Professional Documents
Culture Documents
It is a technical report of practical training at Rajasthan Rajya Vidhyut Prasaran Nigam LTD. It
was commenced on 15/6/2004 and completed on 15/7/2004. It was of 30 days and taken at 132
kv G.S.S Jawahar Nagar, jaipur.
I feel immense pleasure in conveying my heartiest thanks and deep sense of gratitude to
Mr.Monil Mathur, Head of the Electrical Engineering Department of Kautilya Instiute Of
Technology And Engineering. for his efforts and for technical as well as moral support.
I am also thankful to our instructors and other technical and non technical staff, for helping in
understanding the various aspects and constructional details of work and site in 132 kV G.S.S.
Jawahar Nagar, Jaipur.
It may not be possible for me to acknowledge the contribution of all my friends, but I am thankful to all
those who came forward to help me. I express my sincere thanks to my colleagues and other trainees for
their valuable ideas and support during practical training.
RAGINI AGARWAL
III B.E. (ELECTRICAL ENGINEERING)
DETAILS OF TECHNICAL
AND
OTHER OBSERVATIONS
Introduction
A transformer is a static (or stationary) piece of apparatus by means of which electric power of
one circuit is transformed into electric power of same frequency in another circuit.
In brief, a transformer is a device that:
1. Transfer electric power from one circuit to another
2. It does so without change of frequency
3. It accomplishes this by electromagnetic induction
4. Where the two electric circuits are in mutual inductive influence of each other
A high voltage is desirable for transmitting large powers in order to decrease the IR losses and
reduce the amount of conductor material. A very much lower voltage, on the other hand, is
required for distribution, for various reasons connected with safety and convenience. The
transformers make this easily and economically possible.
POWER TRANSFORMER
The x- mer is oil immersed with triple rating of 100 MVA auto under ON (natural cooling) (oil
immersed with natural air-cooling) or (oil immersed with forced oil cooling). The tertiary is suitable
for 11MVA continuos synchronous condenser loading. When the tertiary is load the secondary
load should be limited, such that no industrial individual winding is over loaded and are also that
total losses are not exceeds.
However a simultaneous loading of 100MVA at 0.8p.f. (Lag) on the low voltage and 65MVA at
0.8p.f. (Lag) on the territory is fissible the tertiary can also be loaded to 20MVA 0.8p.f.on low
voltage without exceeding temperature rise. The x-mer is suitable for simultaneous parallel
operation.
It is ensured that the tertiary winding will also operate satisfactory with each other. The x-mer is
provided with separate tank of radiators, fans, pumps and associated control equipment. The
control equipment is housed in a tank mounted marshalling commercial. It is provided with on
load tap charge.
The magnetic circuit is a 3 limbed core type construction each being inter leaved with joints with
top and bottom yokes. The winding surrounded the three limbs the conditions are made from
high grade caused "cold ratted grain oriented" silicon alloy steel. The Insulation on laminations is
of varnish. This has stepped sections with legs and yokes having 100% area cooling ducts are
provided parallel to the plane of laminations. The yoke laminations are clamped with clamp
plates are legs by means of clamping-cum-sling plates. They are clamped with bolts.
For lifting the core with winding high lumbers of lifting bolts are provided. The core clamp plates
are insulated from each other to with stand plates, a test pressure of 2 kV, 50Hz, A.C. for one
minutes.
The innermost coil i.e. nearest to the core transformer is the testing winding. This is wounded
helical on a Bakelite cylinder with radial coil ducts for cooling purpose. Axial oil ducts are provided
inside and out side the coil; means to tertiary winding is wound the common winding. This coil is
wound as a no. of continuous discs with radial oil ducts in between discs. Thus statics shields
rings are provided one at the top and other at the bottom to control the electrostatic stress
distribution in the winding
Just outside the common winding, the tapping coil is placed. The tapping coil is wound as an
inter-wound spiral coil on a Bakelite cylinder. As the tapping arrangement is of the reversing type
the number of sections in the coil is half the number of tapping steps. The required number of
parallel conductors are wound in two parallel conductors respectively one together outside the
coil the outer most coil forms the series winding, the series winding is shielded layer type winding
consists of five layer each wound spiral. The winding is placed in between two shields.
A X - mer double wound or auto wound has minimum of two voltage, one corresponding to the
supply and second to the load side. Many time a third winding is introduced in primary and
secondary, winding requires it because another voltage may be required at the place of supply to
load. In either core the third winding is connected to delta formation and is generally known as
"tertiary" winding in the case of star/star methods of connection three phase shell type X mer is
used which causes a serious problem of the third harmonic components of the magnetic
currents. The tertiary delta provides a short circuit for flow of the third harmonic currents
therefore eliminating third harmonic multiple connection are provided on primary and secondary
winding.
The neutral point of such winding is therefore stable and can earthen without any effect to the X-
mer on the system
The territory winding helps:
(1) To reduce the unbalancing in the phase of the primary side due to unbalanced three
phase loads;
(2) To redistribute the flow of faults currents;
(3) To supply an auxiliary load in addition to the main load. This could be consists of the
power factor improvement synchronous condensers or shunt capacitors. In such a case the
purchaser of a power X mer should always specify the voltage and power ratings of the tertiary
winding;
(4) As compared with star/delta connection of fault current in the event of secondary form
line to neutral tertiary delta consists in the laminations. This of course further depends upon the
impedance between tertiary and main winding.
(5) The X mer having mixed cooling OFB(forced oil air blast cooling) (100 MVA) OB(air
blast) (70 MVA) and ON(natural cooling) (50 MVA) is provided with separately mounted banked
radiators. There are eight radiators of elements 2920 mm. Long. The radiators are mounted on
the top and bottom headers, which are supported by facilitated frames. Each radiator is
connected at the top and bottom with respective header through out let and inlet valves. The top
and bottom headers are connected to the tank by 200 mm diameter pipes and valves one each
radiators as well as headers.
A Inland propeller type of air pump is connected in the bottom pipes, which circulate air through
the tank and radiators. A motor is full of the X mer oil, which serves as a cooling medium. A
window nut is provided on the body of the motor. The coolers are provided with two 915 mm
(36") dia. (weather proof), each blowing with 440 cubic meters of air minute on the radiators
element directed in such as way that the full length of the element is converted by the blast.
There are two type of control
(1) Hand Control and
(2) Automatic Control
Hand Control
For hand control selector switch is set to hard position whereby individual motor can be started by
its own starter push buttons already in the event all 'starts' push button are kept in the depressant
position, the cooler bank can be group started.
Automatic Control
The start push button of the starters is kept locked in depresses position and switch 4313 kept in
Auto position. fans motor conductors are energized by the closing of mercury switch contact
49A-1, 49B-1 or 49C-1. For winding temperature indicator 49A, 49B, 49C respectively with a
further increase in temperature either of contact 49A=2, 49B = 2 or 49C =2 of winding
temperature indicates closed to start the motor.
The bushings are one per phase porcelain steam type of 12 kV class. The neutral bushings are
oil filled porcelain steam type of 36 kV class. The LV and 245 kV class respectively oil filled type
condenser bushings. The active part of the bushings consists of core made of wound synthetic
resin bounded paper (5 RBP) with condenser layers (Aluminum foil) suitable inter posed to field
control.
The control metal tubes are serves as support for the paper wound core during the winding
process. The core adhere to the metal tube. The oil being absolutely oil tighten. The HV, LV
bushings are mounted on the delta detachable adapters, while the neutral bushings are mounted
directly on the cover.
Its temperature operates on the principle of liquid expansion (mercury is in steel). The
temperature indicator is provided with a max-pointer and two mercury switches. The mercury
switches are adjustable to make contacts between 50oC and have a fixed difference of 10oC.
This operates on the principle of liquid expansion (mercury in steel) provides in deal local
indication at the marshalling box. Half of the sheet temperature irrespective of the suitable
conditions, the thermometer bulb is connected by capillary tube to the local indicator.
The marshalling box is a weather proof steel box mounted on the side of X mer tank, the
marshaling box is provided with heater for the prevention of moisture condensation, besides this
the inside of the box is provided with anti condensation point.
TERRITARY WINDING
This core used on the main transformer instead of a separate regulator unit. The cost of tap
changing unit lies in:
(1) The mechanical arrangements for effecting the change
(2) The relay devices to prevent incorrect operation or to ensure that transformers in
parallel are all operated together.
(3) The electrical operation of the gear.
(4) The additional insulation required for tappings, switches, etc.
The booster transformer system is the most expensive, but has the considerable advantage of
employing a standard main transformer, and tap devices dealing only with a small power at low
voltage.
TERRITARY WINDING
Transformers may be constructed with territory windings (i.e. windings additional to the normal
primary and secondary) for any of the following reasons:
(a) For an additional load which for some reason must be kept insulated from that of the
secondary.
(b) To supply phase compensating devices, such as condensers, operated t some voltage
not equal to that of the primary or secondary or with some different connection (e.g. mesh)
(c) In star/star-connected transformers, to allow sufficient earth fault current to flow for
operation of protective gear, to suppress harmonic voltages, and to limit voltage unbalance when
the main load is asymmetrical in each case the territory winding is delta connected.
(d) As a voltage coil in a testing transformer.
(e) To load large split-winding generators
(f) To interconnect three supply systems operating at different voltages.
Territory windings are frequently delta-connected consequently, when faults and short circuits
occur on the primary or secondary sides (particularly between lines and earth), considerable
imbalance of phase voltage may be produced, compensated by large territory circulating current.
The reactance of the winding must be such as to limit the circulating current to that which can be
carried by the copper, otherwise the territory winding may overtreat under fault conditions.
DE-HYDRATING BREATHING
Presence of moisture in oil results into reduction of its di electric strength and may cause failure
of transformer. As such it is necessary to ensure that oil remains clean and dry. Conservator tank
is mounted on the top of the transformer and is connected to main tank by means of a small
diameter pipe. Interior of the conservator tank is connected to a silica gel breather by a pipe.
Silica gel breather absorbs the moisture when the transformer breathes due to expansion and
contraction of the oil on account of changes in temperature thereby ingress of moisture into the
main body of the oil is avoided.
Silica gel breathers are usually dispatched in Position during transit. But in some cases they may
be dispatched separately for transport purposes. In such cases breathers should be fitted as soon
as possible. While fixing the breather make sure that all joints are airtight. Silica gel is blue in
colour when dry with absorption of moisture, its colour changes to violet and then pink. pink
colour indicates that silica gel is saturated and is ineffective. It should then be either replaced or
re activated.
While charging the breather following steps must be considered:-
Remove the wing nuts supporting the body.
Glass container should be squarely fitted on its gasket, then pour reactivated silica gel into the
container up to a level ¼ inch from top.
Fix the assembly to the top plate with inspection window facing out ward from the transformer
and secure it with the wing nuts. Ensure that top gasket is in Position.
Transformer oil should be poured into the oil cup until it overflows through the screw hole and
fixes it to the assembly with the nut.
Applying heat to it in oven until its colour is restored to blue reactivates silica gel.
BUCHHOLZ RELAY
Oil immersed power transformer are fitted with gas actuated relay known as buchholz relay. It
compresses of oil tight cast iron housing and two operating elements. The top operating element
consists of alarm system on gas collection while the bottom-operating element trips the
controlling circuit breaker in case of oil surge. Each element is made up of an aluminum bucket
pivoted on bearings on a fixed stainless steel shaft. Mercury switches are clamped to these
elements control wires is taken to the terminal block. Pet cock and drain plugs are provided at top
and bottom of relay. An inspection window, with graduated scale is provided for viewing the level
of oil.
In case of minor faults, small bubbles of gas while going towards conservator get accumulated in
the relay housing and lower down the level of oil. Top operating element gets tilted and mercury
switch gets closed thereby completing the alarm circuit. In case of major faults due to violent
generation of the gas oil surges towards conservator. Oil surge tilts the bottom element that close
the mercury switch and necessary command is given for tripping the controlling circuit breaker. In
case the level of oil drops below the level of the relay due to heavy leakage, alarm and trip circuit
gets energized and transformer is isolated from the source of power.
Buchholz relay help in detecting various faults as: -
1. Core lamination short circuit.
2. Overheating of the windings.
3. Arcing due to bad conductors.
4. Earth faults.
5. Short circuit of winding.
6. Puncture of bushing insulators inside tank.
INSTRUMENT - TRANSFORMER
The transformer are used in a.c system for the measurement of current , voltage, power and
energy, the actual measurements being done by measuring instruments. Transformer used in
conjucation with measuring instrument for measurement purposes are called as "instrument
transformer". The transformer used for the measurement of current is called "current
transformer". Transformer used for voltage measurement are called as "voltage transformer" or"
potential transformer"
Current and voltage transformer insulate the secondary (Relay, instrument and meter) circuits
from the primary (power) circuit and proceed qualities in the secondary winding which are
proportional to those in primary. The role of a transformer in protective relays is not a readily
defined as that for metering and instrumentation whereas the essential role of a measuring
transformer is to deliver on its secondary a quantity accurately representative or that which is
applied to the primary side, a protective transformer varies in its role accordingly to the type of
protective gear it serves.
Failure of a protective system to perform its function currently is often due to incorrect application
of transformers. Hence current and voltage x-mer must be regarded as constituting part of the
protective system and carefully noticed with the relays to fulfill the essential requirements of the
systems. There is no great distinction between a protective voltage transformer and a measuring
voltage transformer. The difference only being nature of the volt transformer. Quite often the
same transformer can serve between purpose and provided. The protective voltage transformers
reasonably, accurately its duty will have been fulfilled.
Voltage transformers which step-down systems voltage to sufficiently low values are necessary
on every system for:
1. Induction of the voltage conditions
2. Metering of the supply (or exchange of energy)
3. Relaying and
4. Synchronizing
On account of cost and voltage the indicating instruments meters and relays are designed for the
voltage as obtainable from the secondary sides of the voltage transformer. The calibration of the
indicating instruction and meters is however done accordingly to the primary voltage of the V.Ts.
The voltage transformers are classified as under:
(a) Capacitive voltage transformer or Capacitive type
(b) Magnetic type
Capacitive voltage transformer is being used more and more for voltage measurement in high
voltage transmission network, particularly for systems voltage of 132 and above where it become
increasingly more economical. It enables measurement of the line to earth voltage to be made
with simultaneous provision for carrier frequency coupling which has reached wide application in
modern high voltage net work for tale-metering remote control and telephone communication
purposes. The capacitance type voltage transformers are of two types.
1. Coupling capacitor type; and
2. Pushing type.
Fig. On proceeding page shows a line diagram of coupling capacitor type voltage transformer.
The capacitor C1+C2 are made of oil impregnated paper and Aluminum foil. Each capacitor is
composed of a multiage of element provided with special contacts for series connection and
assembled in such a way that the capacitor inductance remains low. A tap is taken in between to
contact the magnetic voltage transformer across the capacitor and earth. This point is fixed in
consideration of the system voltage between line and earth, this is total capacitance of the
coupling capacitor and the primary voltage of the magnetic voltage transformer. It is a usual
practice to diagram the magnetic transformer for a standard primary voltage of 5, 10, 15 or 20 kV
depending on the requirement of burden and accuracy special circuit (auxiliary) element are:
1. Comparating inductance coil,
2. Damping impedance,
3. Resistor (R)
4. Spark gap (F)
The compensating Inductance Coil in series with the primary or the intermediate transformer
compensates the voltage increase on capacitive voltage divider. The damping in the secondary
circuit avoids the Ferro resonance. The resistor and spark gap provide necessary protection.
The condenser type bushings are primarily rolls of varnished, impregnated paper and laid under
heat and pressure with metal sheet lain in between the paper layers. The sheet may consist of
the aluminum foil or a coating of graphite. The voltage distributors between the various layers is
properly designed and predetermined.
A tapping across these can be proper calibration give a replica of the supply voltage. The low
capacitance imposes restriction on the supply voltage. The out put power of such capacitor
voltage x-mers and therefore limits the application to synchronizing and voltage indications. The
following table shows the maximum output for various systems voltage that is obtainable with
typical bushings.
Line to line kV Output power (in watt)
66 kV 5 Watt
110 kV 12 Watt
132 kV 15 Watt
220 kV 25 Watt
Since, however, in a sub-station there are other requirements which needs a greater burden.
These types of current transformer are not very commonly used.
These magnetic type transformer work on the same principle as the power transformer. The
design is, however, different because of different requirement of two used cases. The load to be
transmitted through a voltage transformer is quite limited depending on the purpose for which this
is to be used. This is generally limited to a few hundred VA at the most. The main object in the
design of a voltage transformer is to minimize possible errors in measurement made with its
help. These errors are due to:
1. Voltage drop in the primary winding caused by exciting current and
2. Voltage drop in both the winding caused by the load current.
The former accounts for the errors at zero burden and the latter for the stop of the ratio and
phase angle curves. Since the load current is fixed for a given burden the drop which it cause
can be reduced only by reducing the resistance and reactance of the transformer. This is done by
using relatively few turns and a large cross sectional of both iron and copper. The low primary
impedance thus brought out, causes a small no load drop that may be still further reduced by
running the iron at relatively low induction.
In the lower voltage drop of voltage transformer the active part is contain in a steel housing and
the primary terminal is brought out through a bushing on higher systems voltage above 66 kV. It
is generally practiced to contain the active part in porcelain housing. Whether the voltage
transformer is contained in a steel tank or in a porcelain housing, the secondary terminals are
made and brought out in the steel housing provides as a base in the case of voltage transformer
housed in porcelain bushing.
Another significant distinction between the single-phase voltage transformer and single-phase
power transformer is that in the case of former only one terminal of the primary winding is brought
out for connection to the tank. The secondary terminal is earthen alone the core and the steel
housing.
There are many factors to be considered before the choice between magnetic type voltage
transformer and capacitive type V.T. can be made.
The important amongst these are
(i) Purpose
(ii) Layout
(iii) Price
We should first know the purpose for which voltage transformers are needed. In case we need
voltage supply for voltmeter, synchronizing, energy meters, distance relays (without carrier)
magnetic type voltage transformer done case serve the purpose. It is required to adopt carrier
protection. It is that coupling capacitors are used on each phase along with the voltage
transformers. In such a way we can use either capacitive V.T. with coupling capacitor. If only
carrier communication is required the purpose can be served with only one capacitor coupling per
circuit and magnetic voltage transformer or capacitive voltage transformer only.
Only in 132 kV line's the desirability of providing career protection has to be checked. It may or
may not be necessary generally, if the highest system voltage connecting the various
powerhouses is then greater than 132 kV. The requirement of one coupling capacitor or three
with the magnetic voltage transformer can influence the comparison of price with capacitive
voltage transformers.
As present pricing in the magnetic market the price may work out almost equal. It is therefore,
more a matter of individual preference.
Test for V.T.:
The test for VT are classified as:
(i) Type test
(ii) Routine test
Instrument Transformers
Precision measurement and metering has assumed increasing importance as of the growth of the
supply system and particularly where energy interchanging between different power systems is
concerned with large quantities of energy transferred of the financial effect of measuring error
assume considerable importance. It is also important and required that small fraction of the rated
primary current should be measured with adequate accuracy. Some of them enters beyond rated
current is also necessary to make consideration of the normal system overloads. The instrument
transformers is therefore, required to maintain the accuracy class within says 50% to 120% of
the rated current and small measuring errors with the range as evident.
ISOLATOR
INTRODUCTION
When carrying out inspection to disconnect reliably the unit or section on which the work to be
done from all other live parts on the in-station in order to ensure completely safety of the working
staff.
To afford against minute mistakes it is desirable that it should be done by an apparatus which
makes a visible break in the circuit such an apparatus is the isolating switch (for insulator). It may
be defined as a device used to open (or use) a circuit either when negligible current is interrupted
(or established) or when no significant charge the voltage across the terminals of each pole of the
isolator will result from the operation.
Isolator may be classified as single pole and 3-pole isolator i.e. according to number of poles.
According to the service type these are:
(i) Indoor type and
(ii) Outdoor type
The doubling break rotating centre part isolating switches has
three isolator parts per phase mounted on a base of fabricated
construction.
The centre part carries the moving contacts arms tabular or fault with the intact assembles at the
extremities. The moving contacts engage the fixed contacts on the outer fixed insulator parts.
The designs of moving and fixed contacts vary from manufactures to the other. The variants are
generally simple one of the contacts is the male contacts with the other is contacts.
The rotating centre part of the three phases are inter connected by operating rods 50 that
simultaneous movement of each part, connected by the operating rods and driven form one post
by operating mechanism through an adjustable lever drive rod and torque shaft supporting
structures.
The design of a contact could be different with different manufacturers for closing or both the
isolator parts rotate causing moment of contact arm. The insulator shown is pneumatic operates
but is provided with emergency hand drive mechanism, also.
The contact at extremely which engares with the isolator contacts the line side. The earthing
blade when provided are so inter locked with the main line blade that there can be closed only
when the main blade are in fully open positions. Similarly it is possible to close the main blades
only when the earthing blades are fully in open position. The earthing blade of a line switch have
a separate operating mechanism as well as gallery switch indicate on contact room the open or
close position of the earthing blades.
OPERATION
The operation of an isolator may be manual i.e. by hand without using any other supply or
storage of energy meter power operated isolates during the cause of operation utilize energy
which is not supplied by the operator. The energy may be electrical pneumatic or the energy
previously stored in spring or counter weight.
Control
In case power operated isolators are purchased for any installation it may be worth while to
examine further weather control should be local in switchyard or remote in the control room.
The extra cost enrolled in the isolated is quite substantial particularly at voltage 132 kV and
below. It should therefore considered in detail whether any installation really instifies the
procurement of remote operated isolators keeping in view the past that the frequency of operation
of isolators is rather low.
AUXILIARY SWITCH
This is an operating and important accessory and is designed as a switching device working in
conjunction with an isolator for controlling a circuit for auxiliary device such as trip coils indicators
or indicating lamps. The number of normally closed and normally open contacts should be
specially worked out particularly if electrical interlocking between breakers and isolators is
chosen.
Make before and Break after contacts
These are provided in series with the main contacts so that in case of load isolators, the arcing is
taken and whenever necessary only the arcing contacts are replaced.
ARCING HORNS
These are provided on each stack of post Insulator for the purpose of insulation co-ordination
some time confusion is created in the function of these arcing horns vis a vis (make before and
break after contacts. These may be fixed or adjustable types).
The use of arcing horns is avoided where insulation strength between poles or phases and
between higher than that of earth. This is necessary for safety and security. Any travelling wave
meeting an isolator is the closed position should causes of it must a flash over to earth rather
than between phase or between terminal of the same pole where the design of the isolator itself
provides for this. It is necessary to use arcing hours on the insulator stacks.
INTERLOCKING
In correct operation of an isolating switch may be accidentally harmful effects and may cause
distribution of part of the plant as well as costly service interruption for preventing such incorrect
operation inter locks are used i.e. isolating switches. The mechanical interlocking between
isolating switches and it is earthing switch consists of a rod linkage between isolating switch and
its earthing switch shafts of the respective switches.
The mechanical interlocking between isolation switches and circuit breaker and different isolating
switches is generally in the form of lock and key arrangement. There is usually a common key for
a number of locks mechanical interlocking is generally provided on hand operated are isolating
switch only. Electrical interlocking is achieved with blocking magnets, these magnets are
arranged on the isolating switch on the hand drive or in the value controlled. The pneumatic drive
and are controlled by pilot switch contents. The requirement of interlocking may be summed as:
(i) The isolator can't be operated unless the association breaker is worked in the
position.
(ii) The earthing switch shell close only when the line isolator is open and locked and
net in its stroke.
(iii) The isolator shall close only where the corresponding circuit breaker and the
earthing switch of the corresponding line or open.
(iv) The circuit breaker shall close only after all the isolator associated with it have been
locked either in closed or open position
(v) When one bus bar isolations so that bus is open when on bus isolation of that bus
expecting the bus coupler bus is closed, the other small close only when bus coupler circuit
breaker and both the bus isolation are closed.
(vi) The bus isolator of bus coupler buy shell operates only when all the bus coupler
circuit breaker is open.
(vii) The bypass isolator is provided of the feeder shall also close manually irrespective
of the fact whether the feeder circuit breaker and it is adjoining isolator are open or closed.
CIRCUIT BREAKER
INTRODUCTION
A circuit breaker is equipment, which can open or close circuit under all condition viz. No load, full
loads an fault conditions. It is so designed that it can be operated manually under normal
conditions and automatically under fault conditions, for the later operation, relay circuit is used.
Circuit breaker can be defined as an electrical device, which protects the system from short
circuits or overloads with the help of relays. In case, circuit breaker is not of adequate capacity,
its failure may result into interruption of power, shut downs, injury to personals and damage to
property. Installation of over rated circuit breakers or extra sensitive and costly protective devices
will mean un-warranted expenditure. It is therefore necessary that calculations in respect of short
circuit currents for the concerned system be made before correctly rated circuit breakers are
selected or steps are taken to improve the existing system.
OPERATING PRINCIPLE
A circuit breaker consists of fixed and moving contacts under normal operating conditions, these
contacts remain closed.
In this condition, the emf in the secondary winding of current transformer (CT) in sufficient to
operate the trip coil of the breakers but the contacts can be opened by manual or automatic
control.
When a fault occurs on any part of the system the resulting overcurrent in the C.T. primary
winding increases the secondary winding EMF and hence the current through the relay operating
coils. The relay contacts are closed and the trip coil (tripping coil) of the breaker is energized.
The moving contacts are pulled apart by some mechanism thus operating the circuit breaker.
When the contacts of the circuit breaker are separated under fault conditions, arc is produced
between them (male and female contact). The current is thus able to continue until the arc
ceases. This arc generates enormous heat, which may cause damage to the system or to the
breaker itself.
Therefore, the main problem in a circuit breaker is to extinguish the arc within the shortest time so
that heat generates by it may not reach a dangerous value.
Classification of circuit breakers for various voltages
1. Bulk oil circuit breaker.
2. Air blast circuit breaker.
3. SF-6 circuit breaker.
4. Minimum oil circuit breaker.
5. Vacuums circuit breaker.
PRINCIPLE
When the contacts of the breaker are opened in the vacuum (10 -7 toor and 10 -5 torr) an arc is
produced between the contacts by the ionisation of metal vapours of contact and it is is quickly
extinguished in the vacuum because it has excellent suspension arc quenching properties than any
other medium.
WORKING
When the breakers operates, the moving contact operates from the fixed contact and an arc is
produced between the contacts. The production of arc is due to the ionization of metal ions and
depends very much upon the material of contacts. The arc is quickly extinguished because the
metallic vapours i.e. electrons and ions produced during arc diffused in a short time. Since
vacuum has very fast rate of recovery of dielectric strength, the arc extinction in vacuum breaker
occurs with a short contact separating (say .625 cm) vacuum.
ADVANTAGES
They are compact, reliable and have long life
There are no fire hazards
They require little maintenance and are quiet in operations
APPLICATIONS
They are widely used from 33 kV up to 66 kV voltages.
OPERATION
Under normal operating conditions the moving contacts remain engaged with the upper fixed
contact. When the fault occurs, the moving contact is pulled down by the tripping springs and an
arc is struck. The arc energy vapourises the oil and produces gases under high pressure. This
action constrains (compels) the oil to pass through the central hole in the moving contact and
result in forcing series of oil through the respective passages of the turbulation. The process of
turbulation is orderly one in which the sections of the arc are successively quenched by the effect
of the separate streams of oil moving across each section in turn and bearing away its gases.
ADVANTAGES
(i) It is requires lesser quantity of oil compare to the bulk oil circuit breaker.
(ii) It require smaller space
(iii) There is reduced risk of fire
(iv) Maintenance problem are reduced
Disadvantages
These chambers suffers from the disadvantages that a very low current, they have long arcing
period so a separate oil reflection device has to be used. The contacts are operated by pull rod or
by the spring operating mechanism.
Advantages
1. It requires less oil in comparison to bulk oil circuit breaker.
2. It requires lesser space.
3. There is reduced risk of fire.
4. Maintenance problems are reduced.
CONTROL ROOM
Synchronizing - Panel
There is a hinged synchronized panel mounted at the end of a control board. To take out new
supply on the bus bar supply so the panel handles put to cuts synchronizing and then see the
synchronies scope. There is also two voltmeter one-give busbar voltages. Second in coming
voltage when the syncronoscope stop zero we close the C.B. and the supply is taken on bus bar.
Syncrono scope
A syncronoscope is used to determine the current instance of closing the switch, which connects
new supply to bus bar.
The current instance of syncronising is when the bus bar and the incoming voltage.
1. Are equal in magnitude
2. Are in phase
3. Hare the same frequency
4. The phase sequence should be same.
Introduction
In order to generate the electric power and transmit it to consumer millions of rupees must be
spent on power system equipment. These equipment are to work under specified normal
conditions. However a short circuit may occur due to failure of insulation called by:
(i) Over voltage due to switching
(ii) Over voltage due to direct and indirect lightning strokes
(iii) Briding of conductors by birds
(iv) Break damage of insulation due to decrease of it's di-electric strength.
(v) Mechanical damage of the equipment. The fault takes place in following
properties.
1. Phase to phase 20 - 25%
2. Single phase short circuit 50-60%
3. Double phase S.S. 3-5% 20-25%
4. Three phase short circuit 3-5%
5. Phase to phase and phase to guard 10-15%
Fault may be defined as the rise of current in the several times to normal current resulting the
high temperature rise which can damage the equipment.
It reduces the voltage immediately and considerably.
Basic Equipment or Requirement of Protective Relays
Basic requirements of protective relays are as follows
Speed
Protective relaying should do's connect a faulty element as quickly as possible.
Selectivity
The ability of the protective relay to determine the point of which have the fault occurs and select
the nearest circuit breaker tripping of which will lead the clearing of fault with min-or so damage to
the system.
Sensitivity
It is the capacity of the relaying to operate relay under the actual condition that produces the last
operating condition tendency.
Depending upon the method of element connected primary relay (series element connect directly
on the circuit of protective element) and secondary relay (sensing element connected through a
current and voltage transformer).
Depending upon the time action
Depending upon the kind of contacts
These are called normally opened, normally closed in Heerapura sub station control room there in
panel in which the relays are set and there are many type of relays.
1. Over current relays
2. I.D.M.T. fault relay
3. Impedance relay
4. Earth fault relay
5. Bucheloz's relay
6. Differential relay
7. Auxiliary relays
Over current relay
It is used in over current protection scheme over current protection is the name given to protected
relay scheme devised to rise in current in a protected circuit of to a safe value inherent simplicity
of operation and reliability in operation has resulted in over current protection having obtained the
widest application in short circuit protection scheme and a mean of protection against abnormal
condition's of operation etc in power x mission circuit as here is Heerapura grid station when the
short circuit occurs the fault current which is very much higher than the normal current flow
through the relay i.e. from proportional due to C.T. and the over current relay because operations
(because flow is more than the present value) i.e. is more than Ix where Ip is relay picking up or
operating currents now due to close of C.B. the signal is go to trip coil of C.B. trip.
(a) Electromagnetic relay
(b) Induction over current relays
Inverse time characteristics relay
The relay using here having the inverse time characteristics having the time delays dependent
upon current value. This characteristic is being available in relay of special design. There are
(1) Electromagnetic Induction type
(2) Permanent magnetic moving coil type
(3) Static type
Earth fault relay
The earth fault relay and over current relay resembles because when the conductor break or by
any reason it is earth ment it is short circuited and fault current which flow in many times to
normal current, so there is always over current fault so now we have the over current relay and
both are same. These relays can also be Electro-magnetic induction and static relay.
Directional Relay
The non-directional relay discussed above can operate for fault in either direction in order to
achieve operation for the fault current flowing in a specific direction. It is necessary to add an
additional element, such a relay which corresponds to fault current flow in a particular direction is
closes called a directional relay. These relays are added in the panel.
When a fault takes place, the fault current flows through the current coil of relay which produces a
flux in the lower magnet of the directional while the current in the voltage coil produces another
flux in the upper magnets. The flux produces torque tending to close it's contact (directional
element contacts). The relay also flows through the windings over the magnet of the non-
directional elements. Since this winding provides a closed path the induced emf circulates a
current, which therefore produce another flux.
ANNUNCIATOR AND METER SECTION
In the control room the 'annonciator' is most control box as when the fault across and relay trip by
which we mean that the fault is cleared.
In this there is a box type thing in which probable fault at different feeder and different zone have
written and in front of them there is a bulbs. There is also alarm systems.
When same fault is occurred the relay is trip and is given two signal one for two circuit breaker
and second to annuncitor auxiliary relays. This relays first signal trip the C.B. and signal when
goes to relay i.e. auxiliary type trip, that relay this relay i.e. seeds the signal to annunciator which
give alarm and the bulb is lightning in the front of the type of the fault, which is occurred. The
shift engineer can receives this signal and sees the annunciator at which feeder at which zone
and which type of fault is occurred
Meter Section
Panel at which the C.B. is open it trip again to see that whether it is instantaneous fault (like
monkey made short circuit or bird made a short circuit ) The closes the circuits breaker and reset
the relay is trip or not. It is not other the system coil leak as much as it again announce that the
circuit is still faulty then as we know that suppose fault is at RPS Feeder zone earth fault send a
maintenance party to the fault.
Measuring Instruments
These are certain panel boards, which have the energy meter for differential feeder, wattmeter
and maximum demand indicator.
Energy Meter
The energy meter is the meter, which measures the energy. These are filled to different feeders
and we note hourly reading how much a amount we are importing/exporting. These meters read
in MW.
Watt Meter
This meter is also attached to energy feeder and we can note by the watt meter how much
amount energy power is exporting or importing .
Maximum Demand Indicator
This is also mounted on panel board. The chief requirement of these indicators is that they shall
record the maximum power taken by the feeder during a particular period. The maximum
demand indicator shall be a so designed that any sudden momentary increase in loads such as
due to short circuit not account. Therefore, a maximum demand indication is to record the
average power over successive pre-determined period.
LIGHTNING ARRASTER
Introduction
Lightning Arresters are installed in power houses and sub-stations to safeguard the major
equipment like power-transformers, switch gear and to ensure the flow of power un-interruptedly.
It is true that lightning arresters require minimum post-installation care, but their importance as a
critical equipment can hardly be disputed.
Lightning Strokes and Over-voltages
The overhead transmission lines and connected electrical apparatus i.e. Power Transformers,
Switch gear etc. are subjected to over voltages on account of lightning discharges caused by
atmospheric disturbances and or by switching operations. Abnormal voltages are caused by
atmospheric disturbances as a result of:
(a) Direct Strokes
Direct stroke to the phase conductor or ground wire or to supporting structure results into
abnormal transient voltage, which gets super-imposed on the power net work.
(b) Indirect Strokes
Direct stroke in the vicinity of the line or the equipment or charged cloud over the power line
induces abnormal voltages.
Abnormal transient over voltages super-imposed by direct or indirect strokes travel along the
conductor in both the directions with the speed of light i.e. 186,000 miles per second or 1000 feet
per micro second. These waves are steep fronted in case of direct strokes and travel till the
surge voltage is attenuated or neutralized by reflected waves of opposite polarity from the earthed
object. E.H.V. transmission lines and sub-stations are designed to take care of direct strokes by
providing:
Coupling Capacitor
Coupling of high frequency transmitter receiver units to the power line is done through high
voltage capacitor. The high voltage capacitor, which has a capacitance of about 0.000, 1 MF is
earthen through the drainage coil. This provides insulation of the terminal equip from line by
providing a very high impedance to carrier frequency current.
Coupling Capacitor is used for coupling the carrier current or voltage to the power line. It blocks
the power frequency current to flow into the PLC equipment.
The coupling is usually designed for mounting of the wave traps on it. A corona shield is always
provided. Arcing rings are usually not provided as they may give resistance to corona
discharges, which result in higher noise level in PLCC circuits.
The coupling capacitor is used as a part of filter network which allows a fairly wide band of radio
frequency to pass through to the PLC terminals to be connected in parallel to the coupling unit
and hence results in a saving in the use of installation.
Use of Capacitor Voltage Transformer (CVT) as a Coupling Capacitor
The matching transformer is used for matching the impedance. The two capacitors and voltage
driver circuit. The carrier signals pass through these capacitors.
Signal is transmitted to PLC from the point through co-axial. The voltage drop across C2 is
applied to auxiliary transformer to get potential required for live line indication, metering and
synchronizing circuits.
Driving Coil
Function of this coil is to prevent high frequency signals from transmitter to ground and also
preventing the coming signals from earth the receiver. Its value of order of 100 MH
Receivers
The receivers usually consist of an alternate matching transformer band pass filter and amplifier
detector.
The amplifier detector converts a small incoming signal in to a signal capable of operating a
relatively intensive carrier receiver relay. The transmitter and receiver at the two ends of
protected each corresponds to local as far as transmitting.
Transmission System
The range of freque3ncies used for PLCC communication is generally between 10-500 kHz. In
partial situation, frequencies above 25 kHz are used due to the following reasons:
(1) Harmonics, switching, lightning and corona, which are generally present on HV lines,
have component in the frequency band between 100 HZ and 24 kHz which course considerable
noise in communication circuits. If frequency below 25 kHz are employed, the signal to noise
ratio in such circuit will be quite poor.
(2) Difficulty in separating power frequency and ratio frequency component below 25 kHz.
(3) Cost of coupling equipment becomes prohibitive owing to the size and complexity of
equipment required for operating efficiency at low frequency.
The upper limit of 500 kHz is used because -
(a) Radiation losses are high above 500 kHz
(b) Interference problems are encountered
The following methods can be employed for the speech in PLC Communications.
(i) Amplitude modulation with carrier and double side band transmission
(ii) Amplitude modulation with single side band suppressed or reduced carrier
transmission
(iii) Frequency Modulation
Almost all-modern PLC transmission equipments for speech use single side band suppressed or
reduced carrier transmission. Single side band AM transmission has the following advantages
over double side band AM transmission.
(a) The band width requirement channel is exactly half that of double
side band transmission
(b) As the receiver accepts half the band of frequencies the noise input
to the receiver is correspondingly reduced
(c) As the carrier and one side band are not transmitted, the power
required for these is saved.
BATTERRY ROOM
Introduction
Storage battery is the most dependable source of supply of D.C. power required for closing and
tripping of circuit breakers, operation of automatic protective devices; signaling equipment,
remote control apparatus, telephone service and emergency lighting in case of power plants and
sub-stations. Correctly selected and properly maintained battery will withstand heavy stresses
and strains during service without causing much headaches to the maintenance Engineer. D.C.
Auxiliary power supply is provided from storage batteries maintained continuously charged by
some type of supply set or a charger. The voltage of the auxiliary supply is maintained at
110/220 volt.
Advantages of Storage Batteries
• High Reliability
• Independances of A.C. power circuit conditions of existence of the faults.
D.C. Earth Fault
All D.C. auxiliary supply circuits must have their insulation resistance maintained at an adequate
level, as any breakdown in the insulation with respect the earth may lead to false tripping due to
formation of a path for bypass of the current round the control devices. Because of this danger
every D.C. auxiliary supply installation must include a unit for constantly monitoring the condition
of the insulation.
As fig. Shown, when the insulation is healthy the voltage of each power relative to earth V1 and
V2 will be equal and half the voltage between both the poles.
In case the insulation of one pole drops in value with respect to earth, the voltage to earth of this
pole will also drop, but the voltage to earth of the other pole of the circuit will increase by the
some amount.
Stationary Storage Batteries
Batteries are bring used for the supply of direct current to various types of equipment and
appliances and are broadly divided into two categories i.e. stationary and transportable type. The
stationary type battery, once installed is never moved during the course of its service life.
Lead Acid Storage Battery
Basically, lead acid storage cell consists of electrodes i.e. anode and cathode in the form of
plates immersed in diluted sulphuric acid, placed in acid resistant container. Acid resistant
containers are usually made of vulcanized rubber, glass, plastic, ceramic and good quality of
wood lined with lead. Glass and plastic containers are normally used in case of stationary
storage batteries. Where weight of the Battery does not present problem and simple space is
available wood containers lined with lead may be used. The container is provided with the vent to
facilitate the escape of gases as well as it provides opening for the addition of distilled water or
electrolyte.
Plates as used are in the shape of grids made of an alloy of lead and antimony and active
material. The use of plates in the shape of the grid is helpful in providing support to the active
material, conduction of electric current and maintenance of uniform distribution of the current
throughout the mass of the active material. Heavier grids are used in case of stationary batteries,
while light grids are used in case of batteries designed for heavier discharges when these are of
short duration. Lead non-oxide (lead power and Litharge) is normally used as an active material.
Lamp black, or barium sulphate or organic extract is added as an expander to the active material
in case of active material. An expander helps in decreasing the possibility of shrinkage and
hardening of the negative plates. The positive and negative plates are separated from each
other by means of porous separators made of wood vanear, perforated and slotted hard rubber,
glass fibre, etc. etc.
The Electrolyte
Sulphuric acid of very high purity diluted with distilled water is used as an electrolyte in case of
lead acid batteries. Since specific heat of the water is higher than sulphuric acid as such when it
is mixed with water abnormal increase in temperature takes place, it is, therefore, necessary to
get the solution cooled down before it is poured into the battery, to avoid damage to the plates.
Specific gravity and viscosity of the electrolyte has got great bearing on the condition and
capacity of the battery. The rate of diffusion of the solution through the pores of the plates,
depends upon its viscosity. The viscosity increases with the decrease in temperature, thereby
affecting the capacity of the battery at low temperatures. The value of specific gravity is the
indicator regarding the condition of the battery. It is defined as the ratio between equal volumes
of the liquid and the water at specific temperature and is measured by means of hydrometer. As
the life of the battery is greatly influenced by the chemical reactions taking place in the cell itself
i.e. formation of sulphates, effect of concentrated solution on the separators, temperatures, and
working conditions, it is extremely important to keep careful watch over the specific gravity of the
electrolyte. The range of the concentration of the electrolyte for different types of batteries as
suggested are as follows:
Specific gravity of the Electrolyte for various types of Batteries
Type of Battery Sp Gravity
Stationary batteries 1.200 to 1.225
Truck and tractor batteries 1.260 to 1.280
Starting and lighting batteries (in-topics) 1.200 to 1.233
Aviation Batteries 1.260 to 1.285
Operating Principle of Lead-Acid Cells
1. The decomposition of molecules in to ions due to action of water is called electrolytic
dissociation
H2SO4 2H + + SO4-2
2. Since the sum of the electric charges carried by the positive H 2 ions is equal to the sum
of electric charge carried by the negative acid redical ions, the solution remains electrically
neutral.
3. As a result of interaction of electrolyte with the atoms of lead of the (-)ve plate, some of
the lead atoms become ionized and two charge (+)ve ions of lead pass over in to the electrolytic
solution. This leaves the surface of the (-)ve plate becomes charged negatively in relation to the
electrolyte and the positive plate positively.
Battery Room
The battery room should be ready in all respects by fulfilling the following minimum requirements.
1. The walls and the ceiling of the battery room should be well black washed and should
remain clean and dry.
2. The flooring of the battery room shall be acid resistant tiles and material.
3. The battery room should be well lit. there should be no direct sun light on the cells.
4. Suitable exhaust fans shall be fixed to provide a minimum of six air charges per hour.
5. The exhaust fans shall be suitably distributed and placed on the wall, which open to
atmosphere, equally sufficient air inlet should be provided to prevent any negative pressure
developing in the room.
6. Necessary blowers are to be provided to maintain sufficient air inlet in to room
7. Never the entrance door should be kept closed which will lead to a negative pressure
developing in the batter room due to the continuous operation of exhaust fans.
8. Inlet air should be free from effluents (such as chlorine, acetic acid).
IMPORTANT INSTRUCTIONS
1. Float charger should always be kept on even when the battery set is being boost
charged.
2. In case of failure of A.C. supply to the battery charger, the battery set should be boost
charged at the equalizing current rate for the same number of hours for which A.C. supply
remained failed.
3. The door of battery room should always be kept open when the exhaust fan is running.
Door can be kept closed if sufficient inlet for air is provided in the door itself.
4. Add only distilled water to maintain cell electrolyte level, never add acid.
5. Temperature correction of sp. Gravity
S.G. (27 C) = S.G. (t) + 0.7 ( t - 27)
where t = actual temp. of cell electrolyte
6. If inspite of repeated charging the specific gravity or voltage of some cell(s) does not
improve, these are to be considered weak cells.
7. Premature gassing in any cell is due to (-ve) plate of low capacity because of
sulphation. Such cells should be removed from the battery set.
8. Adjustment of specific gravity: (a) Replacement of electrolyte with distilled water in
cells having high gravity (b) Replacing electrolyte in cells having low gravity with electrolyte from
cells having high gravity.
9. Never store acid i.e. electrolyte of sp. Gravity higher than 1200.
Life of the Lead Acid Battery
Factors, which influence the life of battery, are as follows:
(a) Overcharging of the battery reduces the life of battery due to the following reasons:
(i) Water present in electrolyte is decomposed into hydrogen and Oxygen
due to excessive charging. Gas bubble thus formed remove active material from the plates.
(ii) Removal of water from the electrolyte on account of decomposition makes
the electrolyte more concentrated. Concentrated acid is harmful to the separators and negative
plate material at high temperatures.
(iii) Due to excessive heat, positive plates, separator negative plates get
damaged.
(iv) Over charging results into buckling and warping and of the positive plates.
(v) Under charging results into the formation of sulphates which cannot be converted
electrochemically into active material and thereby causes strain on the positive plates. Strained
positive plates are likely to get buckled.
(vi) If the battery remains idle for longer periods and is undercharged lead sulphates
are formed and may result into "shorts". When such battery is recharged, there is likelihood of
excessive self-discharge.
(vii) Undercharged battery will not feed the required power for which it has been
installed. Under serveres right conditions Electrolyte may freeze.
Safety Precautions
It is in the interest of the Undertaking to provide protective equipment to maintenance crew and
also keep them properly instructed about the precautions, which should be observed while
working on batteries. Protective equipment and recommended safety precautions are listed
below:
(a) Protective equipment
(i) Goggles
(ii) Acid proof Gloves and Aprons
(iii) Water
(iv) Bicarbonate of Soda
(b) Precautions
(1) While preparing electrolyte for lead acid batteries never pour water into the
acid.
(2) Handles of tools required for tightening the bolts should be insulated.
(3) Smoking, presence of naked flame should prohibited in the battery room
(4) Battery room should be well ventilated and provided with exhaust fans
(5) Acid should be stored in separate rooms
(6) Cells should be installed on wooden racks painted with acid resisting paint
(7) Cells should be insulated from the racks by placing insulators in between
(8) Cells should be levelled during installation by using lead shims
(9) Sulphuric acid containers are normally enclosed in wooden crates. These
crates should be handled by two men without any regard to its weight and each crate should be
clearly marked with the label that it contains acid.
(10) Never use metallic vessels while handling acid or distilled water.
General Care
(a) Lead Acid Batteries
(1) Electrolyte level must be maintained 10 to 15 mm above the plates.
(2) Terminal voltage of the cell must not be allowed to fall below 1.85 volts.
(3) Battery should be charged to its rated capacity.
(4) Battery should not be allowed to remain in semi-discharged condition
(5) Commercial sulphuric acid should not be used
(6) Distilled water should be used for topping of the battery.
(7) Excessive charging should be avoided
(8) Bare and insulated leads should be painted with recommended paint
(9) Battery should be kept clean and dry and battery room should be well
ventilated
(10) Should acid be spelt or if any parts are wet, wipe over with wet rag and dry
thoroughly
(11) Terminal posts and connectors should be clean and free from corrosion
(12) Nuts and bolts of cell connectors should be kept tightened and smeared with
Vaseline.
COOLING: The lower half of the condenser is in a closed cemented room in which forced air phenomena
is used which acts as cooling medium for condenser.
Cooling arrangements includes :
(1)Heat exchanger (2) lubricating oil
(3)Radiators (4)Water cools the stator winding of machine.
PROTECTION
Various protective relays are provided for system oil high temperature,
WORKING
The working of the synchronous condenser can be divided into
following steps:
Jacking: It is a phenomenon of the synchronous condenser bearing with the help of forced or jetting oil
operation, the operation makes the main shaft of the motor float in bearing with a thin film of oil. This
operation reduces friction at effects considerably and hence the starting current is reduced.
Starting: Starting operation is accomplished with the help of an auto-transformer designed to give start
within an hour starting transformer is put into circuit by closing the neutral of three windings. A voltage of
3.4 kV is fed into the damped winding and the motor starts, drawing a current of 3000 ampere (starting)
from the auto-transformer.
Running: Once the motor has gained the speed nearly equal to the synchronous speed, the neutral switch is
opened and the bridge circuit is then closed. During the operation the connection between the network and
machine is maintained through the X'mer winding which now acts only as a reactor, the whole operation is
automatic and is provided with interlocking arrangements to overcome any fault or non-correct switching
of apparatus.
Power factor adjustment: Power factor adjustment can be carried out by controlling the exciter field
current. Hence a stepless variation of capacitive or reactive power upto the rated power can be achieved. It
should be noted that synchronous condenser has internally inheritly, sinusoidal waveform and the
harmonics in the waveform do not exist.
A failure of one unit of capacitor bank affects that unit only. The
remaining units continue to do their job. However failure of a
synchronous condenser means loss of total condenser capacity. On
the other hand the failure rate of a synchronous condenser is very
small as compared to the failure rate of a capacitor bank.
Synchronous condenser adds to the short circuit currents in the system and increases the circuit breaker
ratings.
APPENDICES
Appendix 1
Definition of the terms used
It is given as: -
Y=I/V or Y=1/Z if Z=V/I
Where Y is admittance, I is current, V is
voltage and Z is the impedance.
2 Conductance It is the component of the current in phase with
the applied voltage divided by applied voltage or
the resistance divided by the square of the
impedance.
3 Susceptance: It is the component of current in quadrature with the
applied voltage divided by the voltage or the reactance
divided by the square of the impedance.
4 Phase sequence: It is the order in which the phase of polyphase system
reach a maximum voltage in the same direction.
5 Power factor: It is defined as the cosine of the angle of lag of the
current, because it is the factor by which the apparent
power must be multiplied in order to obtain the true power.
6 Synchronous speed: It is the speeds of an A.C. machine which corresponding to the
speed of rotation of the magnetic flux. It is related to the
frequency in cycle per second and number of poles in the
machine.
7 Primary relay: Primary relay are those which are connected directly in
the protected circuit.
8 Secondary relay: These are connected to the protected circuit through
current transformer and potential transformer.
9 Back-up relay A relay, which operates, usually after a slight delay, if the
normal relay does not operate to trip concerned circuit
breaker.
10 Instantaneous relay It is that relay that operate in less than 0.1 second, and
does not have intentional delay.
11 Time delay relay A relay which is equipped with delaying elements.
12 Bulking relay It is the device, which prevents the protecting relay from
tripping, either due to its own characteristics or to an
additional relay.
13 Operating current The minimum value of current at which the relay picks up
is called as operating current.
14 Drop out current The maximum value of current at which the relays drop
out is called the drop out current
15 Re-set ratio It ratio of drop out current to the pick up current
16 Recovery voltage It is the voltage, which appears across the terminal of
each poles of circuit breaker immediately after the braking
of the circuit.
17 Rate of rise of recoveryThe rate of rise of recovery voltage is a rate expressed in
volts per micro second representative of the increase of
voltage (R.R.R.V.):
the recovery voltage, the assessment being made in
accordance with a prescribed method.
18 Spinning reserve Reserve generating capacity connected to the bus and
ready to take load.
19 Demand factor = maximum demand
Connected Load
LIST OF ABBREVIATIONS
So, I thought to take my practical training at 132kv G.S.S. R.R.V.P.L. Jawahar Nagar Jaipur. I
learnt there a lot. I came to know about CT and PT, distribution system, various transformers,
relays, circuit breakers, conductors, LA etc. etc.
In Jawahar Nagar G.S.S. every event added a lot to my practical knowledge during my training
session. As during the practical session, maintenance period was going on thus it made a right
direction to understand and make a clear and absolute approach about various equipment's and
their fittings and features installed there. This made a perfect relation between theoretical and
practical knowledge.