Medium Voltage Switchgear (1) Basics of

Switching Devices
Posted F E B 11 2013 by E MM AN OU IL A NG E L A DAS in EN E R GY A ND P OW E R , ME DI UM VO LTAG E with 5
C OM ME NT S

Medium Voltage Switchgear (1) Basics of Switching Devices

Introduction to Medium Voltage


According to international rules, there are only two voltage levels:
1. Low voltage: up to and including 1kV AC (or 1,500V DC).
2. High voltage: above 1kV AC (or 1,500V DC).
Most electrical appliances used in household, commercial and industrial applications
work with low voltage. High voltage is used not only to transmit electrical energy over

very large distances, but also for regional distribution to the load centers via fine
branches.
However, because different high voltage levels are used for transmission and
regional distribution, and because the tasks and requirements of the switchgear and
substations are also very different, the term medium voltage has come to be used
for the voltages required for regional power distribution that are part of the high voltage
range from 1kV AC up to and including 52kV AC.
Most operating voltages in medium voltage systems are in the 3kV AC to 40.5kV
AC range.
The electrical transmission and distribution systems not only connect power
stations and electricity consumers, but also, with their meshed systems, form a
supraregional backbone with reserves for reliable supply and for the compensation of
load differences.
High operating voltages (and therefore low currents) are preferred for power
transmission in order to minimize losses. The voltage is not transformed to the usual
values of the low voltage system until it reaches the load centers close to the
consumer.
In public power supplies, the majority of medium voltage systems are operated in
the 10kV to30kV range (operating voltage). The values vary greatly from country to
country, depending on the historical development of technology and the local
conditions.

1. Medium voltage equipment


Apart from the public supply, there are still other voltages fulfilling the needs of
consumers in industrial plants with medium voltage systems; in most cases, the
operating voltages of the motors installed are decisive.
Operating voltages between 3kV and 15kV are frequently found in industrial supply
systems.
In power supply and distribution systems, medium voltage equipment is
available in:

1. Power stations, for generators and station supply systems.


2. Transformer substations of the primary distribution level (public supply
system or systems of large industrial companies), in which power supplied from
the high voltage system is transformed to medium voltage.
3. Local supply, transformer or customer transfer substations for large
consumers (secondary distribution level), in which the power is transformed from
medium to low voltage and distributed to the consumer.

Power distribution network scheme

2. Basics of Switching Devices

Switching devices are devices used to close (make) or open (break) electrical
circuits.
The following stress can occur during making and breaking:

No-load switching
Breaking of operating currents
Breaking of short circuit currents

What can the different switching devices do?


Circuit breakers:
Make and break all currents within the scope of their ratings, from small inductive
and capacitive load currents up to the full short circuit current, and this under all fault
conditions in the power supply system, such as earth faults, phase opposition, and so
on.

Switches:
Switch currents up to their rated normal current and make on existing short circuits
(up to their rated short circuit making current).

Disconnectors (isolators):
Used for no-load closing and opening operation. Their function is to isolate
downstream devices so they can be worked on.

Three-position disconnectors:
Combine the functions of disconnecting and earthing in one device. Three-position
disconnectors are typical for GIS Gas insulated switchgear.

Switch disconnectors (load break switches):


The combination of a switch and a disconnector, or a switch with isolating distance.

Contactors:
Load breaking devices with a limited short circuit making or breaking capacity.
They are used for high switching rates.

Earthing switches:
To earth isolated circuits.

Make-proof earthing switches (earthing switches with


making capacity):
Are used for the safe earthing of circuits, even if voltage is present, that is, also in
the event that the circuit to be earthed was accidentally not isolated.

Fuses:
Consist of a fuse base and a fuse link. With the fuse base, an isolating distance can
be established when the fuse link is pulled out in de-energized condition (like in a
disconnector). The fuse link is used for one single breaking of a short circuit current.

Surge arresters:
To discharge loads caused by lightning strikes (external overvoltages) or switching
operations and earth faults (internal overvoltages). They protect the connected
equipment against impermissibly high voltages.
Will be continued very soon
References: SIEMENS Power Engineerind Guide Switchgear and Substations