MCB(MiniatureCircuitBreaker)
Characteristics
Ratedcurrentnotmorethan100A.
Tripcharacteristicsnormallynotadjustable.
Thermalorthermalmagneticoperation.
MCCB(MouldedCaseCircuitBreaker)
Characteristics
Ratedcurrentupto1000A.
Tripcurrentmaybe
adjustable.
Thermalorthermalmagnetic
operation.
AirCircuitBreaker
Characteristics
Ratedcurrentupto10,000
A.
Tripcharacteristicsoftenfully
adjustableincluding
configurabletripthresholdsanddelays.
Usuallyelectronicallycontrolledsomemodelsaremicroprocessorcontrolled.
Oftenusedformainpowerdistributioninlargeindustrialplant,wherethe
breakersarearrangedindrawoutenclosuresforeaseofmaintenance.
VacuumCircuitBreaker
Characteristics
Withratedcurrentupto3000A,
Thesebreakersinterruptthearcinavacuumbottle.
Thesecanalsobeappliedatupto35,000V.Vacuumcircuitbreakerstendto
http://electricalengineeringportal.com/whatisthedifferencebetweenmcbmccbelcbandrccb
1/6
10/21/2015
WhatisthedifferencebetweenMCB,MCCB,ELCB,andRCCB|EEP
havelongerlifeexpectanciesbetweenoverhaulthandoaircircuitbreakers.
RCD(ResidualCurrentDevice/RCCB(ResidualCurrentCircuit
Breaker)
Characteristics
Get
PDF
Phase(line)andNeutralbothwiresconnectedthrough
RCD.
Ittripsthecircuitwhenthereisearthfaultcurrent.
Theamountofcurrentflowsthroughthephase(line)
shouldreturnthroughneutral.
ItdetectsbyRCD.anymismatchbetweentwocurrents
flowingthroughphaseandneutraldetectbyRCDandtrip
thecircuitwithin30Miliseconed.
Ifahousehasanearthsystemconnectedtoanearthrod
andnotthemainincomingcable,thenitmusthaveallcircuitsprotectedbyan
RCD(becauseumitenotbeabletogetenoughfaultcurrenttotripaMCB)
RCDsareanextremelyeffectiveformofshockprotection
TOP
Themostwidelyusedare30mA(milliamp)and100mAdevices.Acurrentflowof30
mA(or0.03amps)issufficientlysmallthatitmakesitverydifficulttoreceivea
SHARE
dangerousshock.Even100mAisarelativelysmallfigurewhencomparedtothe
currentthatmayflowinanearthfaultwithoutsuchprotection(hundredofamps)
A300/500mARCCBmaybeusedwhereonlyfireprotectionisrequired.eg.,on
lightingcircuits,wheretheriskofelectricshockissmall.
LimitationofRCCB
StandardelectromechanicalRCCBsaredesignedtooperateonnormal
supplywaveformsandcannotbeguaranteedtooperatewherenonestandard
waveformsaregeneratedbyloads.Themostcommonisthehalfwaverectified
waveformsometimescalledpulsatingdcgeneratedbyspeedcontroldevices,
semiconductors,computersandevendimmers.
SpeciallymodifiedRCCBsareavailablewhichwilloperateonnormalacand
pulsatingdc.
RCDsdontofferprotectionagainstcurrentoverloads:RCDsdetectan
imbalanceintheliveandneutralcurrents.Acurrentoverload,howeverlarge,
cannotbedetected.Itisafrequentcauseofproblemswithnovicestoreplacean
MCBinafuseboxwithanRCD.Thismaybedoneinanattempttoincrease
shockprotection.Ifaliveneutralfaultoccurs(ashortcircuit,oranoverload),the
http://electricalengineeringportal.com/whatisthedifferencebetweenmcbmccbelcbandrccb
2/6
10/21/2015
WhatisthedifferencebetweenMCB,MCCB,ELCB,andRCCB|EEP
RCDwonttrip,andmaybedamaged.Inpractice,themainMCBforthe
premiseswillprobablytrip,ortheservicefuse,sothesituationisunlikelytolead
tocatastrophebutitmaybeinconvenient.
ItisnowpossibletogetanMCBandandRCDinasingleunit,calledanRCBO
(seebelow).ReplacinganMCBwithanRCBOofthesameratingisgenerally
safe.
NuisancetrippingofRCCB:Suddenchangesinelectricalloadcancausea
small,briefcurrentflowtoearth,especiallyinoldappliances.RCDsarevery
sensitiveandoperateveryquicklytheymaywelltripwhenthemotorofanold
freezerswitchesoff.Someequipmentisnotoriously`leaky,thatis,generatea
small,constantcurrentflowtoearth.Sometypesofcomputerequipment,and
largetelevisionsets,arewidelyreportedtocauseproblems.
RCDwillnotprotectagainstasocketoutletbeingwiredwithitsliveand
neutralterminalsthewrongwayround.
RCDwillnotprotectagainsttheoverheatingthatresultswhenconductorsare
notproperlyscrewedintotheirterminals.
RCDwillnotprotectagainstliveneutralshocks,becausethecurrentinthe
liveandneutralisbalanced.Soifyoutouchliveandneutralconductorsatthe
sametime(e.g.,bothterminalsofalightfitting),youmaystillgetanastyshock.
ELCB(EarthLeakageCircuitBreaker)
Characteristics
Phase(line),NeutralandEarthwireconnected
throughELCB.
ELCBisworkingbasedonEarthleakagecurrent.
OperatingTimeofELCB:
ThesafestlimitofCurrentwhichHumanBodycan
withstandis30masec.
SupposeHumanBodyResistanceis500and
Voltagetogroundis230Volt.
TheBodycurrentwillbe500/230=460mA.
HenceELCBmustbeoperatedin
30maSec/460mA=0.65msec
OverLoad)
RCBO(ResidualCircuitBreakerwith
ItispossibletogetacombinedMCBandRCCBinonedevice(ResidualCurrent
BreakerwithOverloadRCBO),theprincipalsarethesame,butmorestylesof
http://electricalengineeringportal.com/whatisthedifferencebetweenmcbmccbelcbandrccb
3/6
10/21/2015
WhatisthedifferencebetweenMCB,MCCB,ELCB,andRCCB|EEP
disconnectionarefittedintoonepackage
DifferencebetweenELCBandRCCB
ELCBistheoldnameandoftenreferstovoltageoperateddevicesthatareno
longeravailableanditisadvisedyoureplacethemifyoufindone.
RCCBorRCDisthenewnamethatspecifiescurrentoperated(hencethenew
nametodistinguishfromvoltageoperated).
ThenewRCCBisbestbecauseitwilldetectanyearthfault.Thevoltagetype
onlydetectsearthfaultsthatflowbackthroughthemainearthwiresothisiswhy
theystoppedbeingused.
Theeasywaytotellanoldvoltageoperatedtripistolookforthemainearth
wireconnectedthroughit.
RCCBwillonlyhavethelineandneutralconnections.
ELCBisworkingbasedonEarthleakagecurrent.ButRCCBisnothaving
sensingorconnectivityofEarth,becausefundamentallyPhasecurrentisequal
totheneutralcurrentinsinglephase.ThatswhyRCCBcantripwhentheboth
currentsaredeferentanditwithstanduptoboththecurrentsaresame.Boththe
neutralandphasecurrentsaredifferentthatmeanscurrentisflowingthroughthe
Earth.
Finallybothareworkingforsame,butthethingisconnectivityisdifference.
RCDdoesnotnecessarilyrequireanearthconnectionitself(itmonitorsonlythe
liveandneutral).Inadditionitdetectscurrentflowstoeartheveninequipment
withoutanearthofitsown.
ThismeansthatanRCDwillcontinuetogiveshockprotectioninequipmentthat
hasafaultyearth.ItisthesepropertiesthathavemadetheRCDmorepopular
thanitsrivals.Forexample,earthleakagecircuitbreakers(ELCBs)werewidely
usedabouttenyearsago.Thesedevicesmeasuredthevoltageontheearth
conductorifthisvoltagewasnotzerothisindicatedacurrentleakagetoearth.
TheproblemisthatELCBsneedasoundearthconnection,asdoesthe
equipmentitprotects.Asaresult,theuseofELCBsisnolongerrecommended.
MCBSelection
Thefirstcharacteristicistheoverloadwhichisintendedtopreventtheaccidental
overloadingofthecableinanofaultsituation.ThespeedoftheMCBtripping
willvarywiththedegreeoftheoverload.Thisisusuallyachievedbytheuseofa
thermaldeviceintheMCB.
Thesecondcharacteristicisthemagneticfaultprotection,whichisintendedto
operatewhenthefaultreachesapredeterminedlevelandtotriptheMCBwithin
onetenthofasecond.ThelevelofthismagnetictripgivestheMCBitstype
characteristicasfollows:
http://electricalengineeringportal.com/whatisthedifferencebetweenmcbmccbelcbandrccb
4/6
10/21/2015
WhatisthedifferencebetweenMCB,MCCB,ELCB,andRCCB|EEP
Type
TrippingCurrent
OperatingTime
TypeB
3To5timefullloadcurrent
0.04To13Sec
TypeC 5To10timesfullloadcurrent
0.04To5Sec
FuseandMCBcharacteristics
FusesandMCBsareratedinamps.TheampratinggivenonthefuseorMCB
bodyistheamountofcurrentitwillpasscontinuously.Thisisnormallycalledthe
ratedcurrentornominalcurrent.
Manypeoplethinkthatifthecurrentexceedsthenominalcurrent,thedevicewill
trip,instantly.Soiftheratingis30amps,acurrentof30.00001ampswilltripit,
right?Thisisnottrue.
ThefuseandtheMCB,eventhoughtheirnominalcurrentsaresimilar,havevery
differentproperties.
Forexample,For32AmpMCBand30AmpFuse,tobesureoftrippingin0.1
seconds,theMCBrequiresacurrentof128amps,whilethefuserequires300
amps.
Thefuseclearlyrequiresmorecurrenttoblowitinthattime,butnoticehow
muchbiggerboththesecurrentsarethanthe30ampsmarkedcurrentrating.
Thereisasmalllikelihoodthatinthecourseof,say,amonth,a30ampfusewill
tripwhencarrying30amps.Ifthefusehashadacoupleofoverloadsbefore
(whichmaynotevenhavebeennoticed)thisismuchmorelikely.Thisexplains
whyfusescansometimesblowfornoobviousreason
Ifthefuseismarked30amps,butitwillactuallystand40ampsforoveran
hour,howcanwejustifycallingita30ampfuse?Theansweristhatthe
overloadcharacteristicsoffusesaredesignedtomatchthepropertiesofmodern
cables.Forexample,amodernPVCinsulatedcablewillstanda50%overload
foranhour,soitseemsreasonablethatthefuseshouldaswell.
http://electricalengineeringportal.com/whatisthedifferencebetweenmcbmccbelcbandrccb
5/6
10/21/2015
WhatisthedifferencebetweenMCB,MCCB,ELCB,andRCCB|EEP
RecommendedEEarticles//
Sharewithengineers//
AboutAuthor//
authorpic
Jignesh Parmar
jiguparmarJigneshParmarhascompletedM.Tech(Power
SystemControl),B.E(Electrical).HeismemberofInstitutionof
Engineers(MIE),India.MembershipNo:M1473586.Hehasmorethan13years
experienceinTransmissionDistributionElectricalEnergytheftdetectionElectrical
MaintenanceElectricalProjects(PlanningDesigningTechnicalReviewcoordination
Execution).HeisPresentlyassociatewithoneoftheleadingbusinessgroupasa
DeputyManageratAhmedabad,India.HehaspublishednumbersofTechnicalArticles
in"ElectricalMirror","ElectricalIndia","LightingIndia","IndustrialElectrix"(Australian
PowerPublications)Magazines.HeisFreelancerProgrammerofAdvanceExceland
designusefulExcelbaseElectricalProgramsasperIS,NEC,IEC,IEEEcodes.Heis
TechnicalBloggerandFamiliarwithEnglish,Hindi,Gujarati,Frenchlanguages.He
wantstoSharehisexperience&Knowledgeandhelptechnicalenthusiaststofind
suitablesolutionsandupdatingthemselvesonvariousEngineeringTopics.
2015EEPElectricalEngineeringPortal.AllRightsReserved|PrivacyPolicy|TermsofService |50queriesin0.355
seconds.
PoweredbyCsanyiGroup
http://electricalengineeringportal.com/whatisthedifferencebetweenmcbmccbelcbandrccb
6/6