For certain control strategies some valve need to be operated in split range ,
i.e, from 0 to 100 % signal two valves operate to maintain the parameter. In
these cases valves may operate in either of following manner
CASE A
VALVE 2
VALVE 1
50
25
100
% SIGNAL
The above figure shows opening of both valves as signal varies from 0 to 100 %
SIGNAL
%
0
25
50
75
100
OPEN. OF VALVES
VALVE 1 VALVE 2
100
0
50
0
0
0
0
50
0
100
Example LV - 5 A & B :
LV - 5A is the condensate import valve of the carbamate condenser shell side
LV - 5B is the condensate export valve of the carbamate condenser shell side
At 50 % output both valves are closed
At 0 % output LV - 5A valve is full open & LV - 5B full closed
At 100 % output LV - 5A valve is full closed & LV - 5B full open
CASE B
VALVE 1
VALVE 2
25
50
% SIGNAL
100
The above figure shows opening of both valves as signal varies from 0 to 100 %
SIGNAL
%
0
25
50
75
100
Example
OPEN. OF VALVES
VALVE 1 VALVE 2
0
0
50
0
100
0
100
50
100
100
PV - 7 A & B .
IS - 01
IS - 02
IS - 03
IS - 04
IS - 05
IS - 06
IS - 08
IS - 09
IS - 10
IS - 11
IS - 12
IS - 16
DELAY: Minimum time for which a switch has to remain actuated to cause tripping
PLL 98
PLL 97
PLL 96
PSXH 31
WSXH 51
IS 02
On actuation of pump overspeed switch (SXH 51) , the pump return to minimum
speed. It can be restted only with the help of local hardware push button switch
provided.
IS - 4
This trip logic relates to HP CARBAMATE PUMP P-2. All the trip reasons are listed below
IXL 02
ZXH 501
XXH 501
TH 509
TH 510
TH 512
TH 516
TH 518
TH 515
PLL 522
PLL 527
PLL 508
PLL 508
PH521
TL 503
LL 504
IS - 5
This trip is actuated only when for following reasons
IS - 6
In case of instrument air failure PSXL 301 will actuate, the IS 06 will activate, and this will
result in the tripping of CO2 compressor (IS 01) and IS 02
IS - 8
The actuation of this trip will give start / off command to P 12 A/B.
IS - 9
This trip will be actuated only when hydrolyser temp goes very high (TXH 160 )
And this will result in closing HS inlet to R 02 (FV 165)
IS - 10
This trip will be actuated on following:
IXL 14
FXL 158 / 159