Professional Documents
Culture Documents
qo ^ k pcl o j bo p
Electrical Transformer An ISO 9001:2008 Certified Company. Mfr. Quality Electrical Transformer www.reconsindia.com/Enquire_Now
Impulse voltage Test Impulse voltage generator Impulse voltage test systme www.shkaroth.com
Power distribution units Rackmount intelligent PDUs. power management solutions. www.servertech.co.in
Transformer Winding Resistance tester. Automatic - 10 / 20 / 40 Amps www.udeyraj.com
TRANSFORMERS
Power Transformers-Indian
Standards
OBJECTIVE
QUESTIONS
TYPE
HOME takes you to the start page after you have read these Topics. Start page has links to other topics.
MENU-DRIVEN GRAPHICAL USER INTERFACE (GUI) PROGRAMS- by Prof. H. Sadat. -The transformer program obtains the
transformer equivalent circuit from open-circuit and short-circuit tests. It also finds the transformer performance characteristics using the
transformer parameters. In the induction motor program the parameters of the equivalent circuit can be entered on the circuit diagram.
The program draws the Thevenin's equivalent circuit. Performance characteristics are then obtained for the specified slip and the torque slip
curve is plotted on the screen. The analysis can be repeated for different slips. A GUI program deals with the design of a first-order
controller in the forward path of a closed-loop control system. This GUI program designs the following controllers: Proportional, phaseClose Ad
lag, phase-lead, PD,PI, and PID controllers. To run the controller design program at the MATLABprompt type>> rldesigngui
TRANSFORMERS -OBJECTIVE TYPE QUESTIONS
1. For a delta-star 3-phase transformer the primary winding has N1 turns/phase and a secondary has N2 turns /phase. The single-phase equivalent circuit will have a
turns ratio
a. N1/N2
b. N1/ 3/N2
c. N1/N2/ 3
Ans: (b)
2.
a) dc shunt motor
b) transformer
c) induction motor
d) synchronous motor
Ans. b
TOP
Power Transformers [ISD: 2026 (Part 1)-1977]
TYPE TESTS
S. No.
1
2
Type test
Measurement of winding resistance
Measurement of voltage ratio and check of
voltage vector relationship
~K K L SK
Purpose
To know resistance of winding utilized
To know correct voltage ratio at each tap and to check
vector symbol (To ascertain phase displacement)
NLP
NLNVLNP
qo ^ k pcl o j bo p
3
4
5
6
7
8
SPECIAL TESTS
S. No.
1
Special test
Dielectric test (Modified impulse test on Neutral
2
3
Purpose
To verify impulse voltage withstand capacity of
insulation (Neutral terminal to earth & other winding)
To check zero sequence impedance of 3-phase
transformers
To ensure mechanical strength under short circuit
condition
To measure sound level produced by transformer
during rated excitation under no-load condition
To measure harmonics of the no-load current
To know power consumption of fans & oil pumps
ROUTINE TESTS
S. No.
Routine test
Purpose
Type Tests 1,2,3,4,5,6, and 9 will also be the Routine Tests. In addition, the following Dielectric tests will be
performed as a Routine test
Dielectric Tests
Separate AC source
To verify power frequency withstand capacity
Induced over voltage
of winding (winding to other winding and to
earth)
To verify power frequency withstand capacity
of winding (phases to earth and other winding)
ACCEPTANCE TESTS
The routine tests on each transformer are to be considered as acceptance tests
SAMPLE CRITERIA: Each power transformer to be tested
TOP
Insulating Oils- Indian & IEC standards
S. No.
Property
0.89 at 270 C
Appearance
Density
g/cm3
Kinematic viscosity at
27 cSt
16.5 cSt
at 270 C
at 40 0 C
at 40 0 C
270 Max.
Interfacial tension Min.
Flash point
Pansky-Marten (closed)
1400 C
1400 C
1400 C
~K K L SK
OLP
NLNVLNP
qo ^ k pcl o j bo p
10
Min
Pour point
Max.
Neutralization value
Total acidity
Max.
Inorganic
acidity/alkalinity
Corrosive sulpher
Electric Strength
(Breakdown voltage)
Min.
New unfiltered oil
After filtration
Dielectric dissipation
11
6
7
8
9
12
At 900 Min.
At 27 0 Min.
Oxidation stability
Neutralization
value after
oxidation Max.
Total sludge
after oxidation
Max.
-90 C
-300 C
-300 C
0.03mg
KOH/g
Nil
0.03mg
KOH/g
Nil
0.03mg
KOH/g
Nil
Non-corrosive
Non-corrosive
Non-corrosive
30 kV (RMS)
50 kV (RMS)
0.005
30 kV (RMS)
50 kV (RMS)
0.005
30 kV (RMS)
50 kV (RMS)
0.005
0.40 mg
KOH/g
0.40 mg
KOH/g
No limit
0.10% by weight
0.10% by weight
SAMPLING CRITERIA
As per IS:6855-1973 OR relevant specification of equipment where oil is required.
Electrical Transformer An ISO 9001:2008 Certified Company. Mfr. Quality Electrical Transformer www.reconsindia.com/Enquire_Now
Impulse voltage Test Impulse voltage generator Impulse voltage test systme www.shkaroth.com
vacuum circuit breaker Air type Vacuum type www.Panickker.com/vcb.htm
Coil Winding Machine For small transformers and coils At very low cost in india www.namanenterprises.net
~K K L SK
PLP