The application examples are not binding and do not claim to be complete regarding the circuits shown, equipping and any eventuality. The application examples do not represent customer-specific solutions. They are only intended to
provide support for typical applications. You are responsible in ensuring that the
described products are correctly used. These application examples do not relieve you of the responsibility in safely and professionally using, installing, operating and servicing equipment. When using these application examples, you
recognize that we cannot be made liable for any damage/claims beyond the
liability clause described. We reserve the right to make changes to these application examples at any time without prior notice. If there are any deviations between the recommendations provided in these application examples and other
Siemens publications - e.g. Catalogs - then the contents of the other documents
have priority.
We do not accept any liability for the information contained in this document.
Any claims against us - based on whatever legal reason - resulting from the use of
the examples, information, programs, engineering and performance data etc., described in this application example shall be excluded. Such an exclusion shall not
apply in the case of mandatory liability, e.g. under the German Product Liability Act
(Produkthaftungsgesetz), in case of intent, gross negligence, or injury of life, body
or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or breach of a condition which goes to the root of the contract (wesentliche
Vertragspflichten). However, claims arising from a breach of a condition which
goes to the root of the contract shall be limited to the foreseeable damage which is
intrinsic to the contract, unless caused by intent or gross negligence or based on
mandatory liability for injury of life, body or health The above provisions does not
imply a change in the burden of proof to your detriment.
It is not permissible to transfer or copy these application examples or excerpts of
them without first having prior authorization from Siemens Industry Sector in writing.
For questions about this document please use the following e-mail address:
mailto:online-support.automation@siemens.com
V 2.2
09.08.11
2/236
Table of Contents
32201963
Table of Contents
Warranty, liability and support ................................................................................... 2
Table of Contents......................................................................................................... 3
1
Introduction........................................................................................................ 6
3.1
3.2
3.3
3.4
3.5
4
6.3
6.4
6.5
6.6
6.7
6.8
6.9
6.10
V 2.2
Multi-Server ...................................................................................................... 68
7.1
7.2
Client-Server System....................................................................................... 38
6.1
6.2
Starter System.................................................................................... 12
Starter System Separate Engineering System .................................. 14
Starter System Dual Monitor .............................................................. 16
Starter System PCS 7 BOX RTX as OS Client.................................. 18
AS RTX based system Architectur..................................................... 20
09.08.11
3/236
Table of Contents
13.5
V 2.2
15
14
13
12
11
Route Control................................................................................................... 88
9.1
9.2
9.3
9.4
10
32201963
09.08.11
4/236
Table of Contents
V 2.2
18
Introduction....................................................................................... 192
Single Station AS 41x-x-1H Automation System ............................. 192
Redundant Station AS 41x-x-2H Automation System...................... 195
Concepts of Redundancy Terminal Bus........................................ 199
Introduction....................................................................................... 199
Redundant Terminal Bus ................................................................. 200
Redundant Terminal Bus Bill of Material.......................................... 201
17
32201963
09.08.11
5/236
Introduction
32201963
Introduction
This document describes SIMATIC PCS 7 architectures and the components that
are required to implement them. For the described architectures, various options
and design choices are illustrated. SIMATIC PCS 7 is a highly scalable Process
Control System with numerous topologies based on redundancy, optional hardware
and software functions.
This document helps you select:
SIMATIC PCS 7 options for example, SIMATIC BATCH, SIMATIC Route Control and Asset Management
Figure 1-1
NOTE
V 2.2
This legend only show schematic illustrations of the components and does not
reflect a true picture of each component as its shape, method of connection and
modular setup may be different for the selected components
09.08.11
6/236
32201963
V 2.2
09.08.11
7/236
2.1
32201963
one to two
2.2
V 2.2
09.08.11
8/236
2.3
32201963
two to five
2.4
Client-Server System
Table 2-4
Number of I/O points:
800 -2000
Number of users:
three to sixteen
V 2.2
09.08.11
9/236
2.5
32201963
twelve to thirty-two
V 2.2
09.08.11
10/236
Starter System
32201963
Starter System
NOTE
V 2.2
In the following Bills of Material, Field Bus components, racks, modules and Field
devices are not listed.
09.08.11
11/236
Starter System
3.1
32201963
Starter System
Figure 3-1
V 2.2
09.08.11
12/236
Starter System
32201963
Notes
Optional
Required
Product Number
6ES7 650-4AA00-0AA0
6ES7 648-0CB00-0YA0
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
NOTE
V 2.2
1)
2)
1)
Please use the PCS 7 BOX configurator, because the PCS 7 BOX is available
in different configurations, e. g. DC 24 V or AC 110/230 V.
2)
09.08.11
13/236
Starter System
3.2
32201963
Figure 3-2
Plant Bus
V 2.2
09.08.11
14/236
Starter System
32201963
PCS 7 BOX RTX based starter System with separate Engineering System Bill of Materials
Table 3-2
Product Description
Notes
Optional
Required
Product Number
6ES7 650-4AA00-0BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 652-0XD17-2YB5
1)
2)
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AA17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
2)
3)
Terminal Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
4)
4)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
NOTE
V 2.2
1)
Please use the PCS 7 BOX configurator, because the PCS 7 BOX is available
in different configurations, e. g. DC 24 V or AC 110/230 V.
2)
3)
The Engineering System is not intended for use as a second Operator System
4)
09.08.11
15/236
Starter System
3.3
32201963
Figure 3-3
V 2.2
09.08.11
16/236
Starter System
32201963
PCS 7 BOX RTX based starter System Dual Monitor Bill of Materials
Table 3-3
Product Description
Notes
Optional
Required
Product Number
6ES7 650-4AA00-0AA0
6ES7 648-0CB00-0YA0
2
1
1
1
1
1
6ES7 652-0XX04-1XE0
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
NOTE
V 2.2
1)
2)
1)
Please use the PCS 7 BOX configurator, because the PCS 7 BOX is available
in different configurations, e. g. DC 24 V or AC 110/230 V.
2)
09.08.11
17/236
Starter System
3.4
32201963
Figure 3-4
Plant Bus
V 2.2
09.08.11
18/236
Starter System
32201963
Notes
1)
2)
3)
Optional
Required
Product Number
6ES7 650-4AA00-0BA0
6ES7 648-0CB00-0YA0
1
1
6ES7 652-0XD17-2YB5
6ES7 660-0CE13-2BA0
6ES7 648-0CB00-0YA0
1
1
1
1
6ES7 658-2BA17-0YA0
6ES7 652-0XD17-2YB5
2)
Terminal Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
4)
4)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
NOTE
V 2.2
Please use the PCS 7 BOX configurator, because the PCS 7 BOX is available
in different configurations, e. g. DC 24 V
2)
3)
4)
09.08.11
19/236
Starter System
3.5
32201963
Figure 3-5
V 2.2
09.08.11
20/236
Starter System
32201963
Notes
3)
Optional
Required
Product Number
Automation System
1
6ES7 654-0UE13-0XX0
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AA17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
NOTE
V 2.2
1)
2)
3)
09.08.11
2)
21/236
32201963
A Single Station Operator or Engineering System can be equipped with a MultiVGA graphics card 2 Screens or 4 Screens allowing for up to four monitors connected to a system.
V 2.2
09.08.11
22/236
4.1
32201963
Figure 4-1
V 2.2
09.08.11
23/236
32201963
Notes
Optional
Required
Product Number
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AB17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
3)
Automation System
1
6ES7 654-8CJ10-3BB0
NOTE
V 2.2
1)
2)
3)
09.08.11
24/236
4.2
32201963
Figure 4-2
Plant Bus
V 2.2
09.08.11
25/236
32201963
Notes
Optional
Required
Product Number
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 652-0XX04-1XE0
6ES7 658-5AB17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
2)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
3)
4)
Automation System
1
6ES7 654-8CJ10-3BB0
NOTE
V 2.2
1)
2)
3)
4)
09.08.11
26/236
4.3
32201963
Figure 4-3
V 2.2
09.08.11
27/236
32201963
Product Number
Product Description
Notes
1)
Optional
Required
Table 4-3
6ES7 660-0CE13-2BA0
1
1
1
6ES7 648-0CB00-0YA0
6ES7 658-5AB17-0YA5
1
1
1
1
1
6ES7 658-2HX17-2YB0
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
5)
Terminal Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
4)
2)
2)
4)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Wireless LAN
1
6GK5 788-1AA60-2AB0
1
1
6GK1 907-0DC10-6AA3
6XV1 870-3QH60
Automation System
1
6ES7 654-8CJ10-3BB0
3)
5)
V 2.2
6ES7 658-2JX17-2YB0
09.08.11
28/236
2)
3)
4)
Wireless LAN access point with approval for USA and Canada, approval for
countries outside USA and Canada requires a different version of the W7881PRO
5)
6)
NOTE
32201963
V 2.2
09.08.11
29/236
32201963
Redundancy
Optionally the OS Single Stations can be equipped with redundancy software and
hardware to create a redundant Operator System. In this case there will be archive
synchronization between the two redundant single stations. The Terminal Bus,
Plant Bus, Automation System(s) (AS) and Field Bus can be made redundant as
well. This redundancy option for the Operator Stations is limited to two OS single
stations.
Quantity structures
OS Single Station configurations are only intended for small and medium-sized
plants in the lower performance range. If more than two OS Single Stations shall
be used, a Client-Server architecture would be more economic.
Unlike to OS Servers OS Single Stations have the following restrictions:
Dual Monitor
Each Operator or Engineering System can be equipped with a Multi-VGA graphics
card 2 Screens or 4 Screens allowing up to four monitors to be connected to a
system.
NOTE
Archive synchronization and redundancy for alarms and process tags is not
available for than one redundant Operator Systems.
The Multiple Single Station architecture has constraints in the deployment of
SIMATIC BATCH, only one single station system can be used as Batch Server
and Client. In that case a separate project will need to be created for that single
station.
V 2.2
09.08.11
30/236
5.1
32201963
Figure 5-1
Plant Bus
V 2.2
09.08.11
31/236
32201963
Notes
Optional
Required
Product Number
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
1
6ES7 648-0CB00-0YA0
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
Operator System
2
6ES7 660-0AC13-2AA0
2
2
2
6ES7 648-0CB00-0YA0
2
2
6ES7 658-2AB17-0YA0
6ES7 652-0XD17-2YB5
1)
Terminal Bus
1
3
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
3)
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
1
6ES7 654-8CJ10-3BB0
6ES7 653-2BA00-0XB5
NOTE
V 2.2
1)
2)
3)
09.08.11
32/236
5.2
32201963
Figure 5-2
Plant Bus
V 2.2
09.08.11
33/236
32201963
Product Number
Product Description
Notes
Optional
Required
Table 5-2
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
1
6ES7 648-0CB00-0YA0
1
1
1
6GK1 162-3AA00
6ES7 652-0XX01-1XF0
6ES7 658-5AF17-0YA5
1
1
1
1
1
6GK1 716-0HB71-3AC0
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
2)
4)
Operator System
2
6ES7 660-0BF13-2AA0
2
2
2
6ES7 648-0CB00-0YA0
2
1
1
6GK1 162-3AA00
6ES7 652-0XX01-1XF0
6ES7 652-3AB17-2YA0
2
2
6GK1 716-0HB71-3AC0
6ES7 652-0XD17-2YB5
1)
2)
3)
7)
4)
Terminal Bus
2
6
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
5)
5)
6)
Plant Bus
2
8
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
1
6ES7 656-8CM33-1CB0
6ES7 653-2BA00-0XB5
V 2.2
09.08.11
34/236
2)
3)
4)
5)
6)
7)
NOTE
32201963
V 2.2
09.08.11
35/236
5.3
32201963
Figure 5-3
Plant Bus
V 2.2
09.08.11
36/236
32201963
Notes
1)
Optional
Required
Product Number
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 652-0XX04-1XE0
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
Operator System
2
6ES7 660-0AC13-2AA0
4
2
2
6ES7 648-0CB00-0YA0
2
2
6ES7 652-0XX04-1XE0
6ES7 658-2AB17-0YA0
6ES7 652-0XD17-2YB5
1)
2)
Terminal Bus
1
3
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
3)
3)
4)
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
1
6ES7 654-8CJ10-3BB0
6ES7 653-2BA00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
09.08.11
37/236
Client-Server System
32201963
Client-Server System
Redundancy
SIMATIC PCS 7 supports redundancy at all levels by introducing a second OS
Server and the OS redundancy software. The access of OS clients to real-time
and historical data and the storage of historical data is redundant and provides
higher availability. Optionally the system supports redundancy at the terminal bus,
Plant Bus, Automation System and field levels.
Dual Monitor
Operator System Clients can be equipped with a Multi-VGA graphics card 2
Screens or 4 Screens allowing for up to four monitors to be connected to an Operator System Client. You can decide if a Multi-VGA card is used for each Operator
System Client.
Web Server
A dedicated Operator System Client can be equipped with SIMATIC PCS 7 Web
Server software, allowing up to 50 Web Clients to perform monitoring and control
tasks simultaneously. The concurrent server based licensing of the Web Server allows many more than 50 users to access the Web Server over time.
NOTE
V 2.2
09.08.11
38/236
Client-Server System
6.1
32201963
Client-Server System
Figure 6-1
V 2.2
09.08.11
39/236
Client-Server System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 6-1
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
5)
1)
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
Terminal Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
3)
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
4)
4)
40/236
Client-Server System
2)
3)
4)
5)
NOTE
32201963
V 2.2
09.08.11
41/236
Client-Server System
6.2
32201963
Figure 6-2
Plant Bus
V 2.2
09.08.11
42/236
Client-Server System
32201963
Client-Server System Operation on Engineering System and Operator System Server Bill
of Materials
Table 6-2
Product Description
Notes
2)
1)
Optional
Required
Product Number
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-2CX17-0YA5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
Terminal Bus
1
6XV1 870-3RH60
Plant Bus
2
6XV1 870-3QH60
Automation System
1
6ES7 654-8CJ10-3BB0
3
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
09.08.11
3)
4)
4)
43/236
Client-Server System
6.3
32201963
Figure 6-3
Plant Bus
V 2.2
09.08.11
44/236
Client-Server System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 6-3
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
6ES7 658-2BC17-0YA0
6ES7 652-0XD17-2YB5
1)
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
3
3
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
2)
3)
3)
4)
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
5)
5)
45/236
Client-Server System
2)
3)
4)
5)
NOTE
32201963
V 2.2
09.08.11
46/236
Client-Server System
6.4
32201963
Figure 6-4
Plant Bus
V 2.2
09.08.11
47/236
Client-Server System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 6-4
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BC17-2YA0
2
6ES7 652-0XD17-2YB5
1)
6)
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
2)
3)
3)
4)
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
5)
5)
48/236
Client-Server System
3)
4)
5)
6)
NOTE
32201963
V 2.2
09.08.11
49/236
Client-Server System
6.5
32201963
Figure 6-5
Plant Bus
V 2.2
09.08.11
50/236
Client-Server System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 6-5
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 658-5AF17-0YA5
1
1
1
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1
1
1
1
1)
4)
2)
6ES7 660-0DE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BC17-2YA0
2
2
2
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
8)
3)
9)
1)
4)
2)
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
6ES7 652-0XX01-1XF0
6ES7 658-2CX17-0YA5
2 6ES7 652-0XD17-2YB5
2)
Terminal Bus
2
12
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
5)
5)
Plant Bus
2
10
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
51/236
Client-Server System
Product Number
32201963
Product Description
Notes
Optional
Required
Automation System
2
6ES7 656-8CM33-1CB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
1)
2)
3)
4)
V 2.2
5)
6)
7)
8)
9)
09.08.11
52/236
Client-Server System
6.6
32201963
Figure 6-6
V 2.2
09.08.11
53/236
Client-Server System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 6-6
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
6)
1)
6ES7 660-0EA02-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
V 2.2
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
09.08.11
54/236
Client-Server System
Notes
2)
Optional
Required
Product Number
32201963
Web Server
1
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
6ES7 658-2CX17-0YA5
6ES7 658-2GA17-2YB0
Terminal Bus
1
7
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
3)
3)
4)
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
5)
5)
2)
3)
4)
5)
6)
09.08.11
55/236
Client-Server System
6.7
32201963
Figure 6-7
V 2.2
09.08.11
56/236
Client-Server System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 6-7
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
6)
1)
6ES7 660-0EA02-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
V 2.2
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
09.08.11
57/236
Client-Server System
Notes
2)
Optional
Required
Product Number
32201963
DataMonitor Server
1
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2CX17-0YA5
6AV6 371-1DN07-0AX0
Terminal Bus
1
7
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
3)
3)
4)
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
5)
5)
2)
3)
4)
5)
6)
09.08.11
58/236
Client-Server System
6.8
32201963
Figure 6-8
V 2.2
09.08.11
59/236
Client-Server System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 6-8
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
6)
1)
6ES7 660-0EA02-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
V 2.2
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
09.08.11
60/236
Client-Server System
Notes
2)
Optional
Required
Product Number
32201963
Web Server
1
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 658-2CX17-0YA5
1
6ES7 658-2GA17-2YB0
Terminal Server
1
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
2)
3)
3)
4)
1)
1)
Terminal Bus
1
7
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
5)
5)
2)
3)
4)
5)
6)
09.08.11
61/236
Client-Server System
6.9
32201963
Figure 6-9
Plant Bus
V 2.2
09.08.11
62/236
Client-Server System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 6-9
Engineering System
1
6ES7 660-0AC13-2AA0
2
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
1
6ES7 652-0XX04-1XE0
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
6)
2)
6ES7 660-0EA02-2AA0
4
2
6ES7 648-0CB00-0YA0
2
2
2
2
6ES7 658-2CX17-0YA5
6ES7 652-0XX04-1XE0
6ES7 652-0XD17-2YB5
1)
Terminal Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
3)
3)
4)
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
5)
5)
63/236
Client-Server System
2)
3)
4)
5)
6)
NOTE
32201963
V 2.2
09.08.11
64/236
Client-Server System
6.10
32201963
Figure 6-10
Plant Bus
V 2.2
09.08.11
65/236
Client-Server System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 6-10
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
6ES7 660-0AC13-2AA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 658-1AF17-0YA5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
6)
2)
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
Terminal Bus
1
6
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
3)
3)
Plant Bus
1
6
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
66/236
Client-Server System
Notes
4)
Optional
Required
Product Number
32201963
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
5)
6)
09.08.11
5)
5)
67/236
Multi-Server
32201963
Multi-Server
Multi-Server System
For large systems the multi-server architecture of SIMATIC PCS 7 allows the implementation of large distributed systems. In this case multiple Operator System
(OS) Servers, single or redundant, are used to connect a large number of Operator
System (OS) Clients to real-time and historical data. One or more Engineering Systems (ES) connect to both terminal bus and Plant Bus to allow the download of
changes to both OS and Automation Systems (AS). If desired, the engineering system can be used as an OS client when no engineering tasks are performed.
Redundant Bus
The availability of the connection between the OS Servers and the ASs, as well as
between the OS Servers and the OS Clients, can be increased by means of redundant interfaces and network components.
NOTE
V 2.2
09.08.11
68/236
Multi-Server
7.1
32201963
Figure 7-1
Plant Bus
V 2.2
09.08.11
69/236
Multi-Server
32201963
Product Number
Product Description
Notes
1)
Optional
Required
Table 7-1
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
6GK1 716-0HB71-3AC0
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0DE13-2BA0
4
4
6ES7 648-0CB00-0YA0
4
4
2
6GK1 716-0HB71-3AC0
6ES7 652-3BD17-2YA0
6)
1)
2)
7)
6ES7 660-0EA02-2AA0
5
5
6ES7 648-0CB00-0YA0
5
6ES7 658-2CX17-0YA5
5 6ES7 652-0XD17-2YB5
Terminal Bus
2
12
6GK5 216-0BA00-2AA3
6XV1 870-3QH60
3)
3)
Plant Bus
2
11
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 656-8CM33-1CB0
2
2
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
70/236
Multi-Server
2)
3)
4)
5)
6)
7)
NOTE
32201963
V 2.2
09.08.11
71/236
Multi-Server
7.2
32201963
Figure 7-2
V 2.2
09.08.11
72/236
Multi-Server
32201963
Product Number
Product Description
Notes
Optional
Required
Table 7-2
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 658-5AF17-0YA5
1
1
1
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1
1
1
1
6ES7 660-0DE13-2BA0
4
4
6ES7 648-0CB00-0YA0
4
4
4
4
2
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
6ES7 652-3BD17-2YA0
5)
1)
6)
6ES7 660-0EA02-2AA0
5
5
6ES7 648-0CB00-0YA0
5
5
5
6ES7 652-0XX01-1XF0
6ES7 658-2CX17-0YA5
5 6ES7 652-0XD17-2YB5
Terminal Bus
2
4
28
6GK5 216-0BA00-2AA3
6GK5 204-0BA00-2BA3
6XV1 870-3QH60
2)
2)
Plant Bus
2
16
V 2.2
6GK5 216-0BA00-2AA3
6XV1 870-3QH60
09.08.11
73/236
Multi-Server
Product Number
32201963
Product Description
Notes
Optional
Required
Automation System
2
6ES7 656-8CM33-1GB0
2
2
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
5)
6)
09.08.11
74/236
SIMATIC BATCH
32201963
SIMATIC BATCH
SIMATIC BATCH
SIMATIC PCS 7 standard software for ISA-88 Recipe Management and Batch
processing tasks is SIMATIC BATCH. SIMATIC BATCH is based on scalable and
modular software that can be deployed across all SIMATIC PCS 7 architectures.
SIMATIC BATCH deploys a client-server architecture as standard with clients for
recipe editing and batch control. SIMATIC BATCH clients can run on SIMATIC
PCS 7 Single Station, Server and Client systems as well as on PCs with no other
SIMATIC PCS 7 software installed.
Starter System
The smallest system that supports SIMATIC BATCH is the Single Station architecture; all functions, engineering, operation and batch control are installed on a single
computer. Batch phases and operations execute in the Automation System.
Client-Server
Medium size systems that support multiple users and do not require redundancy
are implemented with Client-Server systems. SIMATIC BATCH follows the Operator System architecture seamlessly by distribution of Batch Server and Client applications on the equivalent Operator System Computers.
Client-Server Redundant
If redundancy is required and the number of servers must be kept at a minimum,
SIMATIC BATCH allows deployment of a redundant Batch Server on the pair of redundant Operator System Server Computers.
Client-Multi-Server Redundant
For large and high-performance applications the SIMATIC PCS 7 Client-Server architecture allows for distribution of applications on multiple computers. In this case
the Batch Server and OS Server run on two independent computers. Each of them
can be made redundant providing maximum availability. The OS clients computers
can run the Batch Client application and look at both OS Server and Batch Server
seamlessly. If necessary the OS Client and Batch Client application can also run
on separate computers.
V 2.2
09.08.11
75/236
SIMATIC BATCH
8.1
32201963
Figure 8-1
Plant Bus
V 2.2
09.08.11
76/236
SIMATIC BATCH
32201963
Product Number
Product Description
Notes
Optional
Required
Table 8-1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AB17-0YA5
1
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-1FX17-2YA5
6ES7 657-0SA17-0YB0
1 6ES7 657-0BX17-2YB5
1 6ES7 657-0FX17-2YB0
1 6ES7 657-0GX17-2YB0
1 6ES7 657-0HX17-2YB0
1)
4)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
3)
Automation System
1
6ES7 654-8EK03-5DB0
NOTE
V 2.2
1)
2)
3)
4)
09.08.11
77/236
SIMATIC BATCH
8.2
32201963
Figure 8-2
Plant Bus
V 2.2
09.08.11
78/236
SIMATIC BATCH
32201963
Product Number
Product Description
Notes
Optional
Required
Table 8-2
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
6ES7 658-2BC17-0YA0
6ES7 657-0SA17-0YB0
6ES7 657-0FX17-2YB0
6ES7 657-0GX17-2YB0
6ES7 657-0HX17-2YB0
6)
1)
5)
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
3
2
6ES7 658-2CX17-0YA5
3 6ES7 652-0XD17-2YB5
1 6ES7 657-0LX17-2YB5
1 6ES7 657-0BX17-2YB5
7)
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
Plant Bus
1
4
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
79/236
SIMATIC BATCH
Product Number
32201963
Product Description
Notes
Optional
Required
Automation System
2
6ES7 654-8EK03-5DB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
5)
6)
7)
09.08.11
80/236
SIMATIC BATCH
8.3
32201963
Figure 8-3
V 2.2
09.08.11
81/236
SIMATIC BATCH
32201963
Product Number
Product Description
Notes
Optional
Required
Table 8-3
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 658-5AF17-0YA5
1
1
1
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1
1
1
1
1)
4)
2)
6ES7 660-0DE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BC17-2YA0
2
2
2
2
1
2
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
A5E00504378
6XV1 870-3RH60
6ES7 657-0SA17-0YB0
2
6ES7 657-0FX17-2YB0
2
2
6ES7 657-0GX17-2YB0
6ES7 657-0HX17-2YB0
10)
3)
1)
4)
2)
9)
8)
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
2
2
1
V 2.2
6ES7 652-0XX01-1XF0
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
6ES7 657-0LX17-2YB5
6ES7 657-0BX17-2YB5
09.08.11
2)
11)
82/236
SIMATIC BATCH
Notes
5)
5)
7)
Optional
Required
Product Number
32201963
Terminal Bus
2
12
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Plant Bus
2
10
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 656-8CM33-1GB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
09.08.11
6)
6)
83/236
SIMATIC BATCH
8.4
32201963
Figure 8-4
V 2.2
09.08.11
84/236
SIMATIC BATCH
32201963
Product Number
Product Description
Notes
1)
1)
7)
Optional
Required
Table 8-4
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
6GK1 716-0HB71-3AC0
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
6ES7 660-0DE13-2BA0
4
4
6ES7 648-0CB00-0YA0
4
4
2
6GK1 716-0HB71-3AC0
6ES7 652-3BD17-2YA0
8)
1)
2)
10)
Batch Server
2
6ES7 660-0CE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
1
2
6XV1 870-3RH60
6ES7 657-0SA17-0YB0
2 6ES7 657-0FX17-2YB0
2 6ES7 657-0GX17-2YB0
V 2.2
09.08.11
8)
6)
85/236
SIMATIC BATCH
Product Number
32201963
Product Description
Notes
Optional
Required
6ES7 660-0EA02-2AA0
5
5
6ES7 648-0CB00-0YA0
5
5
3
6ES7 658-2CX17-0YA5
5 6ES7 652-0XD17-2YB5
2 6ES7 657-0LX17-2YB5
1 6ES7 657-0BX17-2YB5
9)
Terminal Bus
2
14
6GK5 216-0BA00-2AA3
6XV1 870-3QH60
3)
3)
Plant Bus
2
10
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 656-8CM33-1CB0
2
2
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
86/236
SIMATIC BATCH
32201963
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
V 2.2
09.08.11
87/236
Route Control
32201963
Route Control
The smallest system that supports all Route Control functions is the Single Station
System. Route Control Engineering, Server and Client functionality are concentrated in one computer and run in parallel with the Operator System.
Client-Server
Medium size systems that support multiple users and do not require redundancy
are implemented with Client-Server systems. SIMATIC Route Control follows the
Operator System architecture seamlessly by distribution of Route Control Server
and Client applications on the equivalent Operator System Computers.
Client-Server Redundant
If redundancy is required and the number of servers must be kept at a minimum,
SIMATIC Route Control allows deployment of a redundant Route Control Server on
the both of the redundant Operator System Server computers.
Client-Multi-Server Redundant
For large and high-performance applications the SIMATIC PCS 7 Client-Server architecture allows for distribution of applications on multiple computers. In this case
the Route Control Server and OS Server run on two independent computers. Each
of them can be made redundant providing maximum availability. The OS clients
computers can run the Route Control Client application and look at both OS Server
and Route Control Server seamlessly. If necessary the OS Client and Route Control Client application can also run on separate computers.
V 2.2
09.08.11
88/236
Route Control
9.1
32201963
Figure 9-1
Plant Bus
V 2.2
09.08.11
89/236
Route Control
32201963
Notes
Optional
Required
Product Number
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AB17-0YA5
1
1
1
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-1FX17-2YA5
6ES7 658-7DX17-0YB5
6ES7 658-7FA17-0YB0
6ES7 658-7EX17-0YB5
1)
4)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
3)
Automation System
1
6ES7 654-8DH03-3BB0
NOTE
V 2.2
1)
2)
3)
4)
09.08.11
90/236
Route Control
9.2
32201963
Figure 9-2
Plant Bus
V 2.2
09.08.11
91/236
Route Control
32201963
Product Number
Product Description
Notes
Optional
Required
Table 9-2
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
1
6ES7 658-7DX17-0YB5
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
6ES7 658-2BC17-0YA0
6ES7 658-7FA17-0YB0
6)
1)
5)
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
3
3
3
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
6ES7 658-7EX17-0YB5
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
3)
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8DH03-3BB1
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
4)
4)
92/236
Route Control
2)
3)
4)
5)
6)
NOTE
32201963
V 2.2
09.08.11
93/236
Route Control
9.3
32201963
Figure 9-3
V 2.2
09.08.11
94/236
Route Control
32201963
Product Number
Product Description
Notes
Optional
Required
Table 9-3
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 658-5AF17-0YA5
1
1
1
1
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
6ES7 658-7DX17-0YB5
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1
1
1
1
1)
4)
2)
6ES7 660-0DE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BC17-2YA0
2
2
2
2
1
2
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
A5E00504378
6XV1 870-3RH60
6ES7 658-7FA17-0YB0
9)
3)
1)
4)
2)
10)
8)
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
2
2
6ES7 652-0XX01-1XF0
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
6ES7 658-7EX17-0YB5
2)
Terminal Bus
2
12
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
5)
95/236
Route Control
Notes
5)
7)
Optional
Required
Product Number
32201963
Plant Bus
2
12
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
1
6ES7 656-8CM33-1CB0
3
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
1)
2)
3)
6)
6)
4)
5)
6)
7)
8)
9)
10)
V 2.2
09.08.11
96/236
Route Control
9.4
32201963
Figure 9-4
V 2.2
09.08.11
97/236
Route Control
32201963
Product Number
Product Description
Notes
1)
1)
Optional
Required
Table 9-4
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
6GK1 716-0HB71-3AC0
6ES7 658-5AF17-0YA5
1
1
1
1
1
6ES7 658-7DX17-0YB5
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
6ES7 660-0DE13-2BA0
4
4
6ES7 648-0CB00-0YA0
4
4
2
6GK1 716-0HB71-3AC0
6ES7 652-3BD17-2YA0
7)
1)
2)
9)
6ES7 660-0DE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
2
1
2
2
A5E00504378
6XV1 870-3RH60
6GK1 716-0HB71-3AC0
6ES7 658-7FA17-0YB0
7)
8)
1)
6)
6ES7 660-0EA02-2AA0
5
5
6ES7 648-0CB00-0YA0
5
5
5
5
V 2.2
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
6ES7 658-7EX17-0YB5
09.08.11
98/236
Route Control
Notes
3)
3)
4)
Optional
Required
Product Number
32201963
Terminal Bus
2
14
6GK5 216-0BA00-2AA3
6XV1 870-3QH60
Plant Bus
2
13
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 656-8CM33-1CB0
2
2
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
5)
6)
7)
8)
9)
09.08.11
5)
5)
99/236
10
32201963
Client-Server
Medium size systems that support multiple users and do not require redundancy
are implemented with Client-Server systems. SIMATIC BATCH and Route Control
follow the Operator System architecture seamlessly by distribution of Batch and
Route Control Server and Client applications on the equivalent Operator System
Computers.
Client-Server Redundant
If redundancy is required and the number of servers must be kept at a minimum,
SIMATIC BATCH and Route Control can be deployed on a pair of redundant Operator System Server Computers. Combining three redundant functions on two
servers.
Client-Multi-Server Redundant
For large and high-performance applications the SIMATIC PCS 7 Client-Server architecture allows for distribution of applications on multiple computers. In this case
the BatchServer, Route Control Server and OS Server run on two or three independent computers. Each of them can be made redundant providing maximum
availability. The OS clients computers can run the Batch and Route Control Client
applications and look at the distributed OS, Batch and Route Control Servers
seamlessly. If necessary the OS Client, Route Control and Batch Client applications can also run on separate computers.
V 2.2
09.08.11
100/236
10.1
32201963
Figure 10-1
Plant Bus
V 2.2
09.08.11
101/236
32201963
Route Control and SIMATIC BATCH Single Station System Bill of Materials
Table 10-1
Product Description
Notes
Optional
Required
Product Number
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AB17-0YA5
1
1
1
1
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-1FX17-2YA5
6ES7 658-7DX17-0YB5
6ES7 658-7FA17-0YB0
6ES7 658-7EX17-0YB5
6ES7 657-0SA17-0YB0
1
1
6ES7 657-0BX17-2YB5
6ES7 657-0FX17-2YB0
1
1
6ES7 657-0GX17-2YB0
6ES7 657-0HX17-2YB0
1)
4)
5)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
3)
Automation System
1
6ES7 654-8EK03-3DB0
NOTE
V 2.2
1)
2)
3)
4)
5)
09.08.11
102/236
10.2
32201963
Figure 10-2
Plant Bus
V 2.2
09.08.11
103/236
32201963
Product Number
Product Description
Notes
Optional
Required
Table 10-2
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
1
6ES7 658-7DX17-0YB5
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
1
6ES7 658-2BC17-0YA0
6ES7 658-7FA17-0YB0
6ES7 657-0SA17-0YB0
1 6ES7 657-0FX17-2YB0
1 6ES7 657-0GX17-2YB0
1 6ES7 657-0HX17-2YB0
6)
1)
5)
5)
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
6ES7 658-7EX17-0YB5
1 6ES7 657-0LX17-2YB5
1 6ES7 657-0BX17-2YB5
3
3
2
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
Plant Bus
1
4
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
104/236
Notes
3)
Optional
Required
Product Number
32201963
Automation System
2
6ES7 654-8EK03-3DB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
4)
4)
1)
2)
3)
4)
5)
Initial number of active routes and units can be increased using Power packs
6)
7)
09.08.11
105/236
10.3
32201963
Figure 10-3
Plant Bus
V 2.2
09.08.11
106/236
32201963
Product Number
Product Description
Notes
Optional
Required
Table 10-3
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 658-5AF17-0YA5
1
1
1
1
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
6ES7 658-7DX17-0YB5
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1
1
1
1
1)
4)
2)
6ES7 660-0DE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BC17-2YA0
2
2
2
2
1
2
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
A5E00504378
6XV1 870-3RH60
6ES7 658-7FA17-0YB0
6ES7 657-0SA17-0YB0
V 2.2
6ES7 657-0FX17-2YB0
6ES7 657-0GX17-2YB0
09.08.11
10)
3)
1)
4)
3)
9)
8)
8)
107/236
Product Number
32201963
Product Description
Notes
Optional
Required
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
2
2
2
1
6ES7 652-0XX01-1XF0
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
6ES7 658-7EX17-0YB5
6ES7 657-0LX17-2YB5
6ES7 657-0BX17-2YB5
3)
11)
Terminal Bus
2
12
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
5)
5)
7)
Plant Bus
2
12
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 656-8CM33-1CB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
6)
6)
108/236
32201963
1)
2)
3)
4)
V 2.2
5)
6)
7)
8)
Initial number of active Routes and units can be increased using Power
packs
9)
10)
11)
09.08.11
109/236
10.4
32201963
Figure 10-4
Plant Bus
V 2.2
09.08.11
110/236
32201963
Product Number
Product Description
Notes
1)
1)
Optional
Required
Table 10-4
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
6GK1 716-0HB71-3AC0
6ES7 658-5AF17-0YA5
1
1
1
1
1
6ES7 658-7DX17-0YB5
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
6ES7 660-0DE13-2BA0
4
4
6ES7 648-0CB00-0YA0
4
4
2
6GK1 716-0HB71-3AC0
6ES7 652-3BD17-2YA0
7)
1)
2)
9)
6ES7 660-0DE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
1
2
2
6GK1 716-0HB71-3AC0
A5E00504378
6XV1 870-3RH60
6ES7 658-7FA17-0YB0
6ES7 657-0SA17-0YB0
2 6ES7 657-0FX17-2YB0
2 6ES7 657-0GX17-2YB0
2 6ES7 657-0HX17-2YB0
V 2.2
09.08.11
7)
1)
8)
6)
6)
111/236
Product Number
32201963
Product Description
Notes
Optional
Required
6ES7 660-0EA02-2AA0
5
5
6ES7 648-0CB00-0YA0
5
5
5
5
3
2
1
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
6ES7 658-7EX17-0YB5
6ES7 657-0LX17-2YB5
6ES7 657-0BX17-2YB5
Terminal Bus
2
14
6GK5 216-0BA00-2AA3
6XV1 870-3QH60
3)
3)
4)
Plant Bus
2
13
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 656-8CM33-1CB0
2
2
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
5)
5)
112/236
NOTE
V 2.2
32201963
1)
2)
3)
4)
5)
6)
Initial number of active routes and units can be increased using Power packs
7)
8)
9)
09.08.11
113/236
SIMATIC PDM
11
32201963
SIMATIC PDM
SIMATIC PDM
Configuration of HART, PROFIBUS PA and PROFIBUS DP devices, based on the
open EDDL (Electronic Device Description Language) is easy by means of the
Process Device Manager or SIMATIC PDM. SIMATIC PDM also is the basis for diagnostics and asset management functionality and is fully integrated in the
SIMATIC PCS 7 Engineering and Operator System.
Stand-alone
If full integration of SIMATIC PDM is not required then the stand-alone version can
be installed on a standard computer and connected to the PROFIBUS DP Field
Bus. With this setup engineering and maintenance tasks on any HART, PROFIBUS
PA and PROFIBUS DP device can be performed.
V 2.2
09.08.11
114/236
SIMATIC PDM
32201963
V 2.2
09.08.11
115/236
SIMATIC PDM
11.1
32201963
Figure 11-1
V 2.2
09.08.11
116/236
SIMATIC PDM
32201963
Notes
1)
1)
Optional
Required
Product Number
Laptop PDM
1
1
1
6GK1 551-2AA00
6GK1 561-1AA01
6ES7 658-3AX06-0YA5
NOTE
1)
1)
V 2.2
09.08.11
117/236
SIMATIC PDM
11.2
32201963
Figure 11-2
Field PG
PDM
V 2.2
09.08.11
118/236
SIMATIC PDM
32201963
Notes
1)
Optional
Required
Product Number
Laptop PDM
1
6ES7 658-3JX06-2YA5
6ES7 658-3CX06-2YB5
Notice
NOTE
V 2.2
For this configuration you can use Service Laptops as well. These Laptops
have to provide an Etherned interface which is ISO capable (MAC Adress)
1)
09.08.11
119/236
SIMATIC PDM
11.3
32201963
Figure 11-3
V 2.2
09.08.11
120/236
SIMATIC PDM
32201963
Notes
1)
1)
Optional
Required
Product Number
Laptop PDM
1
1
1
1
6GK1 551-2AA00
6GK1 561-1AA01
6ES7 658-3JX06-0YA5
6ES7 157-0AC83-0XA0
NOTE
V 2.2
2)
2)
FDC 157-0 DP/PA Coupler requires 24 VDC Power Supply (not listed)
09.08.11
121/236
SIMATIC PDM
11.4
32201963
Figure 11-4
V 2.2
09.08.11
122/236
SIMATIC PDM
32201963
Notes
Optional
Required
Product Number
6ES7 650-4AA00-0AA0
6ES7 648-0CB00-0YA0
1
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-1FX17-2YA5
6ES7 658-3LX06-0YA5
NOTE
V 2.2
1)
2)
1)
Please use the PCS 7 BOX configurator, because the PCS 7 BOX is available
in different configurations, e. g. DC 24 V or AC 110/230 V.
2)
09.08.11
123/236
SIMATIC PDM
11.5
32201963
Figure 11-5
Plant Bus
V 2.2
09.08.11
124/236
SIMATIC PDM
32201963
Notes
Optional
Required
Product Number
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AB17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-1FX17-2YA5
6ES7 658-3LX06-0YA5
1)
5)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
3)
6)
Automation System
1
6ES7 654-8CJ10-3BB0
NOTE
V 2.2
1)
2)
3)
4)
5)
6)
09.08.11
125/236
SIMATIC PDM
11.6
32201963
Figure 11-6
Plant Bus
V 2.2
09.08.11
126/236
SIMATIC PDM
32201963
Product Number
Product Description
Notes
Optional
Required
Table 11-6
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-3LX06-0YA5
6)
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
7)
1)
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
3
3
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
3)
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
6ES7 653-2BA00-0XB5
V 2.2
09.08.11
7)
4)
127/236
SIMATIC PDM
2)
3)
4)
5)
6)
6)
7)
NOTE
32201963
V 2.2
09.08.11
128/236
SIMATIC PDM
11.7
32201963
Figure 11-7
Plant Bus
V 2.2
09.08.11
129/236
SIMATIC PDM
32201963
Notes
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
2)
Optional
Required
Product Number
PDM
1
1
1
6ES7 810-4CC08-0YA5
6ES7 658-3KX06-0YA5
Plant Bus
1
2
1
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
6GK1 411-5AB00
NOTE
V 2.2
1)
2)
3)
09.08.11
1)
3)
130/236
Archiving
12
32201963
Archiving
Client-Server System
The Central Archive Server always runs on a separate computer and the PCS 7
hardware used is the same as for the OS Server. All OS Clients can gather data
from the Central Archive Server seamlessly, e.g. there is no difference in looking at
data from the OS Server or from the Central Archive Server.
Redundant OS Server, Single Central Archive Server
If redundant operation and monitoring is a requirement but high availability of historical data is not required, then a single Central Archive Server can be connected
to a redundant pair of Operator System Servers.
Redundant Central Archive Server
When high availability of the Historical data is a requirement SIMATIC PCS 7 offers, starting with SIMATIC PCS 7 V7.0 SP1, the option of redundant Central Archive Servers.
Storage Plus
For small systems it can be sufficient to use a dedicated system for long term archiving and data retrieval. In this case SIMATIC PCS 7 offers an economical solution based on Storage Plus. Installed on a separate PC it creates and manages a
long term archive. Data can be retrieved from the long term archive on the separate PC and reviewed and exported through a viewer.
V 2.2
09.08.11
131/236
Archiving
12.1
32201963
Figure 12-1
V 2.2
09.08.11
132/236
Archiving
32201963
Product Number
Product Description
Notes
Optional
Required
Table 12-1
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
6)
1)
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2FA17-0YB0
6)
5)
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
6ES7 658-2CX17-0YA5
6ES7 652-0XD17-2YB5
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
Plant Bus
1
4
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
133/236
Archiving
Notes
3)
Optional
Required
Product Number
32201963
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
5)
6)
09.08.11
4)
4)
134/236
Archiving
12.2
32201963
Redundant OS Server,
Single Central Archive Server
Figure 12-2
Plant Bus
V 2.2
09.08.11
135/236
Archiving
32201963
Product Number
Product Description
Notes
Optional
Required
Table 12-2
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 658-5AF17-0YA5
1
1
1
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1
1
1
1
1)
4)
2)
6ES7 660-0DE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BC17-2YA0
2
2
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
9)
3)
10)
1)
4)
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2FA17-0YB0
6ES7 652-0XX01-1XF0
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
V 2.2
6ES7 652-0XX01-1XF0
6ES7 658-2CX17-0YA5
2 6ES7 652-0XD17-2YB5
09.08.11
2)
136/236
Archiving
Product Number
32201963
Product Description
Notes
5)
5)
Optional
Required
Terminal Bus
2
12
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Plant Bus
2
10
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 656-8CM33-1CB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
V 2.2
09.08.11
137/236
Archiving
12.3
32201963
Redundant OS Server,
Redundant Central Archive Server
Figure 12-3
Plant Bus
V 2.2
09.08.11
138/236
Archiving
32201963
Product Number
Product Description
Notes
Optional
Required
Table 12-3
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 658-5AF17-0YA5
1
1
1
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1
1
1
1
1)
4)
2)
6ES7 660-0DE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BC17-2YA0
2
2
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
9)
3)
10)
1)
4)
6ES7 660-0CE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
1
1
2
6AV6 371-1CF07-0AX0
6ES7 902-1AC00-0AA0
6ES7 658-2FA17-0YB0
6ES7 652-0XX01-1XF0
V 2.2
09.08.11
139/236
Archiving
Product Number
32201963
Product Description
Notes
Optional
Required
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
6ES7 652-0XX01-1XF0
6ES7 658-2CX17-0YA5
2 6ES7 652-0XD17-2YB5
2)
Terminal Bus
2
14
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
5)
5)
Plant Bus
2
10
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 656-8CM33-1CB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
140/236
Archiving
NOTE
32201963
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
V 2.2
09.08.11
141/236
Archiving
12.4
32201963
Figure 12-4
Plant Bus
V 2.2
09.08.11
142/236
Archiving
32201963
Product Number
Product Description
Notes
Optional
Required
Table 12-4
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
5)
1)
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 658-2CX17-0YA5
2 6ES7 652-0XD17-2YB5
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 652-0XC17-2YB0
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
Plant Bus
1
4
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
143/236
Archiving
Product Number
32201963
Product Description
Notes
Optional
Required
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
5)
09.08.11
144/236
Asset Management
13
32201963
Asset Management
Single Station
Connected via an Ethernet Plant Bus, Engineering, Operator System and Asset
Management functionality are concentrated on a SIMATIC PCS 7 Single Station
System. Asset Management delivers diagnostics and maintenance of all connected
Field Devices, Automation System components, Active Networking components
and computers.
Client-Server (Redundant)
In a Client-Server architecture the Asset Management system follows SIMATIC
PCS 7 distributed Client-Server structure. The Asset Management System uses
standard PCS 7 OS display and alarming. The Maintenance Server functionality is
integrated in the OS Server and no additional computer is needed. The OS Clients
can access the Maintenance Screens like standard PCS 7 process pictures. For
detailed diagnostics and trouble shooting of intelligent field devices the Asset Management System provides additional information on the Maintenance System.
V 2.2
09.08.11
145/236
Asset Management
13.1
32201963
Figure 13-1
V 2.2
09.08.11
146/236
Asset Management
32201963
Product Number
Product Description
Notes
Optional
Required
Table 13-1
6ES7 650-4AA00-0AA0
6ES7 648-0CB00-0YA0
1
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-1FX17-2YA5
6ES7 658-3LX06-0YA5
1
1
6ES7 658-7GX17-0YB5
6ES7 658-7GB17-0YB0
NOTE
V 2.2
1)
2)
3)
1)
Please use the PCS 7 BOX configurator, because the PCS 7 BOX is available
in different configurations, e. g. DC 24 V or AC 110/230 V.
2)
3)
09.08.11
147/236
Asset Management
13.2
32201963
Figure 13-2
Plant Bus
V 2.2
09.08.11
148/236
Asset Management
32201963
Product Number
Product Description
Notes
Optional
Required
Table 13-2
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AB17-0YA5
1
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-1FX17-2YA5
6ES7 658-3LX06-0YA5
1
1
6ES7 658-7GX17-0YB5
6ES7 658-7GB17-0YB0
1)
5)
6)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
3)
Automation System
1
6ES7 654-8CJ10-3BB0
NOTE
1)
2)
3)
4)
5)
6)
V 2.2
09.08.11
149/236
Asset Management
32201963
1 AS 416-3 IE
Count
Asset
Management
Tags
Process
Objects
PDM Tags
Computers
PROFIBUS PA
200
200
200
Hart
100
100
100
Foundation FieldBus
32
32
32
ET200M modules
50
80
80
80
25
25
Automation System
Networks
Process Devices
120
120
120
120
569
120
531
Totals
V 2.2
09.08.11
150/236
Asset Management
32201963
Product Number
Product Description
Notes
Optional
Required
Table 13-4
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AB17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-1FX17-2YA5
6ES7 658-3LX06-0YA5
1
1
1
1
6ES7 658-3XB06-2YD5
6ES7 658-3XC06-2YD5
6ES7 658-7GX17-0YB5
6ES7 658-7GB17-0YB0
6ES7 658-7GB00-2YB0
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
3)
Automation System
1
6ES7 654-8CJ10-3BB0
NOTE
V 2.2
1)
2)
3)
09.08.11
151/236
Asset Management
13.3
32201963
Figure 13-3
Plant Bus
V 2.2
09.08.11
152/236
Asset Management
32201963
Product Number
Product Description
Notes
Optional
Required
Table 13-5
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-3LX06-0YA5
1
1
6ES7 658-7GX17-0YB5
6ES7 658-2CX17-0YA5
6)
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
6ES7 658-2BB17-0YA0
6ES7 658-7GB17-0YB0
7)
1)
8)
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
6ES7 658-2CX17-0YA5
3 6ES7 652-0XD17-2YB5
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
3)
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
6ES7 653-2BA00-0XB5
V 2.2
09.08.11
4)
153/236
Asset Management
NOTE
32201963
1)
2)
3)
4)
6)
7)
8)
V 2.2
Three OS Clients
2 AS 416-3 IE
09.08.11
154/236
Asset Management
32201963
Asset
Management
Tags
Process
Objects
PDM Tags
Computers
PROFIBUS PA
300
300
300
Hart
180
180
180
Foundation FieldBus
80
80
80
20
20
ET200M modules
135
160
160
160
Item
60
60
Automation System
Networks
10
Process Devices
240
240
240
240
1049
240
960
Totals
V 2.2
09.08.11
155/236
Asset Management
32201963
Product Description
Notes
Optional
Required
Table 13-7
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-3LX06-0YA5
1
1
1
1
6ES7 658-3XB06-2YD5
6ES7 658-3XC06-2YD5
6ES7 658-7GX17-0YB5
6ES7 658-2CX17-0YA5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
6ES7 658-2BC17-0YA0
6ES7 658-7GB17-0YB0
6ES7 658-7GC00-2YB0
7)
1)
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
6ES7 658-2CX17-0YA5
3 6ES7 652-0XD17-2YB5
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
Plant Bus
1
4
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
156/236
Asset Management
Product Number
32201963
Product Description
Notes
Optional
Required
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
7)
09.08.11
157/236
Asset Management
13.4
32201963
Figure 13-4
V 2.2
09.08.11
158/236
Asset Management
32201963
Product Number
Product Description
Notes
Optional
Required
Table 13-8
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-3LX06-0YA5
1
1
6ES7 658-7GX17-0YB5
6ES7 658-2CX17-0YA5
6)
6ES7 660-0CE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BB17-2YA0
7)
1)
9)
Maintenance Server
1
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
6ES7 658-2BB17-0YA0
6ES7 658-7GB17-0YB0
7)
1)
8)
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
6ES7 658-2CX17-0YA5
3 6ES7 652-0XD17-2YB5
Terminal Bus
1
7
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
2)
159/236
Asset Management
Product Number
32201963
Product Description
Notes
2)
3)
Optional
Required
Plant Bus
1
6
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
6ES7 653-2BA00-0XB5
NOTE
1)
2)
3)
4)
6)
7)
8)
9)
V 2.2
4)
09.08.11
160/236
Asset Management
13.5
32201963
Figure 13-5
Plant Bus
V 2.2
09.08.11
161/236
Asset Management
32201963
Product Number
Product Description
Notes
Optional
Required
Table 13-9
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-3LX06-0YA5
1
1
6ES7 658-7GX17-0YB5
6ES7 658-2CX17-0YA5
6)
6ES7 660-0CE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BB17-2YA0
7)
1)
9)
6ES7 660-0CE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BB17-2YA0
6ES7 658-7GB17-0YB0
7)
1)
9)
8)
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
6ES7 658-2CX17-0YA5
3 6ES7 652-0XD17-2YB5
Terminal Bus
1
V 2.2
6GK5 208-0BA10-2AA3
09.08.11
2)
162/236
Asset Management
32201963
Product Number
Product Description
6XV1 870-3QH60
Notes
Optional
Required
Plant Bus
1
7
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
3)
Automation System
2
6ES7 654-8CJ10-3BB0
6ES7 653-2BA00-0XB5
NOTE
1)
2)
3)
4)
6)
7)
8)
9)
4)
V 2.2
Three OS Clients
09.08.11
163/236
Asset Management
32201963
2 AS 416-3 IE
Table 13-10
Count
Asset
Management
Tags
Process
Objects
PDM Tags
Computers
PROFIBUS PA
300
300
300
Hart
180
180
180
Foundation FieldBus
80
80
80
20
20
ET200M modules
135
160
160
160
Item
60
60
Automation System
Networks
10
Process Devices
240
240
240
240
1052
240
960
Totals
V 2.2
09.08.11
164/236
Asset Management
32201963
Product Number
Product Description
Notes
Optional
Required
Table 13-11
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 658-3LX06-0YA5
1
1
1
1
6ES7 658-3XB06-2YD5
6ES7 658-3XC06-2YD5
6ES7 658-7GX17-0YB5
6ES7 658-2CX17-0YA5
6ES7 660-0CE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BC17-2YA0
7)
1)
9)
6ES7 660-0CE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BB17-2YA0
6ES7 658-7GB17-0YB0
6ES7 658-7GC00-2YB0
V 2.2
09.08.11
7)
9)
165/236
Asset Management
Product Number
32201963
Product Description
Notes
Optional
Required
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
6ES7 658-2CX17-0YA5
3 6ES7 652-0XD17-2YB5
Terminal Bus
1
10
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
Plant Bus
1
7
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
2
2
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
2)
3)
4)
7)
9)
09.08.11
166/236
Field Bus
14
32201963
Field Bus
PROFIBUS DP slaves can be connected directly to the high speed PROFIBUS DP,
and via dedicated network transitions acts as the high performance link to intelligent Field Devices based on the PROFIBUS PA and Foundation Fieldbus standards.
Besides data transmission, PROFIBUS PA provides power to the field device on
the same two wire cable. This function is performed by a PROFIBUS PA Couplers
or FF power supplies. Energy limiting components allow it to connect field devices
directly in an explosion hazardous environment.
DP/PA and DP/FF Link components act as gateways between the high speed
PROFIBUS DP networks and bus powered PA/ FF side allowing deployment of a
larger number of PROFIBUS PA slaves and FF Field Devices without exhausting
the available address space of the PROFIBUS DP network.
Single optical PROFIBUS DP
To support larger distances, provide ring fault tolerance and electrical isolation,
PROFIBUS DP allows the introduction of Fiber Optic network components. The
logical bus topology remains a single line, while ring fault tolerance increases
availability.
Redundant optical PROFIBUS DP
Highest availability and isolation are achieved when combining redundant
PROFIBUS DP and Fiber Optic network components. The combination of a double
fault tolerant ring allows the occurrence of multiple disturbances without losing
connectivity to the Field.
Redundant electrical PROFIBUS DP, PROFIBUS PA and FOUNDATION FIELDBUS
When high availability is a requirement, PROFIBUS DP supports extension of redundant networks to IO racks and DP/PA and DP/FF Links. A redundant
PROFIBUS DP network consists of two separate electrical lines connected to two
independent PROFIBUS Masters and several redundant DP Slaves. PROFIBUS
PA and FIELDBUS FOUNDATION offer the unique capability to construct the Field
Device Bus as a fault tolerant ring, increasing the availability of complete Field Device networks. Redundant PROFIBUS PA and redundant FOUNDATION
FIELDBUS are available in combination with single and redundant PROFIBUS DP
networks.
V 2.2
09.08.11
167/236
Field Bus
14.1
32201963
Figure 14-1
V 2.2
09.08.11
168/236
Field Bus
32201963
Product Number
Product Description
Notes
6ES7 654-8CJ10-3BB0
1)
6ES7 654-0XX08-1XA0
2)
2)
4)
Optional
Required
Table 14-1
Automation System
1
ET200M
1
DIAGNOSTICS REPEATER
1
6ES7 972-0AA01-0XA0
DP/PA LINK
1
6ES7 157-0AC83-0XA0
1
1
6ES7 153-2BA82-0XB0
6ES7 195-1GA00-0XA0
6ES7 195-7HA00-0XA0
6ES7 195-7HF80-0XA0
3)
5)
DP/FF LINK
1
1
1
1
6ES7 658-3MD07-0YA5
6ES7 153-2DA80-0XB0
6ES7 157-0AC84-0AX0
6ES7 195-1GA00-0XA0
6ES7 195-7HA00-0XA0
6ES7 195-7HF80-0XA0
V 2.2
09.08.11
169/236
Field Bus
1)
32201963
PROFIBUS NOTES:
Max. number of PROFIBUS Slaves per Master 125 (Typical 30-80)
Max. number of slaves per segment 32, segments are separated by (Diagnostics) Repeaters
2)
3)
4)
5)
V 2.2
09.08.11
170/236
Field Bus
14.2
32201963
Figure 14-2
V 2.2
09.08.11
171/236
Field Bus
32201963
Product Number
Product Description
Notes
1)
6GK1 503-3CB00
6)
6ES7 654-0XX08-1XA0
2)
4)
Optional
Required
Table 14-2
Automation System
1
6ES7 654-8CJ10-3BB0
DP/PA LINK
1
6ES7 157-0AC83-0XA0
1
1
6ES7 153-2BA82-0XB0
6ES7 195-1GA00-0XA0
6ES7 195-7HA00-0XA0
6ES7 195-7HF80-0XA0
3)
5)
DP/FF LINK
1
1
1
1
6ES7 658-3MD07-0YA5
6ES7 153-2DA80-0XB0
6ES7 157-0AC83-0AX0
6ES7 195-1GA00-0XA0
6ES7 195-7HA00-0XA0
6ES7 195-7HF80-0XA0
V 2.2
09.08.11
5)
172/236
Field Bus
1)
32201963
PROFIBUS Notes:
V 2.2
Max. number of slaves per segment 32, segments are separated by (Diagnostics) Repeaters
2)
3)
4)
5)
6)
09.08.11
173/236
Field Bus
14.3
32201963
Figure 14-3
V 2.2
09.08.11
174/236
Field Bus
32201963
Product Number
Product Description
Notes
Optional
Required
Table 14-3
Automation System
1
6ES7 656-8CM33-1CB0
6GK7 443-5DX04-0XE0
ET200M
1
6ES7 153-2AR03-0XA0
6ES7 197-1LA11-0XA0
3)
3)
5)
Y-LINK
DIAGNOSTICS REPEATER
2
6ES7 972-0AA01-0XA0
DP/PA LINK
2
6ES7 157-0AC83-0XA0
2
1
6ES7 153-2BA82-0XB0
6ES7 195-1GA00-0XA0
6ES7 195-7HD80-0XA0
6ES7 195-7HG80-0XA0
6ES7 157-0AF81-0XA0
4)
6)
DP/FF LINK
1
2
2
1
6ES7 658-3MD07-0YA5
6ES7 153-2DA80-0XB0
6ES7 157-0AC84-0AX0
6ES7 195-1GA00-0XA0
6ES7 195-7HD80-0XA0
6ES7 195-7HG80-0XA0
6ES7 157-0AF81-0XA0
V 2.2
09.08.11
6)
175/236
Field Bus
NOTE
V 2.2
32201963
1)
2)
Max. number of slaves per segment 32, segments are separated by (Diagnostics) Repeaters
3)
4)
5)
Max. One pair of redundant FDC 157-0 per DP/PA Link and 3
single FDC 157-0
6)
7)
8)
09.08.11
176/236
Field Bus
14.4
32201963
Figure 14-4
V 2.2
09.08.11
177/236
Field Bus
32201963
Product Number
Product Description
Notes
Optional
Required
Table 14-4
Automation System
1
6ES7 656-8CM33-1CB0
6GK7 443-5DX04-0XE0
6GK1 503-3CB00
8)
6ES7 153-2AR03-0XA0
6ES7 197-1LA11-0XA0
3)
5)
ET200M
1
Y-LINK
2
DP/PA LINK
2
6ES7 157-0AC83-0XA0
2
1
6ES7 153-2BA82-0XB0
6ES7 195-1GA00-0XA0
6ES7 195-7HD80-0XA0
6ES7 195-7HG80-0XA0
6ES7 157-0AF81-0XA0
4)
6)
DP/FF LINK
1
2
2
1
6ES7 658-3MD07-0YA5
6ES7 153-2DA80-0XB0
6ES7 157-0AC84-0AX0
6ES7 195-1GA00-0XA0
6ES7 195-7HD80-0XA0
6ES7 195-7HG80-0XA0
6ES7 157-0AF81-0XA0
V 2.2
09.08.11
6)
178/236
Field Bus
NOTE
V 2.2
32201963
1)
2)
Max. number of slaves per segment 32, segments are separated by (Diagnostics) Repeaters
3)
4)
5)
6)
7)
8)
9)
09.08.11
179/236
Network Architecture
15
32201963
Network Architecture
Star Topologies
The robust SCALANCE network components, active and managed switches, can
be used to create cost-effective network topologies providing connectivity to large
numbers of nodes.
SCALANCE offers a broad line of components to build start topologies with a large
number of ports. If multiple switches are required to accommodate the number of
ports that is to be connected, or to allow for geographical distribution of switches,
then we suggest to connect the switches as a fault tolerant ring.
Fault Tolerant Ring
A unique redundancy manager concept enables two SCALANCE switches to manage disturbances in an optical, electrical or mixed media ring backbone without interrupting network communication. This capability is available in the complete
range of SCALANCE switches offered with SIMATIC PCS 7.
Double Redundant Bus
SIMATIC PCS 7 offers redundancy from Operator System Client to Field connectivity. Network communication between Operator System Clients and Servers, as
well as between Operator System Servers and Automation Systems can reach the
highest level of availability by deploying two network interfaces in each computer
and Automation System and connecting these interfaces to separated fault tolerant
ring structured networks.
Fault Tolerant Ring 1GB
For applications where backbone data throughput cannot be compromised,
SCALANCE offers 1 Giga Bit network backbone switches. These high performance
switches also provide redundancy management functionality allowing the implementation of fault tolerant ring topologies in a single or double redundant manner.
V 2.2
09.08.11
180/236
Network Architecture
15.1
32201963
Star Architectures
Product Description
Notes
1)
Optional
Required
Figure 15-1
Electrical X200
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
NOTE
V 2.2
1)
09.08.11
181/236
Network Architecture
32201963
15.2
15.2.1
Figure 15-2
The Redundancy Manager acts as a switch that opens the Ethernet Ring at a defined Position and monitors the status of the line. If a failure occurs on the line, the
Redundancy Manager recognizes this, closes the switch and
reestablishes communication.
V 2.2
09.08.11
182/236
Network Architecture
15.2.2
32201963
Figure 15-3
The Standby Master and Standby Slave are connected in a logical manner. The
Standby Master activates its connection and the Standby Slave deactivates its
connection.Both switches monitor each others status, in case of a failure in the active connection, the Standby Slave becomes active. The process of enabling the
Standby Slave occurs fast enough to have no communication failure being experienced by connected systems (Controllers, Servers, Clients).
V 2.2
09.08.11
183/236
Network Architecture
15.3
32201963
Terminal Bus
Plant Bus
V 2.2
09.08.11
184/236
Network Architecture
32201963
Product Number
Product Description
Notes
1)
1)
Optional
Required
Table 15-2
Terminal Bus
2
2
5
6GK5 204-2BB10-2AA3
6XV1 820-5BN10
6XV1 870-3QH60
Plant Bus
2
2
6
6GK5 204-2BB10-2AA3
6XV1 820-5BN10
6XV1 870-3QH60
1)
NOTE
V 2.2
09.08.11
185/236
Network Architecture
15.4
32201963
Terminal Bus
Plant Bus
V 2.2
09.08.11
186/236
Network Architecture
32201963
Product Number
Product Description
Notes
1)
1)
Optional
Required
Table 15-3
Terminal Bus
2
7
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Plant Bus
2
8
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
1)
NOTE
V 2.2
09.08.11
187/236
Network Architecture
15.5
32201963
Figure 15-6
V 2.2
09.08.11
188/236
Network Architecture
32201963
Product Number
Product Description
Notes
1)
1)
1)
Optional
Required
Table 15-4
Terminal Bus
2
3
5
14
6GK5 202-2BB00-2BA3
6GK5 204-2BB10-2AA3
6XV1 820-5BN10
6XV1 870-3QH60
Plant Bus
4
4
8
6GK5 204-2BB10-2AA3
6XV1 820-5BN10
6XV1 870-3QH60
1)
NOTE
V 2.2
09.08.11
189/236
Network Architecture
15.6
32201963
Terminal Bus
Plant Bus
V 2.2
09.08.11
190/236
Network Architecture
32201963
Product Number
Product Description
Notes
1)
1)
Optional
Required
Table 15-5
Terminal Bus
2
2
5
6GK5 308-2FL00-2AA3
6XV1 873-6AN10
6XV1 870-3QH60
Plant Bus
2
2
6
6GK5 308-2FL00-2AA3
6XV1 873-6AN10
6XV1 870-3QH60
1)
NOTE
V 2.2
09.08.11
191/236
Network Architecture
15.7
15.7.1
32201963
15.7.2
Single Station AS 41x-x-1H systems consist of one S7-41xH CPU. To support redundant communication, a station can be equipped with two CP443-1 Ethernet
communication processors. The table below lists the different redundancy configurations.
V 2.2
Concept 1, Single network, single OS Server/Single Station network connection, two communication paths
Concept 2, Single network, redundant OS Server/Single Station network connection, two communication paths
09.08.11
192/236
Network Architecture
32201963
Figure 15-8
Concept 1
Concept 3
CP1613_A
CP1613_A
CP1613_B
Plant Bus A
Plant Bus
Plant Bus B
CP443-1_A
CP443-1_B
CP443-1_A
CP443-1_B
Concept 2
CP1613_A
CP1613_B
Plant Bus
CP443-1_A
CP443-1_B
V 2.2
09.08.11
193/236
Network Architecture
32201963
Concept 1
Product Number
Product Description
Notes
1)
2)
3)
Optional
Required
Table 15-6
Automation System
1
6ES7 654-8CM03-3CB0
6GK1 716-0HB71-3AC0
Concept 2, Concept 3
Table 15-7
Product Description
Notes
1)
2)
2)
3)
Optional
Product Number
Required
Automation System
1
6ES7 654-8CM03-3CB1
6GK1 716-0HB71-3AC0
6GK1 162-3AA00
NOTE
SCALANCE switch and network components must be added, refer to network topology descriptions in this chapter to select the appropriate configuration and materials
1) Alternative for the AS417-4-1H are the AS414-4-1H and
AS412-3-1H Automation Systems
2) REDCONNECT Upgrade and CP1613 are required for each Operator
System and Engineering System that is connected to the Plant Bus
3) The Bill of Material is based on the prerequisite that Operator System,
Engineering System hardware is selected that is equipped with a
CP1613 (Industrial Ethernet version of the hardware), only additional
CP1613 communication processors are listed
V 2.2
09.08.11
194/236
Network Architecture
15.7.3
32201963
V 2.2
Concept 1, Single network, single OS Server/Single Station network connection, two communication paths
Concept 2, Single network, redundant OS Server/Single Station network connection, four communication paths
09.08.11
195/236
Network Architecture
32201963
Figure 15-9
Plant Bus B
Plant Bus
Plant Bus A
Plant Bus
Plant Bus B
Plant Bus A
V 2.2
09.08.11
196/236
Network Architecture
32201963
Concept 1
Product Number
Product Description
Notes
1)
2)
3)
Optional
Required
Table 15-8
Automation System
1
6ES7 656-8CM33-1CB0
Concept 2, Concept 3
Table 15-9
Product Description
Notes
1)
2)
2)
3)
Optional
Product Number
Required
Automation System
1
6ES7 656-8CM33-1CB0
V 2.2
6GK1 716-0HB71-3AC0
6GK1 162-3AA00
09.08.11
197/236
Network Architecture
32201963
Concept 4
Table 15-10
Product Description
Notes
1)
2)
2)
3)
Optional
Required
Product Number
Automation System
1
6ES7 656-8CM33-1CB0
6GK1 716-0HB71-3AC0
6GK1 162-3AA00
NOTE
SCALANCE switch and network components must be added, refer to network topology descriptions in this chapter to select the appropriate configuration and materials
1) Alternative for the AS417-4-1H are the AS414-4-1H and
AS412-3-1H Automation Systems
2) REDCONNECT Upgrade and CP1613 are required for each Operator
System and Engineering System that is connected to the Plant Bus
3) The Bill of Material is based on the prerequisite that Operator System,
Engineering System hardware is selected that is equipped with a
CP1613 (Industrial Ethernet version of the hardware), only additional
CP1613 communication processors are listed
V 2.2
09.08.11
198/236
Network Architecture
32201963
15.8
15.8.1
Introduction
Operator System Servers and Clients, as well as Engineering Systems, Batch
Servers, Route Control Servers and Central Archive Servers, can be equipped with
a redundant Terminal Bus connection. The table below lists the different redundancy configurations.
V 2.2
(Double) Redundant Fault Tolerant Ring network, with Standby redundancy between the two rings
09.08.11
199/236
Network Architecture
15.8.2
32201963
Figure 15-10
Figure 15-11
V 2.2
09.08.11
200/236
Network Architecture
15.8.3
32201963
Table 15-11
Product Description
Notes
1)
Optional
Required
Product Number
6ES7 652-0XX01-1XF0
6ES7 652-0XX01-1XF0
NOTE
SCALANCE switch and network components must be added, refer to network topology descriptions in this chapter to select the appropriate configuration and materials
1) Must be selected for each Batch, Route Control and Central Archive
Server, and Engineering System
V 2.2
09.08.11
201/236
Safety System
16
32201963
Safety System
Client-Server
Medium to large systems are implemented by combining standard and Safety
Automation Systems connected to an Operator System Server. The Engineering
and Operation and Monitoring functions are distributed across the Engineering and
Operator System Computers.
Client-Server Redundant
High availability of Operation, Monitoring and Automation System functionality is
provided by redundant Operator System Servers and High Availability Automation
Systems.
V 2.2
09.08.11
202/236
Safety System
16.1
32201963
Figure 16-1
Plant Bus
V 2.2
09.08.11
203/236
Safety System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 16-1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AB17-0YA5
1
1
1
1
1
1
1
6ES7 833-1CC02-0YA5
6ES7 833-1SM02-0YA5
6ES7 833-1SM62-0YA5
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
3)
Automation System
1
6ES7 654-8CF03-3BB0
NOTE
1)
2)
3)
V 2.2
09.08.11
204/236
Safety System
16.2
32201963
Figure 16-2
Plant Bus
V 2.2
09.08.11
205/236
Safety System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 16-2
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
1
1
1
6ES7 833-1CC02-0YA5
6ES7 833-1SM02-0YA5
6ES7 833-1SM62-0YA5
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
5)
1)
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
6ES7 658-2CX17-0YA5
3 6ES7 833-1SM62-0YA5
3 6ES7 652-0XD17-2YB5
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8EN33-1BB1
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
206/236
Safety System
2)
3)
4)
5)
NOTE
32201963
V 2.2
09.08.11
207/236
Safety System
16.3
32201963
Figure 16-3
Plant Bus
V 2.2
09.08.11
208/236
Safety System
32201963
Product Number
Product Description
Notes
Optional
Required
Table 16-3
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 658-5AF17-0YA5
6ES7 833-1CC02-0YA5
1 6ES7 833-1SM02-0YA5
1 6ES7 833-1SM62-0YA5
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
1 6ES7 652-0XD17-2YB5
1 6ES7 658-1CX17-2YA5
1 6ES7 658-1FX17-2YA5
1 6ES7 658-1DX17-2YB5
1
1
1
1)
4)
2)
6ES7 660-0DE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BC17-2YA0
2
2
2
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
8)
3)
9)
1)
4)
2)
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
6ES7 652-0XX01-1XF0
6ES7 658-2CX17-0YA5
2 6ES7 833-1SM62-0YA5
2 6ES7 652-0XD17-2YB5
2)
Terminal Bus
2
10
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
5)
209/236
Safety System
Product Number
32201963
Product Description
Notes
5)
Optional
Required
Plant Bus
2
10
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8EN33-1EB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
5)
6)
7)
8)
9)
09.08.11
210/236
Connectivity
17
32201963
Connectivity
For high performance and large applications OpenPCS 7 runs on its own dedicated
computer, providing access to all data available on multiple redundant SIMATIC
PCS 7 Operator System Server and Central Archive Server systems.
V 2.2
09.08.11
211/236
Connectivity
17.1
32201963
Figure 17-1
Plant Bus
V 2.2
09.08.11
212/236
Connectivity
32201963
Product Number
Product Description
Notes
Optional
Required
Table 17-1
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
5)
1)
6ES7 650-0NG07-0YX0
6ES7 648-0CB00-0YA0
2
2
2
6ES7 658-2CX07-0YA5
6ES7 652-0XD07-2YB5
6ES7 660-0EA02-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
A5E00504378
6ES7 658-0HX17-2YB0
6)
Terminal Bus
1
5
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
Plant Bus
1
4
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
213/236
Connectivity
Product Number
32201963
Product Description
Notes
Optional
Required
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
2)
3)
4)
5)
6)
Firewall applications between Terminal Bus and Perimeter Network and between
Perimeter Network and Enterprise Network are not listed but required
Network components for Perimeter Network and Enterprise Network connection
have not been listed
V 2.2
09.08.11
214/236
Connectivity
17.2
32201963
Figure 17-2
Plant Bus
V 2.2
09.08.11
215/236
Connectivity
32201963
Product Number
Product Description
Notes
Optional
Required
Table 17-2
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
5)
1)
6ES7 660-0EA02-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2CX17-0YA5
1 6ES7 652-0XD17-2YB5
6ES7 660-0EA02-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
1
A5E00504378
6ES7 658-2CX17-0YA5
6ES7 658-0GX17-2YB0
1 6ES7 652-0XD17-2YB5
6)
Terminal Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
2)
Plant Bus
1
3
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
216/236
Connectivity
Product Number
32201963
Product Description
Notes
Optional
Required
Automation System
1
6ES7 654-8CJ10-3BB0
3
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
1)
2)
3)
4)
5)
6)
Firewall applications between Terminal Bus and Perimeter Network and between
Perimeter Network and Enterprise Network are not listed but required
Network components for Perimeter Network and Enterprise Network connection
have not been listed
V 2.2
09.08.11
217/236
Connectivity
17.3
32201963
Figure 17-3
Plant Bus
V 2.2
09.08.11
218/236
Connectivity
32201963
Product Number
Product Description
Notes
Optional
Required
Table 17-3
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 658-5AF17-0YA5
1
1
1
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1
1
1
1
1)
4)
2)
6ES7 660-0DE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BD17-2YA0
2
2
2
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
9)
3)
11)
1)
4)
3)
6ES7 660-0CE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 658-2FA17-0YB0
2
2
6ES7 652-0XX01-1XF0
6ES7 660-0CE13-2BA0
V 2.2
09.08.11
219/236
Connectivity
Product Number
32201963
Product Description
Notes
Optional
Required
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
6ES7 652-0XX01-1XF0
6ES7 658-2CX17-0YA5
2 6ES7 652-0XD17-2YB5
2)
6ES7 660-0EA02-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
1
1
6ES7 652-0XX01-1XF0
A5E00504378
6ES7 658-0HX17-2YB0
2)
10)
Terminal Bus
2
18
6GK5 216-0BA00-2AA3
6XV1 870-3QH60
5)
5)
Plant Bus
2
10
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
1
6ES7 656-8CM33-1CB0
3
2
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
220/236
Connectivity
NOTE
32201963
1)
2)
3)
4)
5)
6)
7)
8)
9)
10)
11)
Firewall applications between Terminal Bus and Perimeter Network and between
Perimeter Network and Enterprise Network are not listed but required
Network components for Perimeter Network and Enterprise Network connection
have not been listed
V 2.2
09.08.11
221/236
AS-OS PO Count
18
32201963
AS-OS PO Count
Table 18-1
Technological Function
I/O
Analog Monitoring
MEAS_MON
1 AI
Digital Status
DIG_MON
1 DI
PID Control
CTRL_PID
1 AI, 1 AO
Motor
MOTOR
1 DI, 1 DO
Valve
VALVE
2 DI, 1 DO
V 2.2
09.08.11
222/236
AS-OS PO Count
32201963
Systems consisting of multiple Operator System Servers allow distribution of Process Objects across multiple Servers. When multiple Engineering Systems are deployed, SIMATIC PCS 7 requires the Automation System Process Objects to be licensed only once.
V 2.2
09.08.11
223/236
AS-OS PO Count
18.1
32201963
Figure 18-1
V 2.2
09.08.11
224/236
AS-OS PO Count
32201963
Product Number
Product Description
Notes
Optional
Required
Table 18-2
6ES7 650-4AA00-0AA0
6ES7 648-0CB00-0YA0
1
1 6ES7 652-0XD17-2YB5
1)
1)
Please use the PCS 7 BOX configurator, because the PCS 7 BOX is available
in different configurations, e. g. DC 24 V or AC 110/230 V.
NOTE
V 2.2
09.08.11
225/236
AS-OS PO Count
18.2
32201963
Figure 18-2
Plant Bus
V 2.2
09.08.11
226/236
AS-OS PO Count
32201963
Product Number
Product Description
Notes
Optional
Required
Table 18-3
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AB17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
Plant Bus
1
2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
2)
3)
Automation System
1
6ES7 654-8CJ10-3BB0
NOTE
V 2.2
1)
2)
3)
09.08.11
227/236
AS-OS PO Count
18.3
32201963
Figure 18-3
Plant Bus
V 2.2
09.08.11
228/236
AS-OS PO Count
32201963
Product Number
Product Description
Notes
Optional
Required
Table 18-4
Engineering System
1
6ES7 660-0AC13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-5AF17-0YA5
1
1
1
1
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
6ES7 660-0CE13-2BA0
1
1
6ES7 648-0CB00-0YA0
1
6ES7 658-2BC17-0YA0
4)
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 658-2CX17-0YA5
2 6ES7 652-0XD17-2YB5
Terminal Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
1)
1)
Plant Bus
1
4
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
Automation System
2
6ES7 654-8CJ10-3BB0
2
1
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
V 2.2
09.08.11
229/236
AS-OS PO Count
2)
3)
4)
NOTE
32201963
V 2.2
09.08.11
230/236
AS-OS PO Count
18.4
32201963
Figure 18-4
Plant Bus
V 2.2
09.08.11
231/236
AS-OS PO Count
32201963
Product Number
Product Description
Notes
Optional
Required
Table 18-5
Engineering System
1
6ES7 660-0BF13-2AA0
1
1
6ES7 648-0CB00-0YA0
1
1
6ES7 658-5AF17-0YA5
1
1
1
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1
1
1
1
1)
3)
2)
6ES7 660-0DE13-2BA0
2
2
6ES7 648-0CB00-0YA0
2
6ES7 652-3BD17-2YA0
2
2
2
6GK1 162-3AA00
6GK1 716-0HB71-3AC0
6ES7 652-0XX01-1XF0
7)
8)
1)
3)
2)
6ES7 660-0EA02-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
6ES7 652-0XX01-1XF0
6ES7 658-2CX17-0YA5
2 6ES7 652-0XD17-2YB5
2)
Terminal Bus
2
10
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
4)
4)
Plant Bus
2
12
V 2.2
6GK5 208-0BA10-2AA3
6XV1 870-3QH60
09.08.11
232/236
AS-OS PO Count
Product Number
32201963
Product Description
Notes
Optional
Required
Automation System
3
6ES7 656-8CM33-1CB0
1
2
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
5)
6)
7)
8)
09.08.11
233/236
AS-OS PO Count
18.5
32201963
Figure 18-5
Plant Bus
V 2.2
09.08.11
234/236
AS-OS PO Count
32201963
Product Number
Product Description
Notes
1)
Optional
Required
Table 18-6
Engineering System
2
6ES7 660-0BF13-2AA0
2
2
6ES7 648-0CB00-0YA0
2
2
2
6GK1 716-0HB71-3AC0
6ES7 658-5AF17-0YA5
2
2
2
2
6ES7 652-0XD17-2YB5
6ES7 658-1CX17-2YA5
6ES7 658-1FX17-2YA5
6ES7 658-1DX17-2YB5
1)
6ES7 660-0DE13-2BA0
4
4
6ES7 648-0CB00-0YA0
4
4
1
6GK1 716-0HB71-3AC0
6ES7 652-3BC17-2YA0
6ES7 652-3BD17-2YA0
5)
1)
6)
6)
6ES7 660-0EA02-2AA0
3
3
6ES7 648-0CB00-0YA0
3
6ES7 658-2CX17-0YA5
3 6ES7 652-0XD17-2YB5
Terminal Bus
1
2
2
7
6GK5 414-3FC00-2AA2
6GK5 204-2BB10-2AA3
6XV1 820-5BN10
6XV1 870-3QH60
2)
2)
2)
2)
Plant Bus
1
1
2
10
V 2.2
6GK5 414-3FC00-2AA2
6GK5 204-2BB10-2AA3
6XV1 820-5BN10
6XV1 870-3QH60
09.08.11
235/236
AS-OS PO Count
Product Number
32201963
Product Description
Notes
Optional
Required
Automation System
2
6ES7 656-8CM33-1CB0
6
3
6ES7 653-2BA00-0XB5
6ES7 653-2BB00-0XB5
NOTE
V 2.2
1)
2)
3)
4)
5)
6)
09.08.11
236/236