Substation applications

Examples of applications
Sepam series 80

To make it easy to choose the right


Sepam series 80 for a protection
application, the most typical applications are
presented with the type of Sepam series 80
for them.

The list of functions is given for information


purposes.
Solid and impedance earthing are
represented by the same icon, i.e. solidly
earthed.

32

DE50094

Protection of feeders in solidly earthed systems, or protection of low


capacitance feeders in low impedance earthed systems: Sepam S80

Protection of feeders in compensated or isolated neutral systems, or


protection of capacitive feeders in low impedance earthed systems:
Sepam S81
b specific feeder protection: 67N/67NC.
DE50122

Each sample application is presented by:


b a single-line diagram indicating:
v equipment to be protected
v network configuration
v position of measurement sensors
b standard and specific Sepam functions to
be implemented to protect the application
concerned.

Feeder protection
b feeder short-circuit and overload protection
b voltage and frequency monitoring.

Substation applications

Examples of applications
Sepam series 80

Selection table

Incomer protection
b busbar short-circuit protection
b voltage and frequency monitoring.

S80 S81 S82

b line voltage and frequency monitoring.

DE50118

DE50117

Incomer protection: Sepam S80


b busbar voltage and frequency
monitoring.

Parallel incomer protection: Sepam S82


b line or source protection: 67, 67N/67NC.
DE50119

Phase overcurrent (1)


50/51
8
8
8
50N/51N
8
8
8
Earth fault /
50G/51G
Sensitive earth fault (1)
Breaker failure
50BF
1
1
1
Negative sequence /
46
2
2
2
unbalance
Thermal overload for cables
49RMS
2
2
Directional phase overcurrent (1) 67
2
67N/67NC
2
2
Directional earth fault (1)
Directional active overpower
32P
2
2
Positive sequence
27D
2
2
2
undervoltage
Remanent undervoltage
27R
2
2
2
4
4
4
Undervoltage (L-L or L-N)
27
Overvoltage (L-L or L-N)
59
4
4
4
Neutral voltage displacement 59N
2
2
2
2
2
2
Negative sequence
47
overvoltage
Overfrequency
81H
2
2
2
Underfrequency
81L
4
4
4
Recloser (4 cycles) (2)
79
v
v
v
The figures indicate the number of units available for each
protection function
b standard, v options.
(1) Protection functions with 2 groups of settings.
(2) According to parameter setting and optional MES120 input/
output modules.

Ring incomer protection: Sepam S82


b line or source protection: 67, 67N/67NC
b directional logic discrimination.

DE50120

ANSI
code

Coupling circuit protection


Coupling of 2 parallel incomers: Sepam S82
b busbar protection: 67, 67N/67NC
b busbar voltage and frequency monitoring
b directional logic discrimination.
DE50121

Protection

33

Transformer applications

Examples of applications
Sepam series 80

Standard transformer application diagrams do not take voltage levels into account:
b the transformer primary winding is always at the top
b the transformer secondary winding is always at the bottom.
The transformer primary and secondary windings need to be protected.
The Sepam proposed can be installed on either the primary or secondary winding of
the transformer. The other winding can be protected by an incomer or feeder type
substation application Sepam.

Transformer feeder protection


b
b
b
b

transformer short-circuit and overload protection


internal transformer protection: Thermostat / Buchholz (ANSI 26/63)
RTD temperature monitoring (ANSI 49T)
voltage and frequency monitoring.
Earth fault protection:
b primary: 50G/51G
b secondary: 50G/51G.

DE50125

DE50124

DE50123

Transformer feeder protection: Sepam T81


Earth fault protection:
Earth fault protection:
b primary: 50G/51G.
b primary: 50G/51G
b tank earth leakage:
50G/51G.

Note: for long feeders, the 50G/51G function may be replaced by the 67N/67NC.

34

Transformer applications

Examples of applications
Sepam series 80

Selection table
Phase overcurrent (1)
50/51
8
8
8
50N/51N
8
8
8
Earth fault /
50G/51G
Sensitive earth fault (1)
Breaker failure
50BF
1
1
1
Negative sequence /
46
2
2
2
unbalance
Thermal overload for machines (1) 49RMS
2
2
2
Restricted earth fault
64REF
2
2
2
1
Two-winding transformer
87T
differential
Directional phase overcurrent (1) 67
2
Directional earth fault (1)
67N/67NC 2
2
Directional active overpower
32P
2
2
2
2
Overfluxing (V / Hz)
24
Positive sequence
27D
2
2
2
undervoltage
Remanent undervoltage
27R
2
2
2
Undervoltage (L-L or L-N)
27
4
4
4
4
4
4
Overvoltage (L-L or L-N)
59
Neutral voltage displacement 59N
2
2
2
Negative sequence
47
2
2
2
overvoltage
Overfrequency
81H
2
2
2
4
4
4
Underfrequency
81L
Thermostat / Buchholz (2)
26/63
v
v
v
Temperature monitoring
38/49T
v
v
v
(16 RTDs) (3)
The figures indicate the number of units available for each
protection function
b standard, v options.
(1) Protection functions with 2 groups of settings.
(2) According to parameter setting and optional MES120 input/
output modules.
(3) With optional MET148-2 temperature input modules.

DE50128

Transformer feeder differential protection: Sepam T87


Transformer differential protection: 87T
Earth fault protection:
Earth fault protection:
Earth fault protection:
b primary: 50G/51G.
b primary: 50G/51G
b primary:
b secondary:
v 64REF
v 64REF
v 50G/51G
v 50G/51G.
b secondary:
v 64REF
v 50G/51G.

T81 T82 T87

DE50127

ANSI
code

DE50126

Protection

35

Transformer applications

Examples of applications
Sepam series 80

Transformer incomer protection


b
b
b
b

transformer short-circuit and overload protection


internal transformer protection: Thermostat / Buchholz (ANSI 26/63)
RTD temperature monitoring (ANSI 49T)
voltage and frequency monitoring.

DE50130

36

Earth fault protection:


b primary :
v 64REF
v 50G/51G
b secondary : 50G/51G.

DE50134

DE50133

DE50132

DE50131

Transformer incomer differential protection: Sepam T87


Transformer differential protection: 87T
Earth fault protection:
Earth fault protection:
Earth fault protection:
b primary : 50G/51G
b primary : 50G/51G
b primary: 50G/51G
b secondary : 50G/51G.
b secondary :
b secondary :
v 64REF
v 64REF
v 50G/51G.
v 50G/51G.

Earth fault protection:


b primary :
v 64REF
v 50G/51G
b secondary :
v 64REF
v 50G/51G.
DE50135

DE50129

Transformer incomer protection: Sepam T81


Earth fault protection:
Earth fault protection:
b secondary: 50G/51G.
b secondary:
v 64REF
v 50G/51G.

Transformer applications

Examples of applications
Sepam series 80

Selection table

Parallel transformer incomer protection


b
b
b
b

T81 T82 T87

Parallel transformer incomer protection: Sepam T82


b transformer directional phase overcurrent protection: 67
b transformer secondary earth fault protection: 50G/51G, 59N.
DE50136

Phase overcurrent (1)


50/51
8
8
8
50N/51N
8
8
8
Earth fault /
50G/51G
Sensitive earth fault (1)
Breaker failure
50BF
1
1
1
Negative sequence /
46
2
2
2
unbalance
Thermal overload for machines (1) 49RMS
2
2
2
Restricted earth fault
64REF
2
2
2
1
Two-winding transformer
87T
differential
Directional phase overcurrent (1) 67
2
Directional earth fault (1)
67N/67NC 2
2
Directional active overpower
32P
2
2
2
2
Overfluxing (V / Hz)
24
Positive sequence
27D
2
2
2
undervoltage
Remanent undervoltage
27R
2
2
2
Undervoltage (L-L or L-N)
27
4
4
4
4
4
4
Overvoltage (L-L or L-N)
59
Neutral voltage displacement 59N
2
2
2
Negative sequence
47
2
2
2
overvoltage
Overfrequency
81H
2
2
2
4
4
4
Underfrequency
81L
Thermostat / Buchholz (2)
26/63
v
v
v
Temperature monitoring
38/49T
v
v
v
(16 RTDs) (3)
The figures indicate the number of units available for each
protection function
b standard, v options.
(1) Protection functions with 2 groups of settings.
(2) According to parameter setting and optional MES120 input/
output modules.
(3) With optional MET148-2 temperature input modules.

transformer short-circuit and overload protection


internal transformer protection: Thermostat / Buchholz (ANSI 26/63)
RTD temperature monitoring (ANSI 49T)
voltage and frequency monitoring.

b transformer directional phase overcurrent protection: 67


b transformer secondary earth fault protection: 67N/67NC, 64REF.
DE50137

ANSI
code

Parallel incomer differential protection: Sepam T87


b transformer differential protection: 87T
b transformer secondary earth fault protection: 50G/51G, 64REF.
DE50138

Protection

37

Motor applications

Examples of applications
Sepam series 80

Motor protection
b
b
b
b
b

internal motor fault protection


power supply fault protection
driven load fault protection
RTD temperature monitoring (ANSI 38/49T)
voltage and frequency monitoring.
Two-way.
DE50254

DE50253

DE50252

Motor protection: Sepam M81


Direct starting.
Auto-transformer starting.

M81

Motor differential protection: Sepam M87


Motor differential protection: 87M.

38

Phase protection by selfbalancing differential


scheme: 50/51.
Direct starting.

DE50257

Auto-transformer starting.

DE50256

DE50255

Direct starting.

38/
49T

Motor-transformer unit
applications

Examples of applications
Sepam series 80

Selection table

Motor-transformer unit protection


b
b
b
b
b
b

M81 M87 M88

motor and transformer protection against internal faults


power supply fault protection
driven load fault protection
internal transformer protection: Thermostat / Buchholz (ANSI 26/63)
RTD temperature monitoring (ANSI 38/49T)
voltage and frequency monitoring.

DE50259

Motor-transformer unit protection: Sepam M81


b motor earth fault protection: 50G/51G
b motor earth fault protection: 59N
b transformer primary earth fault
b transformer primary earth fault
protection: 50G/51G.
protection: 50G/51G.

Motor-transformer unit differential protection: Sepam M88


Motor-transformer unit differential protection: 87T.
b motor earth fault protection: 50G/51G
b motor earth fault protection: 59N
b transformer primary earth fault
b transformer primary earth fault
protection: 50G/51G.
protection: 50G/51G.
DE50261

Phase overcurrent (1)


50/51
8
8
8
50N/51N
8
8
8
Earth fault /
50G/51G
Sensitive earth fault (1)
Breaker failure
50BF
1
1
1
Negative sequence /
46
2
2
2
unbalance
Thermal overload for machines (1) 49RMS
2
2
2
Two-winding transformer
87T
1
differential
Machine differential
87M
1
Directional earth fault (1)
67N/67NC 2
2
2
Directional active overpower
32P
2
2
2
Directional reactive overpower 32Q
1
1
1
1
1
1
Phase undercurrent
37
Excessive starting time,
48/51LR
1
1
1
locked rotor
Starts per hour
66
1
1
1
Field loss (underimpedance)
40
1
1
1
1
1
1
Pole slip
78PS
Overspeed (2 set points) (2)
12
v
v
v
Underspeed (2 set points) (2)
14
v
v
v
2
2
2
Positive sequence
27D
undervoltage
Remanent undervoltage
27R
2
2
2
Undervoltage (L-L or L-N)
27
4
4
4
Overvoltage (L-L or L-N)
59
4
4
4
2
2
2
Neutral voltage displacement 59N
Negative sequence
47
2
2
2
overvoltage
Overfrequency
81H
2
2
2
Underfrequency
81L
4
4
4
26/63
v
v
Thermostat / Buchholz (2)
Temperature monitoring
38/49T
v
v
v
(16 RTDs) (3)
The figures indicate the number of units available for each
protection function
b standard, v options.
(1) Protection functions with 2 groups of settings.
(2) According to parameter setting and optional MES120 input/
output modules.
(3) With optional MET148-2 temperature input modules.

DE50258

ANSI
code

DE50260

Protection

39

Generator applications

Examples of applications
Sepam series 80

Generator protection
b
b
b
b
b
b

internal generator fault protection


network fault protection
driving machine fault protection
control fault protection
RTD temperature monitoring (ANSI 38/49T)
voltage and frequency monitoring.

40

DE50264

Earth fault protection:


b 64REF and 50G/51G
b 50G/51G.

Generator differential protection: 87M.


Earth fault protection:
b 50G/51G
b 59N.

Earth fault protection:


b 50G/51G.

DE50268

Earth fault protection:


b 100% stator earth fault
64G
b 50G/51G.
DE50267

DE50266

DE50265

Generator differential protection: Sepam G87


Phase protection by self-balancing differential scheme:
50/51.
Earth fault protection: 50G/51G.

DE50263

DE50262

Generator protection: Sepam G82


Earth fault protection:
Earth fault protection:
b 50G/51G
b 100% stator earth fault
b 59N.
64G
b 50G/51G.

Generator-transformer unit
applications

Examples of applications
Sepam series 80

Selection table

Generator-transformer unit protection


b
b
b
b
b
b
b

G82 G87 G88

generator and transformer protection against internal faults


protection against network faults
driving machine fault protection
control fault protection
internal transformer protection: Thermostat / Buchholz (ANSI 26/63)
RTD temperature monitoring (ANSI 38/49T)
voltage and frequency monitoring.

DE50270

Generator-transformer unit protection: Sepam G82


b generator earth fault protection:
b generator earth fault protection: 100%
50G/51G
stator earth fault 64G
b transformer secondary earth fault
b transformer secondary earth fault
protection:
protection:
v 50G/51G
v 50G/51G
v 59N.
v 59N.

Generator-transformer unit differential protection: Sepam G88


Generator-transformer unit differential protection: 87T.
b generator earth fault protection:
b generator earth fault protection:
50G/51G
100% stator earth fault 64G
b transformer secondary earth fault
b transformer secondary earth fault
protection:
protection:
v 50G/51G
v 50G/51G
v 59N.
v 64REF.
DE50272

Phase overcurrent (1)


50/51
8
8
8
50N/51N
8
8
8
Earth fault /
50G/51G
Sensitive earth fault (1)
Breaker failure
50BF
1
1
1
Negative sequence /
46
2
2
2
unbalance
Thermal overload for machines (1) 49RMS
2
2
2
Restricted earth fault
64REF
2
2
1
Two-winding transformer
87T
differential
Machine differential
87M
1
Directional phase overcurrent (1) 67
2
Directional earth fault (1)
67N/67NC 2
2
2
2
2
2
Directional active overpower
32P
Directional reactive overpower 32Q
1
1
1
Directional active underpower 37P
2
Field loss (underimpedance)
40
1
1
1
Pole slip
78PS
1
1
1
Overspeed (2 set points) (2)
12
v
v
v
14
v
v
v
Underspeed (2 set points) (2)
Voltage-restrained phase
50V/51V
2
2
2
overcurrent
Underimpedance
21B
1
1
1
Inadvertent energization
50/27
1
1
1
2
2
Third harmonic undervoltage / 27TN/64G2 2
100 % stator earth fault
64G
Overfluxing (V / Hz)
24
2
2
2
Positive sequence
27D
2
2
2
undervoltage
Remanent undervoltage
27R
2
2
2
Undervoltage (L-L or L-N)
27
4
4
4
4
4
4
Overvoltage (L-L or L-N)
59
Neutral voltage displacement 59N
2
2
2
Negative sequence
47
2
2
2
overvoltage
Overfrequency
81H
2
2
2
4
4
4
Underfrequency
81L
Thermostat / Buchholz (2)
26/63
v
v
Temperature monitoring (16
38/49T
v
v
v
RTDs) (3)
The figures indicate the number of units available for each
protection function
b standard, v options.
(1) Protection functions with 2 groups of settings.
(2) According to parameter setting and optional MES120 input/
output modules.
(3) With optional MET148-2 temperature input modules.

DE50269

ANSI
code

DE50271

Protection

41