Professional Documents
Culture Documents
SUBCONTRACTOR DOCUMENT
COVER SHEET
Subcontractor Name: Ingeniera Especializada S.A. - IEB S.A.
Purchase Offer No.: SC-1611
Purchase Offer Title:
Rev.
Rev. Date
SC-1611-BT-P-12
03/25/2014
IMPORTANT
Should the Subcontractor consider that any comments made by the Purchaser change the Scope, the Subcontractor shall advise the
price and delivery implications of such changes within five working days of receipt. The Subcontractor must not incorporate such
changes without prior approval of the Purchaser of the revised price and/or delivery period. RETROSPECTIVE CLAIMS WILL NOT BE
CONSIDERED.
CBI Americas Ltd. 2008-2010. All rights reserved. Contains confidential information proprietary to CB&I, or its
affiliates, clients or suppliers and may not be used, reproduced or disclosed without CB&I's prior written permission.
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
DATE: 03/25/2014
Revision 1
Pgina 2
Substation number:
Voltage Level:
18
Relay Tag Number:
4160
Relay Type:
18-11M-339-005
SR339
Switchgear Tag
Number:
18-MCC-1-01A
Cubicle Number:
Firmware Version:
Unit 1RA
BL2A12001505
1.5
1. INITIAL CHECKS
1.1 Conditions of equipment necessary for testing
1.2 Safety conditions of the working site
1.3 Verify that no current exist through secondary circuits of the CTs
CHECK
IN SERVICE
TROUBLE
LOCKOUT
START INHIBIT
TRIP
ALARM
PICKUP
MAINTENANCE
STOPPED
STARTING
RUNNING
HOT RTD
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
DATE: 03/25/2014
Revision 1
Pgina 3
3. ELECTRICAL TESTS
The following tests will be performed based on the typical wiring diagram shown below.
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
DATE: 03/25/2014
Revision 1
Pgina 4
3.1 Analog current inputs measurement test (maximum error under the accuracy declared by manufacturer in the device's inputs specifications). This test will be done by
secondary injection of the currents shown in the following table, and its result will be positive if the calculated error is below the accuracy specified by the relay
manufacturer as stated in the reference manual.
Calculated Error
Injected Current (1)
Measured Current (2)
(3)={[(1)*CTR - (2)] / (1)*CTR}*100
Description
(A secondary)
(A Primary)
%
A
A1
20% of Rated
Current
30
50% of Rated
Current
2,5
2,5
100% of Rated
Current
Sequence
Current Test
2,5
B2
C3
75
150.1
30<358
75<118
150.1<238
OBSERVATIONS:
3.2 Analog voltage inputs measurement test (maximum error under the accuracy declared by manufacturer in the device's inputs specifications). This test will be done by
secondary injection of the currents shown in the following table, and its result will be positive if the calculated error is below the accuracy specified by the relay
manufacturer as stated in the reference manual.
Description
For the sequence current test this will be the positive sequence current value
For the sequence current test this will be the negative sequence current value
3
For the sequence current test this will be the zero sequence current value
2
Calculated Error
(3)={[(1)*VTR - (2)] / (1)*VTR}*100
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
DATE: 03/25/2014
Revision 1
Pgina 5
(V secondary)
(V Primary)
A-B
B-C
C-A
A-B
20% of Rated
Voltage
24
840
50% of Rated
Voltage
60
100% of Rated
Voltage
120
Voltage
Sequence Test
24
60
120
OBSERVATIONS:
La fase C no se encuentra conectada.
3.3 Self-test alarms inactive in the relay (front panel status LEDs or display)
4
5
6
For the sequence voltage test this will be the positive sequence voltage value
For the sequence voltage test this will be the negative sequence voltage value
For the sequence voltage test this will be the zero sequence voltage value
B-C
%
C-A
A-B
B-C
C-A
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
DATE: 03/25/2014
Revision 1
Pgina 6
3.4 Functional operation test of every function set in the coordination study. Attached to this protocol the summarized settings of the relay being tested are shown.
27
49
66
38
50
TCS
46
50G
47
51LR
IMPORTANT NOTE: Every protection function will be tested using the test set, and the detailed results will appear in the test report, as an attachment to this protocol
OBSERVATIONS:
3.5 Operation of all digital inputs available in the relay (digital input signal recognized by the relay).
C1 52a
C5 INPUT5
C9 INPUT9
C2 52b
C6 INPUT6
C10 INPUT10
C3 INPUT3
C7 INPUT7
C4 INPUT4
C8 INPUT8
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
Pgina 7
DATE: 03/25/2014
Revision 1
This test will be done by applying 125 Vdc from the auxiliary DC output of the test set to the specific input pair of terminals. For example, for testing C5 input, the positive polarity of
the DC signal must be applied to the C5 terminal and the negative polarity to C11 (Common reference terminal for the whole set of digital inputs). The change of state in the digital
input being tested must be verified through the Actual Values menu in the EnerVista SR3 Setup software after establishing connection with the relay being tested, as it is shown in
the next capture.
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
DATE: 03/25/2014
Revision 1
Pgina 8
3.6 Operation of all output contacts available in the relay (closing or opening of the output contacts from the activation of any logic programmed in the
relay).
A2-B3-A3
A8-B9-A9
B4-A4-B5
B10-A10-B11
A5-B6-A6
A11-B12-A11
B7-A7-B8
This test will be done through the activation of an auxiliary logic programmed just for the purpose of testing the output contacts. Such logic will be programmed as a bypass signal,
which means that by the activation of a contact input (using the same method explained before) the contact output being tested is activated. A graphic explanation for programming
this logic is given below:
3.7 Adequate operation of the logic functions programmed in the relay, if applicable, by activating the input elements of such logics, according to the logic scheme implemented
and using the wiring diagrams as a guide.
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
DATE: 03/25/2014
Revision 1
Pgina 9
3.8 All the records, statistics, counters and events reset upon completion of testing
SUBCONTRACTOR SIGNATURE
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
DATE: 03/25/2014
Revision 1
Pgina 10
4. FUNCTIONAL TESTS
4.1 Operation of all active digital inputs (digital input signal recognized by the relay)
Binary Input ID
DNP Point
(if applicable)
Operation Check
C Card INPUT 1
C Card INPUT 2
C Card INPUT 3
C Card INPUT 4
C Card INPUT 5
C Card INPUT 6
C Card INPUT 7
C Card INPUT 8
C Card INPUT 9
C Card INPUT 10
IMPORTANT NOTE: This test will have attached the wiring diagrams detailing the signals wired to the input contacts of the relay.
OBSERVATIONS:
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
DATE: 03/25/2014
Revision 1
Pgina 11
4.2 Operation of the programmed output contacts. Test every output by operating the controlled device (circuit breaker, auxiliary relay or alarm)
Binary Input ID
Operation Check
OUTPUT 1
OUTPUT 2
OUTPUT 3
OUTPUT 4
OUTPUT 5
OUTPUT 6
OUTPUT 7
IMPORTANT NOTE: This test will be done by secondary injection of a trip condition or by activating each logic element programmed to the active output contacts
OBSERVATIONS:
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
DATE: 03/25/2014
Revision 1
Pgina 12
4.3 Perform transfer and/or received DTT specifying the devices interacting
DTT Signal ID/Description
Transmission Check
Reception Check
IMPORTANT NOTE: This test will be done by secondary injection of a trip condition in the source device and checking the receiving of this signal in the destination device.
OBSERVATIONS:
4.4 Verify the correct processing of at least 25% of the signals configured in the DNP points tested. The following is the suggested 25% of the signals to be tested. For a
detailed and complete list of the DNP signals assigned to this specific relay, see the checklist attached at the end of this document.
DNP
Object
Variation
DNP Index
Modbus
Register
XX-11M-339-016_MCC Alarm
D.I
42215
XX-11M-339-016_PCS ON
D.I
42215
XX-11M-339-016_PCS OFF
D.I
43878
Operation
Check
DOCUMENT CODE:
SC-1611-BT-P-12
MULTILIN 339 MOTOR PROTECTION TESTING PROTOCOL
DATE: 03/25/2014
Revision 1
Pgina 13
DNP
Object
Variation
DNP Index
Modbus
Register
XX-11M-339-016_MCC Run
D.I
43879
XX-11M-339-016_MCC Stop
D.I
43880
XX-11M-339-016_MCC Fault/Trip
D.I
43881
XX-11M-339-016_SIS Command
D.I
43882
XX-11M-339-016_CB Open
D.I
30328
XX-11M-339-016_CB Closed
D.I
30330
XX-11M-339-016_Trip (86)
D.I
30332
XX-11M-339-016_Phase A Curr
A.I
30
30328
A.I
30
30330
XX-11M-339-016_Phase C Curr
A.I
30
30332
XX-11M-339-016_Neutral Curr
A.I
30
30326
Operation
Check
4.5 All the records, statistics, counters and events reset upon completion of testing