You are on page 1of 24

INSTRUCTION MANUAL

Electronic Buchholz Relay eBR

5COR472400 eBR REV01

II

CONTENT:
1

SAFETY

1.1
1.2
1.3

Safety instructions
Specified applications
Safety notes on the equipment operation

ELECTRONIC BUCHHOLZ RELAY TYPE eBR

2.1

Drawing

2.1.1

eBR 80

2.2

Operating principle

2.2.1
2.2.2

Adding features
Construction

3
3

2.3

Technical features

2.4

Test

INSTALLATION

ELECTRICAL CONNECTION

FUNCTIONAL TEST

1
1
1
2

5.1

Mechanical testing by test keys

5.1.1
5.1.2

Volume alarm verification


Trip verification

9
9

5.2

Pneumatic testing by pneumatic valve

10

WHAT TO DO IN THE CASE OF GAS ACCUMULATION

10

OPERATION AND MAINTENANCE

11

7.1
7.2
7.3

Operation
Maintenance
Movement, transport and storage

11
11
11

APPENDIX A MODBUS (RTU) REGISTERS

A.1
A.2

Addressing
Registers Tables

12
13

A.2.1
A.2.2

Main registers Table


Memory registers

13
13

A.3

Register Description

14

A.3.1

Main registers Descriptions

14

APPENDIX B PETCOCK

B.1

Connection

15

B.2

Contact Technical Data

15

APPENDIX C GAS SAMPLING DEVICE

C.1

Drawing

16

C.2

Construction

16

APPENDIX D Order sheet

17

APPENDIX E Figure and reference numbers key

18

1. SAFETY
1.1 Safety instructions
Make sure that any personnel installing and operating the electronic Buchholz relay:
Are technically qualified and competent
Fully comply with these assembling instructions
Improper operations or misuse could cause danger to:
Life and limb
To the equipm ent and other assets of the operator
To the proper function of the equipment
Safety instructions in this manual are shown in three different forms to emphasize important information.

WARNING
This information indicates particular danger to life and health. Disregarding such a warning can lead to
serious or fatal injury.

CAUTION
This information indicates particular danger to equipment and/or other property of the user. Serious or fatal
injury cannot be excluded.

NOTE
This note gives important and specific information concerning the equipment.

1.2 Specified applications


The Buchholz Relay is used to protect the transformer when a malfunction occurs (high eddy current, local overheating or partial
discharges) inside the main tank
It is important to observe the limit values indicated on the nameplate and in the operating instruction before commissioning the device.

1.3 Safety notes on the equipment operation


Electrical installation is subject to the relevant national safety rules.
It is mandatory to connect the grounding cable.

CAUTION
Installation, electrical connection and fitting the device may only be performed by qualified personnel and
only in accordance with this instruction manual.
It is the responsibility of the user to ensure that the device is used for specified application only.
For safety reasons, please avoid any unauthorized and improper usage.

WARNING
All relevant fire protection regulations must be strictly followed.

2. ELECTRONIC BUCHHOLZ RELAY TYPE eBR


2.1 Drawing
2.1.1 eBR 80
General dimensions for the electronic Buchholz Relay type eBR80

9
10

10

Fig. A

Fig. C

Fig. B

2.2 General information and operating principle


The generation of gas in an oil filled transformer is a clear indication of a problem. The gas may be a result of the following:
Decomposition/degradation either of solid or liquid insulation inside the transformer due to overheating, or arcing.
From external environment through bad pipeline sealing
From the oil itself due to unsatisfactory de-gassing operations prior filling transformer main tank
Fast and sudden oil movem ent in the pipeline towards the oil conservator is caused by an internal arc, short circuit, or hot spot which
must be correctly addressed.
Oil leaks from the transformer are environmentally unacceptable and a fire hazard will lead to transformer failure.
The Buchholz relay is located in the pipework between the transformer and its conservator and it is filled with oil during normal
transformer operation. When gas is generated in the transformer it rises towards the conservator and collects in the upper chamber of
the relay.
The oil level drops and the top float triggers alarm switch (oil level between 200 to 300 ml).
Gas shall not freely pass from the relay body and escape into the pipework before the alarm contact has operated.
The trip contact shall operate at a steady oil flow. This operation shall not be adversely affected when the alarm contact has already
closed and gas is escaping freely.
In the event of an oil leak the Buchholz relay will only operate after the conservator has exhausted all of its oil.

2.2.1 Adding features


COMEM's proven expertise led to develop a new eBR Electronic Buchholz Relay that noticeably improves the performances, reliability
and safety of your transformer thanks to advanced monitoring features.
The reed based standard electro-mechanical features, an electronic transducer and a dedicated PCB allow you to constantly monitor
the gas accumulation in the Buchholz relay by 4-20mA analog output or MODBUS RTU protocol.
The double flow vanes ensure the detection of two thresholds of oil flow speed. In particular, an alarm and a trip signal are
independently generated at two different values of oil flow (e.g. alarm at 1.5m/s and trip at 3m/s).
A based on the use of dedicated reed contacts for the detection of the oil flow thresholds provides the possibility to immediately and
remotely identify the trip causes (oil flow or oil leakage/gas accumulation) by means of 4-20mA analog output or MODBUS RTU
protocol.
As option there is the possibility to remotely control an electrical contact on the PCB in such a way to command the opening of valve for
the gas discharge.

2.2.2 Construction

eBR Electronic Buchholz Relay is built on a robust foundation which consists of a die casting aluminum main body with two tempered
glass inspection windows (1/A) with graduated scale markings (cubic centimeters) that indicates the oil volume passing through the
relay. The oil drain plug is located at the bottom of the main body (2/A).
The top cover holds the frame which contains the moving parts of the eBR: two floats (3/B) and their associated switch reeds and
magnets, two calibrated flow valves (4/B).
Also:

A gas discharge valve with G1/8 in male thread with protective cap (5/C)
A valve for pneumatically testing the alarm and insulation circuits, with protective cap (6/C)
A push rod for volume alarm mechanical verification of the reed switch with protective cap (7/C)
A push rod for trip mechanical verification of the reed switch with protective cap (8/C)
A terminal box (9/A)

2.3 Technical features


Material

All the external parts are resistant to transformer oils, salt fog and UV rays.

Color

White RAL 9002(1)

Ambient temperature

-40C +80C

Degree of protection

IP65 according to EN60529

Oil temperature

-40C115C

Weight

6,5 Kg

Ventilation valve

1, to prevent the formation of condensation

Cable gland

n2 x M25x1.5

Terminal box

Screw terminal 2.5mm

Wires

Max 2.5mm advised 4x1mm o 6x1mm shielded twisted pair cable for analog/digital
output

Oil flow speed (m/s)

Alarm

Trip

1.0

1.0

1.5

1.0/1.5

2.0

1.0/1.5/2.0

2.5

1.0/1.5/2.0/2.5

3.0

Electronic board features


Power supply (terminals 1-2)

24 Vdc 10% polarized

Power consumption

0,5 W

Analog output (terminals 41-42)

420 mA (dielectric strength between electronic card and analog output:1kV)


Minimum / Maximum resistance: 100 / 470

Distance for analog output

~ 200m

Digital output (terminals 3-4)

Serial RS485 (for more information contact COMEM assistance dept.)

Distance for digital output

~ 500m

Switch electrical data


(according to EN50126-1/2)
Breaking capacity

Dielectric strength of contacts


Between circuits and earth
Between contacts in open positions

(3)

Voltage

Current

Breaking capacity

24 d.c. to 220 V d.c.

2 A for 1000 maneuvers

250 W

L/R<40 ms

230 V a.c.

2 A for 1000 maneuvers

400 VA

cos >0.5

Short duration power frequency


withstand voltage 1 min kV (r.m.s.)
2
(2)

Lightning impulse withstand voltage


kV (peak)
4
(2)

Table 1

(1)

For critical environmental conditions please contact COMEM


This test cannot be performed between the flow vanes contacts in open position in case they are connected to the electronic board
(3)
In case the flow vanes contacts are connected to the electronic board (see order sheet in the appendix D, line Flow vane contacts
status verification via Modbus selected YES), the available voltages are:
24-48 V a.c/d.c.
110-220 V a.c./d.c.
(2)

2.4 Tests

Description

Reference standard

Description

Reference standard

Fast transient/burs immunity test

IEC 61 000-4-4

Immunity test

IEC 61 000-6-2

Conducted disturbances

IEC 61 000-4-6

Emission standard

IEC 61 000-6-4

Electrostatic discharge

IEC 61 000-4-2

IP degree - IP 65

CEI EN 60259

Power-frequency magnetic field

IEC 61 000-4-8

Vibration Test

IEC 60068-3-3

Surge immunity test

IEC 61 000-4-5

Vibration Test

CEI EN 60721-3-4
(Class 4M4)

Harmonic current emission

IEC 61 000-3-2

Low temperature

IEC 60068-2-1

Voltage fluctuations and flicker

IEC 61 000-3-3

Dry heat

IEC 60068-2-2

Magnetic field immunity test

IEC 61 000-4-3

Damp heat, cyclic

IEC 60068-2-30

Supply variation

IEC 61 000-4-11

Damp heat, constant

IEC 60068-2-78
Table 2

3. Installation

CAUTION
The operating and installation requirements described in this manual must be strictly followed. If not, the
device can be damaged or a malfunction may occur.

eBR Electronic Buchholz Relay (1/D) is installed in the pipe (2/D) between the transformer tank (3/D) and the oil conservator (4/D).
Make sure that the pipe and the eBR Electronic Buchholz Relay have the same nominal diameters.

3
Fig. D
The red arrow on the cover at the top of the relay should always point towards the oil conservator.
The eBR must initially be full of oil which means that the minimum oil level of the conservator must be higher than the discharge valve
on the top of the relay (5/C).
The recommended angle of inclination of the eBR pipework should be between 0 to 5 degrees. The pipe from the transformer to the
eBR must exit the transformer at the highest point, it must be straight and the recommended length to the relay should be 10 times the
internal diameter of the pipe (L1). The distance between the eBR and the conservator should be at least 3 times the internal diameter of
the pipe (L2).
Make sure that:
eBR must initially be full of oil which means that the minimum oil level of the conservator must be higher than the discharge valve
on the top of the relay (5/C).
Gases produced in the insulating liquid can flow unimpeded to the eBR
The red arrow on the eBR points to the conservator.
The flanges are stressed evenly when tightening the screws.
The slope of the pipe to the conservator is between 0 and 5.
The position of the eBR in relation to the direction of flow does not deviate from the perpendicular by more than 5.
The pipe has no elbows, and bends are designed preferably with an inside pipe radius R > 100 mm.
The free pipe length between the eBR and the tank should be at least 10 times the internal diameter
The free pipe length between the eBR and the oil conservator should be at least 3 times the internal diameter (Should the distance
exceed the above values, a support has to be provided in the immediate vicinity of the eBR).

CAUTION
Make sure during installation that no dirt, moisture or foreign matters get into the relay.
The insulating liquid of the transformer/reactor may not contain conductive materials!

4. Electrical Connection

CAUTION
Electrical connections should only be performed by qualified and skilled personnel trained in the applicable
health and safety regulations of the relevant country.

WARNING
Dangerous electrical voltages!
It is imperative to deactivate the power supply during wiring of the device.

CAUTION
During the terminal box assembly, use caution not to damage the OR gasket. If this occurs it must be
substituted.
If you do not use all the 2 cable glands pay attention to close the free cable gland with a plug or gasket.

Multicore signal leads can be fitted in the Buchholz relay through cable glands (M25x1.5 3/E). A conductor cross section of 1.5 mm2
2
2
(copper) is recommended (4x1mm o 6x1mm shielded twisted pair cable for analog/digital output). The maximum cross section that can
be clamped is 2.5 mm2.

Proceed following the actions:


Unscrew the 5 un-losable M5 screws M5 (1/E)
Remove the cap (2/E)
Insert the lead through the cable gland (3/E)
Connect the lead to the terminal board (4/E) according to the chosen electrical scheme (tab.3-4)

(5)

Scheme

Alarm
level
(2)

NO

Alarm
Speed

Trip

Analog
output

MODBUS
RTU

Petcock
(1)
control

NO

NO

Available

Available

On demand

Available

Available

On demand

(3)

NO

NO

NC

NO

NO

Available

Available

On demand

NC

NO

NC

Available

Available

On demand

NO

NO

C.O.

Available

Available

On demand

C.O.

NO

NO

Available

Available

On demand

NC

NO

C.O

Available

Available

On demand

C.O

NO

NC

Available

Available

On demand

C.O

NO

C.O

Available

Available

On demand

NC

(4)

3
Fig. E

Table 3

Notes
(1)

See Annex B
NO: normal open contact
(3)
NC: normal closed contact
(4)
C.O.: change over contact
(5)
For other specific electrical scheme please contact COMEM
(2)

Scheme

24 VDC (+)

24 VDC (-)

RS485 (B)

RS485 (A)

4-20m A (+)

41

41

41

41

41

41

41

41

41

4-20m A (-)

42

42

42

42

42

42

42

42

42

24

24

24

24

24

24

21

21

GROUND

LEVEL
ALARM

FLOW
VANE
ALARM

21

21

21

21

22

22

22

22

22

22

22

22

22

31

31

31

31

31

31

31

31

31

32

32

32

32

32

32

32

32

32

14

14

14

14

14

14
TRIP

11
12

11
12

12

12

11

11

11

12

12

12

11
12

12

Table 4
Power supply (terminals 1-2): 24 Vdc 10% polarized
Analog output (terminals 41-42): 420 mA - Minimum / Maximum resistance: 100 / 470
Digital output (terminals 3-4): RS485

NOTE
The inner side of the electrical cap accommodates a label with the electrical schem e. The schemes show
the switching systems in their neutral position. The neutral position is the operating condition when the
Buchholz relay is filled with insulating liquid up the required level and the device to be protected operates
without any fault.

Tighten the cable gland


Fit the cap
Tighten 4 screws M5 (maximum torque 3 Nm)

5. Functional test
The test can be performed with the help of a test key (mechanically) or by a special test pump (pneumatically). Perform the test while
the eBR Electronic Buchholz Relay is filled with insulating liquid up to the required level.

5.1 Mechanical testing by test keys


5.1.1 Volume alarm verification
Proceed following the actions
Remove the higher cap nut (1/F)

Press the test key (2/F) (check of level alarm)


Verification of correct function from the control room
Release the test key
Fit and tighten the higher cap nut

Fig. F

5.1.2 Trip verification

Proceed following the actions


Remove the smaller cap nut (1/G)
Pull toward the higher position the test key (2/G) (check of
trip)
1

Verification of correct function from the control room


Push the test key (2/G) to re-arm the trip
Fit and tighten the higher cap nut

Damper functioning

eBR Electronic Buchholz Relay with the feature damper held in


response position are designed such that the damper after it was
operated due to an unacceptable high flow rate of the insulating liquid
is locked in its position and, hence is kept in this position even after the
flow rate has been reduced. This means that the signal generated is
Fig. G

CAUTION
For electronic Buchholz relays the damper und hence the lower switching system has to be unlocked after
the test by pushing the test key.

5.2 Pneumatic testing by pneumatic valve


This is performed by injecting air using a pump (furnished by COMEM on request as an accessory kit, causing the oil level inside the
eBR to drop down and actuate the alarm float.
Proceed as follows when using the kit:
Remove plug (2/H), screw valve (3/H) and relative nipple on relay valve (1/H)
Remove cap (4/H), insert pump (5/H) using the threaded connection and turn the lever to OFF, inject air as necessary to
activate internal mechanisms.
To restore the oil level and simultaneously bleed out internal air remove plug (7/H) and open ball cock (6/H).
After these procedures close cock (6/H) and plug (7/H), remove pump (5/H) and relative accessories (3/H) and (4/H) and
close valve (1/H) using plug (2/H).

Fig. H

6. What to do in the case of gas accumulation


In case of alarm, the gas should be checked immediately to determine the cause of the fault and avoid additional damages. To this end,
withdraw the gas from the eBR and analyze it. For gas sampling and transport it is recommended to use the Gas Sampling device
supplied by COMEM (see Annex C).

10

7. Operation and maintenance


The eBR Electronic Buchholz Relay is ready for immediate operation after installation, electrical connection and power supply.

7.1 Operation
It is possible to detect the gas accumulation in different way:
Checking the graduated windows
Checking the gas accumulation alarm signal
Continuously via analog output 4-20 mA
Continuously via digital output RS 485 (MODBUS RTU protocol)
It is possible to verify the dampers status:
Checking the alarm/trip signal
Via digital output RS 485 (MODBUS RTU protocol)
It is possible to activate a relay (optional, see annex B) to switch an external electrical petcock

7.2 Maintenance
The eBR Electronic Buchholz Relay is insensitive to ambient conditions, provided these conditions were considered when selecting the
particular design of the Buchholz relay. Therefore, no special maintenance is required during operation.
eBR should be inspected and tested at specified intervals as described in the maintenance instructions of the plant operator. COMEM
recommends performing the following checks:
Check the exterior condition of the device
To verify the contacts function following the chapter 5
Check the gaskets condition and if any leakage exists

7.3 Movement, transport and storage


The eBR storage must remain in the original packaging and in a dry place with temperature range between -10C to 40C.
Upon receiving the eBR, please check:
The outer surface of the packaging to check that it is intact
That there are no breakages to the packaging
If damages are found, please contact COMEM, providing the data given on the shipping list and the serial number of the eBR.

CAUTION
Not to paint the device. In this case any guarantees concerning the corrosion resistance decline.
Only mild soap and water should be used to clean the electrical box cover. Solvents must not be used for
any reason as they will degrade the performance of the paint. Use of solvents on the unit will immediately
void the warranty.

When you install the device please follow section 3, 4 and 5.

11

Appendix A Modbus (RTU) Registers


A.1 Addressing

This electronic Buchholz relay has a default address equal to 32 and its address can be changed from 32 to 47.
It is not possible to give an address outside of range from 32 to 47.
The address can be modified from default value by dipswitches on electronic board.
The dipswitches involved are ones from 1 to 4 and they can be modified according to table 1.

Fig. I

DIPSWITCHES
ADDRESS

32

OFF

OFF

OFF

OFF

33

ON

OFF

OFF

OFF

34

OFF

ON

OFF

OFF

35

ON

ON

OFF

OFF

36

OFF

OFF

ON

OFF

37

ON

OFF

ON

OFF

38

OFF

ON

ON

OFF

39

ON

ON

ON

OFF

40

OFF

OFF

OFF

ON

41

ON

OFF

OFF

ON

42

OFF

ON

OFF

ON

43

ON

ON

OFF

ON

44

OFF

OFF

ON

ON

45

ON

OFF

ON

ON

46

OFF

ON

ON

ON

47

ON

ON

ON

ON
Table 5

12

A.2 Registers Tables


In the tables 6 are showed the visible via Modbus (RTU) registers.

A.2.1 Main register Table


REGISTER

TYPE

R/W

FUNCTION

0x2000

Electronic board input

0x2001

R/W

Electronic board output

0x2002

Level probe value (mml)mml

0x2003

Operation number IN1

0x2004

Operation number IN2

0x2005

Relay operation number

0x2006

Time (minutes) electronic board switched on

0x2007

Time (days) electronic board switched on

0x2008

Max level current day

0x2009

Min level current day

0x200A

Software version

A.2.2 Memory registers

Table 6

Maximum and Minimum values are stored and saved from register 0x2100 to register 0x215F.
th
The last four weeks data (from current day) are stored and saved daily, at the beginning of the 5 week the maximum and minimum
values of the entire older week are stored and saved in 0x2138 and 0x2139 registers and so on.
Summarizing, in this table (7) the data are collected as follows:
1)
2)

In the first 28 rows are saved max and min of the latest 28 days;
In the remaining rows are saved max and min of the oldest 19 weeks.

REGISTER

TYPE

R/W

FUNCTION

0x2100

Level Sensor Maximum Value Day 1

0x2101

Level Sensor Minimum Value Day 1

0x2102

Level Sensor Maximum Value Day 2

0x2103

Level Sensor Minimum Value Day 2

0x2104

Level Sensor Maximum Value Day 3

0x2105

Level Sensor Minimum Value Day 3

..

..

..

0x2134

Level Sensor Maximum Value Day 27

0x2135

Level Sensor Minimum Value Day 27

0x2136

Level Sensor Maximum Value Day 28

0x2137

Level Sensor Minimum Value Day 28

0x2138

Level Sensor Maximum Value Week 5

0x2139

Level Sensor Minimum Value Week 5

...

..

0x215C

Level Sensor Maximum Value Week 23

0x215D

Level Sensor Minimum Value Week 23

0x215E

Level Sensor Maximum Value Week 24

0x215F

Level Sensor Minimum Value Week 24


Table 7

13

A.3 Register Description


A.3.1 Main Register Description
0x2000 Electronic board input
This register shows the input status:
BIT 0: shows the status of the input IN1 or JP10 (0=voltage on, 1 = voltage off).
BIT 1: shows the status of the input IN2 or JP12 (0=voltage on, 1 = voltage off).
BIT between 2 and 15: always 0.
0x2001 Electronic board output
This register shows the output status:
BIT 0: shows the status of the output JP13 (0=output switched off, 1 = output switched on).
BIT between 1 and 15: always 0.
0x2002 Level probe value (mml)mml
This register shows the level probe value.
0x2003: Operation number IN1
This register shows the operations of the input IN1 or JP10 (operation means the passage from switched on to switched off status) input
status). This value can be from 0 to 65535 (from 0x0000 to 0xFFFF).
0x2004: Operation number IN2
This register shows the operations of the input IN2 or JP12 (operation means the passage from switched on to switched off status) input
status). This value can be from 0 to 65535 (from 0x0000 to 0xFFFF).
0x2005: Relay operation number
This register shows the operations of the relay (operation means the passage from switched on to switched off status) input status). This
value can be from 0 to 65535 (from 0x0000 to 0xFFFF).
0x2006: Time (minutes) electronic board switched on
This register shows the minutes passed from the last electronic board powering. This value can be from 0 to 1439 (from 0x0000 to
0x059F). After I it will reset.
0x2007: Time (days) electronic board switched on
This register shows the days passed from the last electronic board powering. This value can be from 0 to 65535 (from 0x0000 to
0xFFFF).
0x2008: Max level current day
This register shows the max level of the current day (this value will be saved in the EEprom when the day finishes). This value can be
from 0 to 1023 (from 0x0000 to 0x03FF).
0x2009: Min level current day
This register shows the min level of the current day (this value will be saved in the EEprom when the day finishes). This value can be
from 0 to 1023 (from 0x0000 to 0x03FF).
0x200A: Software version
This register shows the software version of the electronic board.

14

Appendix B Petcock
On demand the electronic eBR Electronic Buchholz Relay can be supplied with the possibility to manage via MODBUS an output relay.
This output relay could be utilized for the gas discharge valve opening for example

B.1 Connection
The connection can be done directly on the electronic board following the picture below

NC

NO
Fig. L
NO: normal opent
NC: normal closed
C: common

B.2 Contact technical data


Contact Specification
Rated current/Maximum peak current (A)

10/15

Rated voltage/Maximum switching voltage


(V AC)

250/400

Rated load AC1 (VA)

2500

Rated load AC15 (230 V AC) (VA)

500

Breaking capacity DC1: 30/110/220 V (A)

10/0.3/0.12

Minimum switching load mW (V/mA)

300 (5/5)

Technical data
6

Mechanical life AC/DC (cycles)

-/10x10

Electrical life at rated load AC1 (cycles)

100000

Operate/release time (ms)

6/4

Insulation between coil and contacts


(1.2/50 s) kV
Dielectric strength between open contacts
(V AC)
Ambient temperature range C

6(10 mm)
1000
-40 +80C
Table 8

15

Appendix C Gas Sampling Device


C.1 DRAWING

Fig. M

C.2 CONSTRUCTION
The COMEM Gas Sampling device is manufactured from an aluminum alloy casting with the following fittings:
A tempered glass inspection window with graded markings for volume indication.
A gas sampling valve (2/M).
A bleed valve (3/M).
A gas inlet valve for pneumatic testing (5/M).
A valve for draining oil from the relay (this can be mounted on the right or left hand side of the body (6/M) or (7/M).
As a routine test all castings are tested by injecting ambient air at 2.5 bar for 2 minutes.
A certificate to this effect is supplied with the unit.
For the sake of standardization the device is fitted with the left and right hand valve supports but only one valve.
Customer can then choose which side he prefers.
With fittings for outside dia. 6 tubes, code 1RDPG00006 (on request);
with fittings for outside dia. 8 tubes, code 1RDPG00007 (on request);
with fittings for outside dia. 10 tubes, code 1RDPG00005 (standard).

16

Appendix D Order Sheet

Size and Model

Electrical scheme
(see chapter 4)

Seal

BR80

BS80

NBR -40C

HNBR

VITON

Flow Speed

Alarm

1.0 / 1.5 / 2.0 / 2.5 m/s

Speed

1.0 / 1.5 / 2.0 / 2.5 / 3.0 m/s

Flow vane contacts


status verification
via Modbus
Contact supply

YES

NO

24/48V AC/DC

110/220V AC/DC

Table 9

17

Appendix E Figure and Reference number key


Picture

Description

A
B

eBR 80 overall dimension


Internal frame (floats and flow vanes position)

Buchholz relay cover

Buchholz relay installation


eBR terminal board

E
F

Alarm volume mechanical test

Trip mechanical test

H
I

Pneumatic testing
Dip switches

L
M

Petcock connection on the electronic board


Gas sampling device

Table 10
Picture

F
G

Number

Description

1
2
9

Electronic Buchholz relay graduated windows


Drain plug
Electrical box cover

10
3

Cable gland M25x1.5


Floats

Flow vanes

5
6

Discharge valve
Pneumatic valve

Mechanical test key (alarm)

Mechanical test key (trip)

1
2

Buchholz relay
Pipe

Transformer tank

4
1

Transformer conservator
Un-losable screw

2
3
4

Electrical box cover


Cable gland M25x1.5
Terminal board

1
2

Mechanical test key cover (alarm)


Mechanical test key (alarm)

Mechanical test key cover (trip)

2
1

Mechanical test key (trip)


Pneumatic valve

Plug

Screw valve

4
5

Cup
Pump

Discharge valve

7
1

Plug
Upper GSD discharge valve

2
3
4

Gas sampling valve


Bleed valve
Lower GSD discharge valve

5
6

Valve for pneumatic testing


Valve for draining oil

Valve for draining oil

8
9

Upper Buchholz relay discharge valve


Lower Buchholz relay discharge valve

10

Pipe

11

Pipe

Table 11

18

19

20

Strada Regionale 11, Signolo 22


36054 Montebello Vic.No (VI) - Italy
Tel. +39 0444 449311 - Fax -39 0444 449352 440359
http://www.comem.com
e-mail:comem@comem.com

21

You might also like