Professional Documents
Culture Documents
FIRE DETECTORS
Range of application
Your advantages
Function
OWMX 95
The multi-sensor detector OWMX 95 is an optical smoke
detector combined with a heat detector in one housing.
The analysis of the measuring signals can be performed
applying either the linked mode or the separated mode
based on smoke or heat by selecting the stages 1-5. This
guarantees continuous response to many classes of fire.
A synthesis of high-grade optoelectronic and thermoelectronic sensor technology and distributed system
intelligence in detector and detection control panel
guarantee the functional reliability.
OMX 95
The optical smoke detector OMX 95 is a light scatter
detector containing a measuring chamber shielded
against daylight. The measuring chamber consists of a
labyrinth, a pulsating IR-LED and a photodiode placed
outside the IR ray. As soon as smoke penetrates into
the measuring chamber, the pulsating IR light ray will
be scattered and registered by the photodiode. Depending on the selected sensitivity 1 to 5, the processorcontrolled electronic analysing system now switches
the detector into alarm condition. The alarm is indicated
by 2 red LEDs. The self-adjusting quiescent value in the
detector ensures a constant response sensitivity.
WMX 95
The WMX DIS is a reliable heat detector meeting high
demands. The ambient temperature and the temperature
of the detector housing are measured by 2 NTC resistors.
Under normal conditions these measuring values are
similar. The temperature of the NTC exposed to ambience
will increase rapidly in case of fire. Therefore, a rapid
temperature increase cannot only be analysed by maximum temperature measurement but also by differential
measurement, thus supporting early fire detection. The
detector can be set in 5 stages with alarm temperatures
from 60 C to 90 C and indicates an alarm through
2 red LEDs.
IMX 95
The ionisation smoke detector IMX 95 operates with an
open outer and a half-closed inner ionisation chamber.
The air in both chambers will be ionised via a small
carrier with radioactive AM 241 with low radiation,
thus producing a current flow. The current in the outer
ionisation chamber will be reduced and analysed by a
high-grade electronic system when smoke is penetrating
the detector. For the IMX 95 as well the sensitivity can
be set in 5 stages and an alarm is indicated by 2 red LEDs.
Applications
Multi-sensor smoke detector OWMX 95
++
++
++
++
++
++
++
++
++
Kitchen, laundry
++
Heavy industry
++
Application:
++ very suitable
+ well suitable
Technical Data
VdS approval
OWMX 95
G208034
Quiescent current
0,5 mA
OMX 95
G208033
Alarm current
3,5 mA
WMX 95
G208035
Alarm indication
2 LEDs, red
IMX 95
G208036
Ingress protection
IP 43 (WMX 95 = IP 53)
0 95 %, no condensation
Working temperature
20 C to +60 C, no condensation
Storing temperature
30 C to +80 C
Wind velocity
no restriction
Dimensions
Weight
160 g
Connection cable
2 core
Subject to technical alterations.
Certified acc. to
ISO 9001
Relative humidity
Printed in Germany
Type
17 - 28 V DC
Rated current
# Nr. S 89201
All types