Dry Contact Alarm Guideline V1.3


DiGi 3G Neutron Project

Proprietary Confidential

Index
1. BBU Dry Contact Alarm

1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8

BBU Dry contact cable A and B


Alarm cable connection
Convention
Outdoor site: ZTE BBU+ELTEK power(Outdoor
power) A
Outdoor site: ZTE BBU+ELTEK power(Outdoor
power) B
Indoor site: ZTE BBU+ELTEK power(Indoor
power) C
Alarm configuration
Alarm test

2012-2-25

Proprietary Confidential

1.1 BBU Dry contact cable A and B


Cable A:

Cable B:

DB25 Core
Pair.
Definition
DB25_1
1
DB25_14
DB25_2
2
DB25_15
DB25_3
3
DB25_16
DB25_4
4
DB25_17
DB25_5
5
DB25_18
DB25_6
6
DB25_19
DB25_7
7
DB25_20
DB25_8
8
DB25_20

Dry Contact

Cable Color

NODEB_IN1P
NODEB_IN1N
NODEB_IN2P
NODEB_IN2N
NODEB_IN3P
NODEB_IN3N
NODEB_IN4P
NODEB_IN4N
NODEB_IN5P
NODEB_IN5N
NODEB_IN6P
NODEB_IN6N
NODEB_IN7P
NODEB_IN7N
NODEB_IN8P
NODEB_IN8N

White
Blue
White
Orange
White
Green
White
Brown
White
Grey
Red
Blue
Red
Orange
Red
Green

Pair. DB25 Core


Definition
DB25_1
1
DB25_14
DB25_2
2
DB25_15
DB25_3
3
DB25_16
DB25_4
4
DB25_17
DB25_5
5
DB25_18
DB25_6
6
DB25_19
DB25_7
7
DB25_20
DB25_8
8
DB25_20

Dry Contact

Cable Color

NODEB_IN1P
NODEB_IN1N
NODEB_IN2P
NODEB_IN2N
NODEB_IN3P
NODEB_IN3N
NODEB_IN4P
NODEB_IN4N
NODEB_IN5P
NODEB_IN5N
NODEB_IN6P
NODEB_IN6N
NODEB_IN7P
NODEB_IN7N
NODEB_IN8P
NODEB_IN8N

White
Blue
White
Orange
White
Green
White
Brown
Red
Blue
Red
Orange
Red
Green
Red
Brown

Proprietary Confidential

1.2 Alarm cable connection


1.

Dry contact alarm cable connect at the 120 DDF module: NodeB dry contact alarm cable is
punched at down side, existing alarm is up side. Cable punched order is from pair 1 to 8. For
more easily to change and test the connection, used two column is better.

2.

For ZTE power, ZTE CSU is connected to BBU with a RS-232 cable. ZTE CSU report these
alarms to BBU and BBU report to RAN EMS.

2012-2-25

Proprietary Confidential

1.3 Convention:
1.

2.
3.
4.
5.
6.
7.

If the site didnt have the existing alarm, so only punched the dry contact alarm cable at the
external alarm DDF and didnt configure this alarm. Inform Site Eng/DiGi the site do not have
external alarm.
If the site existing alarm cable or sensor cant find, so only punched the dry contact alarm cable
at the external alarm DDF and didnt configure this alarm. Inform DiGi of the missing alarm.
If the site existing external alarm doesnt work, so only punched the dry contact alarm cable at
the external alarm DDF and configure this alarm. Inform DiGi if alarm cant be clear.
If the existing ELTEK Power equipment alarm cant clear by ZTE, need inform DiGi.
W301 door open alarm is only for the outdoor site, and the W301 equipment cabinet is installed.
For 1 PCS dry contact cable only support 8 alarms, FCB FAIL alarm is ignored.
After alarm test, need complete the alarm test report. After that, handover the document to the
cluster manger.

Alarm test
report-template

Proprietary Confidential

Com
NC

NO

Com
NC

NO

NC

Com

NO

NC

Com

NO

Com
NC

NO

Com
NC

NO

1.4 Outdoor site: ZTE BBU+ELTEK power(Outdoor power) A

Intruder(white/green)

Low Battery(white/brown)

High TEMP(white/gray)

FUSE Fail(red/blue)

Rectifier Failure(white/blue)

Main Failure(white/orange)

n/a
n/a

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

*The cable color is ELTEKs cable color.


6

2012-2-25

Proprietary Confidential

NC

Com

NO

NC

Com

NO

Com
NC

NO

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Intruder(white/green)

Low Battery(white/brown)

High TEMP(white/gray)

FUSE Fail(red/blue)

Main Failure(white/orange)

Rectifier Failure(white/blue)

n/a

n/a

n/a
n/a

1 2 3 4 5 6 7 8 9 10

Com
NC

NO

NC

Com

NO

NC

Com

NO

1.5 Outdoor site: ZTE BBU+ELTEK power(Outdoor power) B

*The cable color is ELTEKs cable color.


7

Proprietary Confidential

NO

Com

NC

NO

Com

NC

Com

NO

NC

1.6 Indoor site: ZTE BBU+ELTEK power(Indoor power) C

n/a

Main Failure(white/orange)

Low Battery(white/brown)

Rectifier Failure(white/blue)

n/a

n/a

n/a
n/a

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

*The cable color is ELTEKs cable color.


8

2012-2-25

Proprietary Confidential

1.7 Alarm configuration

Scenario 1
Outdoor
site ZTE
BBU +
Eltek
Power

Scenario 2
Indoor
site ZTE
BBU +
Eltek
Power

Alarm cable

Dry contact
No.

Alarm name

Configuration

Cable

Pair 1

INTRUDER ALARM

Alarm appears if contact is open

Dry contact cable

Pair 2

MAIN FAILURE

Alarm appears if contact is open

Dry contact cable

Pair 3

FUSE FAIL

Alarm appears if contact is open

Dry contact cable

Pair 4

RECTIFIER FAILURE

Alarm appears if contact is open

Dry contact cable

Pair 5

BATTERY UNDER VOLTAGE

Alarm appears if contact is open

Dry contact cable

Pair 6

FAN FAIL/HIGH TEMP

Alarm appears if contact is open

Dry contact cable

Pair 7

W301 DOOR OPEN

Alarm appears if contact is open

Network cable(white/blue)

Pair 8

DCPD4 SURGE PROTECTION FAILURE Alarm appears if contact is open

Network cable(white/brown)

Alarm cable

Dry contact
No.

Alarm name

Configuration

Pair 1

INTRUDER ALARM

Alarm appears if contact is open

Dry contact cable

Pair 2

MAIN FAILURE

Alarm appears if contact is open

Dry contact cable

Pair 3

RECTIFIER FAILURE

Alarm appears if contact is open

Dry contact cable

Pair 4

BATTERY UNDER VOLTAGE

Alarm appears if contact is open

Dry contact cable

Pair 5

COMPRESSOR LOSS

Alarm appears if contact is open

Dry contact cable

Pair 6

HIGH TEMP

Alarm appears if contact is open

Dry contact cable

Pair 7

COMPRESSOR FAILURE

Alarm appears if contact is open

Pair 8

DCPD4 SURGE PROTECTION FAILURE Alarm appears if contact is open

Dry contact cable


Network cable(white/brown)

Proprietary Confidential

1.7 Alarm configuration

Scenario 3
Outdoor
site ZTE
BBU+ZTE
power

Scenario 4
Indoor
site ZTE
BBU + ZTE
power

Alarm cable

Dry contact
No.

Pair 1

Pair 2

Pair 3

Pair 4

Pair 5

Pair 6

Pair 7

Pair 8

Alarm cable

Dry contact
No.

Alarm name

Configuration

Pair 1

INTRUDER ALARM

Alarm appears if contact is open

Dry contact cable

Pair 2

Pair 3

Pair 4

Pair 5

COMPRESSOR LOSS

Alarm appears if contact is open

Dry contact cable

Pair 6

HIGH TEMP

Alarm appears if contact is open

Dry contact cable

Pair 7

COMPRESSOR FAILURE

Alarm appears if contact is open

Pair 8

Alarm name

Configuration

DCPD4 SURGE PROTECTION FAILURE Alarm appears if contact is open

DCPD4 SURGE PROTECTION FAILURE Alarm appears if contact is open

Cable

Network cable(white/brown)

Dry contact cable


Network cable(white/brown)

2012-2-25

Proprietary Confidential

1.8 Alarm test


1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

Intruder alarm: Close and open the door.


Main Failure: Take off the main AC breaker. (Confirm you have the permission to shut down)
Fuse Fail: can not test, only loop test.
Rectifier Failure: Stop the rectifiers fan, it will alarm.
Battery under voltage: can not test, only loop test.
W301 door open: Close and open the door.
High temp: can not test, only loop test.
Compressor loss: Only loop test.
Compressor failure: Only loop test.
DCPD4 surge protection failure: Only loop test.