Professional Documents
Culture Documents
Introduction
Orifice flowmeters are used to determine a liquid or gas flowrate by measuring the
differential pressure (P1 - P2) across the orifice plate. They are generally less expensive to
install and manufacture than the other commonly used differential pressure flowmeters;
however, nozzle and venturi flow meters have the advantage of lower pressure drops.
Equations for orifice meters have the advantage of no Reynolds Number upper limit for
validity.
An orifice flowmeter is typically installed between flanges connecting two pipe sections
(flanges are not shown in the above drawings). The three standard pressure tapping
arrangements are shown in the drawings; the location of the pressure taps affects the
discharge coefficient somewhat. Flange pressure taps penetrate the flange and are at a
standard distance of 1 inch (2.54 cm) from either side of the orifice. For corner taps or D and
D/2 taps, the pressure tap locations are as shown.
Orifices are typically less than 0.05D thick. For exact geometry and specifications for
orifices, see ISO (1991) or ASME (1971). The ASME and ISO have been working on
guidelines for orifices since the early 1900s. The organizations have the most confidence in
orifice accuracy when the Reynolds number exceeds 105, though Reynolds numbers as low as
4x103 are valid for certain d/D ratios as discussed below. The calculation above is for
liquids. Orifice gas flow calculations (D<5 cm, D>5 cm) have an additional factor called
expansibility.
Equations
The calculations on this page are for orifices carrying a liquid as described in ISO (1991) and
ASME (1971). The ISO reference has a more up-to-date discussion of orifices than the
ASME reference, so the ISO equations are used in our calculations.