ABSTRACT
CFD study is performed to understand the Physics of Airflow inside a Hussmann refrigeration system and to check how the gap
between coil and wall is impacting the air flow distribution on the condensing coil. CFD is beneficial in achieving accurate results and
reduce cycle time of conventional Lab testing. This was done by using HyperMesh to build mathematical model and AcuSolve to
simulate the Lab conditions. Hussmann Proto-Aire refrigeration system is an outdoor, air-cooled refrigeration system based on the
Protocol (refrigeration system) concept. It uses multiplexed scroll compressors and is available in a variety of configurations that can
be tailored to specific installations. This system also has a condenser with FAN which throws out the heat from condenser coil.
These are located on the roof top or outside the buildings.
While performing CFD on newly designed Hussmann Proto-Aire refrigeration system it is found that the air flow
distribution over the condensing coils is not uniform. Then we started investigation using AcuSolve CFD solver. CFD study leads us
to redesign the airflow path, for which a prototype was built and tested in Lab. The result from Test lab and Simulation from
AcuSolve have been correlated very well.
Introduction:
Supermarket refrigeration system are a parallel system, often referred to as a distributed
system, is a multiple compressor refrigeration unit piped in parallel to yield smooth capacity control as
compared to a single compressor unit. A parallel system can be located in a back room or on a roof in
close proximity to refrigeration equipment for reduced piping.
Supermarkets are one of the most energy-intensive types of commercial buildings. Significant
electrical energy is used to maintain chilled and frozen food in both product display cases and walk-in
storage coolers. Supermarkets have a wide range of sizes. In North America, store sizes vary from
roughly 2,000 to 11,000 square meters. A typical supermarket consumes roughly 2 million kWh annually,
and roughly half is for refrigeration. Thus, improvement in energy efficiency of supermarket refrigeration
will affect the stores bottom line of profit margin. The most commonly used refrigeration system for
supermarkets today is the parallel rack direct expansion system using a HFC refrigerant such as R404A.
Figure 1 shows a diagram of a typical parallel rack system. Multiple compressors operating at the same
saturated suction temperature (SST) are mounted on a skid, or rack, and are piped with common suction
and discharge refrigeration lines. Using multiple compressors in parallel provides a means of capacity
control, since compressors can be turned on and off to meet refrigeration load. All display cases and cold
1
Simulate to Innovate
store rooms use direct expansion (DX) air-refrigerant evaporator coils that are connected to compressor
racks in a remote machine room typically located in the back or on the roof of the store. Heat rejection is
usually done with air-cooled condensers because these are least costly to install and maintain. A typical
supermarket requires 1400 to 2300 kg of refrigerant
A wide range of compressors is available, including digital scrolls, to better match capacity and
budget needs while providing the most energy efficient and environmentally friendly system. Parallel
units, matched to an appropriate condenser, may be modular allowing you to add or change compressors
as needed. The standard rack housing and frame is made of durable galvanized steel with other materials
as an option.
2
Simulate to Innovate
Process Methodology:
As the PROTOAIRE unit is symmetrical, one fan section was considered for the CFD simulation.
Fig 1 shows the preliminary design of the PROTOAIRE. Fig 2 shows one fan section considered for
performing CFD simulation. This model has coil, fan motor assembly and air flow path. Before starting this
project its necessary to confirm whether given fan and condenser coil geometry is correct or not. To
confirm that, numerical investigation on fan and condenser coil was performed and compared with test
lab results. If the numerical results are promising and matches with manual test lab results then only
these components can used for performing this project.
Numerical investigation on given Fan:
Given Fan CAD model was placed in the virtual wind tunnel and performed simulation to check numerical
fan performance.
3
Simulate to Innovate
For the given rpm mass flow rate predicted from CFD = 2.8 m3/s.
For the same rpm volume flow rate mesured from test lab = 4958 CFM.
Simple calculation to cross check
Known volume flow rate = 4958 CFM (from test lab) = 2.34 m3 /s
so Mass flow rate = 2.34 m3 /s X 1.225 kg/ m3 (density of air)
Mass flow rate = 2.87 kg/s (from calculation)
Hence this shows that the actual and simulation results are matching and confirms given fan geometry is
right.
Numerical investigation on given condenser coil:
Condenser coil is placed inside the wind tunnel (Figure6) to check the pressure drop at given mass flow
rate.
Using the above curve fitting equation (Figure7) CDarcy and CForch values are calculated and used as
inputs in porous media modeling. As fan is delivering 2.8 kg/s mass flow same value is used as input and
performed CFD simulation. CFD predicted 98N/m2 as pressure drop across the coil and the pressure drop
measured in test lab is 0.394 in-w g, after converting, the test lab pressure drop is 98.141N/m2. CFD and
test lab results are very well correlated. From these investigations it proves that the given fan and
condenser coil data are correct and this information can be used for future CFD simulations.
4
Simulate to Innovate
Grid development:
Altair HyperMesh used for surface mesh and then that surface mesh was imported in AcuConsole to
generate solid tet. The dimensions of computations space is shown in figure 8. To capture boundary layer
phenomena accurately, 5 layers were generated on all surfaces with first layer height as 0.1 mm and
growth rate as 1.3. Fine and irregular grid at extended air domain was used for accurate commutation.
Total mesh size was 9.8 Mn. tetrahedral elements.
Boundary condition:
Condenser coil is modeled as porous media and fan is rotating at given rpm. Reference frame is created
for the given rpm and the reference frame is assigned to fan surface. Air entry side bottom wall is
considered as wall because air cannot enter from bottom, other all four surfaces are considered as inlet
so that the air can enter freely. Air exit top surface is considered outlet.
5
Simulate to Innovate
Numerical methodology:
In this work, the Navier-Stokes equations were solved using AcuSolve, a commercially available flow
solver based on the Galerkin/Least-Squares (GLS) finite element method. AcuSolve is a general purpose
CFD flow solver that is used in a wide variety of applications and industries. The flow solver provides fast
and accurate transient and steady state solutions for standard unstructured element topologies. AcuSolve
ensures local conservation for individual elements. Equal-order nodal interpolation is used for all working
variables, including pressure and turbulence equations. The resultant system of equations is solved as a
fully coupled pressure/velocity matrix system using a preconditioned iterative linear solver. The iterative
solver yields robustness and rapid convergence on large unstructured meshes even when high aspect
ratio and badly distorted elements are present.
The following forms of the Navier-Stokes equations were solved by AcuSolve to simulate the flow inside
the PROTOIRE refrigeration system:
Due to low mach number involved in these simulation, the flow was assumed to be incompressible, and
the density time derivative in Eq. (1) was set to zero. The three dimensional steady flow is simulated
using RANS single equation Spalart-Allmaras turbulence model. The turbulence equation is solved using
GLS formulation. The model equation is as follows:
6
Simulate to Innovate
For the steady state solutions presented in this work, a first order time integration approach with infinite
time step size was used to iterate the solution to convergence. Steady state convergence was typically
reached within 500 time steps.
Figure10
Figure11
Figure12
7
Simulate to Innovate
Iteration 1 (Figure10):-Added 8 volume in the cabinet to enhance the air flow distribution over the coil.
Iteration 2 (Figure11):-Added 12 volume in the cabinet to enhance air flow distribution over the coil.
Iteration 3 (Figure12):-Added full volume in the cabinet to enhance air flow distribution over the coil.
All the 3 iterations were performed with the same boundary condition and the results are plotted
below.
From the above results it clearly indicates that iteration 3 velocity distribution is uniform across the coli
inlet area.
Conclusions:
From the above CFD simulations it clearly shows that iteration 3 air flow is better than all the other design,
and the flow distribution is almost uniform across the condenser coil. The result and conclusions obtained
by the present simulation can be summarized as follows.
New PROTOAIRE design is contributing some resistance so the air flow is not uniformly
distributed across the condenser coil.
New PROTOAIRE design with 8 added volume (iteration1) is contributing some resistance so the
air flow is not uniformly distributed across the condenser coil.
New PROTOAIRE design with 12 added volume (iteration2) is looks ok in terms of air distribution
across the condenser coil compare to above 2 conditions.
New PROTOAIRE design with full length added volume (iteration3) is looks good in terms of air
distribution across the condenser coil.
Benefits Summary:
With the help of AcuSolve, Leading commercial finite element CFD code, we at HUSSMANN product
development team quickly take a decision, whether we go for existing new design or suggested iteration3
8
Simulate to Innovate
design, without doing manual test which is expensive. And it was very useful for us to do parametric study
by varying the restriction gap without spending much time as it was in physical test.
Challenges:
When we do parametric study in this project, every time when we modify restriction gap we should
generate volume mesh again and again which is time consuming. It would be useful for Acusolve users, if
automatic volume mesh updating option is there.
ACKNOWLEDGEMENTS
The authors would like to thank Mr. Kamleshwar Rajender, CFD Specialist, Altair Engineering India Pvt
Ltd. and Mr. Balakrishna, Abhijith, Lead Engineer-Modeling&Simulation, Ingersoll Rand for their valuable
support and contributions during this project.
We also would like to thank Mr. Krishna, Mudumby, General Manager, HUSSMANN Services India LLP
for allowing us to publish this paper.