You are on page 1of 3

Residual current devices

DPNa Vigi

Protection
earth leakage protection

PB104343-40

Function
b The DPNa Vigi residual current device provides complete protection of final
circuits (overcurrents and insulation faults):
v protection of people against electric shocks by direct contacts (10 and 30 mA),
v protection of people against electric shocks by indirect contacts (300 mA),
v protection of installations from fire hazards (300 mA).
b Fast closing.
b Positive break indication.
b Display of earth fault on the front panel.

Catalogue numbers
DPNa Vigi
Auxiliaries
1P+N
DB119073

Without auxiliaries

Curve B
N 1

Width in 9-mm
modules

Type A

Type AC

Rated
current

Sensitivity

30 mA

300 mA

10 mA

30 mA

6A
10 A
13 A

19611
19613
-

19790
19791
19792

16 A
20 A
25 A
32 A
40 A

19615
19616
19617
19618
-

19793
19794
19795
19796
-

Sensitivity

30 mA

300 mA

10 mA

30 mA

6A

19621

19430

19531

10 A

19623

19431

19304

19532

13 A

19533

16 A

19625

19432

19305

19534

20 A

19626

19433

19535

25 A

19627

19434

19536

32 A

19628

19435

19537

40 A

19629

19436

19538

N 2
1P+N

Curve C
Rated
current

Voltage rating (Ue)


Operating frequency
Accessories

230 V AC
50/60 Hz
Module 91902

Conformity with standards


b National standard*.
b European standard EN 61009.
b International standard IEC 61009.

* Information to be provided by the country.

version: 1.1

91943E.indd

Residual current devices


DPNa Vigi (cont'd)

Protection
earth leakage protection

Tightening torque

6 to 40 A

3.5 N.m

Copper cables
rigid

PZ2

flexible or with end-piece


DB112805

15 mm

Rating

DB112804

DB122728

Connection

5.5 mm

Insulated connector

Comb busbar
(bag of 2)

14885
13 outgoing feeders 14880

1 to 10 mm2

DB119152

1 to 16 mm2

24 outgoing feeders 14890

Mounting
4
5

Padlocking facility
(bag of 2 parts)
Spacer

Clip-on terminal markers

Interpole barrier

90943E.indd

26970
27062
27001

version: 1.1

Residual current devices


DPNa Vigi (cont'd)

Protection
earth leakage protection

Technical data
Main characteristics

Earth leakage protection with instantaneous


tripping
Setting temperature for ratings 6 to 40 A

10, 30, 300 mA

Tripping curve

Curve B: the magnetic tripping devices act at


between 3 and 5 In
Curve C: the magnetic tripping devices act at
between 5 and 10 In

30C

Breaking capacity
EN61009

Rated breaking capacity (Icn)


Rated residual breaking and making capacity
(IDm)

4,500 A
4,500 A

Endurance
Ratings (A) Mechanical endurance
Number of O/C cycles
20,000

6 to 40

Electrical endurance under rated


current
Number of O/C cycles
20,000 y 20 A
10,000 u 25 A

Autres caractristiques

Degree of protection

IP4/IPxxD for the part outside of the enclosure

Insulation voltage (Ui)

400 V

Rated impulse withstand voltage (Uimp)

4 kV

Service temperature

Type AC: from -5C to +60C


Type A and type A-si: from -25C to +60C

Storage temperature

-30C to +70C

8/20 s impulse withstand

250

Limitation class

Insulation class

Tropicalization

Treatment 2 (relative humidity 95% at 55C)

Dimensions
DB122729

36

5.5

44

16

4.8
81

45
3.6
7

Weight
Residual current device
Type
1P+N

Accessories
page 91902

Comb busbars:
page 91906

Auxiliaries:
page 90142

DPNa Vigi
125 g

Tightening torque:
page 90179

version: 1.1

Interference:
page 91105

Discrimination:
page 91105

Test button:
page 91105