A New Hybrid Series Active Filter Configuration to Compensate Voltage Sag,


Swell, Voltage and Current Harmonics and Reactive Power
Ab. Hamadi, Student Member, IEEE, S. Rahmani and K. AI-Haddad, Fellow, IEEE
Canada Research Chair in Energy Conversion and Power Electronics CRC-ECPE
Ecole de Technologie Superieure, 1100 Notre-Dame West, Montreal, Quebec H3C 1K3, Canada.
Email: abdelhamidhamadi@yahoo.fr.rsalem02@yahoo.fr.kamal@ele.etsmtl.ca
Abstract- This paper proposes a new system configuration
for a series hybrid power filter (SHPF) realized for all
harmonic types of loads. The series hybrid filter consists of
a small rated series active power filter (SAPF) and a shunt
passive filter with variable inductance using a thyristor
control reactor (TCR). The DC voltage available at the load
side of a typical voltage harmonics source, such as a diode
bridge rectifier followed by a capacitor, is utilized as a
source of DC power for the SAPF. To increase the filtering
performance of the shunt passive filter, SAPF is control in
such a way that it increases the network impedance at the
harmonic frequency. This also helps to avoid any series or
parallel resonance that may occur. The shunt passive filter
together with a TCR is used to support the variable load
reactive power demand as well to tackle the current
harmonics generated by non-linear load. The performance
of proposed series hybrid power filter is validated through
MATLAB/Simulink simulation study and successfully
utilized to compensate the voltage sag, voltage swell,
voltage harmonics, current harmonics and load reactive
power demand.

distribution system [1-8]. The other alternative is the use of


a unified power quality conditioner (UPQC) to compensate
voltage and current problem simultaneously. However, the
use of UPQC is an expensive solution [9]. A SAPF
essentially requires a source of energy, such as a DC
battery, in order to compensate for voltage sag and swell.
Generally, a separate rectifier is used to provide the
necessary DC power for the SAPF. A full bridge diode
rectified followed by a capacitor is extensively used in
modern plants, for example, as in adjustable speed drive.
However, such a topology is often considered as a source of
voltage harmonics as it generates harmonics in supply
voltage. This paper proposes a new topology for a SHPF
which utilizes an existing front end diode bridge rectifier as
a source of DC power for the SAPF. This arrangement thus
helps to eliminate the use of additional rectifier require of
the SAPF. A shunt passive filter together with a thyristor
control reactor (TCR) is used to tackle the harmonics
generated by non-linear load as well as to support the load
reactive power demand. The TCR in passive filter is used to
support the variable load reactive power demand [10-12].
Moreover, the TCR considerably reduces the size of overall
shunt passive filter. A hybrid detection method is added to
increase the impedance of the series transformer at the
harmonic frequency, which force the current harmonic to
flow in the shunt passive filter. The DC bus voltage of SAPF
is maintained at a constant level by regulating the voltage at
load bus at desired constant level.

Index Terms- Hybrid active filter, series active filter,


thyristor control reactor, voltage sag and swell, harmonics,
reactive power support.
I. INTRODUCTION

The rapid increase in the technology, especially in electric


power sector, the use of non-linear loads on a typical
distribution system has been increased significantly in
recent years. These non-linear loads are the major source of
harmonics in modem distribution system which is making
the distribution system polluted. On the other side, the
modem equipments are becoming increasingly sophisticated
and require clean power for their proper operation. Any
variation in supply voltage, such as voltage sag and swell or
even harmonics in voltage causes the sensitive equipment to
malfunction.
To improve the quality of power, several solutions have
been proposed by several authors. Among them the shunt
and series active power filters have proven as an important
and flexible alternative to compensate most important
voltage and current related power quality problems in the

II. PROPOSED HYBRID SERIES ACTIVE POWER FILTER


TOPOLOGY

The system configuration of proposed SHPF is shown in


Fig. 1. It consists of - (i) small rated series active power
filter, (ii) shunt passive filter and (iii) a typical voltage and
current harmonics type of source. The SAPF protects the
sensitive load from variation in the supply voltage. It injects
a voltage component in series with the supply voltage and
thus considered as a controlled voltage source. The required
DC bus voltage for SAPF is provided from the load side.
The output of DC voltage of front end diode bridge rectifier,
as shown in Fig.1, is shared with the SAPF. This
arrangement thus eliminates the need of additional separate
rectifier for the SAPF. The regulation of necessary active
286

978-1-4244-4349-9/09/$25.00 2009 IEEE

power during the voltage sag and swell condition is done by


maintaining the load voltage at constant level. Thus in the
proposed configuration the need of SAPF DC bus voltage
regulation is also eliminated.
In the proposed topology a reduced size passive LC filter
alone with a TCR is connected in parallel with the load. The
SAPF controlled as a harmonic isolator, forcing the load
current harmonics to circulate mainly through the passive
filter rather than the power distribution system. The main
advantage of this scheme is that it reduces the required
power rating of SAPF.

Where i cd i eq denote the currents in the SAPF inductors,


expressed in synchronous (d-q) frame. v sd ' v sq represent
the voltages at the primary side of the transformer, isd ' iSq
are the d-q components of the line currents at the primary
side of the SAPF.

upper switches in the inverter topology,


frequency.

IV. REFERENCE CURRENT GENERATION

The SAPF is connected in series with the AC source. The


system can mathematically be represented as: [13, 14]
diea
Le-=vea-van
dt
dieb
(1)
Le - = veb -vbn
dt
dice
Le - = Vee -Ven
dt
dvea .
.
C-= Isa -lea
dt
dveb .
.
(2)
C-- = Isb -leb
dt
dv;
.
.
C-- = Isc -lee
dt
ie,a,b,e

The necessary equations to generate the reference signals


are given below:
d VCd

C ~==
dV cq

is,a,b,e

dt

0]

Sin(lOot) -COS(lOot)
P = ~ cos( mot) sin( mot) 0
[
3
0
0
1

0
3
2

..
-lcq
lsq

(6)

== uq

= k pvcd + k, JVeddt
u q = k pveq + ki JVeq

(7)
(8)

The reference current controller is then given by


ied* = -ud + Cmoveq + t;
(9)

ieq*

= -uq -Cmoved +iSq

(10)

Using PI controller to regulate the current of the SAPF.

= kpicd + k, Jieddt
uiq = kpieq + k, Jieqdt

Uid

(11)
(12)

J3
--

J3
--

-;

side of the SAPF. To reduce the system order and optimize


the mathematical representation the Park transformation is
considered. The transformation matrix P can be defined as:
1

..

%VSq-Zcd+zsd

Using PI controller to regulate the voltage of the SAPF.

are the line currents at the primary

1 -~

C - == -ClOOVsd

are the currents flowing through the SAPF

inductors and the

is the DC

V de

voltage of the inverter and aJo is the mains angular

III. SERIES ACTIVE POWER FILTER MODELING

Where

da dq represent the duty cycles of the

From Eqn. (4), the control law is given by


Uid - ved - Lemoieq
dd =
v de

(3)

Applying the Park transformer to the Eqn. (1) and to the


Eqn. (2), yield to:

(13)

V. IMPROVING FILTER PERFORMANCE

The SHPF control scheme is shown in Fig. 4. The approach


uses a hybrid control; detect simultaneously the source
current is (abc) and the load voltage VL (abc) to get their
harmonic components. The main idea is to increase the
impedance of the series transformer at the harmonics
frequency. The reference compensation voltage of the SAPF
adopting hybrid control approach is: [15]
v = kish -VLh
(15)

(4)

(5)

287

The compensation effects are, to a great extent, dependent


on the control gain k, which is the ratio of the compensating
harmonic voltage generated by the SAPF to the harmonic
current flowing through it. Fig. 2 shows the series voltage
harmonic versus gain k. One can observe that by deceasing
k, from 5 to 2, reduce the amplitude of the series
transformer voltage harmonics which affects negatively the
filtering performance. For k = 5, the reflected impedance of
SAPF becomes high and therefore load current harmonic
flows through the shunt passive branches.
F~ ~!. U5 . lI{I: S11. 62".

i PFa
i LpFa :

: C pF
,

-,..

15

-,..
10

15

20

25

~"o II
o

II.
5

10

15

,...,""

20

25

d i1J' Fd
J .
dipFq i CI' Fd
Ll'lJa) - , - -LpF(a)aT!U'Fd = 2Lpp( a )(J)----'-+ dt
dt
Cw

k =5(THD 1S=3%) k=3(THD 1S=10%) k=2 (THD 1S=30%)

.
d iU >Fq
dilJ' Fd
iCl'Fq
LPF(a)--, --LpF(a)allu'FQ= 2LPF (a ) (JJ----='-"-+ dt
dt
CPF

A. Sag and swell compensation

Only the reactive part is chosen:

The extractions of three phases voltage references signals


are based on Unit Vector Template Generation. A Phase
Locked Loop (PLL) is used to extract the sinusoidal signal
at fundamental frequency. The PLL gives signal in terms of
compared with the measured

VLCa ,b ,c)'

v" Ca ,b,c)

(17)

are

One knows that:

As shown in Fig. 4,

the error signal is feed forwarded to the

V hd

(18)

and the vhq

signal and compared to the compensator voltages vcd


and vcq

'

(16)

Fig. 2 voltage harmonic of series active filter versus gain k

sine and cosine functions. The obtained

:C pF

The main concept behind controlling TCR is the control of


the firing instant of the thyristor to control the current in the
reactor, thus controlling the reactive power absorbed by the
TCR. Kirchoff's laws of voltages and currents neglecting
the resistor of the inductance applied to this system provide
three differential equations in the a-b- c frame. The TCR
control scheme is shown in Fig. 5.
Applying these transformations in dq frame to the shunt
passive filter:

FIlda'rwiI (f(ttl): t2.M,ID l14443'.

.1.1.

10

:i CPFa

Fig. 3. TCR equivalent circuit

= LpFCa):.

The following relation is obtained

The feedforward signal enhances the filtering

performance by compensating sag, swell and voltage


harmonics .

(19)

VI. SH UNT P ASSIVE FI LTER MODELING


Thyristor controlled reactor for continuously variable
reactive power can be obtained across the entire control
range, with full control of both inductive and capacitive of
the compensator. The principal benefit is its optimum
performance during major disturbances in the system such
as sudden load change and load rejections. This type of
TCR is characterized by continuous control, low losses,
redundancy, and flexibility. Fig. 3 shows the TCR
equivalent circuit. [16,17].

To regulate the current iPFq ' a model reference adaptive


control is used. The reactance of the inductance can be
modeled as: [10,11]
Jr

LPl ..{ a) = LpF

2Jr -

iCPFq

2a + sm(2a)

(20)

uj = B(a)--+ o l lLl'Fq
CpF

(21)

, ) CpF
()
(U1-OJ2
I LPFq -.-= B a

(22)

I CPFq

The shunt passive filter presents great impedance at the


fundamental frequency and very low impedance at the
harmonics frequency. This filter combined with the series
active filter is able to absorb practically all the current
288

harmonics generated by the nonlinear load. The passive


filter is reduced in term of components and is very robust
when its parameters change.

load voltage profile show that the SHAF system was


working effectively, reducing the source current THD from
22.34 % to 1.94 % and the load voltage THD from 18.03 %
to 3.31 %, respectively.

VII. SIM ULATION RESU LTS

The proposed series hybrid power filter configuration is


simulated under MATLAB-PSB environment to estimate
its' performance. The set of loads consists of current-source
type of nonlinear load and voltage-source type of nonlinear
load to study of the effectiveness of the proposed scheme.
The SHPF system was tested for several different operating
conditions such as - steady-state, transient condition,
voltage sag, voltage swell, and under balanced
nonsinusoidal utility voltages, intending to validate the
SHPF system performance. The simulation results are
shown in Figs. 6 - 8 and discussed in the following
subsections.

B. Voltage sag, swell and harmonics compensation

The performance of SHPF system is also tested under


voltage swell, voltage sag and balanced non-sinusoidal
utility voltages. The simulation results are shown in Fig.8.
The source voltage has a voltage THD of 18.03% with
dominant 5th and 7th harmonics of 15 % and 10 %,
respectively. In consecutive cycles, the voltage swell is
introduced voluntarily in the utility voltage (20%). And
after that, the voltage sag is also introduced in the utility
voltage (-40%). The SHPF system does not show any
significant effect of distortion present in the utility voltages
on its compensation capability and, the source current and
the load voltage THD under this condition, are found pure
sinusoidal. Since the load voltage is maintained constant.

A. Dynam ic performance under load change condition


In order to verify the performance of the SHPF during
transient response, two types of three phase nonlinear loads
are used simultaneously (diode bridge rectifier followed by
R-L load and diode bridge rectifier followed by R-C load).
Fig.6 shows the transient response of SHPF system. The
load current is abruptly increased and decrease. As viewed
from the simulation results, the changeover from one
operating condition to the other is quite smooth,
maintaining the perfect compensation. The sudden increase
(decrease) in the load though causes a small decrease
(increase) in the DC link voltage. It was observed that this
decrease (increase) in DC link voltage was around 10 V for
nov DC link. Consequently as the load on the system
changes, the control algorithm takes minimum two cycles to
compute the new steady-state load active power demand.
This proves that the SHPF system compensates the
harmonics and reactive power of the load during steadystate as well as transient operating conditions without losing
its performance.
The harmonics spectrums befor and after compensation are
shown in the Fig.7. The compensated source current and

VIII. CONCLUSIO N

To improve the power quality and to reduce the overall cost


of compensator, in this paper a new hybrid series active
power filter configuration has been proposed. The most
important power quality problems, such as, voltage sag,
voltage swell, voltage harmonics, current harmonics and
load reactive power are compensates effectively utilizing
the proposed system configuration. Thus it could be an
economical solution over a UPQC to tackle similar power
quality problems. Moreover, this configuration requires
reduced size of series active power filter. The
MATLAB/Simulink results show that the voltage sag and
swell are compensates effectively providing a regulated
voltage at load terminal. Additionally, the harmonics
present in the load current (load current THD= 22.34%) and
source voltage (source voltage THD= 18.03%) are
significantly reduced to 1.94% in source current and 3.31%
in load voltage. This proposed system configuration thus
eliminates the need of additional energy source required for
the series active power filter.
v/."
VLb
VL c

11

i l ,a :!

Vu l h lAC s u u r ce t ype HO
lin ear lo atl

~--------------Sh u nt
pa s si v e filt er

Fig. I Proposed series hybrid power filter configuration


289

PLL

til

.. ..
..
:=
VI

s(a bc ) {re f)

tlZ

':U

c:

LL

.i;

0>

~ .u;

0>

+
(l 3

.S
"C

U iq

v c (ab c)

i cq

Fig. 4 SHPF contro l scheme

___0-.1
y
.

j3

uqt

controller

H,-----Hr-----~
Eq.22
Look up table c=7..r--

sa _

i"F"u
PFq

Fig. 5 TCR control scheme


~ ~ 20~ V'\
-f\.JCA
~
A7\
-n
A7\
-n
f\.JCA
__f\.JCA~
-'A
A
A~

-200 .
20~

~5 __

~ ~ -20g

0 .05

. ~ ~ -:~o

__

0 .1
0 .1

0 .15

__

0 .15

0 .2 _ _

~5

0 .2

0 .25

__

~ __

0 .3

0 .35

0 .4
0 .4

0 .05

0 .1

0 .15

0 .2

0 .25

0 .3

0 .35

0 .4

0 .05

0.1

0 .15

0 .2

0 .25

0 .3

0 . 35

0.4

",20o.

0 .05

0 .1

0 .15

0 .2

0 .25

0 .3

0 . 35

0 .4

0 .05

0 .1

0 .15

0 .2

0 .25

0 .3

0 .35

0 .05

0 .1

0 .15

0 .2

0 .25

0 .3

0 . 35

0.4

0.05

0.1

0.15

0 .2

0 .25

0 .3

0.35

0.4

~~ -:~o
~ ~ -:g
~g -2~

~~ -:~

~~~!~F " " " " " " " " ' :?=SF

:.~

0 .4

: 3

Fig.6 Sudden load variation

Sou rce Curr ent Har mo nic Spectrum

THO ;; 1.94 %

Load Cu rren t Harmo n ic Spect rum

THO " 22.34%

Lo ad Voltag e Harmo n ic Spectrum

THO = 3.31%

Source Voltage Harmonic Spectrum


80

THD =1 8.03%

-360

'0 40

to

1
10

15

10

Harm onlc o rtl er

15

Harm onI CO.d e .

20

_LI
~_-:-:------=---!
5
10
15
Harmonic orde r

a) Source current
b) Load current
d) Load voltage
c) Source voltage
Fig.? Harmonics spectrum a) source current b) load current c) load voltage d) source voltafe

290

~ ~ -::~

2000

~~

0.05

0.1

0.15

2
o
0.05
0 .1
0.15
",_20

.!e

s,

-2g

0.2_

0.25

?Ln~

0
0.2
0.25

0.3

0.35

0.4

0.45

n~f\~J

0
.
0.3
0.35
0.4
0.45

0 .05

0 .1

0 .15

0 .2

0 .25

0 .3

0.35

0.4

0.45

1000

0.05

0.1

0.15

0.2

0.25

0.3

0 .35

0.4

0.45

~~ _10~f

0 .05

~""""

0.2

0.25

0 .3

0 .35

0.4

0 .45

~ ~ -:~
'"

200

0.1

0.15

~ ~ -2~
~

_2~1

!!::~-20 ~
o

-g ~ ~~~ E
o

0.05

0.1

0 .15

0 .2

0 .25

l i ......; :
0.05

0 .1

0 .15

0.2

0.25

5
0.3

:.;;.;;. 1
0 .3

--

0 .35

0.4

0 .45

0.35

0 .4

0 .45

Fig. 8 Voltage sag, voltage swell and voltage harmonics compensation


IX. REFER ENCES
[1]

S. Bhattacharya and D. M. Divan, "Synchronous frame based


controller implementation for a hybrid series active filter system,"
iEEE/iAS Annu. Meet., 1995, pp. 2531-2540.
[2] S. Bhattacharya, D.M. Divan and 8.8. Banerjee, "Control and
Reduction of Terminal Voltage Total Harmonic Distortion (THD)
in a Hybrid Series Active and Parallel Passive Filter System,"
iEEE Power Electronics Specialists Conference, PESC '93, pp.779
- 786, June 1993.
[3] H. Akagi and H. Fujita, "A Combined System of Shunt Passive
and Series Active Filters - An Alternative to Shunt Active Filters,"
EPE, vol. 3, pp. 12-17, 1991.
[4] H. Fugita and H. Magi, "The Unified Power Quality Conditioner:
The Integration of Series Active Filters and Shunt Active Filters,"
iEEEPESC'96, pp. 494-501,1996.
[5] A. Hamadi, S. Rahmani, and K. AI-Haddad, "A Novel Hybrid
Series Active Filter for Power Quality Compensation," IEEE
Power Electronics Specialists Conference, PESC 2007, pp.10991104, June 2007.
[6] Ab. Hamadi, K. AI-Haddad and R. Rahmani, "Series active filter
to mitigate power quality for medium size industrial loads (multi
Pulses Transformer and modem AC drive)," IEEE international
Symposium on ind. Electronics, vol.2, pp.1510 - 1515, July 2006.
[7] H. Akagi, A. Nabae and S. Atoh, "Control Strategy of Active
Power Filters Using Multiple- Voltage Source PWM Converters",
EEE Trans. on Ind. Appl. vol. IA-22, no.3, pp. 460-465, May
1986.
[8] Ab. Hamadi, K. AI-Haddad, P.J. Lagace and A. Chandra, "Indirect
current control techniques of three phase APF using fuzzy logic
and proportional integral controller: comparative analysis," 11th
International Conference on Harmonics and Quality of Power,
pp.362 - 367, Sept. 2004.
[9] V. Khadkikar, A. Chandra, A.O. Barry and T.D. Nguyen,
"Application of UPQC to Protect a Sensitive Load on a Polluted
Distribution Network," IEEE Power Engineering Society General
Meeting, 2006.
[10] A. Garcia-Cerrada, P. Garcia-Gonzalez, R. Coliantes, T. Gomez
and 1. Anzola, "Comparison of thyristor-controlled reactors and
voltage-source inverters for compensation of flicker caused by arc
furnaces," iEEE Trans. on Power Delivery, vol. 15, no. 4, pp.
1225 - 1231, Oct. 2000.
[II] 1. E. R. Alves, L. A. S. Pilotto and E. H. Watanabe, "ThyristorControlled Reactors Nonlinear and Linear Dynamic Analytical

291

[12]

[13]

[14]

[I5]
[16]

[17]

Models," iEEE Trans. on Power Delivery, vol. 23, no. I, pp. 338
- 346, Jan. 2008
J. G. Mayordomo, M. Izzeddine and R. Asensi, "Load and Voltage
Balancing in Harmonic Power Flows by Means of Static VAR
Compensators," IEEE on Power Engineering Review, vol. 22, no.
4, pp. 80 - 80, April 2002.
S. Rahmani, K. AI-Haddad and H.Y. Kanaan, "Average Modeling
and Hybrid Control of a Three-Phase Series Hybrid Power Filter,"
iEEE International Symposium on Industrial Electronics, 2006,
vul.2, pp. 919-924, July 2006.
H.Y. Kanaan and K. AI-Haddad, "Comparative evaluation of
average-model-based control schemes applied to a three-phase
series active power filter for voltage harmonic cancellation," iEEE
International Symposium on Industrial Electronics, vol.2, pp.783789, May 2004.
W. Zhaoan, W. Qun; Y. Weizheng and L. Jinjun, "A series active
power filter adopting hybrid control approach," IEEE Trans. on
power Electronics, vo1.16, no.3, pp. 301-310, May 200 I.
S. Rahmani, Ab. Hamadi and K. AI-Haddad, "A new single phase
hybrid passive filter to dampen resonances and compensate
harmonics and reactive power under distorted source conditions,"
34th Annual Conference of IEEE industrial Electronics, iECON
2008, pp.473-478, Nov. 2008.
S. Rahmani, A. Hamadi and K. AI-Haddad, "A New Three Phase
Hybrid Passive Filter to Dampen Resonances and Compensate
Harmonics and Reactive Power for Any Type of Load under
Distorted Source Conditions ," IEEE Power Electronics Specialists
Conference, PESC 2007, pp.2594-2599, June 2007.

You might also like