You are on page 1of 8

1

SHOP
FLOOR

138.00

24.00

3312.0 35637.0

KW

820473

KW

71.0

30

135000

252

PLANT Configuration

Room Design
Relative Humidity

Selected TR

353.00

80

Room Design
Temperature

CFT

No of floors

SFT

Selected CFM

MT

Check TR

Volume

MT

No. of Occupancy

AREA

MT

lighting Load
2Watts/SFT

Area

MT

Equipment Heat
Dissipation Load

Height

Units

Width

Sl

DESCRIP
TION
(ROOM
NAME)

Length

BASIS OF DESIGN-SHOP FLOOR

360

60 TR X 6 Nos or 200
TR X 2 Nos or any
other suitable
configuration Air
cooled chiller
packages, connected
AHU's, Ducting , piping
55% +/- 5% and ancillaries

FIRST
FLOOR
(OFFICE
AREAS)

48.00

8.00

384.0

4131.0

13590

KW

KW

8.0

40

29.20

11200

232

PLANT Configuration

Room Design
Relative Humidity

Selected TR

Room Design
Temperature

CFT

No of floors

SFT

Selected CFM

MT

Check TR

MT

No. of Occupancy

Volume

MT

lighting Load
2Watts/SFT

AREA

MT

Equipment Heat
Dissipation Load

Area

Units

Height

DESCRIP
TION
(ROOM
NAME)

Width

Sl

Length

BASIS OF DESIGN-ANNEX 1st FLOOR

33

11 TR X 3 Nos Ceiling
Suspended Ductable
50% +/- 5% Split Ac's

Sr.
No.

AIR CONDITIONING SYSTEM FOR NEW BLADE SHOP-SHOP FLOOR & ANNEX
Dt.15/5/08
Description
Unit
Qty
Rate (Rs.) Total Amount(Rs)

Deviation

Pre-Qualification
for
Vendor shall be
only manufacturer or
hisbidder:
authorised dealer/distributor to participate in the tender.Certificate to
this effect is to be enclosed.
I.SHOP FLOOR:
(A) EQUIPMENT
AIR COOLED CHIILER
Supply, installation, testing and commissioning of air
cooled chilling machine with one/multi compressors
suitable motors,with refrigerant circuits, direct
expansion chiller with insulation, air cooled
condenser,thermostat, vibration isolators,integral
refrigerant copper piping, accossories, controls and
1 safety controls, starter for the condeser fans and
compressor, incoming isolating switch mounted in
control panel, all mounted on a steel base frame.
Motors shall be suitable for 415+/-10%volts, 50
cycles, 3 Ph Ac, Energy Efficient Motors EFF-1 of
IS-12615.

A
2

NEW BLADE SHOP BLDG- SHOP FLOOR


Capacity 60 TR with reciprocating semi hermetic
compressor
OR
Capacity 200 TR with screw rotory type with single or
double ckt or any other configuration of min 360
Tons.
TOTAL(CHILLERS COST)
Pumps
Chilled Water pumps
supply, installation, testing and commissioning of
centrifugal monobloc pump setsmounted on a
common base with suitable electric motor for
circulation of water for central air-conditioning
system. All pumps shall be aligned with proper
viibration isolation. as per specifications.The pump
motor shall be suitable for 415+/- volts 50 cycles 3
Ph power supply(4 W+ 1S).Motors shall be EFF-1 of
IS-12615.
Pump performance charecterstics shall be as follows:

Nos

Nos

no's

no's

Rmt
Rmt
Rmt
Rmt
Rmt
Rmt
Rmt
Rmt

60
80
50
100
50
60
R/o
30

nos
nos

20
16

Chilled water pumps(Grundfos/kirloskar/beacon/IHP)

I)
ii)
iii)
iv)
v)
vi)
vii)
5

Type: Centrifugal-Conforming to IS Stds.


Head : 20 M
Flow rate: 130 US GPM
NEW BLADE SHOP BLDG- SHOP FLOOR
Motor HO: 7.5 HP(6W+1S)
Expansion Tank
Supply, installation, testing and commissioning of an
insulated
expansion
tank
3
mm
M.S.plate
construction.The tank shall be with fittings,overflow,
floatvalve and insulation
The size of the tank shall be as follows:
accessories 1000 X 1000x 1000
Piping
Chilled water Piping
Supply,laying, fixing ,testing and commissioning of
MS B class pipes complete with all necessary fittings
such as bends, tees, reducers, flangesand supports
duly insulated with TF quality expanded polystrene
foam of density 18 Kg/m3 , complete as per spects
and drawings with aluminium foil as vapour barrier
and cladding with 30 G GSS sheet.
150 mm dia pipe
100mm dia pipe
80 mm dia pipe
65mm dia pipe
50mm dia pipe
40mm dia pipe
32mm dia pipe
25mm dia pipe
VALVES
Supply,laying, fixing ,testing and commissioning in
position the following valves, strainers etc in chilled
water line complete with flanges etc duly insulated
with TF quality expanded polystrene foam of density
18 Kg/m3 , complete as per spects and drawings
with aluminium foil as vapour barrier and cladding
with 30 G GSS sheet.

a BUTTERFLY VALVES
I) 80 mm dia
ii) 65mm dia

2/8

Sr.
No.
iii)
iv)
v)
b
I)
ii)
iii)
c
I)
ii)
d
I)
ii)
iii)
e
6

AIR CONDITIONING SYSTEM FOR NEW BLADE SHOP-SHOP FLOOR & ANNEX
Dt.15/5/08
Description
Unit
Qty
Rate (Rs.) Total Amount(Rs)

50mm dia
40mm dia
32mm dia
Balancing valves
80 mm dia
65mm dia
50mm dia
Non- Return Valve
80mm dia
65 mm dia
Y-Strainers
80mm dia
65mm dia
50 mm dia
Air ven valve with ball valve 25 mm dia
3-WAY MODULATING VALVES FOR AHU'S
Supply, installation , testing and commissioning of 3way motorized valves with modulating motor and
proportional thermostat to maintain the inside
temperature conditions . The pipe size of the valves
are as follows:
80 mm dia
I) 65mm dia
ii) 50mm dia
7 PRESSURE GAUGES AND THEMOMETERS
prividing and fixing in positiondial type pressure
gauges with isolating GM gate valves and dial type
thermometers complete as per specifications

nos
nos
nos

16
10
12

nos
nos
nos

9
9
9

nos
nos

12
12

nos
nos
nos
nos

12
12
8
28

nos
nos
nos

6
R/o
R/o

I) Pressure gauges
ii) Temperature gauges
8 CONDENSATE DRAIN PIPES FOR AHU'S
Supply, laying, fixing , testing and commissioning of
GI B class pipes complete with all necessary fittings
such as elbows, tees,reducers, P traps etc and
supports such as clamps etc duly insulated complete
as per specifications and drawings.

no's
no's

20
20

rm
rm

30
30

Nos

I)
ii)
B
(C)

50 mm dia
40 mm dia
TOTAL(PIPING& AUXILLARIES)
AHU s

Deviation

Double Skin Floor Mounted r Air-Handling Units with


0.63 GI prepainted sheet on outer side and GI plain
sheet on inner side with 25mm thick PUF sandwiched
insulation, AHU recirculation type comprising of
supply fan section with DIDW back/forward curved
blowers, mixing box,
chilled water cooling coil
section 6/8 row deep full face area coils, Provision for
2row hot water coil, SS drain pan, drive set with
flame proof TEFC motors selected for minimum of
125 mm SP, fire retardent canvas connection, VCD,
antivibration springs for the drive set and cushy foot
mounting for the entire AHU with auxillary base
frame .

AHU system 1: 10% Fresh air induction, 24000


cfm, 7.5/10 HP with 90/100 mm static 6/8 row A/c
30 TR
10 TREATED FRESH AIR UNIT (HEAT RECOVERY
WHEEL / HEAT PIPE HEAT
EXCHANGER UNIT)
Supply, installation, testing and commissioning
double / single skin 2 tier treated fresh air units
Flexomix - 600 or Manor or Hovar / Unidyne / Zeco /
Crown or approved equavalentcomplete with energy
recovery wheel or energy in used air by heat
exchanger method to pre-cool in the incoming fresh
air so as to cut down power consumption in the
chiller in the order of 12 TR to save consumption at
fresh air related capacity induction.Generallysuitable
for summer and mansoon level air

3/8

Sr.
No.

AIR CONDITIONING SYSTEM FOR NEW BLADE SHOP-SHOP FLOOR & ANNEX
Dt.15/5/08
Description
Unit
Qty
Rate (Rs.) Total Amount(Rs)

Deviation

inputs inlet temperature at heat pipe 41.60 C and


cooled air outlet from Heat pipe Heat exchanger
(HPHE) at 33.6 C, Exhaust inlet to HPHE 27 C,
Exhaust outlet from HPHE 34 C, while fresh air
inflow is 7000 CFM,savings expected in the summer
season summer season shall be in the order of 30
KW from each Chiller set, size of the heat
exchangermay be around 101" (H) X 51" (W) X 15"
(D), size of the Exhaust duct shall be 46" x 46" and
number of rows in HPHE minimum 7 rows & number
of pipes 22 Nos., pressure drops not exceed 18mm
WC, Heat exchanger along with treated fresh air unit
shall be made as factory fabricated and factory
tested with efficiency and quality plan with performance calculations for meeting the energy saving
demand on chiller size.

Cost of Treated fresh air unit complete with supply


and exhaust blower with pre filters, drier set &cooling
coil and heat recovery wheel as a compact pre
tested,
pre
assembled
with
skid
mounting
arrangement ready to instal basis.

Nos

R/o

Sqm
Sqm
Sqm

1000.00
500.00
500.00

Sqm

162.8

Nos

240

sqm

42

Sqm

50

Sqm

R/o

c. TOTAL(AHU'S)
(D) AIR DISTRIBUTION
11 SHEET METAL DUCT :
Supplyi, fabfricating,installation, testing and
commissioning of sheet metal ducts of following
thickness including necessary supports,hangers, nut
nolts, gasket etc,complete as per specifications in
accordance with approved shop drawings as per the
specifications.
a. 24 G galvanized sheet
b. 22 G galvanized sheet
c. 20 G galvanized sheet
11 FILTER PLENUM
Supplying, fabricating, installation, testing and
commissioning of sheet metal plenum for filter
housing in 2 stages ( 5 & 10 Mocron) complete with
housing
frames,
access
doors,
supporting
a.
arrangements and including necessary hangers, nut
bolts , gasket etc. complete as per specifications in
accordance with the shop drawings.
12 FILTERS
Supply, providing and commissioning of fine filters
along with filter box and perforated sheets/ metal
guard and necessary fixing arrangemenmts
a. PLEANUM MOUNTED FINE FILTERS 10 MICRONS
(90% efficiency)
i) Size: 610 X 610 X 300(provision for mounting only)
b. PLENUM FILTERS FLANGE TYPE(AHU) - 5 MICRONS
(95% efficiency)
i) Size: 610 X 610 X 300- 2000 cfm each for AHU
13 FLEXIBLE CONNECTION
Supplying, faricating, installation of convas flexible
connection construction of fire resistant material as
per drawing specifications
14 DAMPERS:
14 VOLUME CONTROL DAMPERS FOR DUCTS
Supplying, installing, testing of GI volume control
damper within the ducts to provided with suitable
links, leversand quadrants for manual control of
volume fo air flow and for proper balancing of the air
distribution system.
14 ACTUATOR DAMPERS
Supplying, installing, testing of GI volume control
damper within the AHU rooms to be provided with
suitable links, levers and quadrants for automatic
control of volume of air flow and for proper balancing
compatible with BMS of the air distribution system at
full flow, half flow and close monitoring as required.
14 FIRE DAMPERS
4/8

Sr.
No.

AIR CONDITIONING SYSTEM FOR NEW BLADE SHOP-SHOP FLOOR & ANNEX
Dt.15/5/08
Description
Unit
Qty
Rate (Rs.) Total Amount(Rs)
Supplying, installation, testing and commissioning of
shutter type fire dampers of at least 90 minutes fire
rating as per specifications & approved shop
drawings complete with control wiring, fusible link/
solenoid operated and provision to shut off AHU
blowers when the damper closes. Dampers shall be
located in supply air ducts & return air passage(BMS
compatible)and compatible for fire safety alarm syste
signal actuator.

Sqm

25

sets

10

Anodized aluminium Grilles


16 LINEAR GRILLES
Supplying,installing and testing of Exhaust air
continous linear grilles wihtout any volume control
dampers as per shop drawings.
Anodized aluminium Continuous grilles
16 SUPPLY AIR CONTINOUS GRILLES
Supplying,installing, testing and balancing of supply
air grilles of various sizes.Each grille shall be
equipped with fixed air distribution grid, removable
key operated volume control damper and antismudge
ring where required as per approved shop drawings.

Sqm

10

Sqm

R/o

a. M.S. coated continous grilles


b. Anodized aluminium grilles
16 RETURN AIR GRIILES
Supplying, installing, testing and balancing of supply
air grilles of various sizes similar to supply air grilles
without any volume control damper as per approved
shop drawings.
a. M.S. coated diffusers
b. Anodized aluminium grilles
17 LOUVERS:
17 FRESH AIR LOUVERS:
Supplying, installing & testing of fresh air GI outlet
louvers with bird screen.
17 EXHAUST AIR LOUVERS:
Supplying, installing & testing of exhaust air GI
outlet louvers with filter section.
18 INSULATION
18 ACOUSTIC LINING(DUCTS):
Supply, installation of acoustic lining within supply air
ducts with 25 mm thick fibre glass + RP tissuge
covered with 28 G Al. Perforated sheet.

Sqm
Sqm

R/o
30

Sqm
Sqm

R/o
32

Sqm

10

Sqm

10

a. 25 mm thick acoustic lining


18 THERMAL INSULATION:

Sqm

250.00

14 FRESH AIR INLET DAMPER


Supplying, installing, testing of fresh air inlet damper
with 10 micron filter for fresh air with suitable links,
levers and quadrants for automatic control of volume
of air flow and for proper bal;acing of the air
distribution system.
15 SUPPLY/ EXHAUST AIR GRILLE:
Supplying, installatiom, testing and balancing of
supply/ exhaust air grills of various sizes. Each grill
shall be provided with individually adjustable air
distribution patterns, grid for straightning the air flow
through the collar and register and removable key
operated volume control dampers.

Deviation

5/8

AIR CONDITIONING SYSTEM FOR NEW BLADE SHOP-SHOP FLOOR & ANNEX
Dt.15/5/08
Description
Unit
Qty
Rate (Rs.) Total Amount(Rs)

Sr.
No.

Deviation

Supply, installation of external thermal insulation


ducts with laminated foil faced fibre resin bonded
glass with vapour barrier & aluminium tape ceiling
with necessary over laps as per approved shop
drawings & specifications.
a. 25 mm thick
b. 50 mm thick
190 ELECTRIC STRIP HEATER PACKAGES
Supply and installation of winter heating package and
Mansoon Dehumidification package in the pre /
reheat path as per requirement.

Sqm
Sqm

300
100.00

19 Suitable for ALL AHU'S.


20 HUMIDIFICATION CHAMBER
Supply, Installation,Testing and commissioning of Pan
humidifier Package each comprising of M.S/
GSSFabricated Tank,
Immerssion Type Heating
elements,Over flow / water levell controller inter
20
connected GI piping with valves, Humidistatic
controller with wiring to makeup humidity levels in 3
stages as per design requirements.

sets

6.00

sets

Sqm

350.00

Sqm

R/o

Sqm

500

c. TOTAL(AIR DISTRIBUTION)
21 MICSELLANEOUS WORKS
21 ACOUSTIC LINING(AC PLANT ROOM):
Supply, installation of acoustic lining within supply air
ducts with 50 mm thick fibre glass + RP tissuge
covered with 28 G Al. Perforated sheet.
50 mm thick acoustic lining
22 THERMAL INSULATION:- FOR EXPOSED DUCTS
Supply, installation of external thermal insulation
ducts with thermocole slabs and covered with wire
mesh and cement plaster as per approved shop
drawings & specifications.
50 mm thick
23 R A BOXING FOR DUT COVERING
Supply, installation and fixing of RA boxing with Gypsum
boards and finishing properly and complete as per shop
drawings
24 UNDER DECK INSULATION
Providing Under deck insulation for roof ceiling with 50 mm
thick thrmocole below roof by suitable buitamen coating and
by suitable metallic wire mesh/ clamp and complete.
D TOTAL ( MISC# WORKS)
25 ELECTRIAL
25.1 MV panels for each Plant room
19 ELECTRICAL
M.V. SWITCH BOARDS FOR Air Cooled chiller system.

460
Sqm

Nos

set

20 M.V SWITCH BOARD FOR AHUS/TFAS


21 POWER WIRING
Supply, laying & clamping of 1.1 KV grad PVC insulated and PVC
sheathed Aluminium conductor armourd cable conductor
confirming to relevent IS standards of following sizes as per
requirement including glands, terminations by crimpimng the ends
with copper lugs as standartd requirement.

set

b) 50 Sq mm 4 C
c) 35 Sq mm 4 C
d) 6 Sq mm 4 C
22 CONTROL WIRING FOR AC SYSTEM
Providing necessary control wiring for various fault diagnostic
indication alarms,safety interlocks,air-start control etc using 1.1
KV grade armoured PVC insulated multicore copper conductor of
1.5 sq mm size including gland, cable terminations, gland earthing
etc .. as required.

Rmt
Rmt
Rmt

50
80
100

a) 2 C
b) 4C
c) 6 C
Supply and fixing of MS fabricated cable tray of the following
sizes of angle irons with 2 Nos MS flats of size 20 mm X 3mm at
23 an interval of 450 mm I.e suitable supports made of MS rods with
suitable hooks , necessary threading, cutting, welding , painting and
fixing bolts & nuts etc as required.

Rmt
Rmt
Rmt

80
100
20

Rmt
Rmt

220
150

a) 40 X 40 X 3 mm width 450 mm
b) 25 X 25 X 3 mm width 150 mm
24 EARTHING

6/8

Sr.
No.
I)

ii)
E

AIR CONDITIONING SYSTEM FOR NEW BLADE SHOP-SHOP FLOOR & ANNEX
Dt.15/5/08
Description
Unit
Qty
Rate (Rs.) Total Amount(Rs)

Deviation

Supply and fixing of 25 mm X 4 mm GI strip 2 Runs on surface of


wall / recess of
wall for body earthing as required
Supply & fixing of 8 SWG GI wire on surface of wall or in recess
for loop earthing of various equipments as required.

Rmt

150

Rmt

150

TOTAL(ELECTRICAL)
GRAND TOTAL(A+B+C+D+E)
II-ANNEX BLDG Ist FLOOR

A
1

EQUIPMENT
CEILING SUSPENDED DUSCTABLE AC UNITS
Supply of ceiling suspended Air Cooled package AC.s make
complete with scroll/recip compressor with all necessary
refrigerant controls ,Cooling coil of DX type having multi row
copper tubes and hydraulically bonded aluminium fins.
Evaporator blower section made of sheet galvanised steel,
statistically and dynamically balanced fan designed for quiet
operation, Motor shall be suitable for 415+ -5% volts 50
cycles, 3 phase AC supply of the following. Blower shall be
preferably direct drive without belt.

b)
c)

Cooling Capacity 11.0 TR with Recip/Scroll ( Multi Ckt)


Cooling Capacity 5.5 TR with Recip/Scroll (single Ckt)
Total

Nos
Nos

LOW SIDE WORKS


1a ITC of Ceilling suspended Ductable AC unit 11 TR
Nos
b ITC of Ceilling suspended Ductable AC unit 5.5 TR
Nos
2 Supply & top up of Refrigerant gas
Lot
Inter connected copper refrigerant piping for liquid and hard
3 gas lines
a) 1/2" dia
Rmt
b) 5/8" dia
Rmt
c) 7/8" dia
Rmt
SUB TOTAL
B AIR DISTRIBUTION
3 SHEET METAL DUCT :
Supplying,
fabricating
,
installation,
testing
and
commissioning of sheet metal ducts of following thickness
including necessary supports , hangers, nut bolts, gasket
splitter damper vanes etc. complete as per specifications in
accordance with the approved shop drawings and required
by the specifications.
a. 24 G galvanized sheet
b. 22 G galvanized sheet
3.1 PLENUM
Supply, installation, testing and commissioning of sheet
metal plenum for filter housing complete with housing
frames, access doors, supporting arrangements and
including necessary hangers, nut bolts, gasket splitter
damper vanes etc. complete as per specifications in
accordance with the approved shop drawings and as
required by the specifications.
a.
4 FLEXIBLE CONNECTION
Supplying, fabricating, installation of double canvas flexible
connection constructed of fire resistant material as per the
drawings and specifications.
5 DAMPERS:
5.1 VOLUME CONTROL DAMPERS FOR DUCTS
Supplying, installing, testing of GI volume control damper
within the ducts to be provided with suitable links, levers and
quadrants for manual control of volume of air flow and for
proper balancing of the air distribution system.
5.2 FIRE DAMPERS:
Supplying, installation, testing and commissioning of shutter
type fire dampers of at least 90 minutes fire rating as per
specifications & approved shop drawings complete with
control wiring , solenide operated / link and provision to shut
off AHU blowers when the damper closes. Dampers shall be
located in supply air ducts & return air passage.
6.1 LINEAR GRILLS:
Supplying, installing and testing of return air continuous
linear grilles without any volume control dampers and as per
shop drawings.
a. Anodized aluminium grilles
6.2 SUPPLY AIR GRILLES/DIFFUSERS
Supplying, installing, testing and balancing of supply air
diffusers/grilles of various sizes. Each diffuser shall be
equipped with fixed air distribution grid, removable keyoperated volume control damper and antismudge ring where
required as per approved shop drawings.
b.

Powder coated aluminium grilles/diffusers

3
R/O

3
R/O
1

R/O
42
42

Sqm
Sqm

170
50

Sqm

10

sets

Sqm

Sqm

R/O

Sqm

Sqm

4
7/8

AIR CONDITIONING SYSTEM FOR NEW BLADE SHOP-SHOP FLOOR & ANNEX
Dt.15/5/08
Sr.
Description
Unit
Qty
Rate (Rs.) Total Amount(Rs)
No.
6.3 RETURN AIR GRILLES/DIFFUSER
Supplying, installing, testing and balancing of supply air
diffusers of various sizes similar to supply air diffuser without
any volume control damper as per approved shop drawings.
b. Powder coated aluminium grilles/Diffusers
7 LOUVERS:
7.1 FRESH AIR LOUVERS:
Supplying, installing & testing of exhaust air GI outlet louvers
with bird screen.
8 FRESH AIR SYSTEM
Supply, installation, testing and commissioning of fresh air
arrangement complete with all accessories and supporting
arrangements .
9

Sqm

Sets

Rmt

30

Sqm

30

Sqm
Nos

70
3

Rmt
Rmt

30
30

Rmt

30

Rmt

30

CONDENSATE DRAIN PIPES FOR PAC S:

Supply, laying , fixing , testing and commissioning of PVC


pipes complete with all necessary fittings such as elbows,
tees, reducers, serviceable P traps etc and supports such as
clamps etc duly insulated complete as per specifications &
drawings.
i) 40 mm dia
c. INSULATION
10.1 ACOUSTIC LINING(DUCTS):
Supply, installation of acoustic lining within Supply air ducts
with 25mm thick Fibre glass + R.P. Tissue covered with 28G
Aluminium Perforated sheet
a. 25 mm thick acoustic lining
10.2 THERMAL INSULATION:
Supply, installation external thermal insulation of ducts with
factory laminated foil faced Fibre resin bonded glass with
vapour barrier & aluminium tape ceiling with necessary over
laps as per approved drawings and specifications
a. 25 mm thick
11 Condenser Supports
C ELECTRICAL
CABLES:
12 CONTROL CABLING

a)
c)

Sqm

Deviation

Supply, installation, testing and commissioning of following sizes


of PVC sheathed PVC insulated aluminium/ copper conductor
armoured cables of 1.1 KV grade inter connected between
Outndoor and Indoor units.
3 C x 2.5 sqmm
4 C x 1.5 sqmm
Supply and fixing of MS fabricated cable tray of the following
sizes of angle irons with 2 Nos MS flats of size 20 mm X 3mm at
an interval of 450 mm I.e suitable supports made of MS rods with
suitable hooks , necessary threading, cutting, welding , painting and
fixing bolts & nuts etc as required.
b) 25 X 25 X 3 mm width 150 mm
EARTHING
Supply and fixing of 25 mm X 4 mm GI strip 2 Runs on surface of
wall / recess of
wall for body earthing as required
Supply & fixing of 8 SWG GI wire on surface of wall or in recess
for loop earthing of various equipments as required.
SUB TOTAL
TOTAL (SUB TOTAL 1 &2)
GRAND TOTAL (SHOP FLOOR and ANNEX 1St FLOOR)

Prove Out of the system to the parameters given in "Basis of


Design" is must for payment.
Payment for "Lowside Works" shall be on actual
measurements only.

8/8