Isolated Phase Bus

Generator Leads with current ratings from 6 kA up


F toor Main
50 kA, Isolated Phase Bus is the solution. Isolated Phase

Bus systems are used exclusively for Main Generator Leads


where minimal external electro-magnetic fields and
maximum phase to phase fault protection is required.
TECHNIBUS offers a complete line of Isolated Phase Bus
systems for those situations calling for high currents with
maximum integrity. TECHNIBUS can provide continuous
current ratings from 1,200A up to 50,000A with short circuit
ratings up to 900,000A.

Conductor

(A)

he conductor consists of high conductivity, conductor


T grade
aluminum.
Depending upon the diameter

required, extruded tubes or tubes rolled of plate metal are


used. The tubes shape permits exact calculation of current
displacement and heat dissipation as well as the short circuit
forces.
Aluminum expansion elements with welded
connections allow for thermal expansion of the conductor.
Maintenance is not required.

Enclosure (B)
nclosures are also made of high conductivity, conductor grade aluminum. The enclosures are
E manufactured
from rolled sheet or plate of variable diameters and wall thicknesses and are welded

together by using the inert-gas-shielded-arc process. The enclosure is self-supporting up to a length of


approximately 65 feet, allowing a free choice of the fixed points. Expansion joints in the form of
aluminum bellows provided at the terminations permit thermal expansion.

Post Insulators (C)


resin post insulators support the conductor and are arranged in the enclosure so as to ensure the
Cast
proper clearance in air between the conductor and earthed enclosure. A sliding surface provided
at the post insulator head permits relative movements between enclosure and conductor in an axial
direction. One insulator of each support system is equipped with an adjustable spring-type element for
compensating any variance in tube diameters during mounting as well as any conductor movements
caused by a short-circuit.

Conductor

Enclosure

Post
Insulator

Please contact your local sales representative to request our complete Isolated Phase brochure.
1501 Raff Road SW Canton, OH 44710

http://www.technibus.com

sales@technibus.com

330-478-6395

TECHNIBUS IPB DESIGN PLAN (65C RISE/40C AMBIENT, 60HZ)


Rated
Voltage

Rated
Current

15KV - 24KV
110/125 KV
BIL
50/60 KV HiPot

23KV - 27 KV
150 KV BIL
80 KV Hi-Pot

3000
6000
8000
9000
10000
11000
12000
14000
16000
17000
20000
22000
24000
26000
30000
32000

(D1) Cond (D2) Encl


Dia (in.)
Dia (in.)

(A) Phs
Spc (in)

4.00
7.50

21.63
25.25

26.75
29.00

11.00

28.75

31.50

14.50

32.25

36.00

18.00

35.75

41.50

21.50
25.25
28.75
32.25
35.75
39.38

39.38
42.75
46.50
50.00
53.50
57.00

47.63
51.50
59.00
63.00
67.00
71.00

39.38

67.75

82.75

Watts
Wt./3-Phs
Loss
per
FT.
3-Phs Ft.

Capacitance Inductance Pico-Farads


Henries per
per Ft./Phase
Ft/Phase

112
115
139
164
163
182
215
263
302
304
387
421
456
544
626

160
392
528
584
694
758
698
741
838
946
1090
1198
1306
1294
1397

10.1
14.1
17.8
17.8
21.4
21.4
25.1
25.2
28.6
32.9
36.0
39.50
43.00
47.50
31.90

0.100
0.074
0.058
0.058
0.048
0.048
0.041
0.041
0.036
0.032
0.029
0.026
0.024
0.022
0.033

670

1476

31.90

0.033

Table for dimensions and locating distances


All dimension sizes are in inches

Typical Isolated Phase Bus configuration.