Professional Documents
Culture Documents
a r t i c l e i n f
o
Article history:
Received 26 April 2012
Received in revised form
18 June 2012
Accepted 10 July 2012
Keywords:
Ofces
Air conditioning
Sick building syndrome
Thermal comfort
Human behavioral adjustment
a b s t r a c t
Poorly operated air conditioning and mechanical ventilation (ACMV) system might cause signicant Sick
Building Syndrome (SBS) symptoms and thermal discomfort in the hot and humid climate. This study
presents our investigations on the prevalence of SBS symptoms and thermal comfort in ofces in
Singapore via two approaches including: (1) the onsite objective monitoring and questionnaire-based
investigation under normal ACMV practices, and (2) the online survey with occupants in controlled
indoor temperatures. The results indicate that the prevalence of individual SBS symptoms is lower than
the similar studies in other geographic regions. Overcooling seems to be the domineering complaint in
the local context and the occupants seem to prefer higher indoor temperature. As such, human
behavioral adjustments such as adding clothing happen quite frequently. Moreover, the data also
suggests that cultural traits might skew the survey results, especially in certain subjective aspects
regarding the satisfactory level and comfort. To sum up, the prevalence of SBS symptoms are generally
acceptable in current local context. However, due to the hot and humid ambient environment,
traditional ACMV system with vapor compression refrigerant tends to trigger the overcooling issue in
relation to the sensible and latent heat. It is invaluable to advance our understanding of the
relationships between the ACMV system, human behavioral adjustments, and building energy
consumptions in the tropical region.
2012 Elsevier Ltd. All rights reserved.
1. Introduction
Singapore is a city-state located in the hot and humid tropical
region. The outdoor air temperature varies from 23 to 34 C with
a mean relative humidity around 90% in the morning and 60% in
the afternoon. In such a climate, the air-conditioning and
mechanical ventilation (ACMV) systems serve close to all local
commercial and institutional buildings. With a high building
density in the urban environment, the Sick Building Syndrome
(SBS) symptoms and thermal comfort level
have become
important concerns, from both the building operation and
occupants health/productivity points of view.
Chamber experiment, modeling simulation, and eld investigation are the three typical approaches to study both the prevalence of SBS symptom and thermal comfort. Chamber experiments
are traditionally carried out in climate-controlled environment,
with stringently controlled conditions and human behaviors to
exam the impacts of targeted variables [1e3]. Previously established numerical methods form the basis of the modeling studies,
with less attention to the uniqueness of specic environmental
conditions and/or individual subjects [3e5]. Filed investigation is
the most challenging approach, because of the uncontrollable and
* Corresponding author. Tel.: 65 6790 4773; fax: 65 67921650.
E-mail address: wcchang@ntu.edu.sg (V.W.-C. Chang).
C,
17
A. Chen,
A. Chen,
V.W.-C.
V.W.-C.
Chang
Chang
/ Building
/ Building
andand
Environment
Environment
58 (2012)
58 (2012)
172e178
172e178
was
0.34, which deviated slightly from
neutrality in the cool
side. Cheong et al. [13] investigated thermal comfort of college
students in an ACMV lecture theater. The results revealed that the
occupants were slightly uncomfortable and dissatised with
overcooling. All these studies mainly aimed to understand human
thermal comfort states assuming that the subjects were
passive sensors of the thermal conditions. However, the fact is,
as indicated by Nicol and Humphreys, that people are active
adaptors to environmental stimuli [3].
To ll up the missing gaps mentioned above, the main
objectives of the study are: (1) to investigate the current
prevalence of SBS symptoms in local ACMV ofce building and
evaluate the potential associations between ventilation, energy
consumption and these symptoms; (2) to study the human
adaptive behaviors and the associated impacts on thermal
comfort level in ACMV buildings.
17
rates (L/s-person), indoor air velocity (m/s), mean radiant temperature (MRT, C). Temperature, RH and CO2 were monitored and
17
A. Chen,
A. Chen,
V.W.-C.
V.W.-C.
Chang
Chang
/ Building
/ Building
andand
Environment
Environment
58 (2012)
58 (2012)
172e178
recorded at a 5-min interval by the IQM172e178
60
Indoor Air Monitors
(Aeroqual Inc., Auckland, New Zealand). Three IQMs were placed
within the human activity zones about 1.1 m above the oor in
each ofce. The sampling period was typically over 24 h.
Ventilation rate was measured by tracer gas dilution method
[16]
with Sulfur hexauoride (SF6) as the tracer gas. Decay
proles of SF6 concen- tration were recorded by an InfraRan
Specic Vapor Analyzer (Wilks Enterprise, Inc., East Norwalk,
17
Table 1
Summary of the indoor parameters in the ofces (95% CI).
Room no.
No. of workers
Air temperature ( C)
Mean radiant
RH (%)
CO2 (ppm)
Ventilation
rates (L/s-person)
64
70
68
67
68
66
68
67
69
58
57
58
55
53
51
68
49
63
785
666
711
706
656
985
760
634
1000
619
603
853
663
642
619
663
765
638
0.09
0.10
0.10
0.10
0.09
0.08
0.08
0.09
0.09
0.10
0.09
0.10
0.08
0.08
0.09
0.12
0.11
0.10
56
35
36
42
47
49
59
78
5
23
24
26
9
27
10
24
77
29
temperature ( C)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
12
6
5
9
6
11
4
7
10
29
12
22
14
11
11
15
5
21
25.1
24.5
23.3
23.7
23.2
23.7
23.8
24.5
24.4
25.9
25.6
26.0
24.3
24.2
23.5
23.5
24.6
24.9
25.6
24.4
24.0
24.4
24.5
23.6
23.8
25.0
24.6
25.7
25.7
26.2
24.1
24.7
24.2
23.4
24.8
25.3
As shown in Table 1, the mean ventilation rate was 36 L/sperson (95% CI: 27e47 L/s-person), which was much higher than
the rec- ommended value in local standards (10 L/s-person)
[23]. This indicates that most of the ofces in this study were
over-ventilated. In the industry practice, ventilation rate is a
good approach to control CO2 concentration. Most of the indoor
CO2 concentrations in this study were found to be lower than 800
ppm, except for the other two ofces with 985 ppm and 1000
ppm. However, excessive
ventilation might also imply the unnecessary energy consumption
in the air-handling unit (AHU). This impact will be discussed
further in Section 3.5.
There are several important factors that contribute to the
occurrence of over-ventilation. The ventilation is dened as
intentionally movement of air into and out of a building by ASHRAE Handbook [24]. This ventilation concern is usually addressed
by the ventilation rate, which is dened as liter of fresh air
provided per second per person. In the industry practice, however,
the AHUs are mainly operated based on the damper openings
which require at least 5% of fresh air in the supply. The ventilation
rate focuses on the number of occupants, while the AHUs
operate on
the indoor volume or air exchange rate. This
sometimes leads to signicant bias in the indoor environment.
As the capacity of local ofces is
commonly designed using 10 m2 of oor space per occupant, the
ACMV systems are very likely to over-supply the fresh air if the
assumption of maximum occupancy level is not met. In this study,
some ofces were not constantly fully occupied due to the work
nature, with the lowest occupancy level at only 30%. This observation explains why the over-ventilation occured at a high
frequency.
3.4. SBS symptoms
Table 2 tabulates the frequencies of individual SBS symptoms
and the comparisons with other similar studies in different
geographic regions. There was a high percentage of occupants who
complained of wide varying SBS symptoms. More than half of the
respondents complained that at least one of the symptoms
happened more than 2 times per week, and 39.4% of the respondents reported that they were suffering from at least two individual
symptoms for more than 2 times per week. However, if we look
into
Table 2
Prevalence of SBS symptoms in different studies.
County/region Building
types
Singapore
Singapore
Sweden
Hong Kong
Brazil
India
Sweden
U.S
U.S.
South Africa
France
UK
Ofces
210 2.82
Ofces
2462 7.1
Computer
355 24.5
classrooms
Library
253 e
Ofces
967 55.5
Ofces
144 54.2
e
2154 12.8
Ofces
301 26
Ofces
4326 15
Ofces
624 17.7
Ofces
425 e
Ofces
477 39.5
33.33
12.3
42.7
18.78
8.3
e
6.57
2.8
e
0.94
0.5
6.7
40
58.5
52.3
33.5
25
15
42.2
49.2
52.5
e
e
e
11.8
22
e
e
e
e
e
e
e
2.5
e
3
4.65
e
e
e
e
e
0.7
e
3
4.34
e
e
2.82
2.3
8.7
e
20
e
1.5
e
2
e
32.3
2.9
10.33
8.7
16.8
18.31
10.9
17.4
e
37.3
31.4
5.2
27
13
21
65.6
17.2
36
51.8
40.2
3.3
e
7
6.9
51.6
e
9.86
4.8
4.6
34
25.8
30.8
22.5
e
5
31.5
e
9.9
15.96
9.1
16.5
This study
[10]
[25]
36
33.3
35.8
8.7
24
22
25.7
49.5
e
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[33]
[34]
Fig. 1. Distributions of thermal sensation votes (TSA) and thermal comfort votes (TCV).
Table 3
Internet-based thermal sensation investigation results.
Section
Section A
Section B
Section C
Temperature,
Occupant number
Week 1
Week 2
Week 3
23
24
23
24
25
24
25
23
25
48
26
24
Week 1
Week 2
Week 3
94
81
88
75
69
71
56
54
58
Week 1
Week 2
Week 3
1.27
1.47
1.38
1.39
1.44
1.24
1.33
1.50
1.36
Long sleeve:
Light jacket:
Long sleeve or light jacket:
Long sleeve & light jacket:
32.9 (26.3e39.5)
43.4 (36.3e50.0)
61.5 (58.9e63.6)
14.2 (9.9e18.9)
A. Chen,
A. Chen,
V.W.-C.
V.W.-C.
Chang
Chang
/ Building
/ Building
andand
Environment
Environment
58 (2012)
58 (2012)
172e178
172e178
17
17
Table 5
Indoor/outdoor parameters in air-conditioning seasons in different countries/regions.
Location
RH (%)
Outdoor temperature
Clothing (clo)
Dt
Refer
Singapore
Singapore
Singapore
Hong Kong
Hong Kong
Taiwan
Hunan
Singapore
24.4
0.4
23
23.5 (Operative temp)
21.8
23.6 (Neutral)
25.6 (Neutral)
28.7
0.2
22.1
62.1
3.2
64
55.5
50e60
50
7
50e85
72.4
62
0.093
0.005
0.1
0.10
0.1e0.15
0.27
0.05
0.19 (0.1e0.5)
0.13
0.14
31.0
0.3
6.5
30.3
30.3
31.5
32.3
29.5
0.7
0.7
0.9
M: 0.57, F: 0.61
N/A
0.44
M: 0.53; F: 0.61
N/A
N/A
0.35
N/A
This study
[10]
[12]
[14]
[20]
[21]
[22]
[43]
7.3
5.9
3.6
7.4
[28] Gupta S, Khare M, Goyal R. Sick building syndrome-a case study in a multistory centrally air-conditioned building in the Delhi city. Build Environ 2007;
42:2797e809.
[29] Eriksson NM, Stenberg BGT. Baseline prevalence of symptoms related to
indoor environment. Scand J Public Health 2006;34:387e96.
[30] Burr G, Alderfer R. Sick building syndrome: factors associated with employeereported symptoms. Appl Occup and Environ Hyg 1992;7:352e4.
[31] Brightman HS, Milton DK, Wypij D, Burge HA, Spengler JD. Evaluating
building-related symptoms using the US EPA BASE study results. Indoor Air
2008;18:335e45.
[32] Bachmann MO, Myers JE. Inuences on sick building syndrome symptoms in
three buildings. Soc Sci Med 1995;40:245e51.
[33] Teculescu DB, Sauleau EA, Massin N, Bohadana AB, Buhler O, Benamghar L,
et al. Sick-building symptoms in ofce workers in northeastern France: a
pilot study. Int Arch Occup Environ Health 1998;71:353e6.
[34] Finnegan MJ, Pickering CAC, Burge PS. The sick building syndrome: prevalence
studies. Br Med J 1984;289:1573e5.
[35] Fisk WJ, Mirer AG, Mendell MJ. Quantitative relationship of sick building
syndrome symptoms with ventilation rates. Indoor Air 2009;19:159e65.
[36] Sundell J, Levin H, Nazaroff WW, Cain WS, Fisk WJ, Grimsrud DT, et al.
Ventilation rates and health: multidisciplinary review of the scientic literature. Indoor Air 2011:191e204.
[37] Wargocki P, Wyon DP, Sundell JAN, Clausen GEO, Fanger PO. The effects of
outdoor air supply rate in an ofce on perceived air quality, Sick Building
Syndrome (SBS) symptoms and productivity. Indoor Air 2000;10:222e36.
[38] Seppnen OA, Fisk WJ. Summary of human responses to ventilation. Indoor
Air 2004;14(Suppl.):102e18.
[39] Fanger PO. Thermal comfort: analysis and applications in environmental
engineering. New York: McGraw-Hill; 1972.
[40] Tham KW, Ullah MB. Building energy performance and thermal comfort in
Singapore. ASHRAE Trans 1993;1(99 Pt):308e21.
[41] Fong KF, Chow TT, Li C, Lin Z, Chan LS. Effect of neutral temperature on energy
saving of centralized air-conditioning systems in subtropical Hong Kong. Appl
Therm Eng 2010;30:1659e65.
[42] Liddament MW, Orme M. Energy and ventilation. Appl Therm Eng 1998;18:
1101e9.
[43] Cheong KW, Chong KY. Development and application of an indoor air quality
audit to an air-conditioned building in Singapore. Build Environ
2001;36:181e8.