You are on page 1of 7

Federal Register / Vol. 70, No.

38 / Monday, February 28, 2005 / Notices 9629

Dated: February 23, 2005. Waiver, go to the U.S. Department of Samsung’s petition requests a waiver
Sally L. Stroup, Energy, Forrestal Building, Room 1J–018 from both the residential and
Assistant Secretary for Postsecondary (Resource Room of the Building commercial test procedures for its DVM
Education. Technologies Program), 1000 products, which are sold for both
[FR Doc. E5–799 Filed 2–25–05; 8:45 am] Independence Avenue, SW., residential and commercial use.
BILLING CODE 4000–01–P Washington, DC (202) 586–9127, As noted above, the test procedures
between 9 a.m. and 4 p.m., Monday for residential products appear at 10
through Friday, except Federal holidays. CFR Part 430, Subpart B, Appendix M.
Please call Ms. Brenda Edwards-Jones at For commercial package air-
DEPARTMENT OF ENERGY
the above telephone number for conditioning and heating equipment,
Office of Energy Efficiency and additional information regarding EPCA provides that the test procedures
Renewable Energy visiting the Resource Room. Please note: shall be those generally accepted
The Department’s Freedom of industry testing procedures developed
Energy Conservation Program for Information Reading Room (formerly or recognized by the Air-Conditioning
Consumer Products: Publication of the Room 1E–190 at the Forrestal Building) and Refrigeration Institute (ARI) or by
Petition for Waiver and Granting of the is no longer housing waiver petition the American Society of Heating,
Application for Interim Waiver of materials. Refrigerating and Air Conditioning
Samsung Air Conditioning From the Engineers (ASHRAE), as referenced in
FOR FURTHER INFORMATION CONTACT: Dr.
DOE Residential and Commercial ASHRAE/IES Standard 90.1 and in
Michael G. Raymond, U.S. Department
Package Air Conditioner and Heat effect on June 30, 1992. (42 U.S.C.
of Energy, Building Technologies
Pump Test Procedures (Case No. 6314(a)(4)(A)) This section also provides
Program, Mail Stop EE–2J, Forrestal
CAC–009) for the Secretary of Energy to amend the
Building, 1000 Independence Avenue,
test procedure for a product if the
AGENCY: Office of Energy Efficiency and SW., Washington, DC 20585–0121, (202)
industry test procedure is amended,
Renewable Energy, Department of 586–9611; e-mail:
unless the Secretary determines that
Energy. Michael.Raymond.ee.doe.gov; or
such a modified test procedure does not
Francine Pinto, Esq., or Thomas
ACTION: Notice of petition for waiver, meet the statutory criteria. (42 U.S.C.
DePriest, Esq., U.S. Department of
granting of application for interim 6314(a)(4)(B)) On October 21, 2004, the
Energy, Office of General Counsel, Mail
waiver, and solicitation of comments. Department published a direct final
Stop GC–72, Forrestal Building, 1000
rule, effective December 20, 2004,
SUMMARY: Today’s notice publishes a Independence Avenue, SW.,
adopting ARI Standard 210/240–2003
Petition for Waiver from Samsung Air Washington, DC 20585–0103, (202) 586–
for small commercial package air
Conditioning (Samsung). The Samsung 9507; e-mail:
conditioning and heating equipment
Petition requests a waiver of the test Francine.Pinto@hq.doe.gov, or
with capacities ≤65,000 Btu/h and ARI
procedures applicable to residential and Thomas.DePriest@hq.doe.gov.
Standard 340/360–2000 for small
commercial package air conditioners SUPPLEMENTARY INFORMATION: Title III of commercial package air conditioning
and heat pumps. The Department of the Energy Policy and Conservation Act and heating equipment with capacities
Energy (DOE) is soliciting comments, (EPCA) sets forth a variety of provisions ≥65,000 Btu/h and <135,000 Btu/h. (69
data, and information with respect to concerning energy efficiency. Part B of FR 61962) The capacities of Samsung’s
the Petition for Waiver. Title III (42 U.S.C. 6291–6309) provides DVM products sold for commercial use
Today’s notice also grants an Interim for the ‘‘Energy Conservation Program fall in a range covered by ARI Standard
Waiver to Samsung from the existing for Consumer Products other than 340/360–2000. Therefore, it is the
Department of Energy (DOE or Automobiles.’’ Part C of Title III (42 applicable test procedure for this
Department) test procedures applicable U.S.C. 6311–6317) provides for an commercial equipment.
to residential and commercial package energy efficiency program entitled The Department’s regulations contain
air conditioners and heat pumps. ‘‘Certain Industrial Equipment,’’ which provisions allowing a person to seek a
DATES: The Department will accept is similar to the program in Part B, and waiver from the test procedure
comments, data, and information with which includes commercial air requirements for covered consumer
respect to this Petition for Waiver not conditioning equipment, packaged products. These provisions are set forth
later than March 30, 2005. boilers, water heaters, and other types of in 10 CFR 430.27. The Department
ADDRESSES: You may submit comments, commercial equipment. proposed waiver provisions for covered
identified by case number CAC–009, by Today’s notice involves both commercial equipment on December 13,
any of the following methods: residential products under Part B, and 1999 (64 FR 69597), as part of the
• Mail: Ms. Brenda Edwards-Jones, commercial equipment under Part C. commercial furnace test procedure rule.
U.S. Department of Energy, Building Both parts specifically provide for The waiver provisions for commercial
Technologies Program, Mailstop EE–2J, definitions, test procedures, labeling equipment are substantively identical to
1000 Independence Avenue, SW., provisions, energy conservation those for covered consumer products.
Washington, DC 20585–0121. standards, and the authority to require The Department published a final rule
• Telephone: (202) 586–2945. Please information and reports from on October 21, 2004, codifying this
submit one signed paper original. manufacturers. With respect to test process in 10 CFR 431.201, effective
• Hand Delivery/Courier: Ms. Brenda procedures, both parts generally November 22, 2004. (69 FR 61915)
Edwards-Jones, U.S. Department of authorize the Secretary of Energy to The waiver provisions allow the
Energy, Building Technologies Program, prescribe test procedures that are Assistant Secretary for Energy Efficiency
Room 1J–018, 1000 Independence reasonably designed to produce results and Renewable Energy to waive
Avenue, SW., Washington, DC 20585. which reflect energy efficiency, energy temporarily test procedures for a
Docket: For access to the docket to use and estimated annual operating particular basic model when a petitioner
read copies of public comments costs, and that are not unduly shows that the basic model contains one
received, this notice, and the Petition burdensome to conduct. (42 U.S.C. or more design characteristics that
for Waiver and Application for Interim 6293, 6314) prevent testing according to the

VerDate jul<14>2003 16:34 Feb 25, 2005 Jkt 205001 PO 00000 Frm 00022 Fmt 4703 Sfmt 4703 E:\FR\FM\28FEN1.SGM 28FEN1
9630 Federal Register / Vol. 70, No. 38 / Monday, February 28, 2005 / Notices

prescribed test procedures, or when the AVMDH072CAOU, AVMDC072CAOU, Waiver is denied, if it appears likely
prescribed test procedures may evaluate AVMWH020CAOU, that the Petition for Waiver will be
the basic model in a manner so AVMWCH020CAOU, granted, and/or the Assistant Secretary
unrepresentative of its true energy AVMWH032CAOU, AVMWC032CAOU, determines that it would be desirable for
consumption as to provide materially AVMWH040CAOU, AVMWC040CAOU, public policy reasons to grant
inaccurate comparative data. (10 CFR AVMWH052CAOU, AVMWC052CAOU, immediate relief pending a
Sections 430.27(a)(1), 431.201(a)(1)) AVMWH072CAOU, AVMWC072CAOU. determination on the Petition for
Waivers generally remain in effect until For these products, the applicable test Waiver. (10 CFR 430.27(g),
final test procedure amendments procedure is the residential test 431.201(e)(3))
become effective, thereby resolving the procedure contained in 10 CFR Part 430, Samsung’s Application for Interim
problem that is the subject of the Subpart B, Appendix M. Waiver does not provide sufficient
waiver. Samsung seeks a waiver from the information to evaluate what, if any,
The waiver process also allows the applicable test procedures because, economic hardship Samsung will likely
Assistant Secretary for Energy Efficiency Samsung asserts, the current test experience if its Application for Interim
and Renewable Energy (Assistant procedures evaluate its DVM (Digital Waiver is denied. However, in those
Secretary) to grant an Interim Waiver Variable Multi) systems in a manner not instances where the likely success of the
from test procedure requirements to representative of their true energy Petition for Waiver has been
manufacturers that have petitioned DOE efficiency. Samsung claims that the demonstrated, based upon DOE having
for a waiver of such prescribed test energy usage of its DVM systems cannot granted a waiver for a similar product
procedures. (10 CFR 430.27(a)(2), be representatively measured using the design, it is in the public interest to
431.201(a)(2)) An Interim Waiver current test procedures for the following have similar products tested and rated
remains in effect for a period of 180 reasons: for energy consumption on a
days or until DOE issues its 1. Unlike the DVM system, no product comparable basis. For Samsung’s
determination on the Petition for currently for sale in the U.S. offers the commercial DVM products, it appears
Waiver, whichever is sooner, and may ability of a direct expansion system to likely that the Petition for Waiver will
be extended for an additional 180 days, vary its capacity every 20 seconds be granted. The Samsung DVM products
if necessary. between 10% and 100% of the building are quite similar to the Mitsubishi City
On October 7, 2003, Samsung filed an design load, and no existing test Multi products, for which DOE granted
Application for Interim Waiver and a procedure can provide a method for a waiver. (69 FR 52660, August 27,
Petition for Waiver from the test rating at those capacity points. 2004) The Mitsubishi waiver was
procedures applicable to residential and 2. No existing test procedure requires granted because Mitsubishi’s products
commercial package air conditioning calculating Integrated Part Load Values cannot be tested according to the
and heating equipment. In particular, (IPLV) in the heating mode. prescribed test procedures, for two
Samsung requested a waiver from the 3. No existing test procedure accounts reasons: (1) Test laboratories cannot test
residential test procedures contained in for the benefits of the DVM system’s products with so many indoor units (up
10 CFR Part 430, Subpart B, Appendix zoned cooling. No existing test standard to sixteen—the practical limit is about
M, and, for commercial products, a allows for the inherent benefits of five); and (2) there are 58 indoor unit
waiver from the test procedures in ARI eliminating duct loss in a ductless models, so for each outdoor unit, there
210/240 (1989), and from the test system. are well over 1,000,000 combinations,
procedures contained in ARI 210/240 4. No existing test procedure provides and it is impractical to test so many
(1994), that the Department, at the time, a method for testing and rating a system combinations.
proposed to adopt. As discussed above, that utilizes one outdoor unit and Samsung’s commercial outdoor units
for Samsung’s commercial products, the sixteen indoor units. are capable of operating up to sixteen
applicable test procedure is now ARI 5. No existing test procedure can indoor units. Samsung’s system also
340/360–2000. Samsung requests a provide a method for rating systems allows for over 1,000 combinations of
waiver from the test procedures for the where the type and capacity of the indoor and outdoor units. The upper
following basic product models: indoor unit can be mixed in the same limit on the number of indoor units that
Commercial: Any product using these system. The DVM system can mix are currently able to be tested is about
outdoor units: RVMH100FAMOU, together six different indoor models six. The Samsung commercial systems
RVMC100FAMOU, RVMC070FAMOU. with seven different capacities, resulting (with 100k and 72k Btu/hr outdoor
For these products, the applicable test in over 1,000 combinations. units) will therefore experience the
procedure is ARI 340/360–2000. The Samsung petition requests that same testing problems that prompted
Residential: Any product using these DOE grant a waiver from existing test DOE to grant Mitsubishi a waiver.
outdoor units: RVMH050CBMOU, procedures until such time as a Samsung’s residential models, with a
RVMC050CBMOU. DVM indoor units: representative test procedure is 50k Btu/hr outdoor unit, are capable of
AVMKH020CAOU, AVMKC020CAOU, developed and adopted for this class of operating up to seven indoor units. This
AVMKH032CAOU, AVMKC032CAOU, products. Samsung intends to work with would still be difficult to test, but it is
AVMKH040CAOU, AVMKC040CAOU, ARI to develop appropriate test not clear that it could not be tested.
AVMCH052CAOU, AVMCC052CAOU, procedures. However, although it may be possible to
AVMCH072CAOU, AVMCC072CAOU, Samsung also requested an Interim test Samsung’s residential DVM
AVMCH105CAOU, AVMCC105CAOU, Waiver to allow it to work with systems, it is not practical to do so. For
AVMBH020CAOU, AVMBC020CAOU, manufacturers of similar products and standard split system air conditioners
AVMBH032CAOU, AVMBC032CAOU, industry organizations to develop a test with one indoor unit, DOE’s regulations
AVMBH040CAOU, AVMBC040CAOU, procedure that accurately reflects the allow use of an alternative rating
AVMBH052CAOU, AVMBC052CAOU, operation and energy consumption of method (ARM) for generating efficiency
AVMBH072CAOU, AVMBC072CAOU, these types of units. An Interim Waiver ratings of different combinations of
AVMHH105CAOU, AVMHC105CAOU, will be granted if it is determined that indoor and outdoor units. There is no
AVMHH128CAOU, AVMHC105CAOU, the applicant will experience economic such ARM for systems with more than
AVMDH052CAOU, AVMDC052CAOU, hardship if the Application for Interim one indoor unit, so Samsung would

VerDate jul<14>2003 16:34 Feb 25, 2005 Jkt 205001 PO 00000 Frm 00023 Fmt 4703 Sfmt 4703 E:\FR\FM\28FEN1.SGM 28FEN1
Federal Register / Vol. 70, No. 38 / Monday, February 28, 2005 / Notices 9631

have to test every combination offered October 7th 2003 into the zones, however it will operate to
for sale. With up to seven indoor units Mr. Michael Raymond satisfy the building demands in the following
of six different types, thousands of Office of Building Research and Standards manner—
combinations are possible, and it would United States Department of Energy First unit calling for operation
not be practical to test so many 1000 Independence Avenue, SW Majority rules for the building
Washington, DC 20585–0121 All other zone requirements
combinations. This is the second of the
two reasons for which Mitsubishi Dear Mr. Raymond The Outdoor and Indoor units
I am writing this letter to you in regard to communicate the control information listed
received a waiver; therefore, it appears
the process for a Petition for Waiver and above every 20 seconds to calculate the
likely that Samsung’s residential DVM indoor capacity required for the next 20
application for interim waiver of test
products will also be granted a waiver. seconds of operation, allowing the unit to
procedures.
Therefore, Samsung’s Application for Samsung Air Conditioning, acting through correctly assess the load characteristics of the
an Interim Waiver from the DOE test it’s exclusive distributors in the USA, building and adjust the capacity output
procedure for its DVM systems is Quietside Corporation hereby petitions the accordingly.
granted. Hence, it is ordered that: United States Department of Energy for a The method for controlling the capacity is
The Application for Interim Waiver Waiver of all Test procedures and makes to vary the quantity of refrigerant flowing
filed by Samsung is hereby granted for application for an interim waiver pursuant to through the entire system at any given time.
any Samsung DVM product using these the provisions of 10 CFR 431.29. The compressor(s) used in the Samsung
To support this petition, please consider DVM system are manufactured by Copeland
outdoor units: RVMH100FAMOU, in Sidney OH, and are a ‘‘Digital Scroll’’ type.
RVMC100FAMOU, RVMC070FAM0U, the following submission.
This revolutionary compressor allows the
RVMC050CBM0U, and 1. Models Covered by the Scope of This system capacity to be varied from 10% to
RVMH050CBM0U. Samsung shall not Petition 100% depending on the indoor load. This is
be required to test or rate these products The Samsung DVM system products accomplished by allowing the fixed and
on the basis of the currently applicable consist of three capacities of Outdoor units, orbiting scrolls inside the compressor to
test procedure, which is ARI 340/360– nominally 100,000 Btu/h, 72,000 Btu/h and separate during unloaded periods, which
2000 for the first three of the above 50,000 Btu/h, operating on 208/230V–3Ph– stops refrigerant flow through the compressor
60Hz (100k & 72k units) and 208/230V–1Ph– and operates the compressor motor in an
outdoor units, which are commercial, unloaded fashion, which greatly reduces the
60Hz (50k unit).
and the test procedures contained in 10 power consumed by the compressor,
These units are available in both Cooling
CFR Part 430, Subpart B, Appendix M, only and Heat Pump models (72k is Cooling The outdoor unit also uses variable speed
for the latter two, which are residential. only) and these outdoor units can be matched condenser fan motor(s) which can alter
This Interim Waiver is based upon the with six different types of indoor unit— condenser airflow to exactly suit the outdoor
presumed validity of statements and Built in Duct air temperature and building load to ensure
allegations submitted by the company. Low Silhouette Duct the unit operates in the most efficient manner
This Interim Waiver may be removed or High Static Pressure Duct possible.
modified at any time upon a 4 Way Ceiling Cassette The Indoor units all utilize an Electronic
1 Way Ceiling Cassette Expansion Valve (EEV) which operates over
determination that the factual basis a 480 step range from fully closed to fully
underlying the Application is incorrect. High Wall Mount unit
open. This extensive range allows precise
The Interim Waiver shall remain in These indoor units are available in monitoring of the refrigerant quantity
effect for a period of 180 days or until capacities from 7,000 Btu/h to 44,000 Btu/h entering the evaporator coil and hence the
DOE acts on the Petition for Waiver, depending on the model type. cooling or heating capacity of the unit.
whichever is sooner, and may be Appendix 1: Full model list and description This type of product will almost always
extended for an additional 180-day of items covered by petition operate below the 100% capacity threshold
period, if necessary. 2. Inherent Characteristics of the Samsung (part load versus full load operation), and
The Department is publishing DVM System due to the enhanced capacity control range
of the DVM system it can operate at 10%
Samsung’s Petition for Waiver in its The Samsung DVM system is a Commercial capacity if the building load has reduced to
entirety. The Petition contains no and Residential multi split, multi zoned that point.
confidential information. The variable refrigerant flow system that will This type of operation is very similar to the
Department solicits comments, data, provide either heating or cooling to the Water Chilling units as detailed in ARI
and information with respect to the building as dictated by the individual zone standard 550/590.
Petition. The Department is particularly temperature.
The 100k & 72k Outdoor units are capable 3. Waiver Requirements
interested in receiving comments and
of operating up to 16 indoor units, and the Samsung/Quietside seeks a waiver of all
views of interested parties concerning 50,000 Btu/h Outdoor unit is capable of current test standards until a test standard
any alternate test procedures, operating up to 7 indoor units can be developed and adopted that will
modifications to test procedures, or All of the indoor units are capable of provide the HVAC market in the United
alternative rating methods, which the operating independently, with their own States (US) with a fair and accurate
Department could use to fairly represent temperature and fan speed setting. Based on assessment of the DVM system energy
the energy efficiency of Samsung’s DVM those controls the outdoor unit will then consumption and efficiency levels.
products. Any person submitting determine the cooling or heating capacity The current test procedures in place may
delivered into the zones. The outdoor unit evaluate the DVM system in a manner that
written comments must also send a
uses the following inputs to determine the is not representative of the true energy
copy of such comments to the capacity required by the zone—
petitioner. 10 CFR 430.27(b)(1)(iv). efficiency of the DVM system and provide
Set Temperature (User selectable) inaccurate ratings which would be used to
Issued in Washington, DC, on February 22, Room temperature (Measured in the return compare the DVM system with other forms
2005. air of the unit) of Air Conditioning/Heat Pumps in the
David K. Garman, Refrigerant temperature at the Evaporator market.
Assistant Secretary, Energy Efficiency and Inlet Due to the constant variation of the system
Renewable Energy. Refrigerant temperature at the Evaporator capacity it is patently inaccurate to rate the
Outlet unit at its full load capacity or at any other
Samsung Air Conditioning Outdoor ambient temperature fixed point of capacity when the unit
2865 Pellissier Place The Samsung DVM system cannot provide capacity is constantly varying between 10%
Whittier CA 90601 simultaneous Heating and Cooling functions and 100% of the capacity.

VerDate jul<14>2003 16:34 Feb 25, 2005 Jkt 205001 PO 00000 Frm 00024 Fmt 4703 Sfmt 4703 E:\FR\FM\28FEN1.SGM 28FEN1
9632 Federal Register / Vol. 70, No. 38 / Monday, February 28, 2005 / Notices

Any test method utilized to rate these types and still not be at 100% capacity load. The Samsung test data, showing EER values
of full variable refrigerant flow units should total number of unit combinations available (Watt for Watt) shows almost a full EER point
be indicative of the ability of these units to is over 1,000, not including the ability to over increase over VAV and compressor control
operate at 10%, 20%, 30% * * * 100% as or under size the indoor capacity with regard units, and a similar increase over an Inverter
this is the true operation of the unit in the to the outdoor unit capacity. Variable Refrigerant Flow system. This test
field. data is included in Appendix 2.
During 2002 a committee was formed by 4. Similar Equipment Currently Offered for
The disadvantage of the lack of an
ARI to discuss alternate test methods for this Sale in the U.S.
applicable test standard will not only impact
type of multi split variable refrigerant flow Sanyo the potential sales of the DVM system, but
unit, however to this date no additional test Mitsubishi Comfort Systems also result in economic losses not only for
methodology has been adopted by the Mitsubishi Electric U.S. Samsung and Quietside but also for the
committee. As the Department is aware the The above companies currently offer Copeland Corporation who have spent
timeframe for drafting and approving such a similar systems for sale in the United States, considerable time and resources in
standard may be months or even years. The these systems offer similar advantages and developing the ‘‘Digital Scroll’’ compressors.
International Standards Organization have energy savings inherent to all Variable Samsung/Quietside formally urges the
been currently working on a standard of their Refrigerant Flow units, however no other Department to grant an interim waiver from
own for several years at this point in time. manufacturer utilizes the ‘‘Digital Scroll’’ existing test standards and allow Quietside to
Due to the lack of an approved standard at technology and the capacity range of the work in conjunction with the other
this present time, the energy savings DVM system. manufacturers of Variable Refrigerant Flow
provided by the DVM System would not be Mitsubishi Electric U.S. currently has a test products and the various organizations
accurately represented should it be tested waiver proposal in front of the Department involved in our industry to formulate a test
under the current standards. This inaccurate that has been published for comment in the standard that accurately reflects the
representation will have a negative impact Federal Register. operation and energy consumption of these
upon the sales of both the Samsung DVM types of units.
system and other Variable Refrigerant 5. Reasons for Granting a Test Waiver to the
Should the Department have any
Volume systems. This will not only greatly DVM System
comments or questions regarding this
affect the business revenue of Quietside and The Samsung DVM System is currently petition please do not hesitate to contact the
Samsung, but it will prevent the country offered for sale in the U.S. marketplace, undersigned.
from realizing energy savings, particularly in however the lack of an existing or proposed Yours truly,
the area of peak load usage reduction. test standard has resulted in the unit having
To summarize, the test waiver for the DVM to be provided with Energy Guide labels John Miles
system is requested for the following reasons: detailing a 10 SEER, the lowest possible Director of Engineering and Technical
A. No product currently for sale in the rating. The true SEER of the DVM system Support
USA offers the ability of a direct expansion would be a minimum of 50% higher. Appendix 1 : Full Model List Samsung DVM
system to vary its capacity every 20 seconds This failure to correctly rate the energy System Products
between 10% and 100% of the building efficiency of the unit also does not allow the Appendix 2 : Samsung performed Tests
design load, and no existing test standard can performance of the DVM system to be detailing Energy Efficiency versus
provide a method for providing ratings at certified by the ARI (no applicable test Delivered Capacity for the DVM System
those capacity points. standard or test availability), which causes a
B. No existing test standard allows for IPLV misconception of the efficiency level of the I hereby certify that copies of this petition
to be calculated in the Heating mode. DVM system and provides wholly inaccurate and application for Interim Waiver of test
C. No existing test standard provides for data to the U.S. consumer. standards have been mailed to the following
the benefits of diversity due to the inherent These types of Variable Refrigerant Flow companies who are known to market similar
ability of the DVM System to provide zoned products are very well established in the Variable Refrigerant Flow products
cooling. Also no existing test standard Asian and European markets, based on the Mitsubishi Electric US
provides for credit for negating duct loss high levels of efficiency and comfort 4505–A Newpoint Place
from the nonducted units available with this provided to the end user. U.S. consumers Lawrenceville GA 30043
system. should not be excluded from these benefits Attn: William Rau, President, HVAC
D. No existing test standard provides a due to the lack of an applicable test standard, Advanced Products Division
method to test and rate a system that utilizes and should not be beholden to inaccurate Sanyo
one outdoor unit and 16 indoor units. data that will heavily disadvantage the DVM 1165 Allgood Road, Suite #22
E. No existing test standard can provide a system or any other Variable Refrigerant Marietta, GA 30062
method for rating systems where the type and Flow system in a very competitive Attn: Tetsushi Yamashita, Engineering
capacity of indoor unit can be used. The marketplace. Manager, HVAC
DVM system can mix 6 different indoor Independent testing of the DVM system Mitsubishi Heavy Industries Climate Control
models in up to 7 different capacities. For against conventional Air conditioning Inc
example a 100,000 Btu/h system can use 2 x systems shows an average of over 30% 3030 E. Victoria Street
11,000 Btu/h units of different models, 2 x reduction on energy consumption, not even Rancho Dominguez CA 90221
13,000 Btu/h units of additional models, 2 x including the reduction in peak load Attn: Caesar Ceballos, Technical Support
24,000 Btu/h models from additional models operating consumption. Manager

APPENDIX 1.—SAMSUNG DVM SYSTEM PRODUCTS AND CAPACITIES


Btu/h cooling/
2003 Model Description heating

RVMH100FAMOU ................................... Condensing Unit Heat Pump ..................................................................................... 95,500/107,500


RVMC100FAMOU ................................... Condensing Unit Cooling Only .................................................................................. 95,500/107,500
RVMH050CBMOU ................................... Condensing Unit Heat Pump ..................................................................................... 50,000/55,000
RVMC050CBMOU ................................... Condensing Unit Cooling Only .................................................................................. 50,000/55,000
RVMC070FAMOU ................................... Condensing Unit Cooling Only .................................................................................. 76,000/85,000
AVMKH020CAOU .................................... 1–Way Ceiling Cassette Heat Pump ......................................................................... 7,000/7,500
AVMKC020CAOU .................................... 1–Way Ceiling Cassette Cooling Only ...................................................................... 7,000/7,500
AVMKH032CAOU .................................... 1–Way Ceiling Cassette Heat Pump ......................................................................... 11,000/12,000
AVMKC032CAOU .................................... 1–Way Ceiling Cassette Cooling Only ...................................................................... 11,000
AVMKH040CAOU .................................... 1–Way Ceiling Cassette Heat Pump ......................................................................... 13,500/14,500

VerDate jul<14>2003 16:34 Feb 25, 2005 Jkt 205001 PO 00000 Frm 00025 Fmt 4703 Sfmt 4703 E:\FR\FM\28FEN1.SGM 28FEN1
Federal Register / Vol. 70, No. 38 / Monday, February 28, 2005 / Notices 9633

APPENDIX 1.—SAMSUNG DVM SYSTEM PRODUCTS AND CAPACITIES—Continued


Btu/h cooling/
2003 Model Description heating

AVMKC04OCAOU ................................... 1–Way Ceiling Cassette Cooling Only ...................................................................... 13,500


AVMCH052CAOU ................................... 4–Way Ceiling Cassette Heat Pump ......................................................................... 18,000/19,000
AVMCC052CAOU ................................... 4–Way Ceiling Cassette Cooling Only ...................................................................... 18,000
AVMCH072CAOU ................................... 4–Way Ceiling Cassette Heat Pump ......................................................................... 24,000/26,000
AVMCC072CAOU ................................... 4–Way Ceiling Cassette Cooling Only ...................................................................... 24,000
AVMCH105CAOU ................................... 4–Way Ceiling Cassette Heat Pump ......................................................................... 36,000/39,000
AVMCC105CAOU ................................... 4–Way Ceiling Cassette Cooling Only ...................................................................... 36,000
AVMBH020CAOU .................................... Built-In Duct Heat Pump ............................................................................................ 7,000/7,500
AVMBC020CAOU .................................... Built-In Duct Cooling Only ......................................................................................... 7,000
AVMBH032CAOU .................................... Built-In Duct Heat Pump ............................................................................................ 11,000/12,000
AVMBC032CAOU .................................... Built-In Duct Cooling Only ......................................................................................... 11,000
AVMBH040CAOU .................................... Built-In Duct Heat Pump ............................................................................................ 13,500/14,500
AVMBC040CAOU .................................... Built-In Duct Cooling Only ......................................................................................... 13,500
AVMBH052CAOU .................................... Built-In Duct Heat Pump ............................................................................................ 18,000/19,000
AVMBC052CAOU .................................... Built-In Duct Cooling Only ......................................................................................... 18,000
AVMBH072CAOU .................................... Built-In Duct Heat Pump ............................................................................................ 24,000/26,000
AVMBC072CAOU .................................... Built-In Duct Cooling Only ......................................................................................... 24,000
AVMHH105CAOU ................................... HSP Duct Heat Pump ............................................................................................... 36,000/39,000
AVMHC105CAOU ................................... HSP Duct Cooling Only ............................................................................................. 36,000
AVMHH128CAOU ................................... HSP Duct Heat Pump ............................................................................................... 44,000/47,000
AVMHC128CAOU ................................... HSP Duct Cooling Only ............................................................................................. 44,000
AVMDH052CAOU ................................... Low Silhouette Duct Heat Pump ............................................................................... 18,000/19,000
AVMDC052CAOU ................................... Low Silhouette Cooling Only ..................................................................................... 18,000
AVMDH072CAOU ................................... Low Silhouette Duct Heat Pump ............................................................................... 24,000/26,000
AVMDC072CAOU ................................... Low Silhouette Cooling Only ..................................................................................... 24,000
AVMWH020CAOU ................................... High Wall Mount Heat Pump ..................................................................................... 7,000/7,500
AVMWC020CAOU ................................... High Wall Mount Cooling Only .................................................................................. 7,000
AVMWH032CAOU ................................... High Wall Mount Heat Pump ..................................................................................... 11,000/12,000
AVMWC032CAOU ................................... High Wall Mount Cooling Only .................................................................................. 11,000
AVMWH040CAOU ................................... High Wall Mount Heat Pump ..................................................................................... 13,500/14,500
AVMWC040CAOU ................................... High Wall Mount Cooling Only .................................................................................. 13,500
AVMWH052CAOU ................................... High Wall Mount Heat Pump ..................................................................................... 18,000/19,000
AVMWC052CAOU ................................... High Wall Mount Cooling Only .................................................................................. 18,000
AVMWH072CAOU ................................... High Wall Mount Heat Pump ..................................................................................... 24,000/26,000
AVMWC072CAOU ................................... High Wall Mount Cooling Only .................................................................................. 24,000

BILLING CODE 6450–01–P

VerDate jul<14>2003 16:34 Feb 25, 2005 Jkt 205001 PO 00000 Frm 00026 Fmt 4703 Sfmt 4703 E:\FR\FM\28FEN1.SGM 28FEN1
9634 Federal Register / Vol. 70, No. 38 / Monday, February 28, 2005 / Notices

EN28FE05.055</GPH>

VerDate jul<14>2003 16:34 Feb 25, 2005 Jkt 205001 PO 00000 Frm 00027 Fmt 4703 Sfmt 4703 E:\FR\FM\28FEN1.SGM 28FEN1
Federal Register / Vol. 70, No. 38 / Monday, February 28, 2005 / Notices 9635

[FR Doc. 05–3782 Filed 2–25–05; 8:45 am] Online service, please e-mail 3. Idaho Power Company
BILLING CODE 6450–01–C FERCOnlineSupport@ferc.gov, or call [Docket No. ER97–1481–007]
(866) 208–3676 (toll free). For TTY, call
(202) 502–8659. Take notice that on February 17, 2005,
DEPARTMENT OF ENERGY Comment Date: 5 p.m. eastern time on Idaho Power (IPC) submitted an
March 4, 2005. amendment to its January 19, 2005,
Federal Energy Regulatory filing regarding IPC’s revised generation
Commission Linda Mitry, market power screen analysis.
Deputy Secretary. Comment Date: 5 p.m. eastern time on
[Docket Nos. EL00–95–125 and EL00–98–
112] [FR Doc. E5–787 Filed 2–25–05; 8:45 am] February 25, 2005.
BILLING CODE 6717–01–P
4. PacifiCorp PPM Energy, Inc.
San Diego Gas & Electric Company,
Complainants v. Sellers of Energy and [Docket No. ER97–2801–005 and ER03–478–
Ancillary Services Into Markets DEPARTMENT OF ENERGY 004]
Operated by the California Take notice that on February 14, 2005,
Independent System Operator and the Federal Energy Regulatory PacifiCorp and PPM Energy, Inc.
California Power Exchange, Commission tendered for filing an updated market
Respondents; Investigation of [Docket No. EC05–20–000, et al.] power analysis.
Practices of the California Independent Comment Date: 5 p.m. eastern time on
System Operator and the California PPL Sundance Energy, LLC, et al.; March 4, 2005.
Power Exchange; Notice of Electric Rate and Corporate Filings
Compliance Filing 5. Pacific Gas and Electric Company
February 18, 2005.
[Docket No. ER03–1091–007]
February 18, 2005. The following filings have been made
with the Commission. The filings are Take notice that on February 11, 2005,
On February 11, 2005, the City of Pacific Gas and Electric Company
Pasadena (Pasadena) submitted its listed in ascending order within each
docket classification. (PG&E) tendered for filing an
emissions calculations in compliance
amendment to its December 30, 2004,
with the Commission’s Order issued 1. PPL Sundance Energy, LLC, PPL compliance filing regarding a Generator
November 23, 2004, in Docket Nos. Energy Plus, LLC, Arizona Public Special Facilities Agreement and
EL00–95–100 and EL00–98–088, 109 Service Company Generator Interconnection Agreement
FERC ¶ 61,218.
[Docket No. EC05–20–000] between PG&E and Duke Energy Morro
Any person desiring to intervene or to
Bay LLC (Duke Morro Bay).
protest this filing must file in Take notice that on February 11, 2005,
accordance with Rules 211 and 214 of PPL Sundance Energy, LLC (PPL PG&E states that copies of this filing
the Commission’s Rules of Practice and Sundance), PPL Energy Plus, LLC and have been served upon Duke Morro Bay,
Procedure (18 CFR 385.211, 385.214). Arizona Public Service Company (APS) the California Independent System
Protests will be considered by the (collectively, Applicants) filed with the Operator Corporation and the California
Commission in determining the Federal Energy Regulatory Commission Public Utilities Commission.
appropriate action to be taken, but will a response to a deficiency letter issued Comment Date: 5 p.m. eastern time on
not serve to make protestants parties to on January 28, 2005, by Jamie L. Simler, March 4, 2005.
the proceeding. Any person wishing to Director, Division of Tariffs and Market 6. The Detroit Edison Company
become a party must file a notice of Development—West, in connection with
[Docket Nos. ER04–14–006 and EL04–29–
intervention or motion to intervene, as a section 203 application filed for 006]
appropriate. Such notices, motions, or authorization to acquire a 450 megawatt
protests must be filed on or before the generating facility owned by PPL Take notice that on February 11, 2005,
comment date. Anyone filing a motion Sundance. Applicants request The Detroit Edison Company (Detroit
to intervene or protest must serve a copy confidential treatment of certain Edison) filed an amendment to its
of that document on the Applicant and supporting data contained in the filing. Ancillary Services Tariff, First Revised
all the parties in this proceeding. Comment Date: 5 p.m. eastern time on Volume No. 5, filed on December 2,
The Commission encourages March 2, 2005. 2004 to repaginate the tariff sheets in
electronic submission of protests and compliance with Order No. 614.
2. Duke Power, a Division of Duke Comment Date: 5 p.m. eastern time on
interventions in lieu of paper using the
Power Corporation March 4, 2005.
‘‘eFiling’’ link at http://www.ferc.gov.
Persons unable to file electronically [Docket Nos. ER96–110–013 and EL05–4– 7. California Independent System
should submit an original and 14 copies 000]
Operator Corporation
of the protest or intervention to the Take notice that on February 14, 2005,
Federal Energy Regulatory Commission, Duke Power, a division of Duke Energy [Docket No. ER05–277–001]
888 First Street, NE., Washington, DC Corporation (Duke Power) submitted a Take notice that on February 14, 2005,
20426. filing in compliance with the the California Independent System
This filing is accessible on-line at Commission’s order issued December Operator Corporation (ISO) submitted a
http://www.ferc.gov, using the 15, 2004, in Docket No. ER96–110–010, filing in compliance with the
‘‘eLibrary’’ link and is available for et al., 109 FERC ¶ 61,270. Commission’s order issued January 28,
review in the Commission’s Public Duke Power states that copies of the 2005, in Docket No. ER05–277–000, 110
Reference Room in Washington, DC. filing were served on parties on the FERC ¶ 61,082.
There is an ‘‘eSubscription’’ link on the official service list in the above- The ISO states that the filing has been
Web site that enables subscribers to captioned proceed as well as its State served on all parties on the official
receive e-mail notification when a commissions. service list for this proceeding. In
document is added to a subscribed Comment Date: 5 p.m. eastern time on addition, the ISO states that it has
docket(s). For assistance with any FERC March 4, 2005. posting the filing on the ISO home page.

VerDate jul<14>2003 16:34 Feb 25, 2005 Jkt 205001 PO 00000 Frm 00028 Fmt 4703 Sfmt 4703 E:\FR\FM\28FEN1.SGM 28FEN1

You might also like