12M
100 NSX100
12M
NSX160
18M
NSX250
24M
NSX630
8M full
GV2L
12M full
GV3L
70
16M full
NS80
100 GV2L
8M full
16M full
NSX100
16M
full
Star Delta
NSX160
24M full
NSX250
50
NS80
100 NSX100
NSX160
NSX250
NSX400
NSX630
28
70 - M
6M
GV2
12M
GV3
70
70-2
24M
NSX400
50
Cubicle
12M full
NSX100
Reverse
8M full
NS80
100 GV2L
30 37
8M half to 8M full
GV2L
GV3L
70
15
12M
12M
18M
24M
70-2
2x18M
2x18M
Motor control
Functional units
Motor control - MotorSys MCC and iMCC 1 & 3 components - rated 690 V - 50 Hz - IP31 / 35C
Iq Circuit
(A) breaker
50
GV2L
75
NS100
Power kW
0.06 0.75 1.1
1.5 2.2 3
5.5 7.5 9
11
15
18.5 22
30 37
45
55
75 90 110
GS2J
Direct On Line
GS2L
12M to
16M full
70 - M
16M full
GS2N
24 M full
GS2QQ
50
TeSys U
3M
3M to 4M
GV2
75
12M
NS100
18M
NS400
GS2F
6M
6M
GS2J
70-2
GS2L
12M
24M
GS2N
GS2QQ
50
GV2L
75
NS100
24M
8M full
16M to 20M full
24M full
NS400
Reverse
Cubicle
4M to 8M full
NS400
Vario V2 +
DF14
Vario V3 +
DF14
70 - M
50
TeSys U
GV2
75
NS100
3M
6M to 12M
12M to 18M
24M full
NS400
70-2
GV2L
75
NS100
12M full
16M to 20M full
Star Delta
50
70 - M
29
Functional units
Altistart ATSU 01
Altistart ATS 48
bb The Altistart ATS 48 soft start - soft stop unit is a controller with 6 thyristors, which
is used for the torque-controlled soft starting and stopping of three-phase squirrel
cage asynchronous motors.
bb The Altistart ATS 48 must be selected on the basis of 3 main criteria:
vv the power supply voltage range (this catalogue deals only whith the devices
connected to a 415V or 690V network),
vv the power and the nominal current of the motor,
vv the type of application and the operating cycle.
Altistart ATS 48
Altivar ATV 61
Altivar ATV 71
ATV61
ATV71
ventilation,
air conditioning,
pumping,
hoisting,
handling,
packing,
process machines,
lifts, ...
fig.1
fig.2
fig.3
fig.4
Functional units
Circuit breaker
ATSU01
1.5 to 15
Tesys U
ATS48
5.5 to 15
5.5 to 37
45 to 55
GV2
NS80
NSX100-160
18
18
18
ATV61
0.75 to 5.5
7.5 to 18.5
0.75 to 18.5
GV2
GV3
NS80
12
18
18
ATV71
0.75 to 5.5
7.5
11 to 15
0.75 to 18.5
GV2
GV3
GV3
NS80
12
12
18
18
ATS 48
5.5 to 11
5.5 to 18.5
22 t o 30
30 to 55
75 to 90
75 to 90
110 to 220
0.75 to 5.5
5.5 to 7.5
11 t o 18.5
22
5.5 to 11
15 to 18.5
22
30 to 37
30 to 75
75 to 110
132 to 220
250
280 to 400
0.37 to 5.5
5.5 to 11
15 to 18.5
22
5.5 to 11
15 to 18.5
22
30
30 to 75
75 to 110
132 to 160
200 to 315
355 to 400
GV2
NS80
NS80
NSX 100-250
NSX 100-250
NSX 250-630
NSX 250-630
GV2
GV3
GV3
GV3
NS80
NS80
NS80
NS80
NSX100-160
NSX250-400
NSX250-400
NSX250-400
NS800
GV2
GV3
GV3
GV3
NS80
NS80
NS80
NS80
NSX100-250
NSX250
NSX400
NSX400-630
NS800
12
18
12
18
18
column - 450mm
12
18
18
column - 450mm
18
18
24
36
48
column - 650mm
column - 650mm
18
18
24
36
18
24
36
48
48
column - 650mm
column - 650mm
column - 1150mm
column - 1150mm
18
18
24
36
18
24
36
48
48
column - 650mm
column - 650mm
column - 1150mm
column - 1150 mm
ATV 61
ATV71
Cubicle
Switchgears
70-2
VSD - SS
ATS48
11 to 18.5
11 to 160
75 to 200
GV2
NS100-400
NS400
18
48
48
column - 650mm
ATV61
2.2 to 11
11 to 30
37 to 90
75 to 200
250 to 315
GV2
NS100-400
NS100-400
NS400
NS630b
18
column - 450mm
36
36
48
column - 650mm
column - 1150mm
ATV71
1.5 to 15
11 to 30
37 to 90
75 to 160
200
250 to 400
GV2
NS100
NS100-400
NS400
NS400
NS630b
18
18
column - 450mm
36
36
48
column - 650mm
column - 1150mm
column - 1150mm
Protection
Cubicle
Switchgears
VSD - SS
31
Cubicles
horizontal
busbar
Cubicle height
2200 mm
No. of poles
3P
2350 mm
3P+N
3P
vertical
busbar
V-BB
conversion
area
3P+N
72 modules
9 + 19 modules
(700 mm)
30 modules
(750 mm)
V-BB conversion
area
8 modules
(200 mm)
36 modules
(900 mm)
70-2 device
zone
device
installation
zone
Cellule 115/70-2
Cubicle 70-M:
Double vertical busbar
Cubicle height
No. of poles
top link
cover
2200 mm
2350 mm
H-BB 3P
4P
V-BB 3P
3P
4P
3P
4P
3P
3P
4P
device
installation
zone
bottom
link cover
2200 mm
2350 mm
H-BB 3P
4P
V-BB 3P
3P
4P
3P
4P
3P
3P
4P
32
Cubicles
Type of connection
Connection
115
115/70
Single
NW
Single
NT/NS
70-2
70-F
VSD(1) 185
PFC
70-M
Rear connection
Side connection
Back to back
Top direct
Bottom direct
A device cubicle
B cable compartment
C auxiliaries (option)
33
Cubicles
Presentation
Cubicle
The Okken switchboards consist of a framework and busbar assembly designed to
combine in the same cubicle functional units of varying technologies, grouping
both distribution and motor control applications.
A complete range of configurations to satisfy the requirements of each site:
bb cubicles available in 2 heights, 5 widths and 2 depths, to allow integration in all
environments and optimize installation modularity,
bb switchboard supplied by busbar trunking and/or cables,
bb front or rear, top and/or bottom connections,
bb choice of functional unit output partitioning:
vv incomers: forms 3b, 4b,
vv feeders: forms 2b, 3b, 4a, 4b,
bb possible customisation of panels, whose components may be delivered
unpainted.
Busbars
Busbar coating
Busbar coating
none
silver
tin
Horizontal busbar
Vertical busbar 115
Vertical busbar 70
Vertical busbar 115 - 70
protection against ...
b
b
b
b
b
b
b
b
nickel
epoxy
b
b
b
b
b
b
corrosive
corrosive
internal
environment environment arc
Optimization
Horizontal busbar
Selection table
34
(kA eff.)
Qty of bars
Bars section 40 x 10 mm
Single busbars
from 0 to 1900
from 1900 to 2500
from 2500 to 3200
from 3200 to 4000
50
80
100
100
2
3
4
6
Double busbars
from 4000 to 5000
from 5000 to 6300
from 6300 to 7300
100
100
150
2x3
2x4
2x6
230
Cubicles
Functional unit
Busbar for 230 cubicle
bb very high power,
bb dedicated to NW40b-63 devices,
bb height-reduced busbar.
Rated current In (A)
IP31 / 35C
No. of bars/
phase
4530
2 x 3 x 40x10
100
5810
2 x 4 x 40x10
100
7320
2 x 6 x 40x10
150
Type of connection
Type of connection
Qty of cubicle
Type of distribution
2 incomers + 1 coupling
bb rear connection
The dimensions of the functional units, PCC > 630A, are in the choice pages, page 18.
direct connection
A: Additionnal= 800 mm
Masterpact NW40b-63
35
115
Cubicles
Functional unit
115mm
115mm
bb high power,
bb designed for NW08-40, NT08-16/NS800-1600
devices,
bb full height busbar.
115mm
No. of bars /
phase
1750
1 x 80x10
50
2780
2 x 80x10
100
3200
3 x 80x10
100
4090
3 x 120x10
100
Type of connection
Type of distribution
Circuit breaker
Type of connection
Qty of cubicle
1 incomer or
1 distribution feeder
Masterpact NW40
Masterpact NW08-32
Masterpact NT08-16
Masterpact NW40
bb rear connection
Masterpact NW08-32
Masterpact NT08-16
2 incomers
+ 1 coupling
The dimensions of the functional units, PCC > 630A, are in the choice pages, page 18.
direct connection
L: long = 600 mm
36
Masterpact NW40
115
Cubicles
Rear connection
column depth 1000 mm
Masterpact NW20-32
Compact NS800-1600
Masterpact NW/NT08-16
S: short= 250 mm
L: long = 600 mm
M: medium= 400 mm
A: additionnal = 800 mm
37
115
Cubicles
Side connection
column width 650 + 450/650 mm
Masterpact NW20-32
Masterpact NW/NT08-16
direct connection
38
Single NW
Cubicles
Functional unit
Vertical 115 busbar
bb high power,
bb designed forNW08-32 devices,
bb height-reduced busbar.
No. of bars /
phase
1750
1 x 100x10
50
2780
2 x 100x10
100
3200
3 x 100x10
100
Type of connection
Type of distribution
Circuit breaker
Type of connection
Qty of cubicle
1 incomer or
1 distribution feeder
Masterpact NW40
Masterpact NW08-32
Masterpact NT08-16
direct connection
Masterpact NW08-32
The dimensions of the functional units, PCC > 630A, are in the choice pages, page 18.
RC
TDC
BDC
column depth
1000/1200 mm
column depth
600 mm
column depth
600 mm
650
650
M: medium = 400 mm
39
115/70-2
Cubicles
Functional unit
Vertical 115/70-2 busbar
bb Mixing high power incomers and feeders,
bb designed for NW08-32 devices and functional
units up to 630 A,
bb full height busbar.
No. of bars /
phase
1750
1 x 80x10
50
2780
2 x 80x10
80
3200
3 x 80x10
80
1 x 80x10
80
zone 115
zone 70-2
1750
Circuit breaker
Type of connection
Qty of cubicle
1 incomer or
1 distribution feeder
Masterpact NW40
Masterpact NW08-32
Masterpact NT08-16
Type of connection
bb side connection from the front
bb rear connection
bb side connection from the front
bb rear connection
bb side connection from the front
bb rear connection
Type of connection
Drawer
The dimensions of the functional units, PCC y 630A, are in the choice pages, page 19.
40
115/70-2
direct connection
L: long = 600 mm
Masterpact NW40
Cubicles
Rear connection
direct connection
Compact NS800-1600
Masterpact NW/NT08-16
Side connection
column width 650 + 450/650 mm
direct connection
Masterpact NW20-32
41
Single NT/NS
Cubicles
Functional unit
Vertical 70 busbar
bb high power,
bb designed for NT08-16/NS800-1600 devices,
bb height-reduced busbar.
No. of bars /
phase
1750
1 x 80 x 10
Type of connection
Type of distribution
1 incomer or
1 distribution feeder
Type of connection
Qty of cubicle
The dimensions of the functional units, PCC > 630A, are in the choice pages, page 18.
42
TDC
BDC
column depth
1000/1200 mm
column depth
600 mm
column depth
600 mm
direct connection
RC
42
70-F
Cubicles
Functional unit
Vertical 70 busbar
bb designed for NT08-16/NS800-1600 and all the
distribution feeders,
bb full height busbar.
No. of bars /
phase
1010
1 x 40x10
50
1200
1 x 50x10
50
1750
1 x 80x10
80
2100
1 x 100x10
100
Circuit breaker
Type of connection
Qty of cubicle
1 incomer or
1 distribution feeder
Masterpact NT08-16
bb rear connection
Type of connection
Compact NSX
Compact NS
direct connection
Masterpact NT08-16
The dimensions of the functional units, PCC y 630A, are in the choice pages, page 19.
TDC
BDC
RC
column depth
600 mm
column depth
600 mm
column depth
600 / 1000 mm
650
43
70-M
Cubicles
Functional unit
Vertical 70-M busbar
bb designed for 70-M drawers,
bb full height busbar.
No. of bars/phase
800
2 x 20 x 8
50
1250
2 x 30 x 8
75
2000
2 x 50 x 8
100
Type of connection
Type of functional unit
Drawer
Type of connection
bb side connection from the front
bb rear connection
bb back to back
Rear connection
44
Cubicles
70-M
Side connection
column width 600 + 200/300/400 mm
45
70-2
Cubicles
70 mm
70 mm
70 mm
Functional unit
Vertical 70 busbar
bb designed for NT08-16/NS800-1600 and all the
distribution feeders and motor control feeders,
bb full height busbar.
No. of bars /
phase
1010
1 x 40x10
50
1200
1 x 50x10
50
1750
1 x 80x10
80
2100
1 x 100x10
100
Circuit breaker
Masterpact NT08-16
Type of connection
bb side connection from the front
bb direct connection from the bottom
bb direct connection from the top
bb rear connection
Compact NS800-1600 A
Qty of cubicle
1
1
1
1
Type of connection
Drawer
Type of connection
bb side connection from the front
bb rear connection
bb side connection from the front
bb rear connection
bb side connection from the front
bb rear connection
Removable on Polyfast
Drawer
Rear connection
direct connection
46
S: short= 250 mm
L: long= 600 mm
M: medium= 400 mm
A: additionnal= 800 mm
Cubicles
70-2
Side connection
column width 650 + 650 mm
direct connection
47
47
Cubicles
Functional unit
No. of bars /
phase
630
1 x 40x10
80
800
1 x 50x10
80
1250
1 x 80x10
80
1500
1 x 100x10
80
Type of connection
Type of functional unit
Drawer
Type of connection
bb side connection from the front
bb rear connection
The dimensions of the MCC functional units are in the choice pages, page 25.
48
Notes
49
Example of configuration
Example
Customers needs
Form
Degree of pollution
Rated auxiliary circuit voltage
Energy compensation
Cable entry
Access
Temperature
Altitude
Panelling color
50
number of phases
material
insulation
external
internal
IEC 61439-2
1000 V
380 / 415 V
3200 A
70 kA
154 kA
50 / 60 Hz
3
copper
air
3b
IP 31
IP 20
230 V
100 kVAR
top / bottom
front / rear
35 C
2000 m
RAL 9003
100 kVAR
45 kW
15 kW
1,5 kW
1,5 kW
15 kW
35 kW
100 A
35 kW
250 A
G
800 A
1250 A
3200 A
1250 A
3200 A
100 A
100 A
250 A
1,5 kW
1,5 kW
1,5 kW
1,5 kW
150 kW
100 kW
35 kW
1,5 kW
35 kW
5,5 kW
Example of configuration
Example
1,5 kW
MC
VVD
VVD
drawer
drawer
fixed
12
18
48
Cubicles,
height = 2350 mm,
rear connection
with around 10 %
of reserve
1 cubicle 70-M
1 cubicle
115 / 70-2
2 cubicles
115
1 cubicle 70-M
2 cubicles
70-2 / VVD
No. of vertical
modules
(1 module = 25 mm)
EC 100 kV
kVAR
45 kW
1,5 kW
MC
drawer
6
800 A
15 kW
15 kW
MC
drawer
35 kW
Polyfast
19
MC
ED
chassis
19
1 cubicle
115 / 70-2
ED
INC
chassis
drawer
ED
chassis
Polyfast
INC
chassis
100 A
C
chassis
35 kW
INC
chassis
30
250 A
ED
Polyfast
6
Technology
ED
ED
Polyfast
6
1250 A
ED
Polyfast
6
Type of functional
units
3200 A
MC
drawer
6
3200 A
1,5 kW
MC
drawer
3
100 A
1,5 kW
MC
drawer
3
1250 A
1,5 kW
MC
drawer
3
100 A
1,5 kW
MC
drawer
18
250 A
150 kW
MC
drawer
3
35 kW
100 kW
VVD
MC
drawer
drawer
1,5 kW
MC
drawer
12
5,5 kW
MC
drawer
35 kW
MC
drawer
2
3
51
Installation
Civil works
Ground fastening
compulsory fastening point
optional fastening point
bb class 8.8 screws: M10 TH screws + washers
( 25 mm external, thickness 3 mm) +
CS 10 mm contact washers
Connection
Rear connection
Side connection
Back to back
52
70-M cubicle
Installation
Side view
Top view
Rear connection
Side connection
230 cubicle.
53
Okken performances
General data
Standard environment
reference standards
IEC 61439-2
IEC 60529
climatic resistance
IEC 60068-2-30
IEC 60068-2-2
IEC 60068-21
IEC 60068-2-11
installation
indoor
earthquake withstand
environment (CEM)
type 2
Mechanical data
cable entry
top/bottom
access
front/rear
22/31/41/54
10
form
2b/3b/4a/4b
withdrawability
dimensions (mm)
FFD/WFD/WFW/WWW
height
2200/2350
width
depth
600/1000/1200/1400
66 modules of 25 mm
average weight
~ 850 kg
cubicle 70-M
~ 400 kg
~ 700 kg
~ 600 kg
72 modules of 25 mm
~ 1300 kg
panel coating
framework
galvanised
panelling colour
RAL 9003
Electrical data
rated insulation voltage (Ui)
1000 V
415 / 690 V CA
50/60 Hz
12 kV
230 V AC max.
overvoltage category
IV
degree of pollution
6300 A
7300 A
54
50/80/100/150 kA rms
110/176/220/330 kA peak
50/80/100 kA rms
110/176/220 kA peak
up to 150 kA
earthing diagram
TT-IT-TNS-TNC
up to 6300 A
up to 250 kW 690 V
DESY014EN
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this document.
This document has been printed on ecological paper.
02-2013