Declared cooling capacity at full load


i.e. Point A (DC, in kW)

Chiller - Fix CAP+Stepless

DC at rating points B, C and D shall not be low


of the cooling demand (PR) -- CR < 1.03

DC = declared cooling capacity at temperatures A, B, C and D

593.00

Degradation Calculation
Cooling demand (PR)
EER A
EER B
EER C
EER D

(=DC(full load)*Partload)
593.00
553.47
513.93
474.40

EER
2.41
3.05
3.66
4.24

DC in kW
(measured or
calculated)

EER at this DC
(measured or
calculated)

593.00
620.00
660.00
710.00

2.41
3.05
3.66
4.24

Tj (C)

hj

Capacity Ratio CR
(=PR/DC)

0.90
0.90
0.90

1.00
0.89
0.78
0.67

If Cc is not determined by test


then the default
degradation coefficient
Cc shall be 0.9

Please consider: Selection of EERA, EERB, EERC, EERD depends on


different ambient temp conditions, load profile and application
temperature (HT, MT, LT)

Degradation coefficient Cc

part load %

cooling
demand

EER at Part Load EER(PL)


(=EER@full cap)*CR/(Cc*CR+(1-Cc))
2.41
3.01
3.56
4.04

Ratio between cooling demand and declared capacity (CR=1, in


case of a continuous capacity adjustment)

EERPL

Ph*Tj

PH*Tj/EERDC

-19

0.1

80%

474.40

4.04

40

10

2
3
4
5
6

-18
-17
-16
-15
-14

0.4
0.6
1.1
1.7
3.0

80%
80%
80%
80%
80%

474.40
474.40
474.40
474.40
474.40

4.04
4.04
4.04
4.04
4.04

193
307
500
826
1,413

48
76
124
204
350

-13

3.8

80%

474.40

4.04

1,799

445

-12

5.7

80%

474.40

4.04

2,697

668

-11

8.9

80%

474.40

4.04

4,240

1,050

10
11
12
13
14
15
16
17
18

-10
-9
-8
-7
-6
-5
-4
-3
-2

11.8
17.3
20.0
28.7
39.7
56.6
76.4
106.1
153.2

80%
80%
80%
80%
80%
80%
80%
80%
80%

474.40
474.40
474.40
474.40
474.40
474.40
474.40
474.40
474.40

4.04
4.04
4.04
4.04
4.04
4.04
4.04
4.04
4.04

5,603
8,201
9,497
13,630
18,837
26,857
36,226
50,317
72,689

1,387
2,030
2,351
3,374
4,663
6,649
8,968
12,457
17,995

19

-1

203.4

80%

474.40

4.04

96,499

23,890

20
21

0
1

248.0
282.0

80%
80%

474.40
474.40

4.04
4.04

117,639
133,784

29,123
33,120

22
23

2
3

275.9
300.6

80%
80%

474.40
474.40

4.04
4.04

130,893
142,610

32,404
35,305

24

310.8

80%

474.40

4.04

147,428

36,498

25

336.5

80%

474.40

4.04

159,625

39,517

26

350.5

81%

478.35

3.99

167,652

42,004

27

363.5

81%

482.31

3.94

175,316

44,459

28

368.9

82%

486.26

3.90

179,384

46,052

29

371.6

83%

490.21

3.85

182,180

47,354

30

10

377.3

83%

494.17

3.80

186,460

49,080

31

11

376.5

84%

498.12

3.75

187,556

50,001

32

12

386.4

85%

502.07

3.70

194,012

52,393

33
34

13
14

389.8
384.4

85%
86%

506.03
509.98

3.65
3.61

197,271
196,061

53,973
54,357

35

15

370.5

87%

513.93

3.56

190,389

53,497

36
37
38

16
17
18

345.0
328.0
305.4

87%
88%
89%

517.89
521.84
525.79

3.50
3.45
3.40

178,652
171,176
160,558

50,980
49,619
47,288

39

19

261.9

89%

529.75

3.34

138,724

41,524

40
41
42
43
44

20
21
22
23
24

223.9
196.3
163.0
141.8
121.9

90%
91%
91%
92%
93%

533.70
537.65
541.61
545.56
549.51

3.29
3.23
3.18
3.12
3.07

119,495
105,544
88,306
77,348
67,002

36,361
32,658
27,793
24,769
21,837

45

25

104.5

93%

553.47

3.01

57,815

19,184

46

26

85.8

94%

557.42

2.95

47,809

16,188

47
48

27
28

71.5
56.6

95%
95%

561.37
565.33

2.89
2.83

40,160
31,983

13,882
11,291

49
50
51

29
30
31

43.3
31.0
20.2

96%
97%
97%

569.28
573.23
577.19

2.77
2.71
2.65

24,677
17,784
11,663

8,901
6,558
4,399

52
53
54

32
33
34

11.9
8.2
3.8

98%
99%
99%

581.14
585.09
589.05

2.59
2.53
2.47

6,887
4,779
2,256

2,658
1,888
913

55

35

2.1

100%

593.00

2.41

1,240

515

56

36

1.2

100%

593.00

2.41

716

297

57
58

37
38

0.5
0.4

100%
100%

593.00
593.00

2.41
2.41

309
238

128
99

4,393,752

1,205,605

total

SEPR

3.64

10/14/2015

289962287.xls

Declared cooling capacity at full load


i.e. Point A (DC, in kW)

Chiller - Step CAP

If Cc is not determined by test then the


coefficient Cc shall be 0.9.

DC = declared cooling capacity at temperatures A, B, C and D

593.00

Degradation Calculation
Cooling demand (PR)
EER A
EER B
EER C
EER D

(=DC(full load)*Partload)
593.00
553.47
513.93
474.40

EER
2.41
3.05
3.66
4.24

DC in kW
(measured or
calculated)

EER at this DC
(measured or
calculated)

DC at part load
(measured or
calculated)

EER at part load


(measured or
calculated)

593.00
620.00
650.00
680.00

2.41
3.05
3.66
4.24

310.00
325.00
340.00

2.90
3.50
4.05

Measured or calculated cooling


capacity equal or above cooling
demand

Please consider: Selection of EERA, EERB, EERC,


EERD depends on different ambient temp
conditions, load profile and application temperature
(HT, MT, LT)

-19
-18
-17

0.1
0.4
0.6

80%
80%
80%

cooling
demand
474.40
474.40
474.40

-16

1.1

80%

-15

1.7

80%

6
7
8
9
10
11

-14
-13
-12
-11
-10
-9

3.0
3.8
5.7
8.9
11.8
17.3

12

-8

13

-7

14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58

Tj (C)

hj

part load %

Capacity Ratio CR
(=PR/DC)
0.90
0.90
0.90

1.00
0.89
0.79
0.70

Measured or calculated part load capacity below cooling


demand. Leave DC and EER blank if step control not
available/necessary.
Lowest part load DC limited to > 10% of DC at full load.

1
2
3

Degradation
coefficient Cc

EERPL

Ph*Tj

PH*Tj/EERDC

4.13
4.13
4.13

40
193
307

10
47
74

474.40

4.13

500

121

474.40

4.13

826

200

80%
80%
80%
80%
80%
80%

474.40
474.40
474.40
474.40
474.40
474.40

4.13
4.13
4.13
4.13
4.13
4.13

1,413
1,799
2,697
4,240
5,603
8,201

343
436
654
1,028
1,358
1,988

20.0

80%

474.40

4.13

9,497

2,302

28.7

80%

474.40

4.13

13,630

3,304

-6
-5
-4
-3
-2
-1
0

39.7
56.6
76.4
106.1
153.2
203.4
248.0

80%
80%
80%
80%
80%
80%
80%

474.40
474.40
474.40
474.40
474.40
474.40
474.40

4.13
4.13
4.13
4.13
4.13
4.13
4.13

18,837
26,857
36,226
50,317
72,689
96,499
117,639

4,566
6,511
8,782
12,198
17,621
23,393
28,518

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38

282.0
275.9
300.6
310.8
336.5
350.5
363.5
368.9
371.6
377.3
376.5
386.4
389.8
384.4
370.5
345.0
328.0
305.4
261.9
223.9
196.3
163.0
141.8
121.9
104.5
85.8
71.5
56.6
43.3
31.0
20.2
11.9
8.2
3.8
2.1
1.2
0.5
0.4

80%
80%
80%
80%
80%
81%
81%
82%
83%
83%
84%
85%
85%
86%
87%
87%
88%
89%
89%
90%
91%
91%
92%
93%
93%
94%
95%
95%
96%
97%
97%
98%
99%
99%
100%
100%
100%
100%

474.40
474.40
474.40
474.40
474.40
478.35
482.31
486.26
490.21
494.17
498.12
502.07
506.03
509.98
513.93
517.89
521.84
525.79
529.75
533.70
537.65
541.61
545.56
549.51
553.47
557.42
561.37
565.33
569.28
573.23
577.19
581.14
585.09
589.05
593.00
593.00
593.00
593.00

4.13
4.13
4.13
4.13
4.13
4.07
4.02
3.97
3.91
3.86
3.81
3.75
3.70
3.65
3.59
3.54
3.48
3.42
3.36
3.31
3.25
3.19
3.13
3.08
3.02
2.96
2.90
2.84
2.77
2.71
2.65
2.59
2.53
2.47
2.41
2.41
2.41
2.41

133,784
130,893
142,610
147,428
159,625
167,652
175,316
179,384
182,180
186,460
187,556
194,012
197,271
196,061
190,389
178,652
171,176
160,558
138,724
119,495
105,544
88,306
77,348
67,002
57,815
47,809
40,160
31,983
24,677
17,784
11,663
6,887
4,779
2,256
1,240
716
309
238
4,393,752

32,432
31,731
34,571
35,739
38,696
41,173
43,625
45,237
46,566
48,317
49,281
51,700
53,325
53,771
52,989
50,531
49,217
46,940
41,251
36,151
32,496
27,679
24,689
21,787
19,158
16,168
13,866
11,280
8,894
6,553
4,396
2,657
1,888
913
515
297
128
99
1,190,160

total

SEPR

3.69

Ratio b
adjust

Tool version 1.5.3

2013-09-01
To check for the latest version of this tool please see:
DG ENTR Ecodesign page for Professional Refrigeration

About this calculation tool


This calculation tool is provided to help suppliers to calculate the Seasonal Energy Perform
their products based upon 4 rating point measurements (or calculations) of EER.

It is intended to assist suppliers to assess the seasonal performance of their products acco
methodology that is to be used under the proposed European ecodesign regulation for indu
chillers.

This tool is provided free of charge and in good faith but without guarantee of a
should satisfy themselves that the output meets the requirement in the docume
'TRANSITIONAL METHOD FOR DETERMINATION OF THE SEPR (SEASONAL ENERGY
RATIO) for INDUSTRIAL PROCESS CHILLERS (DRAFT)' which explains more details
methodology.
What is SEPR? Seasonal Energy Performance Ratio

SEPR is the seasonal energy performance ratio of a process chiller. It is calculated from th
chiller at 4 different ambient temperatures and cooling loads, called rating points.
points are specified in the document 'SEPR calculation method', showing for each rating po
part load ratio and air dry bulb temperature for the outdoor heat exchanger.
Temperature references for chillers with air-cooled and water-cooled condensers see table.
How to use the tool

There are two sheets: One for fixed capacity and stepless chillers; and a second for steppe
Use the one appropriate to the chiller.

To use the spreadsheet:


1. Please insert the full load rated capacity in cell D3,
2. AND THEN declared rated capacity at the 3 part load rating points (B, C and D - cells
3. Insert the declared EER at 4 rating points (cells E8:11).

4. In case of step capacity control also insert part load DC and EER at 3 rating points (B

The spreadsheet then calculates the SEPR automatically using a linear interpolation be
points A, B, C, and D and an assumption of a constant capacity for temperatures above

Feedback will be used to help improve the tool.


If you have any questions or comments about the use of this tool please send an email to:
ENTR-ECODESIGN@ec.europa.eu

Please put the phrase 'professional refrigeration' in the subject line.

Temperature Reference (C):

AIR (inlet)
WATER (inlet)

35

25

15

30
[35C]

23
[25C]

16
[15C]

9
[5C]

Values in square brackets define the related ambient


temperature conditions