Professional Documents
Culture Documents
PSYCHROMETRY
Atmospheric air is moist in nature, consisting of both air and water vapour. The
amount of water vapour in the atmospheric air plays an important role in human
comfort. Study of such air - water vapour mixture is known as psychrometry. For
simplicity the analysis is carried out with the following assumptions:
(i)
(ii)
In
general,
the
state of
water vapour in
the
atmospheric air
is superheated. It can be represented in a T-s diagram as indicated by state 1 in
Figure 10.1. When cooled at constant pressure, temperature of a sample of such air
will decrease until it reached the saturation temperature of steam corresponding to
the partial pressure Rr. This temperature is known as dew point temperature. Air
becomes saturated at this state so that further cooling will result in condensation of
water vapour.
Let a stream of unsaturated air flows over the bulb of a thermometer covered
with thoroughly wetted wick as shown in Figure 10.2. When air passes over the
wick, evaporation of water in the wick is taking place. This vapour is taken along by
the unsaturated air.
The driving potential for this evaporation is the difference in partial pressure of
water vapour in the unsaturated air and that of water in the wick. Thermodynamic
states of water vapour in air and water in the wick are represented respectively as 1
and l in a T-s diagram as shown in Figure 10.3. Heat required for this evaporation is
partially taken from water in the wick and the remaining from air. Hence,
temperature of water and air decreases. Partial pressure of water vapour in the air
decreases partial pressure pf water vapour in the air increases and that of water in
the wick decreases until there exists an equilibrium between these two pressures.
For further evaporation heat is supplied by the air alone. Therefore there will not be
any further decrease in temperature of water in the wick. This temperature is known
as wet bulb temperature. Thus wet bulb temperature is the temperature measured
by the wick-covered bulb of a thermometer in which the wick is thoroughly wetted
with water. The difference between drybulb and wet bulb temperatures is known as
wet bulb depression. That is
WBD DBT WBT
...(10.2)
mv
ma
Assuming ideal gas behaviour for both air and water vapour
pvV R vT
paV RaT
pvR a
paR v
Where pV
pa
...(10.3)
As defined earlier,
Ru
M
Ru
M a
pv
w
pa Ru
M
v
pv M v
pa M a
...(10.4)
Molecular
weight (Mi)
Part by
volume (yi)
N2
28.02
0.7803
O2
32.00
0.2099
Ar
39.91
0.0094
CO2
44.00
0.0003
H2
2.02
0.0001
0.7803 28.02
+ 0.2099 32.00
+ 0.0094 39.91
+ 0.0003 44.0
+ 0.0001 2.02
28.96
pv M v
pa M a
p
0.622 v
pa
0.622
pv kg of w.v.
p pv kg of d .a.
(10.5)
10.3
pv
ps
...(10.6)
Where pv is the partial pressure of water vapour in the mixture.
ps is the partial pressure of water vapour in the same mixture if it is
saturated at the same temperature.
Since ideal gas behavior is being assumed for both dry air and water vapour.
pv
ps
Therefore
mvRT
V
msRT
V
(or)
mv
ms
RH
Thus, the relative humidity is the ratio of mass of water vapour in a certain
volume of unsaturated moist air at a given temperature to the mass of water
vapour in the same volume of saturated air at the same temperature. For dry air
relative humidity is zero
( 0) and one for saturated air ( 100%).
The ratio of specific humidity of the given unsaturated air to that of saturated
air at the same temperature is known as degree of saturation. That is
6
w
ws
...
(10.7)
...(10.8)
v V/mv
...(10.9)
...
(10.10)
v V/(ma+mv)
ha+ hv
...(10.11)
Humidity ratio
a1 m
a2 m
a
m
v1 m
f m
v2
m
Where
is
is
is
is
the
the
the
the
mass
mass
mass
mass
flow
flow
flow
flow
rate
rate
rate
rate
of
of
of
of
...(10.15)
...(10.16)
a1 m
f 2m
a2
1m
Substituting from Equation (10.15) and rearranging, we get
f ( 2 1)m
a
m
...(10.17)
a2h2 m
a1h1 m
f hf
m
..(10.18)
Substituting from Equation (10.15) and (10.17), Equation (10.18) becomes
a(h2 h1) m
a( 2 1)hf
m
...(10.19)
Where h1 and h2 are specific enthalpys of moist per kg of dry air. It can be
expressed as follows:
h1 Cpa (t1) + 1 hv1
...(10.20)
...(10.21)
1
...(10.22)
Examination of the above equation reveals that all the quantities on the right
hand side can be determined if the dry bulb temperature t 1 at the inlet and the
adiabatic saturation temperature t2 at exit can be measured. As mentioned earlier,
the adiabatic saturation temperature is almost equal to the wet bulb temperature
and hence by knowing dry bulb and wet bulb temperature, the moisture content of
humid air can be computed using the above expression.
10
10.8
Processes
Psychrometric
Sensible Heating
Moist air is heated without altering the moisture content of the air. The
following changes are observed due to sensible heating :
1) Dry bulb temperature
- Increases
- Increases
3) Specific enthalpy
- Increases
- Decreases
Figure 10.8 shows the schematic arrangements of the process. Figure 10.9
shows the process on a psychrometric chart.
11
Amount
of
heated added can
expressed as
be
m
a(h2 h1)
Q
10.8.2
...(10.23)
Sensible cooling
It is just the reverse of sensible heating, that is, moist air is cooled such that
the moisture content remains unaltered. The following changes are observed in a
sensible cooling process.
1.
2.
3.
4.
5.
12
Quantity
of heat to be removed is given as
m
... Q
a(h1 h2 )
10.8.3
(10.24)
Dehumidification by cooling
When moist air is cooled below its dew point temperature water vapour is
removed from air as it starts condensing below the dew point temperature. Air is in
saturated state at the end of cooling as shown in Figure 10.12.
Heat removal rate is given as
m
a(h1 h2 )+m
a(1 2 )hf
Q
...(10.25)
- Decreases
- Decreases
- Increases
13
10.8.4
Q
cooling ma(h1 h2 )+ma( 2 1)hf
...(10.26)
Heat load on the heater is given as
a(h2 h2 )
Qheating m
14
...(10.27)
10.8.5
Adiabatic Humidification
15
On the basis of unit mass of dry air, the energy equation is given as
h1 + (2 1) hf h2
...
(10.28)
m
a(h2 h1)
Q
Mass to be added by the sprayer
16
...(10.29)
m
a( 3 2 )
m
10.8.7
...(10.30)
Adiabatic Mixing
a1 +m
a2 m
a3
m
...(10.31)
Mass balance of water vapour gives
17
v1 +m
v2 m
v3
m
...(10.32)
a11 +m
a2 2 m
a3 3
m
Energy balance of the entire control volume gives
a1h1 +m
a2h2 m
a3h3
m
...(10.33)
m
m
1 a3
a2
a2
m
m
a2.
m
It gives
...
(10.34)
Dividing equation (10.32) by , we have
a1
m
m
1 2 a3 3
a2
a2
m
m
a3
m
m
a1 1 2
a2
a2 3 3
m
m
...(10.35)
Substituting equation (10.35) in (10.34) we get
a1
m
m
1 a1 1 2
a2
a2 3 3
m
m
m a1
m a2
1
1
3
...(10.36)
2
3
a1 3 2
3
m
a2
m
3
1 3
a1 3 2
m
a2 1 3
m
18
a1 h3 h2
m
a2 h1 h3
m
...(10.37)
Solved Problems
Prob : 10.1 An air-conditioning unit receives an air-water vapour mixture
o
at 101 kPa, 35 C and 80% relative humidity.
Determine
a) the dew point
b) the humidity ratio
c) the partial pressure of air
d) the mass fraction of water vapour
System
Known
1) DBT 35 C
2) p 101 kPa
3) 80%
Diagram :
To find
Analysis
: 1)
2)
Humidity ratio
3)
4)
0.8 ps
0.8 5.63
4.5 kPa
Thus the dew point is the saturation temperature at 4.5 kPa. From
steam table, it is obtained that
o
DPT 30.93 C.
19
2)
Humidity ratio ()
0.622
pv
ps
4.5
(101 4.5)
=0.622
0.029
3)
kg of w.v
kg of d.a
4)
mv
mv ma
Mass associated with each kg of dry air as indicated by humidity ratio is 0.029 kg.
Therefore
Mass fraction of water vapour 0.02818
Result
: 1)
2)
kg of w.v
kg of d.a
3)
96.5 kPa
4)
0.02818
20
30.93 C
0.029
Prob : 10.2 Given for an air-water vapour mixture that T mix 70 C and pmix
200 kPa and Pair = 180 kPa, find the dew point, humidity ratio and
relative humidity
System
Known
1) Tmix 70 C
2) pmix 200 kPa
3)Pair 180 kPa
To find
Diagram
Analysis
pa + pv
180 + pv
21
20 kPa
pv
2)
0.0691
3)
pv
pa
0.622
Relative Humidity ()
60.06 C
kg of w.v
kg of d.a
pv
ps
0.641 (64.1 %)
Result
Exercises
1.
2.
3.
4.
5.
6.
7.
8.
Which one of the following property can not be read from the psychrometric
chart.
a) Relative humidity
b) Absolute humidity
c) Wet bulb temperature
d) Degree of saturation
[Ans : d]
9.
10.
11.
12.
For all the practical purposes thermodynamic wet bulb temperature is taken
as adiabatic saturation temperature (T/F)
[Ans : True]
13.
14.
15.
16.
23
17.
Use the formulas and the steam tables to find the missing property of ,
and DBT, total pressure is 100 kPa; repeat the answers using the
psychrometric chart.
o
a) 60%, 0.010
b) DPT 10 C, 50 %
c) DTP 25 C, WBT 20 C
o
b) DBT = 21 C ; = 0.0076
[Ans : a) DBT = 23 C
18
c) = 0.0128 ; =
0.64]
A rigid of volume vessel 300 litre contains air water vapour mixture at 150
o
kPa, 40 C, and 10% relative humidity. Calculate the following
a) partial pressure of air and water vapour
b) Moisture content in kg per kg of dry air
c) Dew point temperature
d) degree of saturation
[ Hint : Since the pressure 150 kPa, standard psychrometric charts should not
be referred]
[Ans : a) pv= 6.645 kPa ; pa=143.35 kPa
b) w =
0.0288
c) DPT = 37.62 C
3
d) m = 0.894 ]
19.
10m /min of moist air at 10 C, 90% relative humidity is passed over a heater
o
until the temperature reaches 20 C. Determine the quantity of heat added
per minute.
[Ans : 117.3 kJ/min]
20.
21.
22.
23.
Atmospheric air at 35 C, relative humidity 10%, is too warm and also too dry.
o
An air conditioner should deliver it at 20 C and 60% relative humidity in the
3
amount of 3600 m /min. Sketch a setup to accomplish this, find any amount
o
of liquid (at 20 C) that is needed or discarded and any heat transfer.
[Ans : 18.43 kg/min to be added]
24
24.
25.
26.
Two streams of moist air are mixed adiabatically as shown in the Figure p.28.
Determine the condition of the air after mixing.
28.
29.
30.
26