You are on page 1of 7

SOC - Selected Optimized

Coordination
Coordination tables for
motor protection

Important notice
This book is the result of a web search made from Selected Optimized Coordination - Coordination tables for motor protection
(http:\\applications.it.abb.com\SOC) made on 30 ott 2015.
Please always refer to http:\\applications.it.abb.com\SOC for the lastest updated information.
Used filters:
Protection Device:MCCB, MMS
Protection Device:415Vac
Short-Circuit Current:50
Starter Type:DOL-NS, DOL-HD
Coordination Type:IEC Type 2
Overload<br/>Relay:TOL, Embedded, EOL, UMC
Motor Rated Power:5, 5,5

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.

Page i

Index
MMS....................................................................................................................................................................................................................1
415Vac.............................................................................................................................................................................................................1
50 kA............................................................................................................................................................................................................1
DOL-NS...................................................................................................................................................................................................1
IEC Type 2...........................................................................................................................................................................................1
Embedded.......................................................................................................................................................................................1
MMS - 415Vac - 50kA - DOL-NS - IEC Type 2 - AF....................................................................................................................1
EOL..................................................................................................................................................................................................2
MMS - 415Vac - 50kA - DOL-NS - IEC Type 2 - MO+AF+EF.....................................................................................................2
TOL..................................................................................................................................................................................................3
MMS - 415Vac - 50kA - DOL-NS - IEC Type 2 - MO132+AF+TF...............................................................................................3
UMC.................................................................................................................................................................................................4
MMS - 415Vac - 50kA - DOL-NS - IEC Type 2 - MO+AF+UMC.................................................................................................4

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.

Page ii

MMS - 415Vac - 50kA - DOL-NS - IEC Type 2 - AF

Coordination tables for motor protection


SOC - Selected Optimized Coordination
SCPD type :MMS

Rated voltage :415 Vac

Short circuit current :50 kA

Starting type :DOL-NS

Coordination type :IEC Type 2

Overload relay :Embedded

Disconnecting Mean present :no

Backup / limitor present :no

Current Transformer present :no

Frequency :50-60 Hz

Motor Efficiency Class :IE1 + IE2

Edited on date :06/12/2012

Motor

Manual Motor Starter

Rated Power Rated Current Type


[A]

Contactor

Inst. Trip. Current range [A] Type


Current [A]

Max allowed
load current
[A]

0,06

0,19 MS132-0,25

3,13

0,16 - 0,25

AF09

0,25

0,09

0,29 MS132-0,40

5,00

0,25 - 0,40

AF09

0,40

0,12

0,42 MS132-0,63

7,88

0,40 - 0,63

AF09

0,63

0,18

0,58 MS132-0,63

7,88

0,40 - 0,63

AF09

0,63

0,25

0,82 MS132-1,0

12,50

0,63 - 1,00

AF09

1,00

0,37

1,10 MS132-1,6

20,00

1,00 - 1,60

AF09

1,60

0,55

1,40 MS132-1,6

20,00

1,00 - 1,60

AF09

1,60

0,75

1,80 MS132-2,5

31,25

1,60 - 2,50

AF09

2,50

1,10

2,60 MS132-4,0

50,00

2,50 - 4,00

AF26

4,00

1,50

3,50 MS132-4,0

50,00

2,50 - 4,00

AF26

4,00

2,20

4,70 MS132-6,3

78,75

4,00 - 6,30

AF26

6,30

3,00

6,30 MS132-6,3

78,75

4,00 - 6,30

AF26

6,30

4,00

8,20 MS132-10

150,00

6,30 - 10,00

AF26

10,00

5,50

11,10 MS132-12

180,00

8,00 - 12,00

AF26

12,00

7,50

14,90 MS132-16

240,00

10,00 - 16,00

AF26

16,00

9,00

17,90 MS132-20

300,00

16,00 - 20,00

AF26

20,00

11,00

21,20 MS132-25

375,00

20,00 - 25,00

AF26

25,00

15,00

28,00 MS132-32

480,00

25,00 - 32,00

AF30

32,00

18,50

33,70 MS450-40

520,00

28,00 - 40,00

AF40

40,00

22,00

39,50 MS450-40

520,00

28,00 - 40,00

AF40

40,00

25,00

44,90 MS450-50

650,00

36,00 - 50,00

AF52

50,00

30,00

53,00 MS495-63

819,00

45,00 - 63,00

AF65

63,00

37,00

64,00 MS495-75

975,00

57,00 - 75,00

AF80

75,00

45,00

77,00 MS495-90

1170,00

70,00 - 90,00

AF96

90,00

55,00

93,00 MS495-100

1235,00

80,00 - 100,00

AF96

96,00

Comments:
None.

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.

Page 1 of 4

MMS - 415Vac - 50kA - DOL-NS - IEC Type 2 - MO+AF+EF

Coordination tables for motor protection


SOC - Selected Optimized Coordination
SCPD type :MMS

Rated voltage :415 Vac

Short circuit current :50 kA

Starting type :DOL-NS

Coordination type :IEC Type 2

Overload relay :EOL

Disconnecting Mean present :no

Backup / limitor present :no

Current Transformer present :no

Frequency :50-60 Hz

Motor Efficiency Class :IE1 + IE2

Edited on date :06/12/2012

Motor
Rated
Power

Manual Motor Starter

Rated Type
Current [A]

Contactor

Inst. Trip. Type


Current [A]

Overload Relay
Type

Current range
[A]

Max allowed
load
current [A]

0,12

0,42 MO132-0,63

6,14 AF09

EF19-1,0 10 *

0,30 - 1,00

0,63

0,18

0,58 MO132-1,0

11,50 AF09

EF19-1,0 10 *

0,30 - 1,00

1,00

0,25

0,82 MO132-1,0

11,50 AF09

EF19-1,0 10 *

0,30 - 1,00

1,00

0,37

1,10 MO132-1,6

18,40 AF09

EF19-2,7 10 *

0,80 - 2,70

1,60

0,55

1,40 MO132-1,6

18,40 AF09

EF19-2,7 10 *

0,80 - 2,70

1,60

0,75

1,80 MO132-2,5

28,75 AF09

EF19-2,7 10 *

0,80 - 2,70

2,50

1,10

2,60 MO132-4

50,00 AF26

EF19-2,7 10 *

0,80 - 2,70

2,70

1,50

3,50 MO132-4

50,00 AF26

EF19-6,3 10 *

1,90 - 6,30

4,00

2,20

4,70 MO132-6,3

78,75 AF26

EF19-6,3 10 *

1,90 - 6,30

6,30

3,00

6,30 MO132-10

125,00 AF26

EF19-6,3 10 *

1,90 - 6,30

6,30

4,00

8,20 MO132-10

125,00 AF26

EF19-18,9 10 *

5,70 - 18,90

10,00

5,50

11,10 MO132-12

150,00 AF26

EF19-18,9 10 *

5,70 - 18,90

12,00

7,50

14,90 MO132-16

200,00 AF26

EF19-18,9 10 *

5,70 - 18,90

16,00

9,00

17,90 MO132-20

250,00 AF26

EF19-18,9 10 *

5,70 - 18,90

18,90

11,00

21,20 MO132-25

313,00 AF30

EF45-30 10 *

9,00 - 30,00

25,00

15,00

28,00 MO132-32

400,00 AF30

EF45-30 10 *

9,00 - 30,00

32,00

18,50

33,70 MO450-40

520,00 AF40

EF65-70 10 *

25,00 - 70,00

40,00

22,00

39,50 MO495-40

520,00 AF40

EF65-70 10 *

25,00 - 70,00

40,00

25,00

44,90 MO495-50

650,00 AF52

EF65-70 10 *

25,00 - 70,00

50,00

30,00

53,00 MO495-63

819,00 AF65

EF65-70 10 *

25,00 - 70,00

63,00

37,00

64,00 MO495-75

975,00 AF80

EF65-70 10 *

25,00 - 70,00

70,00

45,00

77,00 MO495-90

1170,00 AF96

EF96-100 10 *

36,00 - 100,00

90,00

55,00

93,00 MO495-100

1235,00 AF96

EF96-100 10 *

36,00 - 100,00

96,00

Comments:
*: selected trip class of Electronic overload relay

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.

Page 2 of 4

MMS - 415Vac - 50kA - DOL-NS - IEC Type 2 - MO132+AF+TF

Coordination tables for motor protection


SOC - Selected Optimized Coordination
SCPD type :MMS

Rated voltage :415 Vac

Short circuit current :50 kA

Starting type :DOL-NS

Coordination type :IEC Type 2

Overload relay :TOL

Disconnecting Mean present :no

Backup / limitor present :no

Current Transformer present :no

Frequency :50-60 Hz

Motor Efficiency Class :IE1 + IE2

Created on date :08/11/2012

Motor
Rated
Power

Manual Motor Starter

Rated Type
Current [A]

Contactor

Inst. Trip. Type


Current [A]

Overload Relay
Type

Current range
[A]

Max allowed
load current
[A]

0,06

0,19 MO132-0,25

2,44 AF09

TF42-0.23

0,17 - 0,23

0,23

0,09

0,29 MO132-0,40

3,90 AF09

TF42-0.31

0,23 - 0,31

0,31

0,12

0,42 MO132-0,63

6,14 AF09

TF42-0.55

0,41 - 0,55

0,55

0,18

0,58 MO132-0,63

6,14 AF09

TF42-0.74

0,55 - 0,74

0,63

0,25

0,82 MO132-1,0

11,50 AF09

TF42-1.0

0,74 - 1,00

1,00

0,37

1,10 MO132-1,6

18,40 AF09

TF42-1.3

1,00 - 1,30

1,30

0,55

1,40 MO132-1,6

18,40 AF09

TF42-1.7

1,30 - 1,70

1,60

0,75

1,80 MO132-2,5

28,75 AF09

TF42-2.3

1,70 - 2,30

2,30

1,10

2,60 MO132-4,0

50,00 AF09

TF42-3.1

2,30 - 3,10

3,10

1,50

3,50 MO132-4,0

50,00 AF09

TF42-4.2

3,10 - 4,20

4,00

2,20

4,70 MO132-6,3

78,75 AF26

TF42-5.7

4,20 - 5,70

5,70

3,00

6,30 MO132-10

125,00 AF26

TF42-7.6

5,70 - 7,60

7,60

4,00

8,20 MO132-10

125,00 AF26

TF42-10

7,60 - 10,00

10,00

5,50

11,10 MO132-12

150,00 AF26

TF42-13

10,00 - 13,00

12,00

7,50

14,90 MO132-16

200,00 AF26

TF42-16

13,00 - 16,00

16,00

9,00

17,90 MO132-20

250,00 AF26

TF42-20

16,00 - 20,00

20,00

11,00

21,20 MO132-25

313,00 AF26

TF42-24

20,00 - 24,00

24,00

15,00

28,00 MO132-32

400,00 AF30

TF42-29

24,00 - 29,00

29,00

Comments:
None.

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.

Page 3 of 4

MMS - 415Vac - 50kA - DOL-NS - IEC Type 2 - MO+AF+UMC

Coordination tables for motor protection


SOC - Selected Optimized Coordination
SCPD type :MMS

Rated voltage :415 Vac

Short circuit current :50 kA

Starting type :DOL-NS

Coordination type :IEC Type 2

Overload relay :UMC

Disconnecting Mean present :no

Backup / limitor present :no

Current Transformer present :yes

Frequency :50-60 Hz

Motor Efficiency Class :IE1 + IE2

Edited on date :06/12/2012

Motor
Rated
Power

Manual Motor Starter

Rated Type
Current
[A]

Contactor

Inst. Trip. Type


Current
[A]

Current transformer
Type

Turns

Overload Relay
Type

Current
range [A]

Max
allowed
load
current
[A]

0,06

0,19 MO132-0,40

3,90 AF09

UMC22/100

0,24 - 63,00

0,40

0,09

0,29 MO132-0,40

3,90 AF09

UMC22/100

0,24 - 63,00

0,40

0,12

0,42 MO132-0,63

6,14 AF09

UMC22/100

0,24 - 63,00

0,63

0,18

0,58 MO132-1,0

11,50 AF09

UMC22/100

0,24 - 63,00

1,00

0,25

0,82 MO132-1,0

11,50 AF09

UMC22/100

0,24 - 63,00

1,00

0,37

1,10 MO132-1,6

18,40 AF09

UMC22/100

0,24 - 63,00

1,60

0,55

1,40 MO132-1,6

18,40 AF09

UMC22/100

0,24 - 63,00

1,60

0,75

1,80 MO132-2,5

28,75 AF09

UMC22/100

0,24 - 63,00

2,50

1,10

2,60 MO132-4

50,00 AF26

UMC22/100

0,24 - 63,00

4,00

1,50

3,50 MO132-4

50,00 AF26

UMC22/100

0,24 - 63,00

4,00

2,20

4,70 MO132-6,3

78,75 AF26

UMC22/100

0,24 - 63,00

6,30

3,00

6,30 MO132-10

125,00 AF26

UMC22/100

0,24 - 63,00

10,00

4,00

8,20 MO132-10

125,00 AF26

UMC22/100

0,24 - 63,00

10,00

5,50

11,10 MO132-12

150,00 AF26

UMC22/100

0,24 - 63,00

12,00

7,50

14,90 MO132-16

200,00 AF26

UMC22/100

0,24 - 63,00

16,00

9,00

17,90 MO132-20

250,00 AF26

UMC22/100

0,24 - 63,00

20,00

11,00

21,20 MO132-25

313,00 AF30

UMC22/100

0,24 - 63,00

25,00

15,00

28,00 MO132-32

400,00 AF30

UMC22/100

0,24 - 63,00

32,00

18,50

33,70 MO450-40

520,00 AF40

UMC22/100

0,24 - 63,00

40,00

22,00

39,50 MO495-40

520,00 AF40

UMC22/100

0,24 - 63,00

40,00

25,00

44,90 MO495-50

650,00 AF52

UMC22/100

0,24 - 63,00

50,00

30,00

53,00 MO495-63

819,00 AF65

UMC22/100

0,24 - 63,00

63,00

37,00

64,00 MO495-75

975,00 AF80

4L185 R/4

UMC22/100

0,24 - 63,00

75,00

45,00

77,00 MO495-90

1170,00 AF96

4L185 R/4

UMC22/100

0,24 - 63,00

90,00

55,00

93,00 MO495-100

1235,00 AF96

4L185 R/4

UMC22/100

0,24 - 63,00

96,00

Comments:
None.

The data are not binding.


ABB reserves the right to modify the content of this document on the basis of technical development
of the products, without prior notice.
Copyright 2012 ABB. All rights reserved.

Page 4 of 4