ON SITE CERTIFICATION OF THE PROTECTION


Production of a short circuit in low voltage :
Advantages :
Final test on a definitive installation.
Benchmarking : same test whatever the detector trademark and
the current sensor type.
Quality of the certification same as real tests.
Reduced use cost : low labour required.
Avoid destruction of equipments nearby the fault (telco, ).
Security of the persons (Test in LV).
Easy to carry in S/S.

ThecontentofthisdocumentisthepropertyofGILLAMFEi.Itistobetreatedstrictlyconfidentialandisnottobe disclosed,
reproduced,orusedexceptasauthorizedbyGILLAMFEi

GILLAM-FEi
Frequency, Electronics & Telecommunications

Production of a short circuit in low voltage :


IDC20K :
Power injector operating in low voltage.
Creation of arbitrary waveforms (reproduction of short
circuits).
Portable equipment.
Modular till 20 000 A (2 500 A per module)

ThecontentofthisdocumentisthepropertyofGILLAMFEi.Itistobetreatedstrictlyconfidentialandisnottobe disclosed,
reproduced,orusedexceptasauthorizedbyGILLAMFEi

GILLAM-FEi
Frequency, Electronics & Telecommunications
Definition of the characteristics of
injected short circuit :

i(t) thorique
Court-circuit 31km
3000

Courant (A)

1. Theoretical template
2000

Scaled according to the distance


and the short circuit resistor.

1000

-1000
75

100

125

150

175

200

225

250

275

300

325

350

375

400

2. Template recorded by RLPROTECT

temps (msec)

Oscillodisturbography
3. Simple instruction
(Constant current)
4. Customized template
(Editable file)
ThecontentofthisdocumentisthepropertyofGILLAMFEi.Itistobetreatedstrictlyconfidentialandisnottobe disclosed,
reproduced,orusedexceptasauthorizedbyGILLAMFEi

GILLAM-FEi
Frequency, Electronics & Telecommunications

ThecontentofthisdocumentisthepropertyofGILLAMFEi.Itistobetreatedstrictlyconfidentialandisnottobe disclosed,
reproduced,orusedexceptasauthorizedbyGILLAMFEi

GILLAM-FEi
Frequency, Electronics & Telecommunications

ThecontentofthisdocumentisthepropertyofGILLAMFEi.Itistobetreatedstrictlyconfidentialandisnottobe disclosed,
reproduced,orusedexceptasauthorizedbyGILLAMFEi

GILLAM-FEi
Frequency, Electronics & Telecommunications

Production of a short circuit in low voltage


MAIN BUS

3kV

BAR
AUXILIARY
BUS BAR
PRECELL WITH
BREAKERS

CIRCUIT BREAKER
CELL

Voltage
probe
Current
probe

Programmable
current source
Ipk < 20 000A

Control
Position
RL PROTECT

Vmax < 10V


de
transient
ArbitrarySchma
principe
dinstallation

ThecontentofthisdocumentisthepropertyofGILLAMFEi.Itistobetreatedstrictlyconfidentialandisnottobe disclosed,
reproduced,orusedexceptasauthorizedbyGILLAMFEi

GILLAM-FEi
Frequency, Electronics & Telecommunications

Power Module IJK20

Rack 19 3U (330x440x134 mm) portable


Weigth :
16kg (transportation case included)
+ 6 kg for the cables
Connexions on the front
Per module: max 2 500 A for 500 msec
8 power modules max
Waveform under PC control: (4-20mA)
Alarm if the difference between PC
waveform and output current > 5%
Delay between pulses : 1 minute max.

IJK20

No security problem: very low voltage

ThecontentofthisdocumentisthepropertyofGILLAMFEi.Itistobetreatedstrictlyconfidentialandisnottobe disclosed,
reproduced,orusedexceptasauthorizedbyGILLAMFEi

GILLAM-FEi
Frequency, Electronics & Telecommunications

Transportation case

Cable management

Front face access

ThecontentofthisdocumentisthepropertyofGILLAMFEi.Itistobetreatedstrictlyconfidentialandisnottobe disclosed,
reproduced,orusedexceptasauthorizedbyGILLAMFEi

GILLAM-FEi
Frequency, Electronics & Telecommunications

Mobility
PC rack

Control module

Power module

ThecontentofthisdocumentisthepropertyofGILLAMFEi.Itistobetreatedstrictlyconfidentialandisnottobe disclosed,
reproduced,orusedexceptasauthorizedbyGILLAMFEi

GILLAM-FEi
Frequency, Electronics & Telecommunications

Supervision

System control:
Portable Windows PV
HMI for:
Short circuit caracteristics definition
Alarm management

ThecontentofthisdocumentisthepropertyofGILLAMFEi.Itistobetreatedstrictlyconfidentialandisnottobe disclosed,
reproduced,orusedexceptasauthorizedbyGILLAMFEi

GILLAM-FEi
Frequency, Electronics & Telecommunications

Location and cabling


IJK10 : Power module

ICK20

Placed in the circuit breaker cell


Flexible cable 95 mm (2m)

IJK20

10m

ICK10 : Control module


Placed remotely, out of the cell
Communication cable (10m)
220Vac cable (10m)

ThecontentofthisdocumentisthepropertyofGILLAMFEi.
Itistobetreatedstrictlyconfidentialandisnottobe
disclosed,reproduced,orusedexceptasauthorizedby
GILLAMFEi

2m

GILLAM-FEi
Frequency, Electronics & Telecommunications

Accessories Cables

Power 95mm 3m

230Vac

Control

ThecontentofthisdocumentisthepropertyofGILLAMFEi.Itistobetreatedstrictlyconfidentialandisnottobe disclosed,
reproduced,orusedexceptasauthorizedbyGILLAMFEi