FAULT CURRENT CALCULATION FOR HT (UP TO NEAREST MOTOR TERMINAL FROM SOURCE)
1.1
33
500
ZO
1.2
IFO
KV
MVA
2
System KV
Short Circuit MVA
ohm
Square (33)
500
ohm
2.178
ohm
1.1 X KV
3 X ZO
kA
1.1 x 33
3 X 2.178
kA
9.62
kA
2.1
Main Incoming power supply through 33kV, 1R X 3C X 300Sq.mm. Aluminium armoured Cable from APTRANSCO Substation to Plant
Substation
Resistance of cable ( R ) (Resistance / Km)
=
0.130
ohm/Km
Length of Cable (L)
1500
R x L
(N x 1000)
ohm
0.195
ohm
0.100
ohm/Km
X x L
(N x 1000)
ohm
0.150
ohm
(Ra2 + Xa2)
ohm
0.2460
ohm
Za + Zo
2.425
Xa
2.3
2.4
Za
Z1
2.5
IF1
1.1 X KV
3 X Z1
Meter
No.
ohm
kA
( 1.1 X 33)
( 3 X 2.425)
kA
8.643
kA
3.1
0.130
25
Meter
No.
R x L
(N x 1000)
ohm
0.00325
ohm
0.100
X x L
(N x 1000)
ohm
0.0025
ohm
(Rb2 + Xb2)
ohm
Xb
3.3
ohm/km
ohm/Km
Zb
3.4
3.5
IF2
0.0041
ohm
Zb + Z1
ohm
2.430
ohm
1.1 X KV
kA
3 X Z2
( 1.1 X 0.15)
( 3 X 2.43)
kA
8.625
kA
4.1
4.2
Vp
33
KV
Vs
6.6
KV
Transformer Capacity
8000
KVA
% Impedance
8.35
Zc
(8.35/100) x 6.6)
(8000/1000)
Zc
Z3
4.3
IF3
0.455
ohm
ohm
{((Vs)/ (Vp))x Z2 }+ Zc
ohm
ohm
0.553
1.1 X KVs
3 X Z3
ohm
KA
( 1.1 X X x L)
( 3 X 0.553)
kA
7.580
KA
5.1
0.129
25
Meter
No.
R x L
(N x 1000)
Rd
5.2
Xd
5.3
5.4
5.5
IF4
ohm/km
ohm
0.001075
0.0830
X x L
(N x 1000)
ohm
0.000691667
ohm
ohm
ohm/Km
(Rd + Xd )
ohm
0.0013
ohm
Zd + Z3
0.555
1.1 X KV
3 X Z4
ohm
kA
( 1.1 X )
( 3 X 0.555)
kA
7.553
kA
6.1
0.264
180
Re
6.2
Xe
6.3
6.4
6.5
R x L
(N x 1000)
No.
ohm
0.04752
ohm
0.0890
ohm/Km
X x L
(N x 1000)
ohm
0.01602
ohm
(Re2 + Xe2)
ohm
0.0501
ohm
Ze + Z4
0.606
IF5
ohm/km
Meter
1.1 X KV
3 X Z5
ohm
kA
( 1.1 X X x L)
( 3 X 0.606)
kA
6.917
kA